Professional Documents
Culture Documents
CRAC Unit - DBAireIII - R410A - 50-60Hz - MM0706B-0922 - Lo - 0
CRAC Unit - DBAireIII - R410A - 50-60Hz - MM0706B-0922 - Lo - 0
CAUTION
¾ The manual is to be retained for the entire service life of the unit
¾ Read the manual carefully before carrying out any operation on the unit
¾ The control is used exclusively for the purpose for which it is intended. Incorrect use of the control shall
release the manufacturer from any liability
This manual is prepared to enable the user to carry out only the operation that can be made with the panels
closed. The panel key which is supplied with the unit must be kept by the person responsible for maintenance.
For identification of the unit (model and serial no.) in case of the necessity for assistance or spare parts, locate
the identification label on the outside of the unit.
TABLE OF CONTENTS
R410A refrigerant is a high-pressure refrigerant. It requires careful attention to proper storage and handling
procedures. Use on manifold gauge sets designed for use with R410A refrigerant. Use only refrigerant recovery
units and cylinders designed for high pressure refrigerants. R410A must only be charged in the liquid state.
TABLE OF CONTENS
Page No
GENERAL INFORMATION
Nomenclature .............................................................................................................................................................................................. 3
Performance and Technical Data ................................................................................................................................................................. 4
Dual Coils Option......................................................................................................................................................................................... 6
Electrical Data ............................................................................................................................................................................................. 7
Dimensional and Weight Data...................................................................................................................................................................... 9
Remote Air-Cooled Condensers ................................................................................................................................................................ 10
INSTALLATION
Inspection .................................................................................................................................................................................................. 11
Transport ................................................................................................................................................................................................... 11
Operating Limits ........................................................................................................................................................................................ 11
Locating the Unit and Installation Clearance .............................................................................................................................................. 11
Dismantling Unit Frame ............................................................................................................................................................................. 12
Removing Fixed Panels ............................................................................................................................................................................. 13
Removing Filters ....................................................................................................................................................................................... 14
Air-Cooled Piping....................................................................................................................................................................................... 15
Pipe Supports ............................................................................................................................................................................................ 15
Field Provided Piping and Wiring ............................................................................................................................................................... 15
Long Refrigeration Piping .......................................................................................................................................................................... 16
Leak Test (System Pressure Test) ............................................................................................................................................................. 17
Vacuum Test and Dehydration................................................................................................................................................................... 18
Replacement of Driers or Sight Glass (R410A Only) .................................................................................................................................. 18
Charging ................................................................................................................................................................................................... 18
Compressor Lubrication (R410A) ............................................................................................................................................................... 19
System Check for Overcharging ................................................................................................................................................................ 19
Water Connections .................................................................................................................................................................................... 19
Humidifier (Optional) .................................................................................................................................................................................. 20
Operation .................................................................................................................................................................................................. 21
Modulating Hot Gas Reheat For DX System .............................................................................................................................................. 21
Remote Air Cooled Condenser (DBRC) ..................................................................................................................................................... 22
Dimensional Clearance - Remote Air Cooled Condenser (DBRC) .............................................................................................................. 23
OPERATION
Electrical Connections ............................................................................................................................................................................... 24
Check for Correct Phasing ......................................................................................................................................................................... 24
Under-Floor Water-Detection Probe (Optional)........................................................................................................................................... 24
DB5+ Vision 2020i Controller ..................................................................................................................................................................... 24
DBGX 4.3” Color Touch Screen Terminal .................................................................................................................................................. 25
Terminal User Interface ............................................................................................................................................................................. 26
DBLAN Address Configuration................................................................................................................................................................... 30
Piping Schematic ....................................................................................................................................................................................... 33
MAINTENANCE INSTRUCTIONS
Maintenance.............................................................................................................................................................................................. 34
Maintenance And Cleaning Procedures For DB/ Heresite Coated Coils ..................................................................................................... 35
Troubleshooting Chart ............................................................................................................................................................................... 37
Sample Log Sheet ..................................................................................................................................................................................... 39
-2-
Product that perform…By people who care
GENERAL INFORMATION
NOMENCLATURE
INDOOR UNIT
String 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22
D B A D 0 3 V A U D N H G N K P S E N N 1 Q
11 FUTURE OPTION
15 PANEL INSULATION OPTIONS
N = Not Selected
K = Double Skin Panel
N = Not Selected. Single Skin Closed Cell Polyethylene
12 HUMIDIFIER OPTION
(PE) Foam Insulation Panel
H = Humidifier (water conductivity 75 to 350μS/cm)***
N = Not Selected
***Please consult factory for other water conductivity. 14 EVAPORATOR CONTROL OPTIONS
N = Standard
13 HOT GAS BYPASS OPTION S = Standard + Liquid Line Solenoid Valve
G = Hot Gas Bypass
N = Not Selected
Outdoor Unit Nomenclature (for Air Cooled DX-System/ Dual Coils System/ DX-System with Hot Gas Reheat)
String 1 2 3 4 5 6 7 8 9 10 11 12 13
D B R C 0 4 G A U A L 1 Q
-3-
Product that perform…By people who care
GENERAL INFORMATION
Sensible Heat Ratio (SHR) 0.92 0.93 0.95 0.94 0.89 0.88 0.95 0.89 0.88 0.91 0.94
Total Cooling MBH 35.9 55.3 108.1 119.6 164.4 188.2 227.9 243.9 286.2 335.7 353.5
Capacity (kW) (10.5) (16.2) (31.7) (35.1) (48.2) (55.2) (66.8) (71.5) (83.9) (98.4) (103.6)
Return Air
72F/60F/50% RH Sensible Cooling MBH 33.2 51.2 101.5 109.9 139.5 171.6 218.0 224.9 262.6 294.1 346.6
(22C/16C/50% RH) Capacity (kW) (9.7) (15.0) (29.8) (32.2) (40.9) (50.3) (63.9) (65.9) (77.0) (86.2) (101.6)
Sensible Heat Ratio (SHR) 0.92 0.93 0.94 0.92 0.85 0.91 0.96 0.92 0.92 0.88 0.98
Return Air Total Cooling MBH 34.6 54.0 104.4 117.5 167.4 180.7 221.5 234.3 275.2 341.4 346.6
75F/52F Dew Point Capacity (kW) (10.1) (15.8) (30.6) (34.4) (49.1) (53.0) (64.9) (68.7) (80.7) (100.1) (101.6)
(24C/11C Dew Point)
Class 1 AHRI 1360 Sensible Cooling MBH 33.4 52.3 102.4 117.5 150.6 175.1 221.5 226.6 264.3 318.4 346.6
rating condition Capacity (kW) (9.8) (15.3) (30.0) (34.4) (44.1) (51.3) (64.9) (66.4) (77.5) (93.3) (101.6)
Number of Compressor(s) 1 1 1 1 2 2 2 2 2 2 2
Fan Qty 1 1 1 2 2 2 2 2 3 3 3
CFM 1,500 2,500 5,000 6,000 8,000 10,000 11,000 11,000 13,000 15,000 18,000
Air Volume
EC FAN (m3/h) (2,548) (4,247) (8.495) (10,194) (13,592) (16,989) (18,688) (18,688) (22,086) (25,485) (30,582)
(INDOOR) in H2O 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5
ESP
(Pa) (374) (374) (374) (374) (374) (374) (374) (374) (374) (374) (374)
Fan Size OD mm 355 355 500 355 355 500 500 500 500 500 500
ft2 5.6 5.6 12.2 12.2 23.9 23.9 23.9 23.9 23.9 33.1 33.1
Face Area 2
(m ) (0.5) (0.5) (1.1) (1.1) (2.2) (2.2) (2.2) (2.2) (2.2) (3.1) (3.1)
FPM 270 450 409 491 335 419 461 461 544 453 544
COIL (DX) Face Velocity
(m/s) (1.4) (2.3) (2.1) (2.5) (1.7) (2.1) (2.3) (2.3) (2.8) (2.2) (2.8)
Condensate Drain
In 7/8 7/8 7/8 7/8 7/8 7/8 7/8 7/8 7/8 7/8 7/8
O.D
20" x 20" x 2" Qty 2 2 N/A N/A N/A N/A N/A N/A N/A N/A N/A
FILTERS
(ASHRAE 52.2 MERV 20" x 20" x 4" Qty N/A N/A 4 4 6 6 6 6 6 4 4
7)
20" x 25" x 4" Qty N/A N/A N/A N/A 2 2 2 2 2 6 6
3-Stages MBH 20.5 20.5 41.0 41.0 61.4 61.4 61.4 61.4 61.4 61.4 61.4
REHEAT (Electric)
(rated at 415V) (kW) (6.0) (6.0) (12.0) (12.0) (18.0) (18.0) (18.0) (18.0) (18.0) (18.0) (18.0)
lbs/hr 17 17 17 17 33 33 33 33 33 33 33
STEAM HUMIDIFIER Capacity (max.) (kg/hr) (8.0) (8.0) (8.0) (8.0) (15.0) (15.0) (15.0) (15.0) (15.0) (15.0) (15.0)
(OPTIONAL)
Power Input (max.) kW 6.0 6.0 6.0 6.0 11.3 11.3 11.3 11.3 11.3 11.3 11.3
-4-
Product that perform…By people who care
GENERAL INFORMATION
CHILLED WATER SYSTEM @ WATER SUPPLY/ RETURN 7°C/ 12°C (44.6°F/ 53.6°F)
DBCD/U DBCD/U DBCD/U DBCD/U DBCD/U DBCD/U DBCD/U DBCD/U DBCD/U DBCD/U DBCD/U
Model
03 05 09 11 14 16 19 22 26 29 32
Total Cooling MBH 43.0 67.9 132.3 162.0 205.3 240.5 280.9 319.0 360.4 444.1 507.4
Capacity (kW) (12.6) (19.9) (38.8) (47.5) (60.2) (70.5) (82.3) (93.5) (105.6) (130.2) (148.7)
Sensible Cooling MBH 37.1 61.0 118.6 145.3 184.9 221.9 255.5 277.1 318.1 385.7 448.3
Capacity (kW) (10.9) (17.9) (34.8) (42.6) (54.2) (65.0) (74.9) (81.2) (93.2) (113.1) (131.4)
Return Air
75F/62.5F/50% RH Sensible Heat Ratio (SHR) 0.86 0.90 0.90 0.90 0.90 0.92 0.91 0.87 0.88 0.87 0.88
(24C/17C/50% RH)
GPM 9.9 15.6 29.7 37.2 47.1 55.1 64.4 73.2 82.7 98.8 112.9
Water Flow Rate
(m3/hr) (2.2) (3.5) (6.7) (8.4) (10.7) (12.5) (14.6) (16.6) (18.8) (22.4) (25.6)
Water Pressure PSI 5.5 2.7 10.1 4.1 2.3 3.0 2.7 6.5 8.1 6.9 8.7
Drop (kPa) (38.0) (18.8) (69.6) (28.4) (15.5) (20.6) (18.5) (45.1) (55.6) (47.5) (60.1)
Total Cooling MBH 64.1 98.8 188.4 235.2 300.5 351.2 409.2 461.3 520.7 602.1 687.4
Capacity (kW) (18.8) (29.0) (55.2) (68.9) (88.1) (102.9) (119.9) (135.2) (152.6) (176.5) (201.5)
Sensible Cooling MBH 42.9 69.0 130.8 164.7 210.5 251.3 289.2 314.6 360.0 423.5 490.8
Return Air Capacity (kW) (12.6) (20.2) (38.3) (48.3) (61.7) (73.7) (84.8) (92.2) (105.5) (124.1) (143.8)
80°F/66.6°F/ 50%
RH Sensible Heat Ratio (SHR) 0.67 0.70 0.69 0.70 0.70 0.72 0.71 0.68 0.69 0.70 0.71
(26.6°C/19.2°C/
50% RH) GPM 14.3 22.0 41.9 52.3 66.8 78.1 91 102.6 115.8 134.0 152.9
Water Flow Rate
(m3/hr) (3.2) (5.0) (9.5) (11.9) (15.2) (17.7) (20.7) (23.3) (26.3) (30.4) (34.7)
Water Pressure PSI 10.4 4.9 18.3 7.5 4.2 5.5 4.9 11.7 14.5 11.8 14.9
Drop (kPa) (71.4) (34.1) (125.8) (51.7) (28.7) (37.7) (34.1) (81.0) (99.8) (81.3) (102.8)
Fan Qty 1 1 1 2 2 2 2 2 3 3 4
CFM 1,500 2,500 5,000 6,000 8,000 10,000 11,000 11,000 13,000 15,000 18,000
Air Volume
EC FAN (m3/h) (2,548) (4,247) (8.495) (10,194) (13,592) (16,989) (18,688) (18,688) (22,086) (25,485) (30,582)
(INDOOR)
External Static in H2O 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5
Pressure (ESP) (Pa) (374) (374) (374) (374) (374) (374) (374) (374) (374) (374) (374)
Fan Size OD mm 355 355 500 355 355 500 500 500 500 500 500
ft2 5.6 5.6 12.2 12.2 23.9 23.9 23.9 23.9 23.9 33.1 33.1
Face Area
(m2) (0.5) (0.5) (1.1) (1.1) (2.2) (2.2) (2.2) (2.2) (2.2) (3.1) (3.1)
Coil FPM 270 450 409 491 335 419 461 461 544 453 544
(Chilled Water) Face Velocity
(m/s) (1.4) (2.3) (2.1) (2.5) (1.7) (2.1) (2.3) (2.3) (2.8) (2.2) (2.8)
Condensate Drain
Inch 7/8 7/8 7/8 7/8 7/8 7/8 7/8 7/8 7/8 7/8 7/8
O.D
DN,
25 25 25 40 40 40 40 40 50 50 50
mm
Chilled Water 3-Way Modulating
Control Valve, Size
Kv,
10 10 10 16 16 16 16 16 25 25 25
m³/h
20" x 20" x 2" Qty 2 2 N/A N/A N/A N/A N/A N/A N/A N/A N/A
Filters
(ASHRAE 52.2 20" x 20" x 4" Qty N/A N/A 4 4 6 6 6 6 6 4 4
MERV 7)
20" x 25" x 4" Qty N/A N/A N/A N/A 2 2 2 2 2 6 6
Reheat 3-Stages MBH 20.5 20.5 41.0 41.0 61.4 61.4 61.4 61.4 61.4 61.4 61.4
(Electric) (rated at 415V) (kW) (6.0) (6.0) (12.0) (12.0) (18.0) (18.0) (18.0) (18.0) (18.0) (18.0) (18.0)
lbs/hr 17 17 17 17 33 33 33 33 33 33 33
Capacity (max.)
Steam Humidifier (kg/hr) (8.0) (8.0) (8.0) (8.0) (15.0) (15.0) (15.0) (15.0) (15.0) (15.0) (15.0)
(Optional)
Power Input (max.) kW 6.0 6.0 6.0 6.0 11.3 11.3 11.3 11.3 11.3 11.3 11.3
-5-
Product that perform…By people who care
GENERAL INFORMATION
CONDENSER SELECTION
Selections are to be based on standard airflow rate and return air temperature of 24°C / 17°C (75°F / 62.5°F) or
lesser at sea level.
DX-System DBAD/U 03 DBAD/U 05 DBAD/U 09 DBAD/U 11 DBAD/U 14 DBAD/U 16
Dual Coils
Model DBDD/U 03 DBDD/U 05 DBDD/U 09 DBDD/U 11 DBDD/U 14 DBDD/U 16
System
DX-System with
DBRD/U 03 DBRD/U 05 DBRD/U 09 DBRD/U 11 DBRD/U 14 DBRD/U 16
Hot Gas Reheat
Total Heat Rejection MBH 46 73 151 171 220 262
(Nominal) (kW) (14) (21) (44) (50) (64) (77)
35°C (95°F) Ambient - DBRC04 DBRC06 DBRC10 DBRC13 DBRC17 DBRC20
37.8°C (100°F) Ambient - DBRC04 DBRC06 DBRC13 DBRC17 DBRC20 DBRC26
40.6°C (105°F) Ambient - DBRC06 DBRC08 DBRC17 DBRC20 DBRC26 DBRC26
43°C (110°F) Ambient See Note 1 DBRC06 DBRC11 DBRC20 DBRC26 DBRC34 DBRC40
46°C (115°F) Ambient See Note 1 DBRC11 DBRC17 DBRC34 DBRC40 DBRC44 DBRC30 x 2
49°C (120°F) Ambient See Note 2 DBRC11 DBRC20 DBRC34 DBRC40 DBRC44 DBRC30 x 2
52°C (125°F) Ambient See Note 3 DBRC13 DBRC26 DBRC40 DBRC44 DBRC26 x 2 DBRC30 x 2
Dual Coils
Model DBDD/U 19 DBDD/U 22 DBDD/U 26 DBDD/U 29 DBDD/U 32
System
DX-System with
DBRD/U 19 DBRD/U 22 DBRD/U 26 DBRD/U 29 DBRD/U 32
Hot Gas Reheat
Total Heat Rejection MBH 293 332 388 445 465
(Nominal) (kW) (86) (97) (114) (130) (136)
35°C (95°F) Ambient - DBRC20 DBRC26 DBRC30 DBRC34 DBRC34
37.8°C (100°F) Ambient - DBRC26 DBRC30 DBRC30 DBRC40 DBRC40
40.6°C (105°F) Ambient - DBRC34 DBRC34 DBRC34 DBRC44 DBRC44
43°C (110°F) Ambient See Note 1 DBRC44 DBRC44 DBRC44 DBRC40 x 2 DBRC40 x 2
46°C (115°F) Ambient See Note 1 DBRC30 x 2 DBRC40 x 2 DBRC40 x 2 DBRC40 x 2 DBRC40 x 2
49°C (120°F) Ambient See Note 2 DBRC34 x 2 DBRC40 x 2 DBRC44 x 2 DBRC44 x 2 DBRC44 x 2
52°C (125°F) Ambient See Note 3 DBRC34 x 2 DBRC44 x 2 DBRC44 x 2 DBRC44 x 2 DBRC44 x 2
-6-
Product that perform…By people who care
GENERAL INFORMATION
ELECTRICAL DATA
AIR COOLED DX & CHILLED WATER SYSTEMS
1.) STANDARD - COOLING & ELECTRIC HEATERS
o o o o o o
At 35 C (95 F) ambient; Return Air at 24 C/17 C/50 %RH (75 F/62.5 F/50 %RH)
Model DBAD/U 03 DBAD/U 05 DBAD/U 09 DBAD/U 11 DBAD/U 14 DBAD/U 16
Power Supply RLA MCA MFS RLA MCA MFS RLA MCA MFS RLA MCA MFS RLA MCA MFS RLA MCA MFS
380-415V/ 3Ph/ 50Hz 13.8 15 20 17.1 19 25 32.5 35.1 50 39.1 43 60 59.2 62 80 60.8 65 80
380V/ 3Ph/ 60Hz 13.8 15 20 17.1 19 25 32.5 35 50 39.1 43 60 59.1 62 80 61.2 66 80
460V/ 3Ph/ 60Hz 12.3 13 20 15.6 17 25 29.3 32 45 35.9 40 60 53.7 56 70 54.9 59 80
Power Supply RLA MCA MFS RLA MCA MFS RLA MCA MFS RLA MCA MFS RLA MCA MFS
380-415V/ 3Ph/ 50Hz 66.4 70 90 71.1 76 100 75.1 81 125 89.5 97 150 103.8 111 150
380V/ 3Ph/ 60Hz 64.9 69 80 73.5 79 100 78.5 85 110 94.0 102 150 103 111 150
460V/ 3Ph/ 60Hz 58.8 63 80 67 72 100 72 78 110 81.1 88 125 93.6 101 150
o o o o
Return Air at 24 C/17 C/50 %RH (75 F/62.5 F/50 %RH)
Model DBCD/U 03 DBCD/U 05 DBCD/U 09 DBCD/U 11 DBCD/U 14 DBCD/U 16
Power Supply RLA MCA MFS RLA MCA MFS RLA MCA MFS RLA MCA MFS RLA MCA MFS RLA MCA MFS
Power Supply RLA MCA MFS RLA MCA MFS RLA MCA MFS RLA MCA MFS RLA MCA MFS
Power Supply RLA MCA MFS RLA MCA MFS RLA MCA MFS RLA MCA MFS RLA MCA MFS RLA MCA MFS
380-415V/ 3Ph/ 50Hz 23.0 24 30 26.3 28 35 41.6 44 60 48.2 52 70 76.4 79 90 78.0 82 100
380V/ 3Ph/ 60Hz 23.0 24 25 26.3 28 35 41.6 44 60 48.2 52 70 76.3 79 90 78.4 83 100
460V/ 3Ph/ 60Hz 19.8 21 25 23.1 25 35 36.9 40 50 43.4 47 70 67.9 71 90 69.1 73 100
Power Supply RLA MCA MFS RLA MCA MFS RLA MCA MFS RLA MCA MFS RLA MCA MFS
380-415V/ 3Ph/ 50Hz 83.6 88 110 88.2 93 110 92.2 98 150 106.7 114 150 121.0 128 175
380V/ 3Ph/ 60Hz 82.1 86 100 90.7 96 110 95.6 102 125 111.1 120 150 120.2 128 150
460V/ 3Ph/ 60Hz 73.0 77 100 81.2 87 110 86.2 92 125 95.3 102 150 107.8 116 150
Note : RLA - Rated Load Amps MCA - Minimum Circuit Amps MFS - Maximum Fuse Size
o o o o
Return Air at 24 C/17 C/50 %RH (75 F/62.5 F/50 %RH)
Model DBCD/U 03 DBCD/U 05 DBCD/U 09 DBCD/U 11 DBCD/U 14 DBCD/U 16
Power Supply RLA MCA MFS RLA MCA MFS RLA MCA MFS RLA MCA MFS RLA MCA MFS RLA MCA MFS
Power Supply RLA MCA MFS RLA MCA MFS RLA MCA MFS RLA MCA MFS RLA MCA MFS
-7-
Product that perform…By people who care
GENERAL INFORMATION
AIR COOLED DUAL COILS (DX + CW) & DX WITH HOT GAS REHEAT SYSTEMS
1.) STANDARD - COOLING & ELECTRIC HEATERS
o o o o o o
At 35 C (95 F) ambient; Return Air at 24 C/17 C/50 %RH (75 F/62.5 F/ 50 %RH)
Model DBDD/U 03 DBDD/U 05 DBDD/U 09 DBDD/U 11 DBDD/U 14 DBDD/U 16
Power Supply RLA RLA MCA MFS RLA RLA MCA MFS RLA RLA MCA MFS RLA RLA MCA MFS RLA RLA MCA MFS RLA RLA MCA MFS
(DX) (CHW) (DX) (CHW) (DX) (CHW) (DX) (CHW) (DX) (CHW) (DX) (CHW)
380-415V/ 3Ph/ 50Hz 14.0 10.2 15 20 17.3 11.3 19 25 32.5 22.1 35 50 40.1 24.0 44 60 59.2 34.8 62 80 61.7 34.4 66 90
380V/ 3Ph/ 60Hz 14.0 10.2 15 20 17.3 11.3 19 25 32.5 22.1 35 50 40.1 24.0 44 60 59.1 34.8 62 80 62.2 34.4 84 80
460V/ 3Ph/ 60Hz 12.4 8.6 13 20 15.7 9.7 17 25 29.3 18.9 32 45 36.9 20.8 41 60 53.7 30.1 56 70 55.9 29.7 60 80
Power Supply RLA RLA MCA MFS RLA RLA MCA MFS RLA RLA MCA MFS RLA RLA MCA MFS RLA RLA MCA MFS
(DX) (CHW) (DX) (CHW) (DX) (CHW) (DX) (CHW) (DX) (CHW)
380-415V/ 3Ph/ 50Hz 68.9 37.6 73 90 73.8 37.8 79 100 77.8 40.0 83 110 89.5 53.3 115 150 107.5 53.3 115 150
380V/ 3Ph/ 60Hz 67.4 37.6 71 80 76.2 37.8 82 100 81.2 40.0 87 110 94.0 41.8 102 150 106.7 53.3 114 150
460V/ 3Ph/ 60Hz 61.2 32.8 65 80 69.8 33.1 75 100 74.7 35.2 81 110 81.1 37.1 88 125 97.2 47.0 105 150
Power Supply RLA RLA MCA MFS RLA RLA MCA MFS RLA RLA MCA MFS RLA RLA MCA MFS RLA RLA MCA MFS RLA RLA MCA MFS
(DX) (CHW) (DX) (CHW) (DX) (CHW) (DX) (CHW) (DX) (CHW) (DX) (CHW)
380-415V/ 3Ph/ 50Hz 23.1 19.3 24 30 26.4 20.4 28 35 41.6 31.2 44 60 49.2 33.1 53 70 76.4 52.0 79 90 78.9 51.6 83 100
380V/ 3Ph/ 60Hz 23.1 19.3 24 30 26.4 20.4 28 35 41.6 31.2 44 60 49.2 33.1 53 70 76.3 52.0 79 90 79.4 51.6 84 100
460V/ 3Ph/ 60Hz 19.9 16.1 21 30 23.2 17.3 25 35 36.9 26.4 40 50 44.4 28.4 49 70 67.9 44.2 71 90 70.0 43.9 74 100
Power Supply RLA RLA MCA MFS RLA RLA MCA MFS RLA RLA MCA MFS RLA RLA MCA MFS RLA RLA MCA MFS
(DX) (CHW) (DX) (CHW) (DX) (CHW) (DX) (CHW) (DX) (CHW)
380-415V/ 3Ph/ 50Hz 86.1 54.8 90 110 91.0 55.0 96 125 95.0 57.1 101 125 106.7 59.0 114 150 124.6 70.5 132 175
380V/ 3Ph/ 60Hz 84.6 54.8 88 100 93.4 55.0 99 110 98.4 57.1 104 125 111.1 59.0 119 150 123.8 70.5 132 150
460V/ 3Ph/ 60Hz 75.4 47.0 79 100 83.9 47.3 89 110 88.9 49.4 95 125 95.3 51.2 102 150 111.4 61.1 119 150
Note : RLA - Rated Load Amps MCA - Minimum Circuit Amps MFS - Maximum Fuse Size
-8-
Product that perform…By people who care
GENERAL INFORMATION
Wa Wb Wc Wd D
DOWNFLOW
Wa Wb Wc Wd D
-9-
Product that perform…By people who care
GENERAL INFORMATION
DBRC 04 870 (34¼) 1 3210 (6800) 100 (220) 1 925 1110 2 1.9 1.8 2.7 5.5
DBRC 06 870 (34¼) 1 3210 (6800) 111 (244) 1 925 1110 2 1.9 1.8 2.7 5.5
DBRC 08 870 (34¼) 1 3210 (6800) 122 (268) 1 925 1110 2 1.9 1.8 2.7 5.5
DBRC 10 870 (34¼) 1 3210 (6800) 134 (295) 1 925 1110 2 1.9 1.8 2.7 5.5
DBRC 11 870 (34¼) 1 3210 (6800) 180 (400) 1 925 1110 2 1.9 1.8 2.7 5.5
DBRC 13 1683 (66¼) 2 6420 (13600) 190 (420) 2 925 1110 4 3.8 3.6 5.4 11
DBRC 17 1683 (66¼) 2 6420 (13600) 204 (450) 2 925 1110 4 3.8 3.6 5.4 11
DBRC 20 1683 (66¼) 2 6420 (13600) 265 (583) 2 925 1110 4 3.8 3.6 5.4 11
DBRC 26 2500 (98¼) 3 9630 (20400) 288 (634) 3 925 1110 6 5.7 5.4 8.1 16.5
DBRC 30 2500 (98¼) 3 9630 (20400) 320 (700) 3 925 1110 6 5.7 5.4 8.1 16.5
DBRC 34 2500 (98¼) 3 9630 (20400) 355 (780) 3 925 1110 6 5.7 5.4 8.1 16.5
DBRC 40 3308 (130¼) 4 12838 (27200) 380 (835) 4 925 1110 8 7.6 7.2 10.8 22
DBRC 44 3308 (130¼) 4 12838 (27200) 410 (900) 4 925 1110 8 7.6 7.2 10.8 22
Note: All dimensions are in mm (inches).
- 10 -
Product that perform…By people who care
INSTALLATION
INSPECTION
The DB-Aire III unit has been tested and inspected prior to shipment. To ensure that the unit has been received in
excellent condition, perform a visual inspection of the outer crating immediately upon delivery, and note any external
damage on the freight carrier’s delivery forms. As soon as possible, inspect the unit itself for possible internal
damage. File a claim with the shipping company if the shipment is damaged or incomplete. Freight damage claims
are the responsibility of the purchaser.
TRANSPORT
The unit is mounted on skid pallet, packed several times in plastic film and crated. It must always be transported
vertically upright on the pallet with a forklift. The unit can be moved by lifting devices with ropes. For this the ropes
have to be fixed at the pallet, and the upper unit edges have to be protected by wooden laths or spreader bars to
prevent damage to the unit.
To avoid any damage to the unit during transportation, it is recommended that the unit should only be removed from
its packaging when the unit has reached its final destination. It is also essential to make sure that the floor on which
the unit is to be installed is capable of supporting its weight. The weight of the unit can be found on the Performance
and Technical Data on this manual.
OPERATING LIMITS
Units are designed to operate within working ranges (See Performance and Technical Data). The limits are referred
to new machines which have been correctly installed and serviced. The warranty clauses are no longer valid for any
possible damage or malfunction that may occur during or due to operation outside the application values.
- 11 -
Product that perform…By people who care
INSTALLATION
All piping and wiring connections are designed from unit bottom. Proper openings should have already been cut on
the raised floor by others.
3 1
2
4
- 12 -
Product that perform…By people who care
INSTALLATION
To reinstall back the fixed panel, reverse the steps. Locate the panel on the frame.
Note that the left and right side stopper bars have to be inserted prior to the top and bottom stopper bars.
- 13 -
Product that perform…By people who care
INSTALLATION
REMOVING FILTERS
All units are supplied together with air filters. Follow the below steps to withdraw the filters.
1. 2. 3.
Filter
Lift up the filter as shown until it touches Tilt the filter (bottom) as shown to One at a time, slide the other
filter rack (top). allow it coming out from the filter filters to the previous filter
rack and remove it from the unit. location. Follow the above steps
to remove the filters from the
unit.
Place in the new filters in
reverse sequence of the above
steps.
- 14 -
Product that perform…By people who care
INSTALLATION
AIR-COOLED PIPING
¾ Direct expansion (DX) system units are shipped pressurized with a nitrogen charge.
¾ Remote air-cooled condensers (DBRC) are shipped pressurized with a nitrogen charge.
Notes:
R410A refrigerant is a high-pressure refrigerant. It requires careful attention to proper storage and handling
procedures. Use on manifold gauge sets designed for use with R410A refrigerant. Use only refrigerant
recovery units and cylinders designed for high pressure refrigerants. R410A must only be charged in the
liquid state.
Excessive refrigerant line length reduces system capacity and efficiency, as well as system reliability
(excessive refrigerant charge). Keep refrigerant lines as short as conditions permit!
The pipe sizes / refrigerant charges quoted are for guidance only. It is the responsibility of the installing
contractor / engineer to check the pipe sizes / refrigerant charges are correct for each system installation.
Split systems may require additional oil, which should be added to the low side of each compressor.
Design should be in accordance with accepted refrigeration practice to ensure good oil return to the
compressor(s) under all normal operating conditions.
The interconnecting lines to the remote air-cooled condenser must be installed by a qualified refrigeration mechanic.
Prior to connecting the tubes, make sure to apply blind caps or water proof tape to prevent dust or water from getting
into the tubes.
Max. Allowable Piping Equivalent Length Elevation Difference between Indoor and Outdoor Units
75 ft (22.9m) 30 ft (9.2m)
PIPE SUPPORTS
The table below identifies the maximum distance between pipe supports on horizontal and vertical pipe runs. All
pipework should be clamped prior to apply insulation. Clamping over insulation is not acceptable.
Pipe OD (inches) Support Distance (meter)
3/8” to 7/8” 1.0
1-1/8” to 2-1/8” 2.0
1. The required copper pipe diameters for discharge hot gas and liquid lines are shown on Performance and
Technical Data. Establish the shortest route for pipework from indoor unit to the outdoor condenser. Try to avoid
unnecessary bends on piping as possible to minimize the total charge of refrigerant and the pressure drops. Lay
the horizontal gas pipes with 1% downward gradient towards the refrigerant flow.
2. Reduce the number of bends which must be of large radius
3. The liquid line of the system must be insulated if passing through extremely warm places.
4. There must be a minimum separation of 20mm between the hot gas and liquid lines. If this is not possible,
insulate both lines.
5. Oil traps are required to be located every 15 to 20ft (4.6 to 6.1m) on hot gas line riser to ensure proper oil
entrapment.
6. Support both horizontal and vertical pipes with vibration damping clamps, which should include rubber gaskets.
- 15 -
Product that perform…By people who care
INSTALLATION
Discharge Line
Liquid Line
For long discharge hot gas vertical riser, it is essential that Careful pipework selection must be done if the liquid
oil separator (field supplied) must be installed in the line rises. Additional subcooling may be required to
system. Oil traps are also required to be located every 4m prevent flash gas occurring in the liquid line due to
to ensure proper oil entrapment. In addition, there should excess pressure drop. Careful pipe sizing is
be an oil trap at the exit of the indoor unit before a vertical recommended to ensure that the liquid line does not
riser is applied. have excessive pressure drop. Increasing liquid line
pipe size can minimize pipe pressure drop.
Approximate discharge and liquid-line sizing up to 200
equivalent feet (61 meter) are shown in the table on next Approximate discharge and liquid-line sizing up to
page. 200 equivalent feet (61 meter) are shown in the table
on next page.
Discharge check valves are recommended on long pipe
(above 31 meters) runs or in cold climates (not on The recommended pressure drop should be between
drawing). 2 to 4 PSI. Liquid-line velocity from the condenser to
the expansion valve should be between 200 and 300
The recommended pressure drop should be between 3 to FPM.
6 PSI. Minimum and maximum gas velocity for proper oil Charging to a minimum of 10F (5.6C) subcooling is
return should be 1000 FPM to 3000 FPM. recommended to ensure a column of liquid is present
at the TXV.
- 16 -
Product that perform…By people who care
INSTALLATION
Recommended Line Sizing Up To 200 Equivalent Feet (61 Meter) For Split Air
Cooled Systems
100 EQUIV FEET [31 METER] 150 EQUIV FEET [46 METER] 200 EQUIV FEET [61 METER]
MODEL
HOT GAS LIQUID HOT GAS LIQUID HOT GAS LIQUID
03 3/4 [19.1] 1/2 [12.7] 3/4 [19.1] 1/2 [12.7] 3/4 [19.1] 1/2 [12.7]
05 7/8 [22.2] 5/8 [15.9] 7/8 [22.2] 5/8 [15.9] 1 1/8 [28.6] 5/8 [15.9]
09 1 1/8 [28.6] 7/8 [22.2] 1 1/8 [28.6] 7/8 [22.2] 1 3/8 [34.9] 7/8 [22.2]
11 1 1/8 [28.6] 7/8 [22.2] 1 1/8 [28.6] 7/8 [22.2] 1 3/8 [34.9] 7/8 [22.2]
14 7/8 [22.2] 5/8 [15.9] 1 1/8 [28.6] 5/8 [15.9] 1 1/8 [28.6] 5/8 [15.9]
16 7/8 [22.2] 5/8 [15.9] 1 1/8 [28.6] 5/8 [15.9] 1 1/8 [28.6] 5/8 [15.9]
19 1 1/8 [28.6] 7/8 [22.2] 1 1/8 [28.6] 7/8 [22.2] 1 3/8 [34.9] 7/8 [22.2]
22 1 1/8 [28.6] 7/8 [22.2] 1 3/8 [34.9] 7/8 [22.2] 1 3/8 [34.9] 7/8 [22.2]
26 1 1/8 [28.6] 7/8 [22.2] 1 3/8 [34.9] 7/8 [22.2] 1 3/8 [34.9] 7/8 [22.2]
29 1 1/8 [28.6] 7/8 [22.2] 1 3/8 [34.9] 7/8 [22.2] 1 3/8 [34.9] 7/8 [22.2]
32 1 1/8 [28.6] 7/8 [22.2] 1 3/8 [34.9] 7/8 [22.2] 1 3/8 [34.9] 7/8 [22.2]
Note : Oil separator is essential for equivalent length more than 100ft [31m]. Please consult factory for further information.
- 17 -
Product that perform…By people who care
INSTALLATION
CHARGING
1.) Connect refrigerant cylinder through charging connection to charging valve.
2.) Loosen flare nut on other end of charging connection and blow air out with refrigerant. Tighten flare nut on
charging connection.
3.) Weight refrigerant cylinder.
4.) Open charging valve and charge in refrigerant liquid through liquid line access valve. Continue charging with
liquid refrigerant until clear glass is observed.
5.) Shut off refrigerant charging valve but keep connected. Check charging valve flare nut for leak. Check and
record down discharge and suction pressure. If more than one system to be charged, follow procedure 1 through
4 for each system. After all the systems have been done up to step 4, proceed with 5 and 6.
6.) Shut off the system (compressor, fans, pumps) and leave for 24 hours.
- 18 -
Product that perform…By people who care
INSTALLATION
WATER CONNECTIONS
Chilled Water Piping
It will be necessary to install inlet and outlet pipes on unit with chilled water coils. The diameters of the pipes are
indicated on the Performance and Technical Data.
Indoor Unit
1. Use pipes made of copper or steel. Support pipes with suitable brackets.
2. Insulate all pipes with Armaflex type insulation.
3. Install shut-off valves to facilitate maintenance.
4. Install a thermometer on the inlet and outlet pipes.
5. Install a pressure gauge on the inlet and outlet pipes.
6. Install a drain outlet in the lowest part of the circuit.
- 19 -
Product that perform…By people who care
INSTALLATION
HUMIDIFIER (OPTIONAL)
General
Steam humidifier is an optional item and it is installed and integrated within the function and method of operation of
the unit. The humidifier produces non-pressurized steam by means of electrodes immersed in the water contained in
the cylinder. The humidifier uses normal main water for the production of steam. The conductivity of the water should
be within the range of 75 to 350 µS/cm. The steam is introduced into the airflow by means of distributor via steam
hose installed in the unit. The humidifier is necessary to be connected a supply pipe.
Supply Connections
The steam humidifier is installed and electrically connected in the unit. Initially the humidifier cylinder is empty.
Ensure a water supply is available to the humidifier with the following characteristics,
¾ Pressure between 1 and 8 bar (14.5 and 116psi)
o
¾ Temperature between 1 and 40 C
The water supply connection to the humidifier should have an internal diameter of at least ¼ inch (6mm). A waterline
shutoff valve and mechanical filter must be installed (by others) outside the unit to trap any solid impurities and for
future disconnection and service.
Supply Connection
(by others)
Supply
Valve
4 Filter
Drain
- 20 -
Product that perform…By people who care
INSTALLATION
Periodical Checks
After 1 hour of operation Check that there are no significant water leaks
Every 15 days or no more than Check that there are no significant water leaks and the general condition of the container.
300 operating hours Check that during operation there are no arcs or sparks between the electrodes
Every 3 months or no more than Check operation that there are no significant water leaks. If necessary replace the cylinder
1000 operating hours
Annually or no more than 2500 Replace the cylinder
operating hours
After extended use or alternatively when using water with a high salt content, the solid deposits that naturally form on
the electrodes may reach the stage where they also stick to the inside wall of cylinder; in the event of especially
conductive deposits, the consequent heat produced may overheat the plastic and melt it, and, in more severe case,
puncture the cylinder. As a precaution, check, at the frequency recommended further on, the deposits and the
blackening of the wall of the cylinder, and replace the cylinder if necessary.
OPERATION
Humidification is provided by an electrode boiler. The sealed humidifier design ensures that only clean sterile steam
is supplied to the conditioned area and corrosive salts and minerals are held in the disposable bottle. The humidifier
features modulating capacity output control as standard. The system provides continuous modulation of steam
output in response to a proportional control signal. The output control range is 20% to 100% of the humidifier rated
value and is designed to give an approximate steam output of +/-5%, thus ensuring precise control of the conditioned
space. The cylinder operating life time is automatically optimized via the integrated water conductivity sensor which
combined with the Vision 2020i controller to monitor and regulate the water refill cycle to reduce excessive salt
deposits and the progressive wear of the cylinder.
All humidifier parameters and alarms are accessible and adjustable via the microprocessor display keypad unit. The
main features include,
¾ Supply water conductivity (μS/cm)
¾ Required steam output (kg/h)
¾ Actual steam output (kg/h)
¾ Required current rating (A)
¾ Actual current rating (A)
Status mode (Start Up, Running, Filling or Draining)
- 21 -
Product that perform…By people who care
INSTALLATION
Leg Assembly
The legs must be unbolted from the shipping position and extended prior to placing the unit on its pad. Each leg
extends down approximately 18 inches [457mm] and reattaches using the same bolts.
Note: Condenser fans are of the propeller type and not suitable for use with ductwork.
The remote heat exchangers must be located in an area that will ensure free air flow into and out of the unit. The unit
should not be placed closer than 36 inches [914mm] from any wall or other obstruction. When two or more units are
used in the same area, space them apart by a minimum of 48 inches [1219mm].
- 22 -
Product that perform…By people who care
INSTALLATION
inches
inches
118
36
118 inches
(3000mm)
- 23 -
Product that perform…By people who care
OPERATION
ELECTRICAL CONNECTIONS
IMPORTANT: Before proceeding with the electrical connections, make certain that the volts, hertz, and phase
correspond to that specified on the unit rating plate. Also, check to be sure that the service provided by the utility is
sufficient to handle the additional load imposed by this equipment. Refer to the unit rating plate for equipment
electrical requirements. The attached typical wiring diagrams show the proper field high and low voltage wiring. Make
all electrical connections in accordance with national electrical code and any applicable local code ordinances. Use
copper conductors only.
WARNING: The unit cabinet must have an uninterrupted electrical ground. An electrical ground wire of adequate
size must be connected to the ground lug provided inside the control box. A ground wire is mandatory with
microprocessor controls.
Supply voltage at the unit must be within 10% of the voltage indicated on the nameplate. Phase-to-phase imbalance
must not exceed 3%. Local utility company should be contacted for correction of improper line voltage. Improper
electrical power supply may cause premature failures, which will void unit warranties.
The computer-room unit and the condenser unit require individual power sources.
For auxiliary-equipment control wiring, such as for the remote condenser, bring NEC Class-2 wires to the control box
and connect to the terminals indicated on the unit wiring diagram. Wiring terminal numbers will typically be the same
in the computer-room unit and the remote heat exchanger. Verify terminal numbers on unit and heat exchanger
wiring diagrams before connecting wiring.
Verify that properly sized fuses or circuit breakers are installed in the remote-mounted disconnect switch. Fuse size
and minimum circuit ampere are listed on the unit nameplate.
Check the wiring connections in the unit control panel to ensure that they are tight. Wiring connections may become
loose in transit.
- 24 -
Product that perform…By people who care
OPERATION
Standard Alarms
High temp, low temp, high humid, low humid, manual override, under floor water detection, no air flow, dirty filters,
humidifier failure, low-voltage warning, fire stat, compressor short cycle, power failure restart, humidity-sensor failure,
temperature-sensor failure, maintenance required based on programmed run time, high pressure, low pressure, no
water flow, smoke alarm, main fan motor overload. On energy-saver units, one programmable local alarm input (#3)
is to be used to change from compressor operation to chilled-water operation. Display will switch to energy saver
with percentage of valve-opening display on screen. On units with compressors, option input (#1) is used for a high-
pressure alarm.
Software
Software has menu-driven programming. Password is required. Opening of unit door not required for the following:
Temperature set point, temperature dead band, temperature high and low alarm points, temperature sensor
calibration, time delay between stages (sequential load activation), unit-start time delay, set tone of alarm buzzer, set
DC voltage range for control valve, set hours of operation until appearance of maintenance-required alarm message,
set power-failure restart method. Factory settings include periodic chilled-water or energy-saver coil flush, low-
voltage dropout point 90%, predictive humidity control, temperature anticipation, automatic lead-lag rotation of
compressors and reheat.
- 25 -
Product that perform…By people who care
OPERATION
Data Collection
The microprocessor will log data for the following items: Run times of fan motor, cool 1, cool 2, heat 1, heat 2, heat 3,
humidification, dehumidification, chilled-water operation and energy-saver operation. Temperature, humidity and
capacity readings will be taken every three minutes and recorded on the unit data base for the past 24 hours. An
alarm data base will be maintained for the last 10 alarms and the time since occurrence. All data may be displayed at
the unit without any additional equipment.
Communications
The unit can communicate over an RS 485 network using a twisted pair of wires in a token ring loop. All data can be
transmitted and displayed at DB-Aire Network. Optional RS 485 or 232 card can be fitted for modem or MODBUS
communication protocol.
Diagnostics
All electronic circuitry contains built-in diagnostics. No additional external devices are required. Automatic self-
diagnostics shall take place when power is applied to the unit. Manual diagnostics will be available with self-
prompting instruction displays.
2. Shortcut Key
The shortcut key available on press up arrow on the
bottom of the screen. There have three shortcut key
button which are alarm, main display and main menu.
4. Alarm Page
The alarm trigger provides description of alarm and time
happen. The alarm page trigger with the buzzer
(dependent model) and alarm relay energized. The buzzer
can be turn off by press “Ack” button (dependent model).
After solve the alarm cause, it can be reset by press
“Reset Alarm”.
- 26 -
Product that perform…By people who care
OPERATION
5. Main Menu
The main menu page come with status, clock, scheduler,
user, technician, factory and password buttons. The clock,
scheduler and user pages required user authorization. The
technician page required technician authorization. The
factory page required factory authorization.
6. Authorization
Log in using technician and factory level access will
automatically allow to access user settings. Touch on the
login button after insert 4-digit number password. If correct
password is entered, the access status display will change
from view only to user, technician or factory. If an incorrect
password is entered, it will display wrong password. If this
message appears, try re-entering the password again.
7. Status Sub-Menu
The status page menu consist of unit, blower, heater,
humidifier (optional), compressor 1, compressor 2 and
DBLAN (master unit only) buttons. All input and output
parameter can be monitor through status pages.
8. Status – Unit
The unit status consist of input and output parameters that
related to unit level.
9. Status – Blower
The blower status consist of input and output parameters
that related to blower and air flow.
- 27 -
Product that perform…By people who care
OPERATION
- 28 -
Product that perform…By people who care
OPERATION
17. Clock
The controller clock can be change by enter the new DB5+
time and press write new to DB5+ button. The new DBGx
display time will auto synchronize to DB5+ controller time.
18. Schedule
The schedule page offer daily time zone control and weekly
time zone control.
- 29 -
Product that perform…By people who care
OPERATION
19. User
The user setpoint consist of room temperature and room
humidity control demand setpoint.
The deadband + and deadband – are temperature different
for comfort zone. The restart deadband is temperature
different to start the compressor. The stop deadband is
temperature different to stop the compressor.
- 30 -
Product that perform…By people who care
OPERATION
- 31 -
Product that perform…By people who care
OPERATION
Unit No. DB5+ Vision2020i Controller Address DBGX Display Terminal Address
1 1 9
2 2 10
3 3 11
4 4 12
5 5 13
6 6 14
7 7 15
8 8 16
Standard Alarms
High temp, low temp, high humid, low humid, manual override, under floor water detection, no air flow, dirty filters,
humidifier failure, low-voltage warning, fire stat, compressor short cycle, power failure restart, humidity-sensor failure,
temperature-sensor failure, maintenance required based on programmed run time, high pressure, low pressure, no
water flow, smoke alarm, main fan motor overload. On energy-saver units, one programmable local alarm input (#3)
is to be used to change from compressor operation to chilled-water operation. Display will switch to energy saver
with percentage of valve-opening display on screen. On units with compressors, option input (#1) is used for a high-
pressure alarm.
Software
Software has menu-driven programming. Password is required. Opening of unit door not required for the following:
Temperature set point, temperature dead band, temperature high and low alarm points, temperature sensor
calibration, time delay between stages (sequential load activation), unit-start time delay, set tone of alarm buzzer, set
DC voltage range for control valve, set hours of operation until appearance of maintenance-required alarm message,
set power-failure restart method. Factory settings include periodic chilled-water or energy-saver coil flush, low-
voltage dropout point 90%, predictive humidity control, temperature anticipation, automatic lead-lag rotation of
compressors and reheat.
Data Collection
The microprocessor will log data for the following items: Run times of fan motor, cool 1, cool 2, heat 1, heat 2, heat 3,
humidification, dehumidification, chilled-water operation and energy-saver operation. Temperature, humidity and
capacity readings will be taken every three minutes and recorded on the unit data base for the past 24 hours. An
alarm data base will be maintained for the last 10 alarms and the time since occurrence. All data may be displayed at
the unit without any additional equipment.
Communications
The unit can communicate over an RS 485 network using a twisted pair of wires in a token ring loop. All data may be
transmitted to and displayed at an optional remote-mounted DB-Aire Network. Optional RS 485 or 232 card can be
fu-fitted for modem or MODBUS communication protocol.
Diagnostics
All electronic circuitry contains built-in diagnostics. No additional external devices are required. Automatic self-
diagnostics shall take place when power is applied to the unit. Manual diagnostics will be available with self-
prompting instruction displays.
- 32 -
Product that perform…By people who care
OPERATION
PIPING SCHEMATIC
DX/ Dual Coil System Only
(I) Model 03 - 11 (Single Compressor)
- 33 -
Product that perform…By people who care
MAINTENANCE INSTRUCTIONS
MAINTENANCE
These units are designed to provide years of services with minimum maintenance. Nonetheless, it is a good practice
to carry out regular inspection and checking to ensure the unit's optimum performance.
- 34 -
Product that perform…By people who care
MAINTENANCE INSTRUCTIONS
CLEANING FREQUENCY
1. At a minimum, coils should be inspected and cleaned at least once per year.
2. In extreme environments, where the coils are exposed to high concentrations of salt air (within 25 miles of any
seacoast), or where they are installed near engine exhausts, plumbing or manufacturing vents, or regularly
exposed to corrosive chemicals, the coils need to be inspected and cleaned more often with a minimum 4 times
per year.
CLEANING PROCESS
1. Turn off electrical power to the unit using lock-out system.
2. Flush the coil with water to rinse off loose residue. Allow the water to soak for 10–20 minutes to loosen surface
residue. Wash at least once in 2 weeks to remove residues on the condenser coils for coil with 5-years warranty.
3. Flush the coil thoroughly with any mild liquid detergent and warm water (~100°F) until all signs of residue are
eliminated.
4. Rinse the unit thoroughly with clean water (it should not be brackish or contain excessive dissolved minerals).
5. Allow the unit to dry completely prior to turning the electrical power on or returning the unit to service.
- 35 -
Product that perform…By people who care
MAINTENANCE INSTRUCTIONS
AVOID
1. Water under high pressure, such as a high-pressure washer. Fins may fold under high pressure causing the
coating to crack
2. Abrasive products or processes to scour or remove dirt
3. Striking the coil with a tool to dislodge or remove soil or residue
4. Corrosive, caustic or alkaline cleaners (with a pH < 5.5 or > 8.5) as these may permanently damage the coating
and void the warranty. If you have questions about the cleaner that you are using, please contact Heresite.
CAUTION: CONTAINS FLAMMABLE SOLVENTS. KEEP AWAY FROM SPARKS AND OPEN FLAMES. IN
CONFINED AREAS WORKMEN MUST WEAR FRESH AIR LINE RESPIRATORS. HYPERSENSITIVE PERSONS
SHOULD WEAR GLOVES OR USE PROTECTIVE CREAM. ALL ELECTRIC EQUIPMENT AND INSTALLATIONS
SHOULD BE MADE AND GROUNDED IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE. IN
AREAS WHERE EXPLOSION HAZARDS EXIST, WORKMEN SHOULD BE REQUIRED TO USE NONFERROUS
TOOLS AND TO WEAR CONDUCTIVE AND NON SPARKING SHOES.
- 36 -
Product that perform…By people who care
MAINTENANCE INSTRUCTIONS
TROUBLESHOOTING CHART
- 37 -
Product that perform…By people who care
MAINTENANCE INSTRUCTIONS
- 38 -
Product that perform…By people who care
MAINTENANCE INSTRUCTIONS
DATE
TIME
COMP. NO.
1.
2.
SUCTION PRESSURE
3.
4.
1.
2.
SUCTION TEMPERATURE
3.
4.
1.
2.
DISCHARGE PRESSURE
3.
4.
1.
2.
DISCHARGE TEMPERATURE
3.
4.
1.
DISCHARGE SUPERHEAT 2.
(DISC. TEMP.-SAT. DISCH.) 3.
4.
1.
SUCTION SUPERHEAT 2.
(SAT. SUCT .- SUC. TEMP) 3.
4.
RETURN AIR TEMPERATURE – DB/WB
SUPPLY AIR TEMPERATURE – DB/WB
AIR VOLUME
AMBIENT AIR TEMPERATURE
OFF CONDENSER AIR TEMPERATURE
1.
2.
COMPRESSOR AMPS
3.
4.
CONDENSER FAN AMPS
EVAPORATOR FAN AMPS
VOLTS
This log sheet is provided as a recommendation of the readings that should be taken on a periodic basis. The actual readings taken and the frequency
will depend upon the units application, hours of use, etc. This type of information can prove very useful in preventing and/ or solving problems that
might occur during the life of the unit.
- 39 -