Professional Documents
Culture Documents
ABB No.26 - Removed
ABB No.26 - Removed
—
9. Applications
9.3 Circuit breakers for protecting Consider that in DY800 “Secondary substations
24 kV prefabricated switchgear and controlgear in
lines and cables internal arc-proof metal enclosures with circuit
breaker (ICS)”, Public Utility Company ENEL
Distribution requires 16 A rated breaking current
for no-load cables.
Fig. 9.19: example of cable marking
9.3.1 Protection relays for cable lines
If line protection is performed by a circuit breaker
We will now calculate the charging current of a
with protection relay, bear in mind that line
medium voltage cable.
protection is adequate when protection against
A single-conductor cable type RG7H1M1 12/20kV
overloads is ensured and when polyphase short-
with 1·50 mm2 section will be used as an example.
circuit faults and single-phase earth faults can be
We will also assume that the operating voltage is
identified. This means that the protection is
17.5 kV at a frequency of 50 Hz and that the
extremely simple and generally limited to the
cable is 2 km in length.
following protection
functions:
The following formula will be applied:
• relay 49 thermal overload
1 U
XC = = protection;
ωC 3.I • relay 51 overcurrent
where: protection; 49
• relay 50 short-circuit 50/51
XC is the capacitive reactance of the cable, 51G
overcurrent protection;
C' is is the cable capacitance in µF/km • relè 87L line residual current
protection, applicable when
U is the line-to-line voltage of the network in V
selective protection is
I is the charging current of the cable in A required in a particular part
of the distribution network
Supposing that the capitance value provided by
(e.g.: in industrial
the manufacturer is, for the cable in question,
installations with ring
0.25 µF/km
networks); Fig. 9.20
T
W1 Q
R
F Q1 W2
M
3~
Fig. 9.23
104 TECHNICAL APPLICATION PAPERS NO. 26 – MEDIUM VOLTAGE SWITCHING DEVICES: TECHNOLOGIES AND APPLICATION
—
9. Applications
Using the formulas in chap. 4.2.3 and since the Protection against short-circuits is provided by the
reactances of cable W1, busbars W and the fuse are fuses. Always choose fuses with a higher rated
negligible: current than the motor, to prevent them from
tripping when the motor starts. This prevents
them from being used for protection against
overloads, a function for which fuses are generally
unsuitable.
This means that it is always necessary to use them
in conjunction with an inverse time relay for
protection against overloads. This protection must
The voltage at the terminals of the motor on start- be coordinated with the function provided by the
up is: fuse so that the curves of the relay and fuses
intersect in a point enabling:
1) protection of the motor against overcurrents
provided by indirect relays and which act on the
And the voltage drop is: contactor, as described further on;
2) protection of the circuit against fault currents
which exceed the breaking capacity of the
contactor, up to the maximum admissible fault
current. Protection provided by the fuse.
In this case, direct starting is possible since the
Proceed in the following way to assess the service
voltage drop is acceptable and the starting torque
conditions (see IEC 60644 “Specification for high-
higher than the breakaway torque of the load
voltage fuse-links for motor circuit applications”
(0.72>0.2).
and Technical Report IEC/TR 62655 “Tutorial and
application guide for high-voltage fuses”):
• Rated voltage Un. must be the same as the
9.4.2 How to choose fuses operating voltage of the installation or higher.
ABB CMF fuses conform to DIN 43625 Standards Also make sure that the insulation level of the
and are suitable for protecting motors. They must electrical system is higher than the value of the
be chosen by assessing the service conditions, i.e. switching over-voltage generated by the fuses
• supply voltage; which, for the fuses used by ABB, is well below
• starting current; the limit established by the IEC 60282-1 “High-
• starting time; voltage fuses-– Part 1: Current-limiting fuses”
• number of starts/hour; Standards illustrated in tab.19.
• full load current of motor;
• short circuit current of installation. Rated voltage Maximum switching
overvoltages
kV kV
3.6 12
7.2 23
12 38
17.5 55
24 75
36 112
Tab. 19
DISTRIBUTION SOLUTIONS 105
Un In K *) Minimum
I2 x t
Rated current of fuses [A]
*) The K factor refers to the mean value of the current 315RC280, fuse
Rated current of fuses [A]
with typical time-current characteristic for 315 A but with 280 A maximum
rated current.
Maximum motorstart
2x315
time 6 s Tab. 20
2x250
2x200
• Breaking capacity. The breaking capacity of the
315
fuse (or rated maximum breaking current) must
250 be higher than the short-circuit current of the
200 32 16 8 4 2 Number of starts per hour installation. In addition, the short-circuit current
limiting curves provided by the manufacturer
160 allow short-current limitation on the supply side
of fuses affected by faults to be ascertained.
100
This means that sizing the switchgear and
controlgear on the load side will be less
63 problematical.
200 1000 10000
Motor starting current [A]
Fig. 9.24
106 TECHNICAL APPLICATION PAPERS NO. 26 – MEDIUM VOLTAGE SWITCHING DEVICES: TECHNOLOGIES AND APPLICATION
—
9. Applications
160
100
63
For this reason, we will use the graph with start
200 1000 10000
time ta=15s and at inrush current Is= 6.5 · 140 = 910
Motor starting current [A]
A with 4 starts an hour, the result is a 315 A fuse.
Fig. 9.25
0.1
0.01
100 1000 10000 100000
Fig. 9.26
DISTRIBUTION SOLUTIONS 107
9.4.3 Example of coordination between fuse - in- 2. the switching device must be able to support
verse time relay for protection against the conditions defined by the combination of
overloads the two protections;
The need for an inverse time-delay or independent 3. the rated current of the fuse must be chosen so
time relay for protection against overloads can be that when it is in its service state, the fuse is
appreciated by observing the fusing curve of the able to continuously carry full-rate operating
315 A fuse. Prolonged overtemperature, beyond current without temperature rises;
the temperature specified for the insulation class, 4. the current corresponding to the point of
is harmful and seriously compromises the life of intersection between the curve of the fuse and
electric machines. that of the relay must be less than the breaking
Generally speaking, the following steps are taken capacity of the switching device;
to coordinate the two devices (indicated in 5. the minimum breaking current of the fuse
IEC 60644 and with reference to fig. 9.27): should not exceed the minimum take-over
1. when multiplied by the K factor, the time-pre- current indicated by the letter B;
arcing current characteristic of the fuse must 6. if an instantaneous protection is used,
be to the right of the motor start current; intersection point B moves to C. Attention must
therefore be paid to the fact that the switching
device could open to a current higher than its
breaking capacity;
7. the limited current of the fuse at the maximum
fault current of the system should not exceed
Time (s)
—
9. Applications
1
0 10 100
b c 6000 V
e Icc max ) 19.78 kA
10000 s
d
a
f
1000 s
100 s
Figure 9.29
10 s
1s
d'
100 ms
Figure 9.30
DISTRIBUTION SOLUTIONS 109
M M
In this case, the recommended relays are: REM 611, REM 615,
REM 620, REM 630 (fig. 9.32).
Fig. 9.32