Etihad Etisalat Company ‫شركة إتحـــــاد إتصـــاالت‬

Facility & Administration ‫المرافق واإلدارة‬


Technical Building Planning & Optimization ‫تخطيط وتطوير أداء المباني الفنية‬

Division 16 - Electrical Specifications for Technical Buildings (TB)

ii). Unless otherwise specified or shown on the lighting fixture schedule, ballast shall be
of rabid start, Energy saving type, electronic RFI protected, of Philips manufacture
or equal approved.

iii). Dimming: Suitable for use with dimming system as specified or as shown on
drawings.

x. High-Intensity Discharge Lamp Ballasts: HID lamp ballasts, of ratings, types and
makes as recommended by lamp manufacturer, which properly mates’ lamps to
electrical supply by providing appropriate voltage and impedance for which lamps
are designed. Design ballast to operate lamp within the lamp’s power trapezoid
requirements.

y. Lamps:

i). Provide fluorescent lamps of energy saving types as indicated. Tubular fluorescent
lamps shall comply with IEC 81, BS, 853 / SSA B8 and SSA/39. The color shall be
day light unless otherwise indicated.

The individual tube sizes shall have not less than the following lumens output after
100 hours life.

58W : 4700 lumens


36 : 2800 lumens
18W : 1100 lumens

ii). Provide clear / phosphor coated metal halide lamps in wattage indicated. Lamps
shall be self-extinguishing in the event of outer bulb breakage or puncture.

iii). Provide high-pressure sodium lamps in wattage indicated.

iv). Provide incandescent lamps in wattage and types as indicated, rated 220 volts 60 HZ
unless otherwise indicated. Lamps 200W and below shall have BC screw sockets
and 300W and larger GES screw type base.

z. Lighting Fixture Types:

i). Fixtures must comply with minimum requirements are stated herein. Review
architectural drawings and specifications to verify ceiling types, modules,
suspension systems appropriate to installation.

ii). Fixture Type: Appropriate lighting fixture shall be used for each room requirements.

aa. Electrical Poles and Standards

16.20 – Lighting System