SUB HEAD 'A' - EQUIPMENTS(PART II)


1 AIR HANDLING UNITS
Supplying of factory built Ceiling Suspended/ Floor Mounted double skin type air handling
units with mixing box and perforance shall be equivalent to AHRI/ Eurovent units
performance, made of 25/40 mm thick panels consisting of pre-plasticized GI casing of
thickness 0.8 mm outside layer and 0.6 mm thick plane GI sheet at inside layer with
polyurethane foam (PUF) insulation of density 40 + 2 kg/m3 factory injected between them
by injection moulding machine, complete with blower section with blower, 6/4 row deep
cooling coil section with aluminium finned copper tubes (tube thickness not less than 0.41
mm), Coils shall be AHRI tested, filter sections with 50 mm thick washable synthetic type Pre
filter (MERV-8) having efficiency 90% down to 10 micron, Fine filters (MERV-13) having
efficiency 99% down to 5 micron to be low pressure drop with MPD not exceeding 90 Pa,
Filters complying to ISO 16890 as applicable, TEFC drive motor (IE-3 or higher) at 415 ± 10%
volts, 50 Hz, 3 phase, A.C supply, drain connections with drain valve, stainless steel drain
pan, necessary vibration isolation arrangement etc, complete in all respect of following
capacities. The unit shall not be selected at end of the curve and should have allowance for
statics and flow adjustment of minimum 15%. The neoprene rubber pads to be provided
between AHU foundation and AHU selected based on AHU point loads, SIlicone coated
Flexible Duct connector meeting BS 476 Part 7 for Class 1 to use for conection between AHU
and duct to be provided . Refer New AHUS Schedule for further details:

1.1
All the AHU Should be with mixing box and Aluminum tight shutt-off damper
with aerofoil blades.
1.1.1 BM- 09 Nos 0 0 0
1.1.2 BM- 04 Nos 1 210152 210152 1 210152
1.1.8 BM- 01 Nos 1 233570 233570 0
1.1.12 BM- 02 A & B Nos 1 260981 260981 1 260981
1.1.13 BM-15 Nos 1 414132 414132
1.1.19 BM- 23 Nos 1 235965 235965 1 235965
1.1.20 BM- 16 Nos 1 109826 109826
1.1.21 BM- 22 Nos 1 250602 250602 1 250602
1.1.22 BM- 03 Nos 1 195516 195516
1.1.23 BM- 24 Nos 1 251578 251578 1 251578
1.1.24 BM- 11 A & B Nos 1 484076 484076 1 484076
1.1.35 GR- 13 & 14 Nos 1 274464 274464
1.1.37 GR- 19 Nos 1 192766 192766
1.1.46 1ST- 17 Nos 1 274464 274464
1.1.47 1ST- 16 Nos 1 238893 238893
1.1.48 1ST- 20 Nos 1 198177 198177
1.1.58 1ST- 15 Nos 1 239691 239691
1.1.60 2ND- 16 Nos 1 264972 264972 1 264972
1.1.61 2ND- 06 Nos 1 252820 252820 1 252820
1.1.62 2ND- 07 Nos 1 294689 294689 1 294689
1.1.63 2ND- 08 Nos 1 242441 242441
1.1.64 2ND- 25 Nos 1 266392 266392
1.1.65 2ND- 04 Nos 1 255392 255392 1 255392
1.1.66 2ND- 25 Nos 1 267811 267811 1 267811
1.1.67 2ND- 26 Nos 1 470238 470238
1.1.68 2ND- 26 Nos 1 330704 330704 1 330704
1.1.69 2ND- 18 Nos 1 112930 112930
1.1.71 2ND- 24 Nos 1 244925 244925 1 244925
1.1.80 3RD- 26 Nos 1 260005 260005 1 260005
1.1.81 3RD- 28 Nos 1 231175 231175
1.1.82 3RD- 27 Nos 1 235788 235788
1.1.83 3RD- 18 Nos 1 199152 199152
1.1.84 3RD- 09 & 10 Nos 1 283335 283335
1.1.85 3RD- 11 & 12 Nos 1 283335 283335
1.1.86 3RD- 13 & 14 Nos 1 283335 283335
1.1.87 3RD- 30 Nos 1 283335 283335
1.1.88 3RD- 22 Nos 1 197911 197911
1.1.98 5th - 01 Nos 1 97407 97407
1.1.99 CSU Nos 0 0 0
As Per PO This Bill
S. No. Item Description Unit Qty Rate Amount Rs Qty Amount Rs

0 0
2 TREATED FRESH UNITS 0 0
Supplying of factory built Floor Mounted double skin type air handling units with mixing
box and performance shall be equivalent to AHRI/ Eurovent units performance, made of 40
mm thick panels consisting of pre-plasticized GI casing of thickness 0.8 mm outside layer and
0.6 mm thick plane GI sheet at inside layer with polyurethane foam (PUF) insulation of
density 40 + 2 kg/m3 factory injected between them by injection moulding machine,
complete with blower section with blower, 8 row deep cooling coil section with aluminium
finned copper tubes (tube thickness not less than 0.41 mm), Coils shall be AHRI tested, filter
sections with 50 mm thick washable synthetic type Pre filter (MERV-8) having efficiency 90%
down to 10 micron as applicable, TEFC drive motor (IE-3 or higher) at 415 ± 10% volts, 50 Hz,
3 phase, A.C supply, drain connections with drain valve, stainless steel drain pan, necessary
vibration isolation arrangement etc, complete in all respect of following capacities. The unit
shall not be selected at end of the curve and should have allowance for statics and flow
adjustment of minimum 15%. The neoprene rubber pads to be provided between AHU
foundation and AHU selected based on AHU point loads, Silicone coated Flexible Duct
connector meeting BS 476 Part 7 for Class 1 to use for connection between AHU and duct to
be provided .. Refer TFAs Schedule for further details:

2.1 0 0
External Static Pressure as 35 mm of WG. 0 0
2.1.3 5-FM-TFA-02 Nos 1 351254 351254
2.1.4 5-FM-TFA-01 Nos 1 324203 324203
2.1.5 6-FM-TFA-01 Nos 1 362186 362186
0 0
2.2 FLOOR MOUNTED HEAT RECOVERY TREATED FRESH AIR UNIT 0 0
Supply of factory built Floor Mounted double skin type, thermal break profile TFA,
made of 40 mm thick panels consisting of pre plasticized G.I casing of thickness 0.8
outside and 0.8 inside layer with polyurethane foam (PUF) insulation of density 40 + 2
kg/m3 factory injected between them by injection moulding machine, complete with
blower section with blower EC of 25 mm WG external static pressure, 8 row deep cooling
coil section in 4+4 configuration with aluminium finned copper tubes( tube thickness not less
than 0.5mm), with suitable Heat pipe to achieve the desired humidity condition, filter
sections with 50 mm thick washable synthetic type Pre filter (MERV-8) having efficiency 90%
down to 10 micron low pressure drop, Fine filters (MERV-13) having efficiency 99% down to 5
micron to be low pressure drop with IPD not exceeding 90 Pa, Filters complying to ISO
16890, TEFC drive motor (IE-3) suitable for 415 ± 10% volts, 50Htz 3 phase, A.C supply, drain
connection, stainless steel (18G) drain pan with PUF insulation, Binder test points at the inlet
and outlet of coil, Descaling valve, auto air purge valve at the inlet and outlet of coils,
necessary vibration isolation arrangement, canvas connection etc., complete as per
specifications and of followings capacities. The neoprene rubber pads to be provided
between AHU foundation and AHU selected based on AHU point loads, Silicone coated
Flexible Duct connector meeting BS 476 Part 7 for Class 1 to use for connection between
AHU and duct to be provided .
The unit shall not be selected at end of the curve and should have allowance for statics and
flow adjustment of minimum 15%

0 0
Cross-flow heat Exchanger with minimum efficiency of 70% for efficient heat recovery
through exhaust air 0 0
The Unit shall be selected as per the following duty points.
Ambient Condition- 38 Deg. C DBT, 65% Relative Humidity.
Indoor Condition- 24 Deg. C & 50% Relative Humidity. 0 0
2.2.1 2500 CFM Fresh / 2500 CFM Exhaust Air for 2nd floor OTs Nos 1 857988 857988
2.2.2 3200 CFM Fresh / 3200 CFM Exhaust Air for 3rd floor OTS Nos 1 990480 990480
0 0
3 Fan Coil Unit 0 0
Supply of horizontal FAN COIL UNITS (2 PIPE SYSTEMS), blow thru type, each complete
with 3 / 4 rows deep Chilled Water Coil, one or more centrifugal fans, cleanable fabric filters,
main condensate extended SS drain pans to cover the valve set, internal tilted drain pan, RA
insulated plenum, necessary rubber grommet for vibration control as described in
specifications, casing, coil piping connections, through copper pipes, condensate drain
connections, wiring, control wiring in conduit upto thermostat boxes. Fan coil unit shall be
factory fitted with valve package comprising of dynamic balancing valve, pressure
independent balancing cum control valve with integrated 2 way motorized actuator in a
single body for modulating operation suitable for static pressure of 1600 kPa and actuator
shall be capable of withstanding 400 kPa shut off pressure, 24 V AC/ 230 AC incoming power
supply, ball valve with Y-strainer at inlet & Ball valve at outlet and necessary copper coil
piping connections. The actuator of modulating valve shall be provided with interface cards
to receive 0-10V or 4-20 mA signal from Digital Thermostat.

3.1 0 0
The actuator of the valve shall have necessary torque to overcome pressure
differential of 4 bars rating. All fan coil units shall be suitable for 220±6% volts, 50
cycles, single phase power supply. Fan coil units shall be of following refrigeration
capacities as listed. 0 0
Horizontal unit with cabinet (Ceiling Hung) 0 0
3.1.1 1 TR nominal capacity - 400 CFM Nos 0 0 0
3.1.2 1.5 TR nominal capacity - 600 CFM Nos 34 23617 802978
3.1.3 2 TR nominal capacity - 800 CFM Nos 27 25434 686710
3.1.4 2.5 TR nominal capacity - 1000 CFM Nos 0 0 0
3.1.5 3 TR nominal capacity - 1200 CFM Nos 0 0 0
3.1.6 3.5 TR nominal capacity - 1400 CFM Nos 1 42238 42238

Total Basic Amount 13840978 3864671