HEAVY DUTY EARTH ELECTRODE INSPECTION HOUSING – PI244


TEST REPORT
Unique identification number: 185

PITTAS-DRAGNIS
LABORATORY TEST SERVICES
FOR LIGHTNING PROTECTION
AND EARTHING SYSTEMS

Page 1 of 13
REPORT IDENTIFICATION
Subject of Report: Heavy Duty Earth Electrode Inspection Housing – PI244

PITTAS-DRAGNIS LABORATORY TEST SERVICES


Test laboratory
services: FOR LIGHTNING PROTECTION AND EARTHING
SYSTEMS
Agias Marinas avenue 19
Address:
19400 Koropi, Athens-Greece

E-mail: info@pittas.gr Telephone: +30 210 9408595

Unique Id number: 185


Nbr of specimens: 185a, 185b, 185c, 185d, 185e, 185f

Supplier: HENG HARDWARE ENG. PTE LTD

Address of 7 Yishun Industrial Street 1, #01-48 Northspring Bizhub, Singapore, 768162


supplier: T: 6846 4111 F: 6846 4222 | W: www.heng.com.sg

Total pages of
13
report:
Applied standard: IEC 62561-5:2017

Load test: 03/05/2019


Date of tests:
Marking test: 03/05/2019
Protocol date of
15/05/2019
issue:
Responsible Name: Vasilios Antonados – El. Engineer
engineer for
conducting the
tests: Signature:

Name: Vasilios Pittas – Technical Director


Checked and
authorized by:
Signature:

VALIDITY CONDITIONS OF THE PRESENT DOCUMENT:

This type test report may not be reproduced other than in full, except with the prior written approval of
the issuing laboratory. This type test report only covers the samples submitted for test and does not
produce evidence of the quality for series production.

Page 2 of 13
Table of Contents

TABLE OF CONTENTS .............................................................................................. 3


1. Sample Description ........................................................................................... 4
2. Test procedure .................................................................................................. 5
2.1 Load test ................................................................................................... 5
2.2 Marking test .............................................................................................. 6
2.3 Electromagnetic compatibility (EMC) ........................................................ 6
3. Results and parameters recorded ..................................................................... 6
4. Conclusions....................................................................................................... 6
5. APPENDIX A: Test Report Approval ................................................................. 7
6. APPENDIX B: Tables – Photographs................................................................ 8

HENG – HD Inspection Housing – PI244


Protocol number: 185 Pittas - Dragnis Page 3 of 13
1. SAMPLE DESCRIPTION
Heng’s 'Polymer Type', heavy duty earth electrode inspection housing has been
manufactured from polymer to provide chemical resistance and UV protection. Suitable
for brick paved walkways or concrete installation.

Dimensions:
Length (L): 260 mm Length Lid (L1): 245 mm
Width (W): 260 mm Width Lid(W1): 245 mm
Height (H): 210 mm Height Lid(H1): 54 mm

Date of receipt of test samples: 17th April 2019.

Photograph of Component

The earth electrode inspection housing PI244 is classified for Heavy Duty usage,
for slow moving vehicular traffic. multi-axle, etc.
Manufacturer’s name, part number, as well as maximum load withstand force
were molded on the cover. The load withstand force mentioned on the cover was 6000
kg.
The manufacturer has provided all adequate information for proper installation
in a suitable and safe manner.

HENG – HD Inspection Housing – PI244


Protocol number: 185 Pittas - Dragnis Page 4 of 13
2. TEST PROCEDURE
All tests were carried out at PITTAS–DRAGNIS testing facilities at Koropi-Attica.
Tests were performed on two sets of three new lid specimens using two
housings.

One set, with one housing and three lid specimens 185a, 185b and 185c, was
tested with “pit set in concrete” installation. A second set with one housing and three lid
specimens 185d, 185e and 185f, was tested with “pit set in blocks or slabs on sand and
hardcore base” installation.

Specimens have been subjected to the following tests:

2.1 LOAD TEST


The item is applicable for heavy duty usage and was subjected to a force of 30kN
vertically applied through a circular steel plate with a 170 mm ± 0.5 mm diameter and
thickness of 20 mm ± 1 mm with a radius of both edges (top and bottom) of minimum 2
mm.
The centre of circular plate was positioned over the centre of the lid.
Force was applied gradually over 60s ± 10s and was maintained for 120s ± 5s.

Load test was also performed with manufacturer declared load force of 6000 kg.

HENG – HD Inspection Housing – PI244


Protocol number: 185 Pittas - Dragnis Page 5 of 13
2.2 MARKING TEST
The specimens were inspected to check if they are marked at least with:
a) manufacturer’s name or trademark
b) part number
c) classification
d) load withstand force

2.3 ELECTROMAGNETIC COMPATIBILITY (EMC)


Products covered by standard IEC 62561-5 are, in normal use, passive in
respect of electromagnetic influences (emission and immunity)

3. RESULTS AND PARAMETERS RECORDED

PASS/
Required passing
Test Specimen Results of tests FAIL
criteria
Status
Specimens should show no 185a, 185b, No disintegration nor crack, as
signs of disintegration nor well as no deformation was

PASS
crack. One minute after the 185c present, after examining the
Load test load has been removed, there specimens with normal and
shall be no permanent 185d, 185e, corrected vision without any
deformation exceeding 3mm 185f. additional magnification.
185a, 185b,
Manufacturer trademark, part

PASS
Markings made by moulding,
Marking 185c number and load withstand
pressing or engraving are not
test subjected to this test force were moulded on the
185d, 185e, specimens.
185f.
Electro-
N/A

magnetic Products covered by this standard are, in normal use, passive in respect
capability of electromagnetic influences (emission and immunity)
(EMC)

4. CONCLUSIONS
The tests were successful, and the results are in the range of limits set by the
IEC 62561-5:2017 standard.

Additionally, Heng’s Heavy Duty Earth Electrode Inspection Housing – PI244,


has been tested, installed in concrete and has withstood the 6000 kg applied force,
without breaking, as per manufacturer’s declaration.

HENG – HD Inspection Housing – PI244


Protocol number: 185 Pittas - Dragnis Page 6 of 13
5. APPENDIX A: TEST REPORT APPROVAL
The undersigned acknowledge they have reviewed the Heavy Duty Earth
Electrode Inspection Housing – PI244 Test Report and agree with the approach it
presents. Changes to this Test Report will be coordinated with and approved by the
undersigned or their designated representatives.

Signature: Date: 15/05/2019


Print Name: Mr. Vasilios Pittas
Electrical Engineering
Technical University UEL London
Member of Technical Chamber of Greece
151530
Position: Technical Director

HENG – HD Inspection Housing – PI244


Protocol number: 185 Pittas - Dragnis Page 7 of 13
6. APPENDIX B: TABLES – PHOTOGRAPHS

Photo2. Specimens 185a, 185b, 185c arrangements preparing for the Load test

Photo3. Specimens 185d, 185e, 185f arrangements preparing for the Load test

HENG – HD Inspection Housing – PI244


Protocol number: 185 Pittas - Dragnis Page 8 of 13
Photo4. Specimen 185a under Load test

Photo5. Specimen 185d under Load test

HENG – HD Inspection Housing – PI244


Protocol number: 185 Pittas - Dragnis Page 9 of 13
185a Applied force/time diagram for 30kN, concrete setup.

185b Applied force/time diagram for 30kN, concrete setup.

185c Applied force/time diagram for 30kN, concrete setup.

HENG – HD Inspection Housing – PI244


Protocol number: 185 Pittas - Dragnis Page 10 of 13
185a Applied force/time diagram for 6000kg, concrete setup.

185b Applied force/time diagram for 6000kg, concrete setup.

185c Applied force/time diagram for 6000kg, concrete setup.


HENG – HD Inspection Housing – PI244
Protocol number: 185 Pittas - Dragnis Page 11 of 13
185d Applied force/time diagram for 30kN, block setup.

185e Applied force/time diagram for 30kN, block setup.

185f Applied force/time diagram for 30kN, block setup.


HENG – HD Inspection Housing – PI244
Protocol number: 185 Pittas - Dragnis Page 12 of 13
Moulded manufacturer’s information on Specimen.

--- End of test report ---