TEST CERTIFICATE OF TRANSFORMER AKSHAR ELECINFRA PVT. LTD.

Client M/S. RELIANCE INDUSTRIES LTD., ASOJ Tested On 25/01/2022


Plant MAIN FIRE SUBSTATION Tested By MNS
Location 800 KVA TRANSORMER Comp. Code

1.0 NAME PLATE DETAILS :


Make Voltamp Transformers Ltd Vector Group Dyn11
Serial No. 47917/1 Tap Changer OLTC
Rating in KVA 800 kVA No. Of Taps 17
Voltage Ratio 11 kV/433 V Normal Tap 9
Type of Cooling ONAN % Impedance(Z) 5.36%

2.0 INSULATION RESISTANCE (IR) & POLARISATION INDEX(PI) TEST :


Range : 0 ‐ 5 T‐
APPLIED VOLTAGE IR (1 min) IR (10 min) PI
HV‐EARTH 5 KV 16.8 GΩ 29.0 GΩ 1.72
LV‐EARTH 500 V 22.7 GΩ 50.8 GΩ 2.23
HV‐LV 5 KV 9.76 GΩ 20.4 GΩ 2.09
3.0 VOLTAGE RATIO & TAP CONTINUITY TEST :
Tap Applied Measured voltage on LV side
Position Voltage r‐y y‐b b‐r r‐n y‐n b‐n Tap Continuity
1 R‐Y 418 15.17 15.16 15.19 8.76 8.72 8.76 OK
2 Y‐B 420 15.34 15.33 15.33 8.85 8.85 8.87 OK
3 B‐R 420 15.47 15.47 15.46 8.93 8.93 8.93 OK
4 15.63 15.60 15.61 9.02 9.02 9.02 OK
5 15.78 15.78 15.77 9.11 9.11 9.09 OK
6 15.98 15.98 15.98 9.23 9.24 9.22 OK
7 16.18 16.20 16.15 9.33 9.35 9.33 OK
8 16.35 16.46 16.36 9.42 9.49 9.49 OK
9 16.52 16.62 16.54 9.51 9.56 9.58 OK
10 16.73 16.80 16.75 9.64 9.68 9.69 OK
11 16.95 17.06 16.98 9.78 9.83 9.83 OK

Date 25/01/2022 Date 25/01/2022 Date 28/01/2022


Witness by DILIP PARMAR Tested by MRUGESH Prepared by NOEL
Sign Sign Sign
AKSHAR ELECINFRA PVT. LTD.
12 17.16 17.24 17.18 9.90 9.94 9.95
13 17.40 17.40 17.38 10.03 10.06 10.06
14 17.59 17.68 17.62 10.14 10.18 10.20
15 17.82 17.93 17.87 10.29 10.32 10.33
16 18.09 18.18 18.07 10.41 10.48 10.42
17 18.33 18.44 18.37 10.58 10.65 10.65

4.0 MAGNETIC BALANCE TEST :


Supply Voltage Voltage measured (HV side) Voltage measured (LV side)
(HV Side) R‐Y Y‐B B‐R r‐n y‐n b‐n
R – Y (B –OFF) 418 313 105.3 9.49 7.13 2.37
Y – B (R‐ OFF) 278 422 143.3 6.32 9.58 3.24
B – R (Y‐ OFF) 162.9 258 421 3.70 5.85 9.57

5.0 VECTOR GROUP TEST : Short 1R‐2R and apply 440V on HT side.
2r 1. 1R1Y = 1R2n + 1Y2n.
421 = 9.59 + 412
1R 2. 1Y2b = 1Y2y.
2 2n 408 = 408
2y 3. 1B2b < 1B2y
2b
409 < 432

1B 1Y

6.0 Winding Resistance Measurement:


HV SIDE (Measured in Ω)
Tap Position R Y B
01 1.387 1.382 1.385
09 1.205 1.198 1.203
17 0.987 0.989 0.991

Date 25/01/2022 Date 25/01/2022 Date 28/01/2022


Witness by DILIP PARMAR Tested by MRUGESH Prepared by NOEL
Sign Sign Sign
AKSHAR ELECINFRA PVT. LTD.
7.0 Magnetic Current Test :
HV SIDE (Measured in mA)
Tap Position R Y B
01 7.1 4.5 6.6
02 7.2 4.6 6.7
03 7.3 4.7 6.8
04 7.5 4.8 6.9
05 7.6 4.9 7.0
06 7.8 5.0 7.2
07 7.9 5.1 7.3
08 8.1 5.2 7.5
09 9.7 5.8 9.1
10 9.9 5.9 9.3
11 10.2 6.1 9.6
12 10.4 6.2 9.8
13 10.7 6.4 10.0
14 11.0 6.5 10.3
15 11.2 6.7 10.5
16 11.5 6.9 10.9
17 11.9 7.2 11.2

8.0 CONFORMITY TESTS :


1 Visual External damage to any part of the transformer OK
2 Colour of silica gel / oil level in bottom seal/Leakage if any OK
3 Proper Connections of body and neutral earthling OK
4 Buchholz relay test for alarm/trip contact float operations OK
5 Winding alarm/trip contact operations OK
6 MOG float switch contact operation OK
7 Local / remote operations of OLTC OK
8 Cooling System OK

9.0 REMARKS : TESTED OK.

Date 25/01/2022 Date 25/01/2022 Date 28/01/2022


Witness by DILIP PARMAR Tested by MRUGESH Prepared by NOEL
Sign Sign Sign
AKSHAR ELECINFRA PVT. LTD.