Unit 3 Main-1
Unit 3 Main-1
Hardware Configuration
.
Test Equipment
Type Serial Number
CMC356 PE408Y
. .
Hardware Check
Performed At Result Details
6/10/2023 9:56:17 AM Passed
19 Digital Input 19 OK
20 Digital Input 20 OK
21 Digital Input 21 OK
22 Digital Input 22 OK
23 Digital Input 23 OK
24 Digital Input 24 OK
25 Digital Input 25 OK
26 HIPASE-P Digital Input 26 OK
27 Digital Input 27 OK
28 Digital Input 28 OK
29 Digital Input 29 OK
30 Digital Input 30 OK
31 Digital Input 31 OK
32 Digital Input 32 OK
33 Digital Input 33 OK
34 Digital Input 34 OK
35 Digital Input 35 OK
36 Digital Input 36 OK
37 Digital Input 37 OK
38 Digital Input 38 OK
39 Digital Input 39 OK
40 Digital Input 40 OK
41 Digital Input 41 OK
42 Digital Input 42 OK
43 Digital Input 43 OK
44 Digital Input 44 OK
45 Digital Input 45 OK
46 Digital Input 46 OK
47 Digital Input 47 OK
48 Digital Input 48 OK
49 Digital Output 1 OK
50 Digital Output 2 OK
51 Digital Output 3 OK
52 Digital Output 4 OK
53 Digital Output 5 OK
54 Digital Output 6 OK
55 Digital Output 7 OK
56 Digital Output 8 OK
57 Digital Output 9 OK
58 Digital Output 10 OK
59 Digital Output 11 OK
Page 2 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
60 Digital Output 12 OK
61 Digital Output 13 OK
62 Digital Output 14 OK
63 Digital Output 15 OK
64 Digital Output 16 OK
Besides, Digital inputs and outputs, LEDs were tested and found ok.
.
2. Measurement Test:
. .
Test Module
Name: OMICRON QuickCMC Version: 4.30
Test Start: 05-Jun-2023 15:45:41 Test End: 05-Jun-2023 16:16:16
User Name: Manager:
Company:
Test Results
Title: CT-309/R
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 5.000 A 0.00 ° 50.000 Hz
I L2 0.00 A -120.00 ° 50.000 Hz
I L3 0.00 A 120.00 ° 50.000 Hz
Generator Settings
I L1 5.000A 0.00° +90°
I L1
180° 0°
5.0 A -90°
I L2 0.000A -120.00°
I L3 0.000A 120.00°
Binary Inputs
Name Slope Time
TRIP 0
Overload 0
Comment
CT-01 = 12.023 kA
CT-02 = 0 kA
CT-03 = 0 kA
Title: CT-309/Y
Page 3 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 0.00 A 0.00 ° 50.000 Hz
I L2 5.000 A -120.00 ° 50.000 Hz
I L3 0.00 A 120.00 ° 50.000 Hz
Generator Settings
I L1 0.000A 0.00° +90°
180° 0°
I L2
5.0 A -90°
I L2 5.000A -120.00°
I L3 0.000A 120.00°
Binary Inputs
Name Slope Time
TRIP 0
Overload 0
Comment
CT-01 = 0 kA
CT-02 = 12.017 kA
CT-03 = 0 kA
Title: CT-309/B
.
Fault Calculator:
Table Input mode Parameters (All values are secondary)
Direct I L1 0.00 A 0.00 ° 50.000 Hz
I L2 0.00 A -120.00 ° 50.000 Hz
I L3 5.000 A 120.00 ° 50.000 Hz
Generator Settings
I L1 0.000A 0.00° +90°
I L3
180° 0°
5.0 A -90°
I L2 0.000A -120.00°
I L3 5.000A 120.00°
Binary Inputs
Name Slope Time
Page 4 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
TRIP 0
Overload 0
Comment
CT-01 = 0 kA
CT-02 = 0 kA
CT-03 = 12.024 kA
Title: CT-309/RYB
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 5.000 A 0.00 ° 50.000 Hz
I L2 5.000 A -120.00 ° 50.000 Hz
I L3 5.000 A 120.00 ° 50.000 Hz
Generator Settings
I L1 5.000A 0.00° +90°
I L3
I L1
180° 0°
I L2
5.0 A -90°
I L2 5.000A -120.00°
I L3 5.000A 120.00°
Binary Inputs
Name Slope Time
TRIP 0
Overload 0
Comment
CT-01 = 12.035 kA
CT-02 = 12.011 kA
CT-03 = 12.018 kA
Title: CT-305/R
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 5.000 A 0.00 ° 50.000 Hz
I L2 0.00 A -120.00 ° 50.000 Hz
I L3 0.00 A 120.00 ° 50.000 Hz
Generator Settings
Page 5 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
I L1
180° 0°
5.0 A -90°
I L2 0.000A -120.00°
I L3 0.000A 120.00°
Binary Inputs
Name Slope Time
TRIP 0
Overload 0
Comment
CT-01 = 12.016 kA
CT-02 = 0 kA
CT-03 = 0 kA
Title: CT-305/Y
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 0.00 A 0.00 ° 50.000 Hz
I L2 5.000 A -120.00 ° 50.000 Hz
I L3 0.00 A 120.00 ° 50.000 Hz
Generator Settings
I L1 0.000A 0.00° +90°
180° 0°
I L2
5.0 A -90°
I L2 5.000A -120.00°
I L3 0.000A 120.00°
Binary Inputs
Name Slope Time
TRIP 0
Overload 0
Comment
CT-01 = 0 kA
CT-02 = 12.014 kA
CT-03 = 0 kA
Title: CT-305/B
Page 6 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 0.00 A 0.00 ° 50.000 Hz
I L2 0.00 A -120.00 ° 50.000 Hz
I L3 5.000 A 120.00 ° 50.000 Hz
Generator Settings
I L1 0.000A 0.00° +90°
I L3
180° 0°
5.0 A -90°
I L2 0.000A -120.00°
I L3 5.000A 120.00°
Binary Inputs
Name Slope Time
TRIP 0
Overload 0
Comment
CT-01 = 0 kA
CT-02 = 0 kA
CT-03 = 12.025 kA
Title: CT-305/RYB
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 5.000 A 0.00 ° 50.000 Hz
I L2 5.000 A -120.00 ° 50.000 Hz
I L3 5.000 A 120.00 ° 50.000 Hz
Generator Settings
I L1 5.000A 0.00° +90°
I L3
I L1
180° 0°
I L2
5.0 A -90°
I L2 5.000A -120.00°
I L3 5.000A 120.00°
Binary Inputs
Name Slope Time
TRIP 0
Page 7 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
Overload 0
Comment
CT-01 = 12.019 kA
CT-02 = 12.008 kA
CT-03 = 12.025 kA
Title: CT-317/R
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 1.000 A 0.00 ° 50.000 Hz
I L2 0.00 A -120.00 ° 50.000 Hz
I L3 0.00 A 120.00 ° 50.000 Hz
Generator Settings
I L1 1.000A 0.00° +90°
I L1
180° 0°
1.0 A -90°
I L2 0.000A -120.00°
I L3 0.000A 120.00°
Binary Inputs
Name Slope Time
TRIP 0
Overload 0
Comment
CT-01 = 500.7 A
CT-02 = 0 A
CT-03 = 0 A
Title: CT-317/Y
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 0.00 A 0.00 ° 50.000 Hz
I L2 1.000 A -120.00 ° 50.000 Hz
I L3 0.00 A 120.00 ° 50.000 Hz
Generator Settings
I L1 0.000A 0.00° +90°
180° 0°
I L2
1.0 A -90°
I L2 1.000A -120.00°
Page 8 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
I L3 0.000A 120.00°
Binary Inputs
Name Slope Time
TRIP 0
Overload 0
Comment
CT-01 = 0 A
CT-02 = 500.5 A
CT-03 = 0 A
Title: CT-317/B
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 0.00 A 0.00 ° 50.000 Hz
I L2 0.00 A -120.00 ° 50.000 Hz
I L3 1.000 A 120.00 ° 50.000 Hz
Generator Settings
I L1 0.000A 0.00° +90°
I L3
180° 0°
1.0 A -90°
I L2 0.000A -120.00°
I L3 1.000A 120.00°
Binary Inputs
Name Slope Time
TRIP 0
Overload 0
Comment
CT-01 = 0 A
CT-02 = 0 A
CT-03 = 501.2 A
Title: CT-317/RYB
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 1.000 A 0.00 ° 50.000 Hz
I L2 1.000 A -120.00 ° 50.000 Hz
I L3 1.000 A 120.00 ° 50.000 Hz
Generator Settings
Page 9 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
I L1
180° 0°
I L2
1.0 A -90°
I L2 1.000A -120.00°
I L3 1.000A 120.00°
Binary Inputs
Name Slope Time
TRIP 0
Overload 0
Comment
CT-01 = 500.8 A
CT-02 = 500.5 A
CT-03 = 500.2 A
Title: CT-310/R
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 5.000 A 0.00 ° 50.000 Hz
I L2 0.00 A -120.00 ° 50.000 Hz
I L3 0.00 A 120.00 ° 50.000 Hz
Generator Settings
I L1 5.000A 0.00° +90°
I L1
180° 0°
5.0 A -90°
I L2 0.000A -120.00°
I L3 0.000A 120.00°
Binary Inputs
Name Slope Time
TRIP 0
Overload 0
Comment
CT-01 = 12.018 kA
CT-02 = 0 kA
CT-03 = 0 kA
Title: CT-310/Y
.
Page 10 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 0.00 A 0.00 ° 50.000 Hz
I L2 5.000 A -120.00 ° 50.000 Hz
I L3 0.00 A 120.00 ° 50.000 Hz
Generator Settings
I L1 0.000A 0.00° +90°
180° 0°
I L2
5.0 A -90°
I L2 5.000A -120.00°
I L3 0.000A 120.00°
Binary Inputs
Name Slope Time
TRIP 0
Overload 0
Comment
CT-01 = 0 kA
CT-02 = 12.024 kA
CT-03 = 0 kA
Title: CT-310/B
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 0.00 A 0.00 ° 50.000 Hz
I L2 0.00 A -120.00 ° 50.000 Hz
I L3 5.000 A 120.00 ° 50.000 Hz
Generator Settings
I L1 0.000A 0.00° +90°
I L3
180° 0°
5.0 A -90°
I L2 0.000A -120.00°
I L3 5.000A 120.00°
Binary Inputs
Name Slope Time
TRIP 0
Overload 0
Page 11 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
Comment
CT-01 = 0 kA
CT-02 = 0 kA
CT-03 = 12.034 kA
Title: CT-310/RYB
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 5.000 A 0.00 ° 50.000 Hz
I L2 5.000 A -120.00 ° 50.000 Hz
I L3 5.000 A 120.00 ° 50.000 Hz
Generator Settings
I L1 5.000A 0.00° +90°
I L3
I L1
180° 0°
I L2
5.0 A -90°
I L2 5.000A -120.00°
I L3 5.000A 120.00°
Binary Inputs
Name Slope Time
TRIP 0
Overload 0
Comment
CT-01 = 12.022 kA
CT-02 = 12.020 kA
CT-03 = 12.031 kA
Title: CT-303/R
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 5.000 A 0.00 ° 50.000 Hz
I L2 0.00 A -120.00 ° 50.000 Hz
I L3 0.00 A 120.00 ° 50.000 Hz
Generator Settings
I L1 5.000A 0.00° +90°
I L1
180° 0°
5.0 A -90°
I L2 0.000A -120.00°
I L3 0.000A 120.00°
Page 12 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
Binary Inputs
Name Slope Time
TRIP 0
Overload 0
Comment
CT-01 = 12.027 kA
CT-02 = 0 kA
CT-03 = 0 kA
Title: CT-303/Y
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 0.00 A 0.00 ° 50.000 Hz
I L2 5.000 A -120.00 ° 50.000 Hz
I L3 0.00 A 120.00 ° 50.000 Hz
Generator Settings
I L1 0.000A 0.00° +90°
180° 0°
I L2
5.0 A -90°
I L2 5.000A -120.00°
I L3 0.000A 120.00°
Binary Inputs
Name Slope Time
TRIP 0
Overload 0
Comment
CT-01 = 0 kA
CT-02 = 12.031 kA
CT-03 = 0 kA
Title: CT-303/B
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 0.00 A 0.00 ° 50.000 Hz
I L2 0.00 A -120.00 ° 50.000 Hz
I L3 5.000 A 120.00 ° 50.000 Hz
Generator Settings
Page 13 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
180° 0°
5.0 A -90°
I L2 0.000A -120.00°
I L3 5.000A 120.00°
Binary Inputs
Name Slope Time
TRIP 0
Overload 0
Comment
CT-01 = 0 kA
CT-02 = 0 kA
CT-03 = 12.027 kA
Title: CT-303/RYB
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 5.000 A 0.00 ° 50.000 Hz
I L2 5.000 A -120.00 ° 50.000 Hz
I L3 5.000 A 120.00 ° 50.000 Hz
Generator Settings
I L1 5.000A 0.00° +90°
I L3
I L1
180° 0°
I L2
5.0 A -90°
I L2 5.000A -120.00°
I L3 5.000A 120.00°
Binary Inputs
Name Slope Time
TRIP 0
Overload 0
Comment
CT-01 = 12.035 kA
CT-02 = 12.025 kA
CT-03 = 12.027 kA
Title: CT-217/R (CORE-IV)
Page 14 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 1.000 A 0.00 ° 50.000 Hz
I L2 0.00 A -120.00 ° 50.000 Hz
I L3 0.00 A 120.00 ° 50.000 Hz
Generator Settings
I L1 1.000A 0.00° +90°
I L1
180° 0°
1.0 A -90°
I L2 0.000A -120.00°
I L3 0.000A 120.00°
Binary Inputs
Name Slope Time
TRIP 0
Overload 0
Comment
CT-04 = 501.4 A
Title: CT-NGT21
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 1.000 A 0.00 ° 50.000 Hz
I L2 0.00 A -120.00 ° 50.000 Hz
I L3 0.00 A 120.00 ° 50.000 Hz
Generator Settings
I L1 1.000A 0.00° +90°
I L1
180° 0°
1.0 A -90°
I L2 0.000A -120.00°
I L3 0.000A 120.00°
Binary Inputs
Name Slope Time
TRIP 0
Overload 0
Page 15 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
Comment
CT-05 = 500.9 A
Summary
22 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed
Title: VT-3/R
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V(1)-1 63.51 V 0.00 ° 50.000 Hz
V(1)-2 0.00 V -120.00 ° 50.000 Hz
V(1)-3 0.00 V 120.00 ° 50.000 Hz
Generator Settings
V(1)-1 63.509V 0.00° +90°
V(1)-1
180° 0°
80.0 V -90°
V(1)-2 0.000V -120.00°
V(1)-3 0.000V 120.00°
Binary Inputs
Name Slope Time
TRIP 0
Comment
VT-01 = 7.964 kV
VT-02 = 0 kV
VT-03 = 0 kV
Title: VT-3/Y
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V(1)-1 0.00 V 0.00 ° 50.000 Hz
V(1)-2 63.51 V -120.00 ° 50.000 Hz
V(1)-3 0.00 V 120.00 ° 50.000 Hz
Generator Settings
V(1)-1 0.000V 0.00° +90°
180° 0°
V(1)-2
80.0 V -90°
Page 16 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
Binary Inputs
Name Slope Time
TRIP 0
Comment
VT-01 = 0 kV
VT-02 = 7.965 kV
VT-03 = 0 kV
Title: VT-3/B
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V(1)-1 0.00 V 0.00 ° 50.000 Hz
V(1)-2 0.00 V -120.00 ° 50.000 Hz
V(1)-3 63.51 V 120.00 ° 50.000 Hz
Generator Settings
V(1)-1 0.000V 0.00° +90°
V(1)-3
180° 0°
80.0 V -90°
V(1)-2 0.000V -120.00°
V(1)-3 63.509V 120.00°
Binary Inputs
Name Slope Time
TRIP 0
Comment
VT-01 = 0 kV
VT-02 = 0 kV
VT-03 = 7.963 kV
Title: VT-3/RYB
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V(1)-1 63.51 V 0.00 ° 50.000 Hz
V(1)-2 63.51 V -120.00 ° 50.000 Hz
V(1)-3 63.51 V 120.00 ° 50.000 Hz
Generator Settings
Page 17 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
V(1)-3
V(1)-1
180° 0°
V(1)-2
80.0 V -90°
V(1)-2 63.509V -120.00°
V(1)-3 63.509V 120.00°
Binary Inputs
Name Slope Time
TRIP 0
Comment
VT-01 = 7.964 kV
VT-02 = 7.965 kV
VT-03 = 7.962 kV
Title: VT-1/R
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V(1)-1 63.51 V 0.00 ° 50.000 Hz
V(1)-2 0.00 V -120.00 ° 50.000 Hz
V(1)-3 0.00 V 120.00 ° 50.000 Hz
Generator Settings
V(1)-1 63.509V 0.00° +90°
V(1)-1
180° 0°
80.0 V -90°
V(1)-2 0.000V -120.00°
V(1)-3 0.000V 120.00°
Binary Inputs
Name Slope Time
TRIP 0
Comment
VT-04 = 7.967 kV
VT-05 = 0 kV
VT-06 = 0 kV
Title: VT-1/Y
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V(1)-1 0.00 V 0.00 ° 50.000 Hz
Page 18 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
Generator Settings
V(1)-1 0.000V 0.00° +90°
180° 0°
V(1)-2
80.0 V -90°
V(1)-2 63.509V -120.00°
V(1)-3 0.000V 120.00°
Binary Inputs
Name Slope Time
TRIP 0
Comment
VT-04 = 0 kV
VT-05 = 7.966 kV
VT-06 = 0 kV
Title: VT-1/B
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V(1)-1 0.00 V 0.00 ° 50.000 Hz
V(1)-2 0.00 V -120.00 ° 50.000 Hz
V(1)-3 63.51 V 120.00 ° 50.000 Hz
Generator Settings
V(1)-1 0.000V 0.00° +90°
V(1)-3
180° 0°
80.0 V -90°
V(1)-2 0.000V -120.00°
V(1)-3 63.509V 120.00°
Binary Inputs
Name Slope Time
TRIP 0
Comment
VT-04 = 0 kV
VT-05 = 0 kV
VT-06 = 7968 kV
Title: VT-1/RYB
Page 19 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V(1)-1 63.51 V 0.00 ° 50.000 Hz
V(1)-2 63.51 V -120.00 ° 50.000 Hz
V(1)-3 63.51 V 120.00 ° 50.000 Hz
Generator Settings
V(1)-1 63.509V 0.00° +90°
V(1)-3
V(1)-1
180° 0°
V(1)-2
80.0 V -90°
V(1)-2 63.509V -120.00°
V(1)-3 63.509V 120.00°
Binary Inputs
Name Slope Time
TRIP 0
Comment
VT-04 = 7.967 kV
VT-05 = 7.966 kV
VT-06 = 7.967 kV
Summary
8 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed
Test Settings
.
General
No. of ramp states: 1
Total steps per test: 21
Total time per test: 16.800 s
No. of test executions: 1
Ramped Quantities
I(1)-1 / Magnitude
.
Page 20 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
Ramp States
Ramp Ramp 1
I L1 0.00 A
0.00 °
50.000 Hz
I L2 0.00 A
-120.00 °
50.000 Hz
I L3 0.00 A
120.00 °
50.000 Hz
I(1)-1 800.0 mA
0.00 °
50.000 Hz
I(1)-2 0.00 A
-120.00 °
50.000 Hz
I(1)-3 0.00 A
120.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 800.0 mA
Sig 1 To 900.0 mA
Sig 1 Delta 5.000 mA
Sig 1 d/dt 6.250 mA/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 800.0 ms
Ramp Steps 21
Ramp Time 16.800s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s
. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 06-Jun-2023 10:09:45 Test End: 06-Jun-2023 10:09:55
User Name: Manager:
Company:
Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 I(1)-1 850.0 mA 850.0 mA 25.50 mA 25.50 mA 0.00 A + 57.70 ms
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed
Test Settings
.
General
No. of ramp states: 1
Total steps per test: 21
Total time per test: 16.800 s
No. of test executions: 1
Ramped Quantities
I(1)-2 / Magnitude
.
Ramp States
Ramp Ramp 1
I L1 0.00 A
0.00 °
50.000 Hz
I L2 0.00 A
-120.00 °
50.000 Hz
I L3 0.00 A
120.00 °
50.000 Hz
I(1)-1 0.00 A
0.00 °
50.000 Hz
I(1)-2 800.0 mA
-120.00 °
50.000 Hz
I(1)-3 0.00 A
120.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 800.0 mA
Sig 1 To 900.0 mA
Sig 1 Delta 5.000 mA
Sig 1 d/dt 6.250 mA/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 800.0 ms
Ramp Steps 21
Ramp Time 16.800s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s
Page 22 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 06-Jun-2023 10:08:50 Test End: 06-Jun-2023 10:09:00
User Name: Manager:
Company:
Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 I(1)-2 850.0 mA 850.0 mA 25.50 mA 25.50 mA 0.00 A + 35.60 ms
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed
Test Settings
.
General
No. of ramp states: 1
Total steps per test: 21
Total time per test: 16.800 s
No. of test executions: 1
Ramped Quantities
I(1)-3 / Magnitude
.
Ramp States
Ramp Ramp 1
I L1 0.00 A
0.00 °
50.000 Hz
I L2 0.00 A
-120.00 °
50.000 Hz
I L3 0.00 A
120.00 °
50.000 Hz
I(1)-1 0.00 A
0.00 °
50.000 Hz
I(1)-2 0.00 A
-120.00 °
50.000 Hz
I(1)-3 800.0 mA
120.00 °
Page 23 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
50.000 Hz
Force abs. Phases No
Sig 1 From 800.0 mA
Sig 1 To 900.0 mA
Sig 1 Delta 5.000 mA
Sig 1 d/dt 6.250 mA/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 800.0 ms
Ramp Steps 21
Ramp Time 16.800s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s
. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 06-Jun-2023 10:11:35 Test End: 06-Jun-2023 10:11:45
User Name: Manager:
Company:
Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 I(1)-3 850.0 mA 850.0 mA 25.50 mA 25.50 mA 0.00 A + 47.90 ms
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed
Test Settings
.
General
No. of ramp states: 1
Total steps per test: 21
Total time per test: 16.800 s
No. of test executions: 1
Ramped Quantities
I(1)-1, -2, -3 / Magnitude
.
Ramp States
Ramp Ramp 1
I L1 0.00 A
Page 24 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
0.00 °
50.000 Hz
I L2 0.00 A
-120.00 °
50.000 Hz
I L3 0.00 A
120.00 °
50.000 Hz
I(1)-1 800.0 mA
0.00 °
50.000 Hz
I(1)-2 800.0 mA
-120.00 °
50.000 Hz
I(1)-3 800.0 mA
120.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 800.0 mA
Sig 1 To 900.0 mA
Sig 1 Delta 5.000 mA
Sig 1 d/dt 6.250 mA/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 800.0 ms
Ramp Steps 21
Ramp Time 16.800s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s
. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 06-Jun-2023 10:12:53 Test End: 06-Jun-2023 10:13:03
User Name: Manager:
Company:
Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 I(1)-1, -2, 850.0 mA 850.0 mA 25.50 mA 25.50 mA 0.00 A + 44.30 ms
-3
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed
Test Settings
Page 25 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
.
General
No. of ramp states: 1
Total steps per test: 21
Total time per test: 16.800 s
No. of test executions: 1
Ramped Quantities
I L1 / Magnitude
.
Ramp States
Ramp Ramp 1
I L1 800.0 mA
0.00 °
50.000 Hz
I L2 0.00 A
-120.00 °
50.000 Hz
I L3 0.00 A
120.00 °
50.000 Hz
I(1)-1 0.00 A
0.00 °
50.000 Hz
I(1)-2 0.00 A
-120.00 °
50.000 Hz
I(1)-3 0.00 A
120.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 800.0 mA
Sig 1 To 900.0 mA
Sig 1 Delta 5.000 mA
Sig 1 d/dt 6.250 mA/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 800.0 ms
Ramp Steps 21
Ramp Time 16.800s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s
. .
Test Module
Page 26 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 I L1 850.0 mA 850.0 mA 25.50 mA 25.50 mA 0.00 A + 36.30 ms
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed
Gen. Terminal Pickup L2:
Test Settings
.
General
No. of ramp states: 1
Total steps per test: 21
Total time per test: 16.800 s
No. of test executions: 1
Ramped Quantities
I L2 / Magnitude
.
Ramp States
Ramp Ramp 1
I L1 0.00 A
0.00 °
50.000 Hz
I L2 800.0 mA
-120.00 °
50.000 Hz
I L3 0.00 A
120.00 °
50.000 Hz
I(1)-1 0.00 A
0.00 °
50.000 Hz
I(1)-2 0.00 A
-120.00 °
50.000 Hz
I(1)-3 0.00 A
120.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 800.0 mA
Sig 1 To 900.0 mA
Page 27 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 06-Jun-2023 10:15:19 Test End: 06-Jun-2023 10:15:29
User Name: Manager:
Company:
Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 I L2 850.0 mA 850.0 mA 25.50 mA 25.50 mA 0.00 A + 169.6 ms
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed
Test Settings
.
General
No. of ramp states: 1
Total steps per test: 21
Total time per test: 16.800 s
No. of test executions: 1
Ramped Quantities
I L3 / Magnitude
.
Ramp States
Ramp Ramp 1
I L1 0.00 A
0.00 °
50.000 Hz
I L2 0.00 A
-120.00 °
Page 28 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
50.000 Hz
I L3 800.0 mA
120.00 °
50.000 Hz
I(1)-1 0.00 A
0.00 °
50.000 Hz
I(1)-2 0.00 A
-120.00 °
50.000 Hz
I(1)-3 0.00 A
120.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 800.0 mA
Sig 1 To 900.0 mA
Sig 1 Delta 5.000 mA
Sig 1 d/dt 6.250 mA/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 800.0 ms
Ramp Steps 21
Ramp Time 16.800s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s
. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 06-Jun-2023 10:17:09 Test End: 06-Jun-2023 10:17:19
User Name: Manager:
Company:
Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 I L3 850.0 mA 850.0 mA 25.50 mA 25.50 mA 0.00 A + 39.60 ms
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed
Test Settings
.
General
No. of ramp states: 1
Total steps per test: 21
Page 29 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
Ramped Quantities
I L1, L2, L3 / Magnitude
.
Ramp States
Ramp Ramp 1
I L1 800.0 mA
0.00 °
50.000 Hz
I L2 800.0 mA
-120.00 °
50.000 Hz
I L3 800.0 mA
120.00 °
50.000 Hz
I(1)-1 0.00 A
0.00 °
50.000 Hz
I(1)-2 0.00 A
-120.00 °
50.000 Hz
I(1)-3 0.00 A
120.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 800.0 mA
Sig 1 To 900.0 mA
Sig 1 Delta 5.000 mA
Sig 1 d/dt 6.250 mA/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 800.0 ms
Ramp Steps 21
Ramp Time 16.800s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s
. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 06-Jun-2023 10:19:12 Test End: 06-Jun-2023 10:19:22
User Name: Manager:
Company:
Page 30 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 I L1, L2, 850.0 mA 850.0 mA 25.50 mA 25.50 mA 0.00 A + 36.50 ms
L3
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed
Test Results
Title: Gen. Terminal L1
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 1.700 A 0.00 ° 50.000 Hz
I L2 0.00 A -120.00 ° 50.000 Hz
I L3 0.00 A 120.00 ° 50.000 Hz
Generator Settings
I L1 1.700A 0.00° +90°
I L1
180° 0°
2.0 A -90°
I L2 0.000A -120.00°
I L3 0.000A 120.00°
I(1)-1 0.000A 0.00°
I(1)-2 0.000A -120.00°
I(1)-3 0.000A 120.00°
Binary Inputs
Name Slope Time
TRIP 0->1 0.036s
Overload 1->0 n/a
Comment
Actual Trip time = 0 second (Instantaneous trip)
Page 31 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 0.00 A 0.00 ° 50.000 Hz
I L2 1.700 A -120.00 ° 50.000 Hz
I L3 0.00 A 120.00 ° 50.000 Hz
Generator Settings
I L1 0.000A 0.00° +90°
180° 0°
I L2
2.0 A -90°
I L2 1.700A -120.00°
I L3 0.000A 120.00°
I(1)-1 0.000A 0.00°
I(1)-2 0.000A -120.00°
I(1)-3 0.000A 120.00°
Binary Inputs
Name Slope Time
TRIP 0->1 0.033s
Overload 1->0 n/a
Comment
Actual Trip time = 0 second (Instantaneous trip)
Generator Settings
I L1 0.000A 0.00° +90°
I L3
180° 0°
2.0 A -90°
I L2 0.000A -120.00°
I L3 1.700A 120.00°
I(1)-1 0.000A 0.00°
I(1)-2 0.000A -120.00°
I(1)-3 0.000A 120.00°
Page 32 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
Binary Inputs
Name Slope Time
TRIP 0->1 0.036s
Overload 1->0 n/a
Comment
Actual Trip time = 0 second (Instantaneous trip)
Generator Settings
I L1 1.700A 0.00° +90°
I L3
I L1
180° 0°
I L2
2.0 A -90°
I L2 1.700A -120.00°
I L3 1.700A 120.00°
I(1)-1 0.000A 0.00°
I(1)-2 0.000A -120.00°
I(1)-3 0.000A 120.00°
Binary Inputs
Name Slope Time
TRIP 0->1 0.034s
Overload 1->0 n/a
Comment
Actual Trip time = 0 second (Instantaneous trip)
Generator Settings
Page 33 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
I(1)-1
180° 0°
2.0 A -90°
I L2 0.000A -120.00°
I L3 0.000A 120.00°
I(1)-1 1.700A 0.00°
I(1)-2 0.000A -120.00°
I(1)-3 0.000A 120.00°
Binary Inputs
Name Slope Time
TRIP 0->1 0.036s
Overload 1->0 n/a
Comment
Actual Trip time = 0 second (Instantaneous trip)
Generator Settings
I L1 0.000A 0.00° +90°
180° 0°
I(1)-2
2.0 A -90°
I L2 0.000A -120.00°
I L3 0.000A 120.00°
I(1)-1 0.000A 0.00°
I(1)-2 1.700A -120.00°
I(1)-3 0.000A 120.00°
Binary Inputs
Name Slope Time
TRIP 0->1 0.033s
Overload 1->0 n/a
Comment
Page 34 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
Generator Settings
I L1 0.000A 0.00° +90°
I(1)-3
180° 0°
2.0 A -90°
I L2 0.000A -120.00°
I L3 0.000A 120.00°
I(1)-1 0.000A 0.00°
I(1)-2 0.000A -120.00°
I(1)-3 1.700A 120.00°
Binary Inputs
Name Slope Time
TRIP 0->1 0.036s
Overload 1->0 n/a
Comment
Actual Trip time = 0 second (Instantaneous trip)
Generator Settings
I L1 0.000A 0.00° +90°
I(1)-3
I(1)-1
180° 0°
I(1)-2
2.0 A -90°
I L2 0.000A -120.00°
I L3 0.000A 120.00°
Page 35 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
Binary Inputs
Name Slope Time
TRIP 0->1 0.033s
Overload 1->0 n/a
Comment
Actual Trip time = 0 second (Instantaneous trip)
Summary
8 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed
3.3 Stability Test
Test Results
Title: Test 1
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 850.0 mA 0.00 ° 50.000 Hz
I L2 850.0 mA -120.00 ° 50.000 Hz
I L3 850.0 mA 120.00 ° 50.000 Hz
Generator Settings
I L1 0.850A 0.00° +90°
I L3 I(1)-2
I(1)-1 I L1
180° 0°
I L2 I(1)-3
1.0 A -90°
I L2 0.850A -120.00°
I L3 0.850A 120.00°
I(1)-1 0.850A 180.00°
I(1)-2 0.850A 60.00°
I(1)-3 0.850A 300.00°
Page 36 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
Binary Inputs
Name Slope Time
TRIP 0
Overload 0
Comment
Id1 = 0.012 kA, Ir1 = 2.046 kA
Id2 = 0.012 kA, Ir2 = 2.042 kA
Id3 = 0.010 kA, Ir3 = 2.045 kA
Therefore, No Trip.
Summary
1 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed
Test Results
Title: Test 1
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 850.0 mA 0.00 ° 50.000 Hz
I L2 850.0 mA -120.00 ° 50.000 Hz
I L3 850.0 mA 120.00 ° 50.000 Hz
Generator Settings
I L1 0.850A 0.00° +90°
I(1)-3
I L3
I(1)-1
I L1
180° 0°
I(1)-2
I L2
1.0 A -90°
I L2 0.850A -120.00°
I L3 0.850A 120.00°
I(1)-1 0.850A 0.00°
I(1)-2 0.850A -120.00°
I(1)-3 0.850A 120.00°
Binary Inputs
Name Slope Time
TRIP 1
Page 37 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
Overload 0
Comment
Id1 = 4.088 kA, Ir1 = 2.043 kA
Id2 = 4.085 kA, Ir2 = 2.043 kA
Id3 = 4.091 kA, Ir3 = 2.045 kA
Therefore, Relay Tripped.
Summary
1 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed
Test Settings
.
General
No. of ramp states: 1
Total steps per test: 61
Total time per test: 6.100 s
No. of test executions: 1
Ramped Quantities
I L1 / Magnitude
.
Ramp States
Ramp Ramp 1
I L1 150.0 mA
0.00 °
50.000 Hz
I L2 0.00 A
-120.00 °
50.000 Hz
I L3 0.00 A
120.00 °
50.000 Hz
I(1)-1 0.00 A
0.00 °
50.000 Hz
I(1)-2 0.00 A
-120.00 °
50.000 Hz
I(1)-3 0.00 A
Page 38 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
120.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 150.0 mA
Sig 1 To 210.0 mA
Sig 1 Delta 1.000 mA
Sig 1 d/dt 10.00 mA/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 61
Ramp Time 6.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s
. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 06-Jun-2023 11:51:01 Test End: 06-Jun-2023 11:51:08
User Name: Manager:
Company:
Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 I L1 195.0 mA 196.0 mA 5.850 mA 5.850 mA 1.000 mA + 35.40 ms
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed
Test Settings
.
General
No. of ramp states: 1
Total steps per test: 61
Total time per test: 6.100 s
No. of test executions: 1
Ramped Quantities
I L2 / Magnitude
.
Ramp States
Page 39 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
Ramp Ramp 1
I L1 0.00 A
0.00 °
50.000 Hz
I L2 150.0 mA
-120.00 °
50.000 Hz
I L3 0.00 A
120.00 °
50.000 Hz
I(1)-1 0.00 A
0.00 °
50.000 Hz
I(1)-2 0.00 A
-120.00 °
50.000 Hz
I(1)-3 0.00 A
120.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 150.0 mA
Sig 1 To 210.0 mA
Sig 1 Delta 1.000 mA
Sig 1 d/dt 10.00 mA/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 61
Ramp Time 6.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s
. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 06-Jun-2023 11:52:58 Test End: 06-Jun-2023 11:53:05
User Name: Manager:
Company:
Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 I L2 195.0 mA 195.0 mA 5.850 mA 5.850 mA 0.00 A + 34.40 ms
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed
Page 40 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
Test Settings
.
General
No. of ramp states: 1
Total steps per test: 61
Total time per test: 6.100 s
No. of test executions: 1
Ramped Quantities
I L3 / Magnitude
.
Ramp States
Ramp Ramp 1
I L1 0.00 A
0.00 °
50.000 Hz
I L2 0.00 A
-120.00 °
50.000 Hz
I L3 150.0 mA
120.00 °
50.000 Hz
I(1)-1 0.00 A
0.00 °
50.000 Hz
I(1)-2 0.00 A
-120.00 °
50.000 Hz
I(1)-3 0.00 A
120.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 150.0 mA
Sig 1 To 210.0 mA
Sig 1 Delta 1.000 mA
Sig 1 d/dt 10.00 mA/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 61
Ramp Time 6.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s
. .
Page 41 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 06-Jun-2023 11:54:32 Test End: 06-Jun-2023 11:54:38
User Name: Manager:
Company:
Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 I L3 195.0 mA 194.0 mA 5.850 mA 5.850 mA -1.000 mA + 41.40 ms
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed
Test Settings
.
General
No. of ramp states: 1
Total steps per test: 21
Total time per test: 21.000 s
No. of test executions: 1
Ramped Quantities
I L1, L2, L3 / Magnitude
.
Ramp States
Ramp Ramp 1
I L1 120.0 mA
0.00 °
50.000 Hz
I L2 120.0 mA
-120.00 °
50.000 Hz
I L3 120.0 mA
120.00 °
50.000 Hz
I(1)-1 0.00 A
0.00 °
50.000 Hz
I(1)-2 0.00 A
-120.00 °
50.000 Hz
I(1)-3 0.00 A
120.00 °
50.000 Hz
Force abs. Phases Yes
Page 42 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 06-Jun-2023 11:56:17 Test End: 06-Jun-2023 11:56:29
User Name: Manager:
Company:
Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 I L1, L2, 130.0 mA 130.0 mA 3.900 mA 3.900 mA 0.00 A + 37.80 ms
L3
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed
Test Settings
.
General
No. of ramp states: 1
Total steps per test: 201
Total time per test: 20.100 s
No. of test executions: 1
Ramped Quantities
I(1)-1 / Magnitude
.
Ramp States
Ramp Ramp 1
I L1 0.00 A
0.00 °
Page 43 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
50.000 Hz
I L2 0.00 A
-120.00 °
50.000 Hz
I L3 0.00 A
120.00 °
50.000 Hz
I(1)-1 1.300 A
0.00 °
50.000 Hz
I(1)-2 0.00 A
-120.00 °
50.000 Hz
I(1)-3 0.00 A
120.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 1.300 A
Sig 1 To 1.700 A
Sig 1 Delta 2.000 mA
Sig 1 d/dt 20.00 mA/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 201
Ramp Time 20.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s
. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 06-Jun-2023 11:59:11 Test End: 06-Jun-2023 11:59:21
User Name: Manager:
Company:
Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 I(1)-1 1.482 A 1.446 A 44.40 mA 44.40 mA -36.00 mA + 22.20 ms
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed
Test Settings
.
General
Page 44 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
Ramped Quantities
I(1)-2 / Magnitude
.
Ramp States
Ramp Ramp 1
I L1 0.00 A
0.00 °
50.000 Hz
I L2 0.00 A
-120.00 °
50.000 Hz
I L3 0.00 A
120.00 °
50.000 Hz
I(1)-1 0.00 A
0.00 °
50.000 Hz
I(1)-2 1.300 A
-120.00 °
50.000 Hz
I(1)-3 0.00 A
120.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 1.300 A
Sig 1 To 1.700 A
Sig 1 Delta 2.000 mA
Sig 1 d/dt 20.00 mA/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 201
Ramp Time 20.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s
. .
Test Module
Name: OMICRON Ramping Version: 4.30
Page 45 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 I(1)-2 1.482 A 1.444 A 44.40 mA 44.40 mA -38.00 mA + 44.90 ms
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed
Test Settings
.
General
No. of ramp states: 1
Total steps per test: 201
Total time per test: 20.100 s
No. of test executions: 1
Ramped Quantities
I(1)-3 / Magnitude
.
Ramp States
Ramp Ramp 1
I L1 0.00 A
0.00 °
50.000 Hz
I L2 0.00 A
-120.00 °
50.000 Hz
I L3 0.00 A
120.00 °
50.000 Hz
I(1)-1 0.00 A
0.00 °
50.000 Hz
I(1)-2 0.00 A
-120.00 °
50.000 Hz
I(1)-3 1.300 A
120.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 1.300 A
Sig 1 To 1.700 A
Page 46 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 06-Jun-2023 12:01:34 Test End: 06-Jun-2023 12:01:43
User Name: Manager:
Company:
Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 I(1)-3 1.482 A 1.442 A 44.40 mA 44.40 mA -40.00 mA + 46.70 ms
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed
Test Settings
.
General
No. of ramp states: 1
Total steps per test: 31
Total time per test: 31.000 s
No. of test executions: 1
Ramped Quantities
I(1)-1, -2, -3 / Magnitude
.
Ramp States
Ramp Ramp 1
I L1 0.00 A
0.00 °
20.000 Hz
I L2 0.00 A
-120.00 °
Page 47 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
50.000 Hz
I L3 0.00 A
120.00 °
50.000 Hz
I(1)-1 750.0 mA
0.00 °
50.000 Hz
I(1)-2 750.0 mA
-120.00 °
50.000 Hz
I(1)-3 750.0 mA
120.00 °
50.000 Hz
Force abs. Phases Yes
Sig 1 From 750.0 mA
Sig 1 To 1.200 A
Sig 1 Delta 15.00 mA
Sig 1 d/dt 15.00 mA/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 1.000 s
Ramp Steps 31
Ramp Time 31.000s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s
. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 06-Jun-2023 12:05:10 Test End: 06-Jun-2023 12:05:18
User Name: Manager:
Company:
Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 I(1)-1, -2, 856.0 mA 840.0 mA 25.68 mA 25.68 mA -16.00 mA + 37.80 ms
-3
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed
Test Results
Title: Trans. HV side L1
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 390.0 mA 0.00 ° 50.000 Hz
I L2 0.00 A -120.00 ° 50.000 Hz
I L3 0.00 A 120.00 ° 50.000 Hz
Generator Settings
I L1 0.390A 0.00° +90°
I L1
180° 0°
400.0 mA -90°
I L2 0.000A -120.00°
I L3 0.000A 120.00°
I(1)-1 0.000A 0.00°
I(1)-2 0.000A -120.00°
I(1)-3 0.000A 120.00°
Binary Inputs
Name Slope Time
TRIP 0->1 0.037s
Overload 1->0 n/a
Comment
Actual Triptime = 0 second. (Instantaneous trip)
Generator Settings
I L1 0.000A 0.00° +90°
180° 0°
I L2
400.0 mA -90°
I L2 0.390A -120.00°
Page 49 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
I L3 0.000A 120.00°
I(1)-1 0.000A 0.00°
I(1)-2 0.000A -120.00°
I(1)-3 0.000A 120.00°
Binary Inputs
Name Slope Time
TRIP 0->1 0.033s
Overload 1->0 n/a
Comment
Actual Triptime = 0 second. (Instantaneous trip)
Generator Settings
I L1 0.000A 0.00° +90°
I L3
180° 0°
400.0 mA -90°
I L2 0.000A -120.00°
I L3 0.390A 120.00°
I(1)-1 0.000A 0.00°
I(1)-2 0.000A -120.00°
I(1)-3 0.000A 120.00°
Binary Inputs
Name Slope Time
TRIP 0->1 0.037s
Overload 1->0 n/a
Comment
Actual Triptime = 0 second. (Instantaneous trip)
Generator Settings
Page 50 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
I L3
I L1
180° 0°
I L2
300.0 mA -90°
I L2 0.260A -120.00°
I L3 0.260A 120.00°
I(1)-1 0.000A 0.00°
I(1)-2 0.000A -120.00°
I(1)-3 0.000A 120.00°
Binary Inputs
Name Slope Time
TRIP 0->1 0.033s
Overload 1->0 n/a
Comment
Actual Triptime = 0 second. (Instantaneous trip)
Generator Settings
I L1 0.000A 0.00° +90°
I(1)-1
180° 0°
3.0 A -90°
I L2 0.000A -120.00°
I L3 0.000A 120.00°
I(1)-1 2.960A 0.00°
I(1)-2 0.000A -120.00°
I(1)-3 0.000A 120.00°
Binary Inputs
Name Slope Time
TRIP 0->1 0.035s
Overload 1->0 n/a
Comment
Page 51 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
Generator Settings
I L1 0.000A 0.00° +90°
180° 0°
I(1)-2
3.0 A -90°
I L2 0.000A -120.00°
I L3 0.000A 120.00°
I(1)-1 0.000A 0.00°
I(1)-2 2.960A -120.00°
I(1)-3 0.000A 120.00°
Binary Inputs
Name Slope Time
TRIP 0->1 0.033s
Overload 1->0 n/a
Comment
Actual Triptime = 0 second. (Instantaneous trip)
Generator Settings
I L1 0.000A 0.00° +90°
I(1)-3
180° 0°
3.0 A -90°
I L2 0.000A -120.00°
I L3 0.000A 120.00°
Page 52 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
Binary Inputs
Name Slope Time
TRIP 0->1 0.038s
Overload 1->0 n/a
Comment
Actual Triptime = 0 second. (Instantaneous trip)
Generator Settings
I L1 0.000A 0.00° +90°
I(1)-3
I(1)-1
180° 0°
I(1)-2
2.0 A -90°
I L2 0.000A -120.00°
I L3 0.000A 120.00°
I(1)-1 1.712A 0.00°
I(1)-2 1.712A -120.00°
I(1)-3 1.712A 120.00°
Binary Inputs
Name Slope Time
TRIP 0->1 0.035s
Overload 1->0 n/a
Comment
Actual Triptime = 0 second. (Instantaneous trip)
Summary
8 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed
Test Module
Name: OMICRON QuickCMC Version: 4.30
Test Start: 06-Jun-2023 12:07:51 Test End: 06-Jun-2023 12:10:05
User Name: Manager:
Company:
Test Results
Title: Test 1
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 130.0 mA 0.00 ° 50.000 Hz
I L2 130.0 mA -120.00 ° 50.000 Hz
I L3 130.0 mA 120.00 ° 50.000 Hz
Generator Settings
I L1 0.130A 0.00° +90°
I(1)-3
I L1 I(1)-1
I L2
L3
180° 0°
I(1)-2
1.0 A -90°
I L2 0.130A -120.00°
I L3 0.130A 120.00°
I(1)-1 0.856A 0.00°
I(1)-2 0.856A -120.00°
I(1)-3 0.856A 120.00°
Binary Inputs
Name Slope Time
TRIP 1
Overload 0
Comment
Id1 = 127.5 A, Ir1 = 66.7 A
Id2 = 127.4 A, Ir2 = 66.8 A
Id3 = 127.5 A, Ir3 = 66.7 A
Therefore, Relay Tripped.
Summary
1 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed
Page 54 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
Test Results
Title: Test 1
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 130.0 mA 0.00 ° 50.000 Hz
I L2 130.0 mA -120.00 ° 50.000 Hz
I L3 130.0 mA 120.00 ° 50.000 Hz
Generator Settings
I L1 0.130A 0.00° +90°
I(1)-2
I(1)-1 I L1
I L2
L3
180° 0°
I(1)-3
1.0 A -90°
I L2 0.130A -120.00°
I L3 0.130A 120.00°
I(1)-1 0.856A 180.00°
I(1)-2 0.856A 60.00°
I(1)-3 0.856A 300.00°
Binary Inputs
Name Slope Time
TRIP 0
Overload 0
Comment
Id1 = 34.3 A, Ir1 = 66.7 A
Id2 = 34.2 A, Ir2 = 66.7 A
Id3 = 34.4 A, Ir3 = 66.8 A
Therefore, No Trip.
Summary
1 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed
Pickup L1:
Test Settings
Page 55 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
.
General
No. of ramp states: 1
Total steps per test: 61
Total time per test: 6.100 s
No. of test executions: 1
Ramped Quantities
I L1 / Magnitude
.
Ramp States
Ramp Ramp 1
I L1 900.0 mA
0.00 °
50.000 Hz
I L2 0.00 A
-120.00 °
50.000 Hz
I L3 0.00 A
120.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 900.0 mA
Sig 1 To 1.200 A
Sig 1 Delta 5.000 mA
Sig 1 d/dt 50.00 mA/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 61
Ramp Time 6.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s
. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 06-Jun-2023 12:36:04 Test End: 06-Jun-2023 12:36:08
User Name: Manager:
Company:
Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 I L1 1.020 A 1.020 A 30.60 mA 30.60 mA 0.00 A + 48.00 ms
Assess: + .. Passed x .. Failed o .. Not assessed
Page 56 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
Test State:
Test passed
Test Settings
.
General
No. of ramp states: 1
Total steps per test: 61
Total time per test: 6.100 s
No. of test executions: 1
Ramped Quantities
I L2 / Magnitude
.
Ramp States
Ramp Ramp 1
I L1 0.00 A
0.00 °
50.000 Hz
I L2 900.0 mA
-120.00 °
50.000 Hz
I L3 0.00 A
120.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 900.0 mA
Sig 1 To 1.200 A
Sig 1 Delta 5.000 mA
Sig 1 d/dt 50.00 mA/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 61
Ramp Time 6.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s
. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 06-Jun-2023 12:37:34 Test End: 06-Jun-2023 12:37:38
Page 57 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 I L2 1.020 A 1.020 A 30.60 mA 30.60 mA 0.00 A + 43.60 ms
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed
Test Settings
.
General
No. of ramp states: 1
Total steps per test: 61
Total time per test: 6.100 s
No. of test executions: 1
Ramped Quantities
I L3 / Magnitude
.
Ramp States
Ramp Ramp 1
I L1 0.00 A
0.00 °
50.000 Hz
I L2 0.00 A
-120.00 °
50.000 Hz
I L3 900.0 mA
120.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 900.0 mA
Sig 1 To 1.200 A
Sig 1 Delta 5.000 mA
Sig 1 d/dt 50.00 mA/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 61
Ramp Time 6.100s
Trigger Bin
Trigger Logic OR
Page 58 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
TRIP 1
Step back No
Delay Time 0.00 s
. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 06-Jun-2023 12:38:51 Test End: 06-Jun-2023 12:38:55
User Name: Manager:
Company:
Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 I L3 1.020 A 1.015 A 30.60 mA 30.60 mA -5.000 mA + 93.30 ms
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed
Test Results
Title: Triptime L1
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 2.040 A 0.00 ° 50.000 Hz
I L2 0.00 A -120.00 ° 50.000 Hz
I L3 0.00 A 120.00 ° 50.000 Hz
Generator Settings
I L1 2.040A 0.00° +90°
I L1
180° 0°
3.0 A -90°
I L2 0.000A -120.00°
I L3 0.000A 120.00°
Binary Inputs
Name Slope Time
Page 59 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
Title: Triptime L2
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 0.00 A 0.00 ° 50.000 Hz
I L2 2.040 A -120.00 ° 50.000 Hz
I L3 0.00 A 120.00 ° 50.000 Hz
Generator Settings
I L1 0.000A 0.00° +90°
180° 0°
I L2
3.0 A -90°
I L2 2.040A -120.00°
I L3 0.000A 120.00°
Binary Inputs
Name Slope Time
TRIP 0->1 5.042s
Overload 1->0 n/a
Comment
Actual Triptime = 5 seconds.
Title: Triptime L3
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 0.00 A 0.00 ° 50.000 Hz
I L2 0.00 A -120.00 ° 50.000 Hz
I L3 2.040 A 120.00 ° 50.000 Hz
Generator Settings
I L1 0.000A 0.00° +90°
I L3
180° 0°
3.0 A -90°
I L2 0.000A -120.00°
I L3 2.040A 120.00°
Page 60 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
Binary Inputs
Name Slope Time
TRIP 0->1 5.049s
Overload 1->0 n/a
Comment
Actual Triptime = 5 seconds.
Summary
3 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed
Test Results
Title: Test 1
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 21.30 A 0.00 ° 50.000 Hz
I L2 0.00 A -120.00 ° 50.000 Hz
I L3 0.00 A 120.00 ° 50.000 Hz
Generator Settings
I L1 21.300A 0.00° +90°
I L1
180° 0°
30.0 A -90°
I L2 0.000A -120.00°
I L3 0.000A 120.00°
Binary Inputs
Name Slope Time
TRIP 0->1 44.705s
Overload 1->0 n/a
Page 61 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
Comment
Actual Triptime = 44.99 seconds.
Summary
1 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed
Test Results
Title: Test 1
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 21.30 A 0.00 ° 50.000 Hz
I L2 21.30 A -120.00 ° 50.000 Hz
I L3 21.30 A 120.00 ° 50.000 Hz
Generator Settings
I L1 21.300A 0.00° +90°
I L3
I L1
180° 0°
I L2
30.0 A -90°
I L2 21.300A -120.00°
I L3 21.300A 120.00°
Binary Inputs
Name Slope Time
TRIP 0->1 44.712s
Overload 1->0 n/a
Comment
Operate Value load = 110 degree celcius
Calculated Triptime = 44.99 seconds
Summary
1 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed
Page 62 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
Test Results
Title: Test 1
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V L1-E 63.51 V 0.00 ° 50.000 Hz
V L2-E 63.51 V -120.00 ° 50.000 Hz
V L3-E 63.51 V 120.00 ° 50.000 Hz
I(1)-1 115.0 mA 180.00 ° 50.000 Hz
I(1)-2 115.0 mA 60.00 ° 50.000 Hz
I(1)-3 115.0 mA 300.00 ° 50.000 Hz
Generator Settings
V L1-E 63.510V 0.00° +90°
V L3-E I(1)-2
I(1)-1 V L1-E
180° 0°
V L2-E I(1)-3
Binary Inputs
Name Slope Time
TRIP 0
Overload 0
Comment
Currently, the relay does not trip as the power is:
P = 110V x 0.115 A x 1.732
= 21.9 Watt.
Title: Test 2
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Page 63 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
Generator Settings
V L1-E 63.510V 0.00° +90°
V I(1)-3
L3-E
VI(1)-1
L1-E
180° 0°
V I(1)-2
L2-E
Binary Inputs
Name Slope Time
TRIP 0->1 0.061s
Overload 1->0 n/a
Comment
The relay tripped when the power value reached the start value for reverse power i.e., -21.9 Watt
Summary
2 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed
Test Results
Title: Test 1
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V L1-E 63.51 V 0.00 ° 50.000 Hz
V L2-E 63.51 V -120.00 ° 50.000 Hz
Page 64 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
Generator Settings
V L1-E 63.510V 0.00° +90°
V I(1)-3
L3-E
VI(1)-1
L1-E
180° 0°
V I(1)-2
L2-E
Binary Inputs
Name Slope Time
TRIP 0->1 10.054s
Overload 1->0 n/a
Comment
Actual Operate Time delay = 10 seconds.
Summary
1 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed
Test Settings
.
General
No. of ramp states: 1
Total steps per test: 101
Total time per test: 10.100 s
No. of test executions: 1
Page 65 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
Ramped Quantities
V L1-E, L2-E / Magnitude
.
Ramp States
Ramp Ramp 1
V L1-E 70.00 V
0.00 °
50.000 Hz
V L2-E 70.00 V
-120.00 °
50.000 Hz
V L3-E 63.50 V
120.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 70.00 V
Sig 1 To 75.00 V
Sig 1 Delta 50.00 mV
Sig 1 d/dt 500.0 mV/s
dt per Step 100.0 ms
Ramp Steps 101
Ramp Time 10.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s
. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 06-Jun-2023 14:30:52 Test End: 06-Jun-2023 14:31:00
User Name: Manager:
Company:
Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 V L1-E, 73.03 V 73.05 V 730.3 mV 730.3 mV 20.00 mV + 55.90 ms
L2-E
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed
Test Settings
.
General
Page 66 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
Ramped Quantities
V L2-E, L3-E / Magnitude
.
Ramp States
Ramp Ramp 1
V L1-E 63.51 V
0.00 °
50.000 Hz
V L2-E 70.00 V
-120.00 °
50.000 Hz
V L3-E 70.00 V
120.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 70.00 V
Sig 1 To 75.00 V
Sig 1 Delta 50.00 mV
Sig 1 d/dt 500.0 mV/s
dt per Step 100.0 ms
Ramp Steps 101
Ramp Time 10.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s
. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 06-Jun-2023 14:37:28 Test End: 06-Jun-2023 14:37:36
User Name: Manager:
Company:
Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 V L2-E, 73.03 V 73.10 V 730.3 mV 730.3 mV 70.00 mV + 42.10 ms
L3-E
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed
Page 67 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
Test Settings
.
General
No. of ramp states: 1
Total steps per test: 101
Total time per test: 10.100 s
No. of test executions: 1
Ramped Quantities
V L3-E, L1-E / Magnitude
.
Ramp States
Ramp Ramp 1
V L1-E 70.00 V
0.00 °
50.000 Hz
V L2-E 63.51 V
-120.00 °
50.000 Hz
V L3-E 70.00 V
120.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 70.00 V
Sig 1 To 75.00 V
Sig 1 Delta 50.00 mV
Sig 1 d/dt 500.0 mV/s
dt per Step 100.0 ms
Ramp Steps 101
Ramp Time 10.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s
. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 06-Jun-2023 14:44:10 Test End: 06-Jun-2023 14:44:18
User Name: Manager:
Company:
Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Page 68 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
Pick-up Ramp 1 TRIP 0->1 V L3-E, 73.03 V 73.05 V 730.3 mV 730.3 mV 20.00 mV + 57.00 ms
L1-E
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed
Test Settings
.
General
No. of ramp states: 1
Total steps per test: 101
Total time per test: 10.100 s
No. of test executions: 1
Ramped Quantities
V L1-E, L2-E, L3-E / Magnitude
.
Ramp States
Ramp Ramp 1
V L1-E 70.00 V
0.00 °
50.000 Hz
V L2-E 70.00 V
-120.00 °
50.000 Hz
V L3-E 70.00 V
120.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 70.00 V
Sig 1 To 75.00 V
Sig 1 Delta 50.00 mV
Sig 1 d/dt 500.0 mV/s
dt per Step 100.0 ms
Ramp Steps 101
Ramp Time 10.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s
. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 06-Jun-2023 14:48:45 Test End: 06-Jun-2023 14:48:53
Page 69 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 V L1-E, 73.03 V 73.05 V 730.3 mV 730.3 mV 20.00 mV + 48.80 ms
L2-E, L3-
E
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed
Test Results
Title: Trip time L1L2
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V L1-E 76.00 V 0.00 ° 50.000 Hz
V L2-E 76.00 V -120.00 ° 50.000 Hz
V L3-E 0.00 V 120.00 ° 50.000 Hz
Generator Settings
V L1-E 76.000V 0.00° +90°
V L1-E
180° 0°
V L2-E
80.0 V -90°
V L2-E 76.000V -120.00°
V L3-E 0.000V 120.00°
Binary Inputs
Name Slope Time
TRIP 0->1 3.051s
.
Page 70 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
Comment
Actual Triptime = 3 seconds.
Generator Settings
V L1-E 0.000V 0.00° +90°
V L3-E
180° 0°
V L2-E
80.0 V -90°
V L2-E 76.000V -120.00°
V L3-E 76.000V 120.00°
Binary Inputs
Name Slope Time
TRIP 0->1 3.060s
Comment
Actual Triptime = 3 seconds.
Generator Settings
V L1-E 76.000V 0.00° +90°
V L3-E
V L1-E
180° 0°
80.0 V -90°
V L2-E 0.000V -120.00°
V L3-E 76.000V 120.00°
Binary Inputs
Name Slope Time
TRIP 0->1 3.055s
Page 71 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
Comment
Actual Triptime = 3 seconds.
Generator Settings
V L1-E 76.000V 0.00° +90°
V L3-E
V L1-E
180° 0°
V L2-E
80.0 V -90°
V L2-E 76.000V -120.00°
V L3-E 76.000V 120.00°
Binary Inputs
Name Slope Time
TRIP 0->1 3.059s
Comment
Actual Triptime = 3 seconds.
Summary
4 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed
Test Settings
.
General
No. of ramp states: 1
Total steps per test: 31
Total time per test: 3.100 s
No. of test executions: 1
Ramped Quantities
V L1-E, L2-E / Magnitude
.
Ramp States
Ramp Ramp 1
Page 72 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
V L1-E 78.00 V
0.00 °
50.000 Hz
V L2-E 78.00 V
-120.00 °
50.000 Hz
V L3-E 63.51 V
120.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 78.00 V
Sig 1 To 81.00 V
Sig 1 Delta 100.0 mV
Sig 1 d/dt 1.000 V/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 31
Ramp Time 3.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s
. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 06-Jun-2023 15:08:33 Test End: 06-Jun-2023 15:08:36
User Name: Manager:
Company:
Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 V L1-E, 79.38 V 79.40 V 793.8 mV 793.8 mV 20.00 mV + 54.80 ms
L2-E
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed
Test Settings
.
General
No. of ramp states: 1
Total steps per test: 31
Total time per test: 3.100 s
No. of test executions: 1
Page 73 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
Ramped Quantities
V L2-E, L3-E / Magnitude
.
Ramp States
Ramp Ramp 1
V L1-E 63.51 V
0.00 °
50.000 Hz
V L2-E 78.00 V
-120.00 °
50.000 Hz
V L3-E 78.00 V
120.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 78.00 V
Sig 1 To 81.00 V
Sig 1 Delta 100.0 mV
Sig 1 d/dt 1.000 V/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 31
Ramp Time 3.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s
. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 06-Jun-2023 15:09:41 Test End: 06-Jun-2023 15:09:45
User Name: Manager:
Company:
Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 V L2-E, 79.38 V 79.50 V 793.8 mV 793.8 mV 120.0 mV + 36.40 ms
L3-E
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed
Page 74 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
Test Settings
.
General
No. of ramp states: 1
Total steps per test: 31
Total time per test: 3.100 s
No. of test executions: 1
Ramped Quantities
V L3-E, L1-E / Magnitude
.
Ramp States
Ramp Ramp 1
V L1-E 78.00 V
0.00 °
50.000 Hz
V L2-E 63.51 V
-120.00 °
50.000 Hz
V L3-E 78.00 V
120.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 78.00 V
Sig 1 To 81.00 V
Sig 1 Delta 100.0 mV
Sig 1 d/dt 1.000 V/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 31
Ramp Time 3.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s
. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 06-Jun-2023 15:10:54 Test End: 06-Jun-2023 15:10:57
User Name: Manager:
Company:
Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 V L3-E, 79.38 V 79.50 V 793.8 mV 793.8 mV 120.0 mV + 5.800 ms
Page 75 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
L1-E
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed
Test Settings
.
General
No. of ramp states: 1
Total steps per test: 31
Total time per test: 3.100 s
No. of test executions: 1
Ramped Quantities
V L1-E, L2-E, L3-E / Magnitude
.
Ramp States
Ramp Ramp 1
V L1-E 78.00 V
0.00 °
50.000 Hz
V L2-E 78.00 V
-120.00 °
50.000 Hz
V L3-E 78.00 V
120.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 78.00 V
Sig 1 To 81.00 V
Sig 1 Delta 100.0 mV
Sig 1 d/dt 1.000 V/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 31
Ramp Time 3.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s
. .
Test Module
Page 76 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 V L1-E, 79.38 V 79.40 V 793.8 mV 793.8 mV 20.00 mV + 49.30 ms
L2-E, L3-
E
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed
Test Results
Title: Triptime L1
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V L1-E 81.00 V 0.00 ° 50.000 Hz
V L2-E 81.00 V -120.00 ° 50.000 Hz
V L3-E 0.00 V 120.00 ° 50.000 Hz
Generator Settings
V L1-E 81.000V 0.00° +90°
V L1-E
180° 0°
V L2-E
100.0 V -90°
V L2-E 81.000V -120.00°
V L3-E 0.000V 120.00°
Binary Inputs
Name Slope Time
TRIP 0->1 1.053s
Comment
Actual Triptime = 1 seconds.
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V L1-E 0.00 V 0.00 ° 50.000 Hz
V L2-E 81.00 V -120.00 ° 50.000 Hz
V L3-E 81.00 V 120.00 ° 50.000 Hz
Generator Settings
V L1-E 0.000V 0.00° +90°
V L3-E
180° 0°
V L2-E
100.0 V -90°
V L2-E 81.000V -120.00°
V L3-E 81.000V 120.00°
Binary Inputs
Name Slope Time
TRIP 0->1 1.058s
Comment
Actual Triptime = 1 seconds.
Generator Settings
V L1-E 81.000V 0.00° +90°
V L3-E
V L1-E
180° 0°
100.0 V -90°
V L2-E 0.000V -120.00°
V L3-E 81.000V 120.00°
Binary Inputs
Name Slope Time
TRIP 0->1 1.053s
Comment
Actual Triptime = 1 seconds.
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V L1-E 81.00 V 0.00 ° 50.000 Hz
V L2-E 81.00 V -120.00 ° 50.000 Hz
V L3-E 81.00 V 120.00 ° 50.000 Hz
Generator Settings
V L1-E 81.000V 0.00° +90°
V L3-E
V L1-E
180° 0°
V L2-E
100.0 V -90°
V L2-E 81.000V -120.00°
V L3-E 81.000V 120.00°
Binary Inputs
Name Slope Time
TRIP 0->1 1.054s
Comment
Actual Triptime = 1 seconds.
Summary
4 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed
Test Settings
.
General
No. of ramp states: 1
Total steps per test: 201
Total time per test: 20.100 s
No. of test executions: 1
Ramped Quantities
V L1-E / Frequency
.
Ramp States
Ramp Ramp 1
Page 79 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
V L1-E 63.51 V
0.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 50.000 Hz
Sig 1 To 48.000 Hz
Sig 1 Delta -10.000 mHz
Sig 1 d/dt -100.0 mHz/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 201
Ramp Time 20.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s
. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 06-Jun-2023 15:32:33 Test End: 06-Jun-2023 15:32:44
User Name: Manager:
Company:
Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 V L1-E 49.000 Hz 48.990 Hz 10.000 mHz 10.000 mHz -10.000 + 90.50 ms
mHz
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed
Test Settings
.
General
No. of ramp states: 1
Total steps per test: 135
Total time per test: 13.500 s
No. of test executions: 1
Ramped Quantities
V L1-E / Magnitude
.
Page 80 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
Ramp States
Ramp Ramp 1
V L1-E 84.00 V
0.00 °
48.990 Hz
Force abs. Phases No
Sig 1 From 84.00 V
Sig 1 To 80.00 V
Sig 1 Delta -30.00 mV
Sig 1 d/dt -300.0 mV/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 135
Ramp Time 13.500s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 06-Jun-2023 15:38:36 Test End: 06-Jun-2023 15:38:43
User Name: Manager:
Company:
Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 V L1-E 82.56 V 82.59 V 825.0 mV 825.0 mV 30.00 mV + 50.30 ms
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed
Test Settings
.
General
No. of ramp states: 1
Total steps per test: 201
Total time per test: 20.100 s
No. of test executions: 1
Ramped Quantities
V L1-E / Frequency
Page 81 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
.
Ramp States
Ramp Ramp 1
V L1-E 110.0 V
0.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 50.000 Hz
Sig 1 To 48.000 Hz
Sig 1 Delta -10.000 mHz
Sig 1 d/dt -100.0 mHz/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 201
Ramp Time 20.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s
Comment
At rated frequency, if the Voltage is less than the set blocking undervoltge i.e., 44.45 V then the relay doesnot trip.
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 06-Jun-2023 15:42:30 Test End: 06-Jun-2023 15:42:52
User Name: Manager:
Company:
Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 V L1-E 49.000 Hz 10.000 mHz 10.000 mHz x
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed (manually assessed)
Test Settings
.
General
No. of ramp states: 1
Total steps per test: 201
Total time per test: 20.100 s
No. of test executions: 1
Page 82 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
Fault Type:
Ramped Quantities
V L1-E / Magnitude
.
Ramp States
Ramp Ramp 1
V L1-E 40.00 V
0.00 °
48.990 Hz
Force abs. Phases No
Sig 1 From 40.00 V
Sig 1 To 46.00 V
Sig 1 Delta 30.00 mV
Sig 1 d/dt 300.0 mV/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 201
Ramp Time 20.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s
Comment
At underfrequency less than 49 Hz, if the Voltage is less than the blocking undervoltage then the relay does not trip.
If the voltage is more than the blocking undervoltage then the relay trips.
. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 06-Jun-2023 15:52:30 Test End: 06-Jun-2023 15:52:47
User Name: Manager:
Company:
Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 V L1-E 44.45 V 44.53 V 444.0 mV 444.0 mV 80.00 mV + 45.10 ms
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed
Test Settings
.
General
No. of ramp states: 1
Total steps per test: 201
Page 83 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
Ramped Quantities
V L1-E / Frequency
.
Ramp States
Ramp Ramp 1
V L1-E 43.00 V
0.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 50.000 Hz
Sig 1 To 48.000 Hz
Sig 1 Delta -10.000 mHz
Sig 1 d/dt -100.0 mHz/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 201
Ramp Time 20.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s
Comment
At rated frequency, if the Voltage is less than the set blocking undervoltge i.e., 44.45 V then the relay doesnot trip.
. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 06-Jun-2023 15:53:34 Test End: 06-Jun-2023 15:53:56
User Name: Manager:
Company:
Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 V L1-E 49.000 Hz 10.000 mHz 10.000 mHz x
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed (manually assessed)
Test Module
Name: OMICRON QuickCMC Version: 4.30
Test Start: 06-Jun-2023 15:57:14 Test End: 06-Jun-2023 15:57:18
User Name: Manager:
Company:
Test Results
Title: Test 1
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V L1-E 63.51 V 0.00 ° 48.990 Hz
Generator Settings
V L1-E 63.510V 0.00° +90°
V L1-E
180° 0°
80.0 V -90°
Binary Inputs
Name Slope Time
TRIP 0->1 5.635s
Comment
Operate time delay = 5 seconds.
Summary
1 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed
Test Settings
.
General
No. of ramp states: 1
Total steps per test: 401
Total time per test: 40.100 s
No. of test executions: 1
Ramped Quantities
V L1-E / Frequency
Page 85 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
.
Ramp States
Ramp Ramp 1
V L1-E 63.51 V
0.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 50.000 Hz
Sig 1 To 46.000 Hz
Sig 1 Delta -10.000 mHz
Sig 1 d/dt -100.0 mHz/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 401
Ramp Time 40.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s
. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 06-Jun-2023 16:05:36 Test End: 06-Jun-2023 16:06:03
User Name: Manager:
Company:
Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 V L1-E 47.500 Hz 47.490 Hz 10.000 mHz 10.000 mHz -10.000 + 94.80 ms
mHz
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed
81U Stage2 overvoltage blocking:
Test Settings
.
General
No. of ramp states: 1
Total steps per test: 135
Total time per test: 13.500 s
No. of test executions: 1
Ramped Quantities
Page 86 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
V L1-E / Magnitude
.
Ramp States
Ramp Ramp 1
V L1-E 84.00 V
0.00 °
47.000 Hz
Force abs. Phases No
Sig 1 From 84.00 V
Sig 1 To 80.00 V
Sig 1 Delta -30.00 mV
Sig 1 d/dt -300.0 mV/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 135
Ramp Time 13.500s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 06-Jun-2023 16:07:55 Test End: 06-Jun-2023 16:08:01
User Name: Manager:
Company:
Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 V L1-E 82.56 V 82.59 V 825.6 mV 825.6 mV 30.00 mV + 46.60 ms
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed
Test Settings
.
General
No. of ramp states: 1
Total steps per test: 301
Total time per test: 30.100 s
No. of test executions: 1
Ramped Quantities
V L1-E / Frequency
Page 87 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
.
Ramp States
Ramp Ramp 1
V L1-E 110.0 V
0.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 50.000 Hz
Sig 1 To 47.000 Hz
Sig 1 Delta -10.000 mHz
Sig 1 d/dt -100.0 mHz/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 301
Ramp Time 30.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s
Comment
At rated frequency, if the Voltage is less than the set blocking undervoltge i.e., 44.45 V then the relay doesnot trip.
.
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 06-Jun-2023 16:08:57 Test End: 06-Jun-2023 16:09:29
User Name: Manager:
Company:
Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 V L1-E 47.500 Hz 10.000 mHz 10.000 mHz x
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed (manually assessed)
Test Settings
.
General
No. of ramp states: 1
Total steps per test: 201
Total time per test: 20.100 s
No. of test executions: 1
Page 88 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
Ramped Quantities
V L1-E / Magnitude
.
Ramp States
Ramp Ramp 1
V L1-E 40.00 V
0.00 °
47.000 Hz
Force abs. Phases No
Sig 1 From 40.00 V
Sig 1 To 46.00 V
Sig 1 Delta 30.00 mV
Sig 1 d/dt 300.0 mV/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 201
Ramp Time 20.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s
Comment
At underfrequency less than 49 Hz, if the Voltage is less than the blocking undervoltage then the relay does not trip.
If the voltage is more than the blocking undervoltage then the relay trips.
. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 06-Jun-2023 16:10:41 Test End: 06-Jun-2023 16:10:58
User Name: Manager:
Company:
Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 V L1-E 44.45 V 44.53 V 444.0 mV 444.0 mV 80.00 mV + 52.60 ms
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed
Test Settings
.
General
Page 89 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
Ramped Quantities
V L1-E / Frequency
.
Ramp States
Ramp Ramp 1
V L1-E 43.00 V
0.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 50.000 Hz
Sig 1 To 47.000 Hz
Sig 1 Delta -10.000 mHz
Sig 1 d/dt -100.0 mHz/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 301
Ramp Time 30.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s
Comment
At rated frequency, if the Voltage is less than the set blocking undervoltge i.e., 44.45 V then the relay doesnot trip.
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 06-Jun-2023 16:11:43 Test End: 06-Jun-2023 16:12:15
User Name: Manager:
Company:
Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 V L1-E 47.500 Hz 10.000 mHz 10.000 mHz x
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed (manually assessed)
Test Module
Name: OMICRON QuickCMC Version: 4.30
Test Start: 06-Jun-2023 16:13:17 Test End: 06-Jun-2023 16:14:02
User Name: Manager:
Company:
Test Results
Title: Test 1
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V L1-E 63.51 V 0.00 ° 47.000 Hz
Generator Settings
V L1-E 63.510V 0.00° +90°
V L1-E
180° 0°
80.0 V -90°
Binary Inputs
Name Slope Time
TRIP 0->1 0.485s
Comment
Operate Time delay = 0 second.
Summary
1 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed
10. Overfrequency Protection (81o)
Test Settings
.
General
No. of ramp states: 1
Total steps per test: 401
Total time per test: 40.100 s
No. of test executions: 1
Page 91 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
Ramped Quantities
V L1-E / Frequency
.
Ramp States
Ramp Ramp 1
V L1-E 63.50 V
0.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 50.000 Hz
Sig 1 To 52.000 Hz
Sig 1 Delta 5.0000 mHz
Sig 1 d/dt 50.00 mHz/s
dt per Step 100.0 ms
Ramp Steps 401
Ramp Time 40.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s
. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 07-Jun-2023 09:12:05 Test End: 07-Jun-2023 09:12:27
User Name: Manager:
Company:
Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 V L1-E 51.000 Hz 51.010 Hz 10.000 mHz 10.000 mHz 10.000 mHz + 36.70 ms
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed
Test Settings
.
General
No. of ramp states: 1
Total steps per test: 401
Total time per test: 40.100 s
No. of test executions: 1
Ramped Quantities
V L1-E / Magnitude
Page 92 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
.
Ramp States
Ramp Ramp 1
V L1-E 84.00 V
0.00 °
51.500 Hz
Force abs. Phases No
Sig 1 From 84.00 V
Sig 1 To 80.00 V
Sig 1 Delta -10.00 mV
Sig 1 d/dt -100.0 mV/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 401
Ramp Time 40.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s
Comment
1. At 81o stage 1, if the voltage is greater than blocking overvoltage then relay does not trip.
2. If the voltage is less than the blocking overvoltage then the relay trips.
. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 07-Jun-2023 09:13:28 Test End: 07-Jun-2023 09:13:44
User Name: Manager:
Company:
Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 V L1-E 82.50 V 82.63 V 825.0 mV 825.0 mV 130.0 mV + 58.00 ms
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed
Test Settings
.
General
No. of ramp states: 1
Total steps per test: 201
Total time per test: 20.100 s
No. of test executions: 1
Page 93 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
Ramped Quantities
V L1-E / Frequency
.
Ramp States
Ramp Ramp 1
V L1-E 84.00 V
0.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 50.000 Hz
Sig 1 To 52.000 Hz
Sig 1 Delta 10.000 mHz
Sig 1 d/dt 100.0 mHz/s
dt per Step 100.0 ms
Ramp Steps 201
Ramp Time 20.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s
Comment
If the voltage is more than the blocking overvoltage then the 81o function doesnot take place.
. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 07-Jun-2023 09:14:15 Test End: 07-Jun-2023 09:14:37
User Name: Manager:
Company:
Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 V L1-E 51.000 Hz 10.000 mHz 10.000 mHz x
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed (manually assessed)
Test Settings
.
General
No. of ramp states: 1
Total steps per test: 151
Total time per test: 15.100 s
No. of test executions: 1
Page 94 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
Ramped Quantities
V L1-E / Magnitude
.
Ramp States
Ramp Ramp 1
V L1-E 43.00 V
0.00 °
51.010 Hz
Force abs. Phases No
Sig 1 From 43.00 V
Sig 1 To 46.00 V
Sig 1 Delta 20.00 mV
Sig 1 d/dt 200.0 mV/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 151
Ramp Time 15.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s
Comment
If the voltage is more than the Blocking undervoltage at Stage 1, then the relay trips.
. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 07-Jun-2023 09:15:56 Test End: 07-Jun-2023 09:16:06
User Name: Manager:
Company:
Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 V L1-E 44.50 V 44.52 V 400.0 mV 400.0 mV 20.00 mV + 50.50 ms
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed
Test Settings
.
General
Page 95 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
Ramped Quantities
V L1-E / Frequency
.
Ramp States
Ramp Ramp 1
V L1-E 43.00 V
0.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 50.000 Hz
Sig 1 To 52.000 Hz
Sig 1 Delta 10.000 mHz
Sig 1 d/dt 100.0 mHz/s
dt per Step 100.0 ms
Ramp Steps 201
Ramp Time 20.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s
Comment
If the voltage is less than the blocking undervoltage then the 81o function doesnot take place.
. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 07-Jun-2023 09:16:41 Test End: 07-Jun-2023 09:17:03
User Name: Manager:
Company:
Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 V L1-E 51.000 Hz 10.000 mHz 10.000 mHz x
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed (manually assessed)
Page 96 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
Test Results
Title: Test 1
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V L1-E 63.51 V 0.00 ° 52.000 Hz
Generator Settings
V L1-E 63.510V 0.00° +90°
V L1-E
180° 0°
80.0 V -90°
Binary Inputs
Name Slope Time
TRIP 0->1 5.435s
Comment
Operate Time delay = 5 seconds.
Summary
1 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed
Test Settings
.
General
No. of ramp states: 1
Total steps per test: 601
Total time per test: 60.100 s
No. of test executions: 1
Ramped Quantities
V L1-E / Frequency
.
Ramp States
Page 97 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
Ramp Ramp 1
V L1-E 63.50 V
0.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 50.000 Hz
Sig 1 To 53.000 Hz
Sig 1 Delta 5.0000 mHz
Sig 1 d/dt 50.00 mHz/s
dt per Step 100.0 ms
Ramp Steps 601
Ramp Time 60.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s
. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 07-Jun-2023 09:26:20 Test End: 07-Jun-2023 09:27:11
User Name: Manager:
Company:
Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 V L1-E 52.500 Hz 52.510 Hz 10.000 mHz 10.000 mHz 10.000 mHz + 38.20 ms
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed
Test Settings
.
General
No. of ramp states: 1
Total steps per test: 401
Total time per test: 40.100 s
No. of test executions: 1
Ramped Quantities
V L1-E / Magnitude
.
Ramp States
Ramp Ramp 1
V L1-E 84.00 V
0.00 °
Page 98 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
52.700 Hz
Force abs. Phases No
Sig 1 From 84.00 V
Sig 1 To 80.00 V
Sig 1 Delta -10.00 mV
Sig 1 d/dt -100.0 mV/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 401
Ramp Time 40.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s
Comment
1. At 81o stage 1, if the voltage is greater than blocking overvoltage then relay does not trip.
2. If the voltage is less than the blocking overvoltage then the relay trips.
. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 07-Jun-2023 09:27:55 Test End: 07-Jun-2023 09:28:10
User Name: Manager:
Company:
Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 V L1-E 82.50 V 82.63 V 825.0 mV 825.0 mV 130.0 mV + 54.00 ms
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed
Test Settings
.
General
No. of ramp states: 1
Total steps per test: 301
Total time per test: 30.100 s
No. of test executions: 1
Ramped Quantities
V L1-E / Frequency
Page 99 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
.
Ramp States
Ramp Ramp 1
V L1-E 84.00 V
0.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 50.000 Hz
Sig 1 To 53.000 Hz
Sig 1 Delta 10.000 mHz
Sig 1 d/dt 100.0 mHz/s
dt per Step 100.0 ms
Ramp Steps 301
Ramp Time 30.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s
Comment
If the voltage is more than the blocking overvoltage then the 81o function doesnot take place.
. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 07-Jun-2023 09:28:45 Test End: 07-Jun-2023 09:29:17
User Name: Manager:
Company:
Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 V L1-E 52.500 Hz 10.000 mHz 10.000 mHz x
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed (manually assessed)
Test Settings
.
General
No. of ramp states: 1
Total steps per test: 151
Total time per test: 15.100 s
No. of test executions: 1
Ramped Quantities
Page 100 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
V L1-E / Magnitude
.
Ramp States
Ramp Ramp 1
V L1-E 43.00 V
0.00 °
52.700 Hz
Force abs. Phases No
Sig 1 From 43.00 V
Sig 1 To 46.00 V
Sig 1 Delta 20.00 mV
Sig 1 d/dt 200.0 mV/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 151
Ramp Time 15.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s
Comment
If the voltage is more than the Blocking undervoltage at Stage 1, then the relay trips.
. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 07-Jun-2023 09:29:55 Test End: 07-Jun-2023 09:30:05
User Name: Manager:
Company:
Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 V L1-E 44.50 V 44.50 V 400.0 mV 400.0 mV 0.00 V + 97.10 ms
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed
Test Settings
.
General
No. of ramp states: 1
Total steps per test: 301
Total time per test: 30.100 s
No. of test executions: 1
Ramped Quantities
V L1-E / Frequency
.
Ramp States
Ramp Ramp 1
V L1-E 43.00 V
0.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 50.000 Hz
Sig 1 To 53.000 Hz
Sig 1 Delta 10.000 mHz
Sig 1 d/dt 100.0 mHz/s
dt per Step 100.0 ms
Ramp Steps 301
Ramp Time 30.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s
Comment
If the voltage is less than the blocking undervoltage then the 81o function doesnot take place.
. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 07-Jun-2023 09:30:42 Test End: 07-Jun-2023 09:31:14
User Name: Manager:
Company:
Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 V L1-E 52.500 Hz 10.000 mHz 10.000 mHz x
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed (manually assessed)
Test Results
Page 102 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
Title: Test 1
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V L1-E 63.51 V 0.00 ° 52.700 Hz
Generator Settings
V L1-E 63.510V 0.00° +90°
V L1-E
180° 0°
80.0 V -90°
Binary Inputs
Name Slope Time
TRIP 0->1 0.519s
Comment
Operate Time delay = 0 second.
Summary
1 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed
Test Settings
.
General
No. of ramp states: 1
Total steps per test: 85
Total time per test: 8.500 s
No. of test executions: 1
Ramped Quantities
V L1-E, L2-E / Magnitude
.
Ramp States
Page 103 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
Ramp Ramp 1
V L1-E 46.19 V
0.00 °
50.000 Hz
V L2-E 46.19 V
-120.00 °
50.000 Hz
V L3-E 63.50 V
120.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 46.19 V
Sig 1 To 42.00 V
Sig 1 Delta -50.00 mV
Sig 1 d/dt -500.0 mV/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 85
Ramp Time 8.500s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s
. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 10-Jun-2023 09:53:40 Test End: 10-Jun-2023 09:53:45
User Name: Manager:
Company:
Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 V L1-E, 44.45 V 44.44 V 444.0 mV 444.0 mV -11.00 mV + 51.60 ms
L2-E
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed
Test Settings
.
General
No. of ramp states: 1
Total steps per test: 85
Total time per test: 8.500 s
No. of test executions: 1
Ramped Quantities
V L2-E, L3-E / Magnitude
.
Ramp States
Ramp Ramp 1
V L1-E 63.50 V
0.00 °
50.000 Hz
V L2-E 46.19 V
-120.00 °
50.000 Hz
V L3-E 46.19 V
120.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 46.19 V
Sig 1 To 42.00 V
Sig 1 Delta -50.00 mV
Sig 1 d/dt -500.0 mV/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 85
Ramp Time 8.500s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s
. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 10-Jun-2023 09:54:39 Test End: 10-Jun-2023 09:54:44
User Name: Manager:
Company:
Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 V L2-E, 44.45 V 44.44 V 444.0 mV 444.0 mV -11.00 mV + 41.30 ms
L3-E
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed
Test Settings
Page 105 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
.
General
No. of ramp states: 1
Total steps per test: 85
Total time per test: 8.500 s
No. of test executions: 1
Ramped Quantities
V L3-E, L1-E / Magnitude
.
Ramp States
Ramp Ramp 1
V L1-E 46.19 V
0.00 °
50.000 Hz
V L2-E 63.50 V
-120.00 °
50.000 Hz
V L3-E 46.19 V
120.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 46.19 V
Sig 1 To 42.00 V
Sig 1 Delta -50.00 mV
Sig 1 d/dt -500.0 mV/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 85
Ramp Time 8.500s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s
. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 10-Jun-2023 09:55:17 Test End: 10-Jun-2023 09:55:23
User Name: Manager:
Company:
Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 V L3-E, 44.45 V 44.44 V 444.0 mV 444.0 mV -11.00 mV + 61.70 ms
L1-E
Test Settings
.
General
No. of ramp states: 1
Total steps per test: 85
Total time per test: 8.500 s
No. of test executions: 1
Ramped Quantities
V L1-E, L2-E, L3-E / Magnitude
.
Ramp States
Ramp Ramp 1
V L1-E 46.19 V
0.00 °
50.000 Hz
V L2-E 46.19 V
-120.00 °
50.000 Hz
V L3-E 46.19 V
120.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 46.19 V
Sig 1 To 42.00 V
Sig 1 Delta -50.00 mV
Sig 1 d/dt -500.0 mV/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 85
Ramp Time 8.500s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s
. .
Test Module
Name: OMICRON Ramping Version: 4.30
Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 V L1-E, 44.45 V 44.44 V 444.0 mV 444.0 mV -11.00 mV + 49.10 ms
L2-E, L3-
E
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed
Test Results
Title: NO TRIP condition
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V L1-E 63.51 V 0.00 ° 50.000 Hz
V L2-E 63.51 V -120.00 ° 50.000 Hz
V L3-E 63.51 V 120.00 ° 50.000 Hz
Generator Settings
V L1-E 63.509V 0.00° +90°
V L3-E
V L1-E
180° 0°
V L2-E
80.0 V -90°
V L2-E 63.509V -120.00°
V L3-E 63.509V 120.00°
Binary Inputs
Name Slope Time
TRIP 0
Generator Settings
V L1-E 43.000V 0.00° +90°
V L3-E
V L1-E
180° 0°
V L2-E
50.0 V -90°
V L2-E 43.000V -120.00°
V L3-E 43.000V 120.00°
Binary Inputs
Name Slope Time
TRIP 0->1 4.063s
Comment
Firstly, inject nominal voltage i.e., 63.51 V then hold the values and inject values less than the rated undervoltage value.
Then give the feedback and unhold the values.
Summary
2 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed
Test Settings
.
General
No. of ramp states: 1
Total steps per test: 301
Total time per test: 30.100 s
No. of test executions: 1
Ramped Quantities
V L1-E / Frequency
.
Ramp States
Ramp Ramp 1
V L1-E 110.0 V
0.00 °
47.000 Hz
Force abs. Phases No
Sig 1 From 47.000 Hz
Sig 1 To 44.000 Hz
Sig 1 Delta -10.000 mHz
Sig 1 d/dt -100.0 mHz/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 301
Ramp Time 30.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s
. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 07-Jun-2023 12:14:10 Test End: 07-Jun-2023 12:14:28
User Name: Manager:
Company:
Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 V L1-E 45.450 Hz 45.450 Hz 454.00 mHz 454.00 mHz 0.000 Hz + 13.00 ms
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed
Test Settings
.
General
No. of ramp states: 1
Total steps per test: 301
Total time per test: 30.100 s
No. of test executions: 1
Ramped Quantities
V L1-E, L2-E, L3-E / Frequency
.
Ramp States
Ramp Ramp 1
V L1-E 63.51 V
0.00 °
47.000 Hz
V L2-E 63.51 V
-120.00 °
47.000 Hz
V L3-E 63.51 V
120.00 °
47.000 Hz
Force abs. Phases No
Sig 1 From 47.000 Hz
Sig 1 To 44.000 Hz
Sig 1 Delta -10.000 mHz
Sig 1 d/dt -100.0 mHz/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 301
Ramp Time 30.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s
. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 07-Jun-2023 12:15:14 Test End: 07-Jun-2023 12:15:31
User Name: Manager:
Company:
Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 V L1-E, 45.450 Hz 45.440 Hz 454.00 mHz 454.00 mHz -10.000 + 46.80 ms
L2-E, L3- mHz
E
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed
Test Results
Title: Test 1
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V L1-E 63.51 V 0.00 ° 40.000 Hz
V L2-E 63.51 V -120.00 ° 40.000 Hz
V L3-E 63.51 V 120.00 ° 40.000 Hz
Generator Settings
V L1-E 63.510V 0.00° +90°
V L3-E
V L1-E
180° 0°
V L2-E
80.0 V -90°
V L2-E 63.510V -120.00°
V L3-E 63.510V 120.00°
Binary Inputs
Name Slope Time
TRIP 0->1 5.397s
Comment
1. Actual Volts/Hertz = 2.42
2. Operate Time Delay = 5 seconds
Saturation, S = Volts/Hertz
110/40= 2.75
Summary
1 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed
Test Settings
.
General
No. of ramp states: 1
Total steps per test: 121
Total time per test: 12.100 s
No. of test executions: 1
Ramped Quantities
V L1-E / Frequency
.
Ramp States
Ramp Ramp 1
V L1-E 110.0 V
0.00 °
47.000 Hz
Force abs. Phases No
Sig 1 From 47.000 Hz
Sig 1 To 35.000 Hz
Sig 1 Delta -100.00 mHz
Sig 1 d/dt -1.000 Hz/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 121
Ramp Time 12.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s
. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 07-Jun-2023 12:28:17 Test End: 07-Jun-2023 12:28:26
User Name: Manager:
Company:
Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 V L1-E 40.000 Hz 39.900 Hz 400.00 mHz 400.00 mHz -100.00 + 77.30 ms
mHz
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed
Test Settings
.
General
No. of ramp states: 1
Total steps per test: 121
Total time per test: 12.100 s
No. of test executions: 1
Ramped Quantities
V L1-E, L2-E, L3-E / Frequency
.
Ramp States
Ramp Ramp 1
V L1-E 63.51 V
0.00 °
47.000 Hz
V L2-E 63.51 V
-120.00 °
47.000 Hz
V L3-E 63.51 V
120.00 °
47.000 Hz
Force abs. Phases No
Sig 1 From 47.000 Hz
Sig 1 To 35.000 Hz
Sig 1 Delta -100.00 mHz
Sig 1 d/dt -1.000 Hz/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 121
Ramp Time 12.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s
. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 07-Jun-2023 12:29:39 Test End: 07-Jun-2023 12:29:48
User Name: Manager:
Company:
Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 V L1-E, 40.000 Hz 40.000 Hz 400.00 mHz 400.00 mHz 0.000 Hz + 94.00 ms
L2-E, L3-
E
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed
Test Module
Name: OMICRON QuickCMC Version: 4.30
Test Start: 07-Jun-2023 12:31:45 Test End: 07-Jun-2023 12:31:48
User Name: Manager:
Company:
Test Results
Title: Test 1
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V L1-E 63.51 V 0.00 ° 35.000 Hz
V L2-E 63.51 V -120.00 ° 35.000 Hz
V L3-E 63.51 V 120.00 ° 35.000 Hz
Generator Settings
V L1-E 63.510V 0.00° +90°
V L3-E
V L1-E
180° 0°
V L2-E
80.0 V -90°
V L2-E 63.510V -120.00°
V L3-E 63.510V 120.00°
Binary Inputs
Name Slope Time
TRIP 0->1 0.398s
Comment
1. Actual Volts/Hertz = 2.75
2. Operate Time Delay = 0.3 seconds
Saturation, S = Volts/Hertz
110/40= 2.75
Summary
1 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed
Company:
Test Results
Title: Test 1
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V L1-E 0.00 V 0.00 ° 50.000 Hz
V L2-E 63.51 V -120.00 ° 50.000 Hz
V L3-E 63.51 V 120.00 ° 50.000 Hz
I(1)-1 14.00 A 0.00 ° 50.000 Hz
I(1)-2 0.00 A -120.00 ° 50.000 Hz
I(1)-3 0.00 A 120.00 ° 50.000 Hz
Generator Settings
V L1-E 0.000V 0.00° +90°
V L3-E
I(1)-1
180° 0°
V L2-E
Binary Inputs
Name Slope Time
TRIP 0->1 0.055s
Overload 1->0 n/a
Comment
1. To find the start value rotor angle i.e., 70 degree, we inject one of the phase current with its opposite phase voltages.
2. Here we ramp either current or the phase angle. (The exact current and exact phase angle to find the rotor angle is not
defined)
Summary
1 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed
Test Results
Title: Test 1
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V L1-E 0.00 V 0.00 ° 50.000 Hz
V L2-E 63.51 V -120.00 ° 50.000 Hz
V L3-E 63.51 V 120.00 ° 50.000 Hz
I(1)-1 18.00 A 0.00 ° 50.000 Hz
I(1)-2 0.00 A -120.00 ° 50.000 Hz
I(1)-3 0.00 A 120.00 ° 50.000 Hz
Generator Settings
V L1-E 0.000V 0.00° +90°
V L3-E
I(1)-1
180° 0°
V L2-E
Binary Inputs
Name Slope Time
TRIP 0->1 3.057s
Overload 1->0 n/a
Comment
Operate Time Delay = 3 seconds
Summary
1 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed
Test Settings
.
General
No. of ramp states: 1
. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 07-Jun-2023 15:54:41 Test End: 07-Jun-2023 15:54:45
User Name: Manager:
Company:
Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 I(1)-1 100.0 mA 105.0 mA 6.000 mA 6.000 mA 5.000 mA + 49.60 ms
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed
Company:
Test Results
Title: Test 1
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I(1)-1 1.940 A 0.00 ° 50.000 Hz
Generator Settings
I(1)-1 1.940A 0.00° +90°
I(1)-1
180° 0°
2.0 A -90°
Binary Inputs
Name Slope Time
TRIP 0->1 0.043s
Overload 1->0 n/a
Summary
1 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed
Test Settings
.
General
No. of ramp states: 1
Total steps per test: 201
Total time per test: 20.100 s
No. of test executions: 1
Ramped Quantities
V L1-E / Magnitude
.
Ramp States
Ramp Ramp 1
V L1-E 6.000 V
0.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 6.000 V
Sig 1 To 8.000 V
Sig 1 Delta 10.00 mV
Sig 1 d/dt 100.0 mV/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 201
Ramp Time 20.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s
. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 08-Jun-2023 16:09:43 Test End: 08-Jun-2023 16:09:57
User Name: Manager:
Company:
Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 V L1-E 7.210 V 7.200 V 72.10 mV 72.10 mV -10.00 mV + 56.20 ms
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed
14.2 Triptime:
. .
Test Module
Name: OMICRON QuickCMC Version: 4.30
Test Start: 08-Jun-2023 16:10:21 Test End: 08-Jun-2023 16:11:19
User Name: Manager:
Company:
Test Results
Title: Test 1
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V L1-E 10.00 V 0.00 ° 50.000 Hz
Generator Settings
V L1-E 10.000V 0.00° +90°
V L1-E
180° 0°
10.0 V -90°
Binary Inputs
Name Slope Time
TRIP 0->1 5.055s
Comment
Actual Trip time = 5 seconds
Summary
1 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed
16.1 PickupTest
Pickup L1:
Test Settings
.
General
No. of ramp states: 1
Total steps per test: 31
Total time per test: 3.100 s
No. of test executions: 1
Ramped Quantities
I(1)-1 / Magnitude
.
Ramp States
Ramp Ramp 1
V L1-E 43.00 V
0.00 °
50.000 Hz
V L2-E 43.00 V
-120.00 °
50.000 Hz
V L3-E 43.00 V
120.00 °
50.000 Hz
I(1)-1 3.500 A
0.00 °
50.000 Hz
I(1)-2 0.00 A
-120.00 °
50.000 Hz
I(1)-3 0.00 A
120.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 3.500 A
Sig 1 To 5.000 A
Sig 1 Delta 50.00 mA
Sig 1 d/dt 500.0 mA/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 31
Ramp Time 3.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s
. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 08-Jun-2023 09:29:12 Test End: 08-Jun-2023 09:29:15
User Name: Manager:
Company:
Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 I(1)-1 4.110 A 4.150 A 123.0 mA 123.0 mA 40.00 mA + 46.50 ms
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed
Pickup L2:
Test Settings
Page 122 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
.
General
No. of ramp states: 1
Total steps per test: 31
Total time per test: 3.100 s
No. of test executions: 1
Ramped Quantities
I(1)-2 / Magnitude
.
Ramp States
Ramp Ramp 1
V L1-E 43.00 V
0.00 °
50.000 Hz
V L2-E 43.00 V
-120.00 °
50.000 Hz
V L3-E 43.00 V
120.00 °
50.000 Hz
I(1)-1 0.00 A
0.00 °
50.000 Hz
I(1)-2 3.500 A
-120.00 °
50.000 Hz
I(1)-3 0.00 A
120.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 3.500 A
Sig 1 To 5.000 A
Sig 1 Delta 50.00 mA
Sig 1 d/dt 500.0 mA/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 31
Ramp Time 3.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s
. .
Test Module
Page 123 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 I(1)-2 4.110 A 4.150 A 123.0 mA 123.0 mA 40.00 mA + 38.70 ms
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed
Pickup L3:
Test Settings
.
General
No. of ramp states: 1
Total steps per test: 31
Total time per test: 3.100 s
No. of test executions: 1
Ramped Quantities
I(1)-3 / Magnitude
.
Ramp States
Ramp Ramp 1
V L1-E 43.00 V
0.00 °
50.000 Hz
V L2-E 43.00 V
-120.00 °
50.000 Hz
V L3-E 43.00 V
120.00 °
50.000 Hz
I(1)-1 0.00 A
0.00 °
50.000 Hz
I(1)-2 0.00 A
-120.00 °
50.000 Hz
I(1)-3 3.500 A
120.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 3.500 A
Sig 1 To 5.000 A
Sig 1 Delta 50.00 mA
Sig 1 d/dt 500.0 mA/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 31
Ramp Time 3.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s
. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 08-Jun-2023 09:32:19 Test End: 08-Jun-2023 09:32:23
User Name: Manager:
Company:
Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 I(1)-3 4.110 A 4.150 A 123.0 mA 123.0 mA 40.00 mA + 38.40 ms
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed
Pickup L1L2L3:
Test Settings
.
General
No. of ramp states: 1
Total steps per test: 21
Total time per test: 2.100 s
No. of test executions: 1
Ramped Quantities
I(1)-1, -2, -3 / Magnitude
.
Ramp States
Ramp Ramp 1
V L1-E 43.00 V
0.00 °
50.000 Hz
V L2-E 43.00 V
-120.00 °
50.000 Hz
V L3-E 43.00 V
120.00 °
50.000 Hz
I(1)-1 4.000 A
0.00 °
50.000 Hz
I(1)-2 4.000 A
-120.00 °
50.000 Hz
I(1)-3 4.000 A
120.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 4.000 A
Sig 1 To 5.000 A
Sig 1 Delta 50.00 mA
Sig 1 d/dt 500.0 mA/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 21
Ramp Time 2.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s
. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 08-Jun-2023 09:33:35 Test End: 08-Jun-2023 09:33:37
User Name: Manager:
Company:
Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 I(1)-1, -2, 4.110 A 4.150 A 123.0 mA 123.0 mA 40.00 mA + 45.30 ms
-3
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed
Comment
1. Arming Pickup time = 5 sec
. .
Test Module
Name: OMICRON State Sequencer Version: 4.30
Test Start: 08-Jun-2023 11:06:13 Test End: 08-Jun-2023 11:06:21
User Name: Manager:
Company:
Test Results
.
Time Assessment
Name Ignore Start Stop Tnom Tdev- Tdev+ Tact Tdev Assess
before
Trip Energisatio Energisatio TRIP 0>1 60.00 ms 30.00 ms 30.00 ms 54.40 ms -5.600 ms +
n n
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed
Comment
1. Arming Pickup time = 5 sec
2. If the CB closes after the Arming pickup time, then the function picks up.
. .
Test Module
Name: OMICRON State Sequencer Version: 4.30
Test Start: 08-Jun-2023 11:09:00 Test End: 08-Jun-2023 11:09:10
User Name: Manager:
Company:
Test Results
.
Time Assessment
Name Ignore Start Stop Tnom Tdev- Tdev+ Tact Tdev Assess
before
Trip Energisatio Energisatio TRIP 0>1 60.00 ms 30.00 ms 30.00 ms x
n n
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed (manually assessed)
Comment
1. The Arming Dropoff time = 2 sec
2. If the CB is closed within the arming dropoff time then the function picks up following relay trip.
. .
Test Module
Name: OMICRON State Sequencer Version: 4.30
Test Start: 08-Jun-2023 11:09:53 Test End: 08-Jun-2023 11:10:00
User Name: Manager:
Company:
Test Results
.
Time Assessment
Name Ignore Start Stop Tnom Tdev- Tdev+ Tact Tdev Assess
before
Trip Energisatio Energisatio TRIP 0>1 60.00 ms 30.00 ms 30.00 ms 56.80 ms -3.200 ms +
n n
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed
Comment
1. Arming dropoff time = 2 sec
2. If the CB does not closes within the Arming dropoff time then the function does not pick up. Therefore, the Arming dropoff
blocks.
. .
Test Module
Name: OMICRON State Sequencer Version: 4.30
Test Start: 08-Jun-2023 11:10:28 Test End: 08-Jun-2023 11:10:38
User Name: Manager:
Company:
Test Results
.
Time Assessment
Name Ignore Start Stop Tnom Tdev- Tdev+ Tact Tdev Assess
before
Trip Energisatio Energisatio TRIP 0>1 60.00 ms 30.00 ms 30.00 ms x
n n
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed (manually assessed)
17. Generator Transformer Backup Earthfault Protection
Test Settings
.
General
No. of ramp states: 1
Total steps per test: 21
Total time per test: 6.300 s
No. of test executions: 1
Ramped Quantities
I(1)-1 / Magnitude
.
Ramp States
Ramp Ramp 1
I(1)-1 150.0 mA
0.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 150.0 mA
Sig 1 To 250.0 mA
Sig 1 Delta 5.000 mA
Sig 1 d/dt 16.67 mA/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 300.0 ms
Ramp Steps 21
Ramp Time 6.300s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s
. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 07-Jun-2023 10:58:28 Test End: 07-Jun-2023 10:58:33
User Name: Manager:
Company:
Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 I(1)-1 200.0 mA 200.0 mA 6.000 mA 6.000 mA 0.00 A + 54.70 ms
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed
Test Results
Title: Test 1
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I(1)-1 400.0 mA 0.00 ° 50.000 Hz
Generator Settings
I(1)-1
180° 0°
400.0 mA -90°
Binary Inputs
Name Slope Time
TRIP 0->1 6.053s
Overload 1->0 n/a
Summary
1 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed
Test Results
Title: Test 1
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Symmetrical components V1 13.00 V 0.00 ° 50.000 Hz
V2 0.00 V -120.00 ° 50.000 Hz
V0 0.00 V 120.00 ° 50.000 Hz
I1 500.0 mA 0.00 ° 50.000 Hz
I2 0.00 A -120.00 ° 50.000 Hz
I0 0.00 A 120.00 ° 50.000 Hz
Generator Settings
V L1-E
I(1)-1
180° 0°
V L2-E
I(1)-2
15.0 V -90° 500.0 mA
V L2-E 13.000V -120.00°
V L3-E 13.000V 120.00°
I(1)-1 0.500A 0.00°
I(1)-2 0.500A -120.00°
I(1)-3 0.500A 120.00°
Binary Inputs
Name Slope Time
TRIP 0
Overload 0
Comment
Positive sequence release current = 0.43 A
Positive sequence voltage start value = 11 V
Title: Test 2
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Symmetrical components V1 9.000 V 0.00 ° 50.000 Hz
V2 0.00 V -120.00 ° 50.000 Hz
V0 0.00 V 120.00 ° 50.000 Hz
I1 500.0 mA 0.00 ° 50.000 Hz
I2 0.00 A -120.00 ° 50.000 Hz
I0 0.00 A 120.00 ° 50.000 Hz
Generator Settings
V L1-E 9.000V 0.00° +90°
I(1)-3
V L3-E
V L1-E
I(1)-1
180° 0°
V L2-E
I(1)-2
10.0 V -90° 500.0 mA
V L2-E 9.000V -120.00°
V L3-E 9.000V 120.00°
I(1)-1 0.500A 0.00°
I(1)-2 0.500A -120.00°
I(1)-3 0.500A 120.00°
Binary Inputs
Name Slope Time
Generator Settings
V L1-E 13.000V -120.00° +90°
I(1)-3
V L3-E
V L2-E
I(1)-2
180° 0°
V L1-E
I(1)-1
15.0 V -90° 500.0 mA
V L2-E 13.000V 0.00°
V L3-E 13.000V -240.00°
I(1)-1 0.500A -120.00°
I(1)-2 0.500A 0.00°
I(1)-3 0.500A -240.00°
Binary Inputs
Name Slope Time
TRIP 0
Overload 0
Comment
Negative sequence release current = 0.43 A
Negative sequence voltage start value = 11 V
Relay doesnot trip.
Title: Test 4
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Symmetrical components V1 0.00 V 0.00 ° 50.000 Hz
V2 13.00 V -120.00 ° 50.000 Hz
V0 0.00 V 120.00 ° 50.000 Hz
I1 0.00 A 0.00 ° 50.000 Hz
I2 300.0 mA -120.00 ° 50.000 Hz
I0 0.00 A 120.00 ° 50.000 Hz
Generator Settings
V L1-E 13.000V -120.00° +90°
V L3-E
I(1)-3
V L2-E
I(1)-2
180° 0°
I(1)-1
V L1-E
Binary Inputs
Name Slope Time
TRIP 0->1 0.057s
Overload 1->0 n/a
Comment
Negative sequence release current = 0.43 A
Negative sequence voltage start value = 11 V
Thus, the relay trips.
Summary
4 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed
Test Settings
.
General
No. of ramp states: 1
Total steps per test: 71
Total time per test: 7.100 s
No. of test executions: 1
Ramped Quantities
V 1 / Magnitude
.
Ramp States
Ramp Ramp 1
V L1-E 15.00 V
0.00 °
50.000 Hz
V L2-E 15.00 V
-120.00 °
50.000 Hz
V L3-E 15.00 V
120.00 °
50.000 Hz
I(1)-1 450.0 mA
0.00 °
50.000 Hz
I(1)-2 450.0 mA
-120.00 °
50.000 Hz
I(1)-3 450.0 mA
120.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 15.00 V
Sig 1 To 8.000 V
Sig 1 Delta -100.0 mV
Sig 1 d/dt -1.000 V/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 71
Ramp Time 7.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s
. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 08-Jun-2023 14:30:14 Test End: 08-Jun-2023 14:30:20
User Name: Manager:
Company:
Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 V1 11.00 V 11.00 V 330.0 mV 330.0 mV 0.00 V + 63.30 ms
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed
Company:
Test Results
Title: Negative Sequence Condition
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Symmetrical components V1 0.00 V 0.00 ° 50.000 Hz
V2 15.00 V -120.00 ° 50.000 Hz
V0 0.00 V 120.00 ° 50.000 Hz
I1 0.00 A 0.00 ° 50.000 Hz
I2 90.00 mA -120.00 ° 50.000 Hz
I0 0.00 A 120.00 ° 50.000 Hz
Generator Settings
V L1-E 15.000V -120.00° +90°
V L3-E
I(1)-3
I(1)-2
V L2-E
180° 0°
I(1)-1
V L1-E
15.0 V -90° 100.0 mA
V L2-E 15.000V 0.00°
V L3-E 15.000V -240.00°
I(1)-1 0.090A -120.00°
I(1)-2 0.090A 0.00°
I(1)-3 0.090A -240.00°
Binary Inputs
Name Slope Time
TRIP 0->1 5.056s
Overload 1->0 n/a
Generator Settings
V L1-E
I(1)-1
180° 0°
V L2-E
I(1)-2
10.0 V -90° 500.0 mA
V L2-E 9.000V -120.00°
V L3-E 9.000V 120.00°
I(1)-1 0.500A 0.00°
I(1)-2 0.500A -120.00°
I(1)-3 0.500A 120.00°
Binary Inputs
Name Slope Time
TRIP 0->1 5.063s
Overload 1->0 n/a
Comment
Actual time delay = 5 seconds.
Summary
2 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed
Test Settings
.
General
No. of ramp states: 1
Total steps per test: 51
Total time per test: 5.100 s
No. of test executions: 1
Ramped Quantities
I(1)-1 / Magnitude
.
Ramp States
Ramp Ramp 1
I(1)-1 4.000 A
0.00 °
50.000 Hz
I(1)-2 0.00 A
-120.00 °
50.000 Hz
I(1)-3 0.00 A
120.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 4.000 A
Sig 1 To 6.000 A
Sig 1 Delta 40.00 mA
Sig 1 d/dt 400.0 mA/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 51
Ramp Time 5.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s
. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 08-Jun-2023 16:30:22 Test End: 08-Jun-2023 16:30:27
User Name: Manager:
Company:
Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 I(1)-1 5.110 A 5.120 A 153.0 mA 153.0 mA 10.00 mA + 48.70 ms
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed
Test Settings
.
General
No. of ramp states: 1
Total steps per test: 101
Total time per test: 10.100 s
No. of test executions: 1
Ramped Quantities
I(1)-1, -2, -3 / Magnitude
.
Ramp States
Ramp Ramp 1
I(1)-1 4.000 A
0.00 °
50.000 Hz
I(1)-2 4.000 A
-120.00 °
50.000 Hz
I(1)-3 4.000 A
120.00 °
50.000 Hz
Force abs. Phases Yes
Sig 1 From 4.000 A
Sig 1 To 6.000 A
Sig 1 Delta 20.00 mA
Sig 1 d/dt 200.0 mA/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 101
Ramp Time 10.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s
. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 08-Jun-2023 16:34:36 Test End: 08-Jun-2023 16:34:44
User Name: Manager:
Company:
Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 I(1)-1, -2, 5.110 A 5.100 A 153.0 mA 153.0 mA -10.00 mA + 52.30 ms
-3
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed
Company:
Test Results
Title: SIngle phase triptime
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I(1)-1 7.000 A 0.00 ° 50.000 Hz
I(1)-2 0.00 A -120.00 ° 50.000 Hz
I(1)-3 0.00 A 120.00 ° 50.000 Hz
Generator Settings
I(1)-1 7.000A 0.00° +90°
I(1)-1
180° 0°
8.0 A -90°
I(1)-2 0.000A -120.00°
I(1)-3 0.000A 120.00°
Binary Inputs
Name Slope Time
TRIP 0->1 2.058s
Overload 1->0 n/a
.
Comment
Actual triptime = 2 seconds.
Generator Settings
I(1)-1 7.000A 0.00° +90°
I(1)-3
I(1)-1
180° 0°
I(1)-2
8.0 A -90°
I(1)-2 7.000A -120.00°
I(1)-3 7.000A 120.00°
Page 141 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
Binary Inputs
Name Slope Time
TRIP 0->1 2.058s
Overload 1->0 n/a
Comment
Actual triptime = 2 seconds.
Summary
2 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed
Test Settings
.
General
No. of ramp states: 1
Total steps per test: 61
Total time per test: 6.100 s
No. of test executions: 1
Ramped Quantities
I(1)-1 / Magnitude
.
Ramp States
Ramp Ramp 1
I(1)-1 20.00 A
0.00 °
50.000 Hz
I(1)-2 0.00 A
-120.00 °
50.000 Hz
I(1)-3 0.00 A
120.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 20.00 A
Sig 1 To 23.00 A
Sig 1 Delta 50.00 mA
Sig 1 d/dt 500.0 mA/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 61
Ramp Time 6.100s
Trigger Bin
Page 142 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s
. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 08-Jun-2023 16:44:54 Test End: 08-Jun-2023 16:45:00
User Name: Manager:
Company:
Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 I(1)-1 22.10 A 22.05 A 663.0 mA 663.0 mA -50.00 mA + 62.30 ms
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed
Test Settings
.
General
No. of ramp states: 1
Total steps per test: 61
Total time per test: 6.100 s
No. of test executions: 1
Ramped Quantities
I(1)-1, -2, -3 / Magnitude
.
Ramp States
Ramp Ramp 1
I(1)-1 20.00 A
0.00 °
50.000 Hz
I(1)-2 20.00 A
-120.00 °
50.000 Hz
I(1)-3 20.00 A
120.00 °
50.000 Hz
Force abs. Phases Yes
Sig 1 From 20.00 A
Sig 1 To 23.00 A
Sig 1 Delta 50.00 mA
Sig 1 d/dt 500.0 mA/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 61
Ramp Time 6.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s
. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 08-Jun-2023 16:50:10 Test End: 08-Jun-2023 16:50:16
User Name: Manager:
Company:
Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 I(1)-1, -2, 22.10 A 22.05 A 663.0 mA 663.0 mA -50.00 mA + 44.60 ms
-3
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed
Test Results
Title: Single phase triptime
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I(1)-1 23.00 A 0.00 ° 50.000 Hz
I(1)-2 0.00 A -120.00 ° 50.000 Hz
I(1)-3 0.00 A 120.00 ° 50.000 Hz
Generator Settings
I(1)-1
180° 0°
30.0 A -90°
I(1)-2 0.000A -120.00°
I(1)-3 0.000A 120.00°
Binary Inputs
Name Slope Time
TRIP 0->1 0.058s
Overload 1->0 n/a
.
Comment
Actual Triptime = 0 second
Generator Settings
I(1)-1 23.000A 0.00° +90°
I(1)-3
I(1)-1
180° 0°
I(1)-2
30.0 A -90°
I(1)-2 23.000A -120.00°
I(1)-3 23.000A 120.00°
Binary Inputs
Name Slope Time
TRIP 0->1 0.061s
Overload 1->0 n/a
Comment
Actual Triptime = 0 second
Summary
2 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed