Professional Documents
Culture Documents
Pid 3822983
Pid 3822983
Abstract—Harmonic levels and their propagation in the power As the rectifier bridge opens and closes every half cycle, the
system are mainly determined by the network harmonic impedance. impedance changes twice per half cycle, which is not reflected
It is also an essential parameter for the calculation of harmonic by most of the available measurement methods. Fig. 1
current emission limits. Different methods for measuring the illustrates this characteristic by the current waveform of a
network harmonic impedance have been developed in the last simple compact fluorescent lamp (CFL). When the DC-link
decades, but all of them assume that the impedance is constant capacitor is not recharging (state 1) the simplified equivalent
within a cycle at fundamental frequency, which is true in case of circuit is open. During recharging (state 2), the capacitor is
passive elements only. As nowadays most of the equipment in low connected directly to the grid impacting the network harmonic
voltage grids contains power electronics including rectifier circuits,
impedance.
network harmonic impedance will vary within a half cycle of power
frequency. As more and more equipment operates with switching State 1
frequencies of several ten kHz, knowledge about the network State 1 State 2 State 1
V, I
harmonic impedance in the frequency range up to 150 kHz is also
of significant importance. Based on a review of existing
measurement methods, the paper presents an extended
State 2
measurement method, which is able to address both, above C
mentioned issues. The application of the method is illustrated by t
two example measurements in different low voltage grids.
Fig. 1. Current waveform of a CFL and simplified equivalent circuit
Keywords—impedance measurement; network harmonic The already significant and still increasing share of
impedance; nonlinear loads; harmonics; low voltage network electronic devices in low voltage grids raises the question, how
network harmonic impedance shall be interpreted and how it
I. INTRODUCTION
can be obtained. The issue of “momentary” impedance
Nonlinear devices emit harmonic currents, which cause variation is also addressed in [1], but with focus on input
harmonic voltages that are determined by the network impedance characteristic of different loads and their impact on
harmonic impedance. If these harmonic voltages exceed certain power line communication.
levels (e.g. the compatibility levels), other connected devices
might be disturbed. Therefore knowledge of network harmonic II. GENERAL MEASUREMENT PRINCIPLE
impedance is crucial for determining the level and spread of The network impedance (Zhn) at a node in a grid can be
harmonic emission in low voltage grids. calculated for a particular harmonic order (h) by injecting a
Virtually all common methods for calculating harmonic current Ih at the respective node and solving Ohm’s law
current emissions limits require accurate knowledge of network assuming Thevenin’s equivalent of the remaining network.
harmonic impedance. As it is often not known, only a Direct use of this method in measurement devices leads to
simplified representation by impedance line (short circuit
h
impedance multiplied by harmonic order) is applied. h I
V
h Z pre h
Strictly the network harmonic impedance is only defined in
n
V
h Z L
pre
presence of passive loads. Most of the simple electronic mass-
market devices have a rectifier circuit with a capacitor for Fig. 2. Pre-excitation state of the network
energy storage as DC link. During the recharging state the
rectifier bridge is open and the capacitor is directly connected h
to the network thus having significant impact on the effective
h Z
h I post h
network harmonic impedance at the connection point. The V n
V
h Z L I
h
A/D converter
h
Z
Computer
h n
V Vm I
h
Im
Shunt
Signal
conditioning
Fig. 5. Scheme of measurement system
channel for current measurement is always utilized with 50%
Window
Vm(t) DFT or more due to the automatic adaption of the input range to the
selection V m f
Z f measured current. Based on the datasheet specifications for
Window I m f both input channels, a worst-case uncertainty can be calculated:
Im(t) DFT
selection
VC 400V
CC Zero-crossing Z N 0,1% Z N 0, 025% h (2)
detection I
Fig. 7. Scheme of the impedance calculation method where Ih is the current injected in the network.
(VC: Voltage cycle based, CC: Current cycle based)
V. GRID MEASUREMENTS
CC windows In order to test the measurement system, several
400 2
1 2 3 4 5 6 7 8 9 10 measurements were carried out in two different grids.
200 1 A. Office building
Vm in V
I m in V
The first measurement has been performed in an office
0 0
building at a sub-distribution box, where the lighting (24
CFL’s) is connected. A current of 1 A was injected for
-200 -1 measurement. Fig. 9 shows magnitude of the network harmonic
impedance measured with the VC method at frequencies up to
-400 -2 50 kHz. The impedance has a distinct first resonance at approx.
0 90 180 270 360
V in ° 17 kHz and a second one at 45 kHz. Due to their simple
Fig. 8. Selected windows for the CC method, injected current with 500 Hz
rectifier circuits (cf. Fig. 1) the CFLs have significant impact
on the “momentary” network harmonic impedance measured
The principle processing scheme for both calculation with the CC method. Fig. 10 and Fig. 11 show different ways
methods is shown in Fig. 7. The VC method uses a window of of presentation. Both figures show the magnitude of the
10 voltage fundamental cycles. For the CC method each network harmonic impedance for one voltage fundamental
individual cycle of the injected current is used in order to cycle (0°.. 360°). Both resonances can be clearly seen as well,
obtain “momentary” impedance values within a single voltage but the “momentary” impedance characteristic further reveals
fundamental. Fig. 8 shows an example of the windows for the around the resonances a significant impedance drop at approx.
CC method and a frequency of the injected current of 500 Hz. 97°, where all rectifier bridges of the CFLs conducting and
In this case 10 windows and subsequently 10 impedance values
can be calculated for each cycle of the voltage fundamental. 6
The resolution of the method increases with frequency. For 5
Z N in
Z N in
Z N in
4
f in kHz
5
4 several locations within the network including the end of a
longer feeder. Due to the very low impedance a measurement
3 current of 7 A was chosen. The measurement results differ
2 CC Method
between the sites with highest impedances and most significant
1 VC Method resonances at the end of the longer feeder. Due to the limited
0 space therefore only the measurements for L1-N at the end of
0 45 90 135 180 225 270 315 360 the longer feeder are presented and discussed in detail in this
V in ° paper.
Fig. 12. Time characteristic of impedance at first resonance (17 kHz)
including uncertainty ranges Compared to Fig. 11 the color-map in Fig. 14 shows
significantly different resonance locations. Beside a sharp
therefore all DC-link capacitors are connected to the grid.
resonance at 530 Hz, a second, wider resonance is observed at
Fig. 12 exemplarily compares the time characteristic of 2.4 kHz. Furthermore the impedance state around the
network harmonic impedance at the first resonance frequency maximum/minimum of voltage fundamental lasts longer than
(17 kHz) calculated by the VC method and the CC method. in the office building. This results in a larger difference
The VC method reflects some kind of mean value of the between the “momentary” impedance around 0° and the results
“momentary” impedance within the considered fundamental of the VC method (Fig. 15 and Fig. 16). This can be explained
cycle. At the voltage maximum/minimum (90°/270°) the by the use of more diverse equipment with different circuit
impedance drops to a minimum of about 50 % compared to the topologies, which have different firing angles and conducting
impedance close to the zero crossing of voltage fundamental times of the rectifier bridges. Detailed discussions about
(0°/180°). As this variation is exclusively caused by the different circuit topologies can be found e.g. in [12]. The
nonlinear equipment with line-commutating topology, it could synchronicity of the CFLs in the office building is much higher
be e.g. used as indicator for the penetration level of a network and subsequently the duration of the impedance stay is shorter.
with this type of equipment.
Fig. 13 presents the network harmonic impedance based on 10 0.6
CC method for the two extreme cases at 0° and 97° together
0.5
7 CC Method, 0° 8
6 CC Method, 97° 0.4
Z N in
Z N in
f in kHz
5 VC Method 6
4 0.3
3 4
0.2
2
1 2 0.1
0
0 10 20 30 40 50 0 0
f in kHz 0 45 90 135 180 225 270 315 360
V in °
Fig. 13. Magnitude and phase angle of network harmonic impedance
measured according to the different methods Fig. 14. Measurement results with CC method (color-map)
troubleshoot e.g. problems with signal damping in mains-
0.6
signaling applications. On the other hand the significant
0.5 differences raise the question, how network harmonic
Z N in
0.4 ACKNOWLEDGMENT
We wish to thank NRM Netzdienste Rhein-Main GmbH for
0.3
supporting parts of the project.
0.2 CC Method, 0°
REFERENCES
0.1 CC Method, 90°
VC Method [1] R. Jahn, D. Lemmens, S. Uytterhoeven, W. Foubert, “PLC noise and
0 impedance measurements on loads and in the distibution grid”, 22nd
0 2 4 6 8 10 International Conference on Electricity Distribution (CIRED),
f in kHz Stockholm, June 2013.
Fig. 16. Magnitude and phase angle of network harmonic impedance [2] M. J. Bridgeman, R. E. Morrison, S. B. Tenakoon, “Measurement of
measured according to the different methods harmonic impedance on a LV system utilising power capacitor switching
Furthermore Fig. 15 shows that the impedance variation is and consequent predictions of capacitor induced harmonic distortion”,
8th International Conference on Harmonics and Quality of Power
with about seven times significantly higher than for the office (ICHQP), Athens, Greece, October 1998.
building with two times. Both examples show that the [3] C. Xie, S.B. Tennakoon, R. Langella, D. Gallo, A. Testa, A. Wixon,
variability within the voltage fundamental cycle caused by “Harmonic Impedance Measurement of 25KV Single Phase AC Supply
nonlinear electronic equipment can significantly vary in terms Systems”, Ninth International Conference on Harmonics and Quality of
of max/min ratio as well as duration of the change. Power (ICHQP), Orlando, October 2000.
[4] W. Wang, E. E. Nino, W. Xu, “Harmonic Impedance Measurement
VI. SUMMARY using a Thyristor-Controlled ShortCircuit”, IET publication on
Generation, Transmission, Distribution,1,(5),pp.707-713, 2007.
The knowledge of the network harmonic impedance is an
[5] Staroszczyk, Z., "A method for real-time, wide-band identification of the
important base for the assessment of harmonic levels in low source impedance in power systems," IEEE Transactions on
voltage grids. Many measurement methods have been Instrumentation and Measurement, vol.54, no.1, pp.377-385, Feb. 2005.
developed, but always based on the analysis of one or more [6] G. Moreau, H. H. Le, G. Croteau, G. Beaulieu, E. Portales,
cycles of voltage fundamental. These methods do not “Measurement System for Harmonic Impedance of the Network and
adequately address the impact of electronic equipment, which Validation Steps”, Cigre/IEEE PES International Symposium, 2003.
can change the network harmonic impedance multiple times [7] M. Jordan, H. Langkowski, T. Do Thanh, D. Schulz, “Frequency
within the voltage fundamental cycle due to the Dependent Grid-Impedance Determination with Pulse-Width-
Modulation-Signals”, IEEE 7th International Conference-Workshop
conduction/non-conduction of the rectifier bridges. This paper Compatibility and Power Electronics (CPE), Tallinn, Estonia, June 2011
presents a measurement system based on single sweep method, [8] F. Zavoda, “Measurement of the harmonic impedance of LV distribution
which is able to identify variations of the “momentary” supply system (120/240V)”, 19th International Conference on Electricity
network harmonic impedance within the cycle of voltage Distribution (CIRED), Vienna, May 2007.
fundamental and which is applicable for frequencies up to [9] J. Xie, Y. X. Feng, N. Krap, “Network Impedance Measurement for
150 kHz. Three-phase High-voltage Power Systems”, Asia-Pacific Power and
Energy Engineering Conference (APPEEC), Chengdu, March 2010.
First measurements in an office building and a residential [10] D. Roggo, L. Merendaz, D. Furrer, “On-line 2 to 150 kHz network
grid have confirmed that the nonlinear equipment has a imoedance meter”, 22nd International Conference on Electricity
significant impact on the “momentary” impedance, particular Distribution (CIRED), Stockholm, June 2013.
within resonances. Differences of up to 80% have been [11] R. Gretsch, M. Neubauer, “System impedance and background noise in
observed between the minimum of “momentary” impedance the frequency range 2kHz to 9kHz ”, European Transaction on Electrical
Power, vol 8, issue 5, pp. 369-374, September,1998.
and the impedance obtained by the classical method. This
information is useful to develop improved models for harmonic [12] A. M. Blanco, S. Yanchenko,J. Meyer, P. Schegner, “Impact of Supply
Voltage Distortion on the Harmonic Emission of Electronic Household
network simulations (estimation of equivalent capacity of Equipment”, VII Simposio Internacional sobre Calidad de la Energia
connected customers for resonance studies), to quantify the Electrica (SICEL), Medellin, November 2013.
ratio of penetration of nonlinear devices in a network or to