Test Report

Project/Customer: 6*200 MW PHPA-I


Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

Test Object - Device Settings


. . .
Substation/Bay:
Substation: Substation address:
Bay: Bay address:
. . .
Device:
Name/description: Test Object Manufacturer:
Device type: Device address:
Serial/model number:
Additional info 1:
Additional info 2:

Hardware Configuration
.
Test Equipment
Type Serial Number
CMC356 PE408Y
. .
Hardware Check
Performed At Result Details
6/10/2023 9:56:17 AM Passed

1. I/O Signal Test

Sl.No. Device Digital Input/Digital Output Result Remarks


1 Digital Input 1 OK
2 Digital Input 2 OK
3 Digital Input 3 OK
4 Digital Input 4 OK
5 Digital Input 5 OK
6 Digital Input 6 OK
7 Digital Input 7 OK
8 Digital Input 8 OK
9 HIPASE-P Digital Input 9 OK
10 Digital Input 10 OK
11 Digital Input 11 OK
12 Digital Input 12 OK
13 Digital Input 13 OK
14 Digital Input 14 OK
15 Digital Input 15 OK
16 Digital Input 16 OK
17 Digital Input 17 OK
18 Digital Input 18 OK
Page 1 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

19 Digital Input 19 OK
20 Digital Input 20 OK
21 Digital Input 21 OK
22 Digital Input 22 OK
23 Digital Input 23 OK
24 Digital Input 24 OK
25 Digital Input 25 OK
26 HIPASE-P Digital Input 26 OK
27 Digital Input 27 OK
28 Digital Input 28 OK
29 Digital Input 29 OK
30 Digital Input 30 OK
31 Digital Input 31 OK
32 Digital Input 32 OK
33 Digital Input 33 OK
34 Digital Input 34 OK
35 Digital Input 35 OK
36 Digital Input 36 OK
37 Digital Input 37 OK
38 Digital Input 38 OK
39 Digital Input 39 OK
40 Digital Input 40 OK
41 Digital Input 41 OK
42 Digital Input 42 OK
43 Digital Input 43 OK
44 Digital Input 44 OK
45 Digital Input 45 OK
46 Digital Input 46 OK
47 Digital Input 47 OK
48 Digital Input 48 OK
49 Digital Output 1 OK
50 Digital Output 2 OK
51 Digital Output 3 OK
52 Digital Output 4 OK
53 Digital Output 5 OK
54 Digital Output 6 OK
55 Digital Output 7 OK
56 Digital Output 8 OK
57 Digital Output 9 OK
58 Digital Output 10 OK
59 Digital Output 11 OK

Page 2 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

60 Digital Output 12 OK
61 Digital Output 13 OK
62 Digital Output 14 OK
63 Digital Output 15 OK
64 Digital Output 16 OK

Besides, Digital inputs and outputs, LEDs were tested and found ok.

.
2. Measurement Test:
. .
Test Module
Name: OMICRON QuickCMC Version: 4.30
Test Start: 05-Jun-2023 15:45:41 Test End: 05-Jun-2023 16:16:16
User Name: Manager:
Company:

Test Results
Title: CT-309/R
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 5.000 A 0.00 ° 50.000 Hz
I L2 0.00 A -120.00 ° 50.000 Hz
I L3 0.00 A 120.00 ° 50.000 Hz

Generator Settings
I L1 5.000A 0.00° +90°

I L1
180° 0°

5.0 A -90°
I L2 0.000A -120.00°
I L3 0.000A 120.00°

Binary Inputs
Name Slope Time
TRIP 0
Overload 0
Comment
CT-01 = 12.023 kA
CT-02 = 0 kA
CT-03 = 0 kA
Title: CT-309/Y

Page 3 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 0.00 A 0.00 ° 50.000 Hz
I L2 5.000 A -120.00 ° 50.000 Hz
I L3 0.00 A 120.00 ° 50.000 Hz

Generator Settings
I L1 0.000A 0.00° +90°

180° 0°

I L2
5.0 A -90°
I L2 5.000A -120.00°
I L3 0.000A 120.00°

Binary Inputs
Name Slope Time
TRIP 0
Overload 0

Comment
CT-01 = 0 kA
CT-02 = 12.017 kA
CT-03 = 0 kA
Title: CT-309/B
.
Fault Calculator:
Table Input mode Parameters (All values are secondary)
Direct I L1 0.00 A 0.00 ° 50.000 Hz
I L2 0.00 A -120.00 ° 50.000 Hz
I L3 5.000 A 120.00 ° 50.000 Hz

Generator Settings
I L1 0.000A 0.00° +90°
I L3

180° 0°

5.0 A -90°
I L2 0.000A -120.00°
I L3 5.000A 120.00°

Binary Inputs
Name Slope Time

Page 4 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

TRIP 0
Overload 0

Comment
CT-01 = 0 kA
CT-02 = 0 kA
CT-03 = 12.024 kA
Title: CT-309/RYB
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 5.000 A 0.00 ° 50.000 Hz
I L2 5.000 A -120.00 ° 50.000 Hz
I L3 5.000 A 120.00 ° 50.000 Hz

Generator Settings
I L1 5.000A 0.00° +90°
I L3

I L1
180° 0°

I L2
5.0 A -90°
I L2 5.000A -120.00°
I L3 5.000A 120.00°

Binary Inputs
Name Slope Time
TRIP 0
Overload 0

Comment
CT-01 = 12.035 kA
CT-02 = 12.011 kA
CT-03 = 12.018 kA
Title: CT-305/R
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 5.000 A 0.00 ° 50.000 Hz
I L2 0.00 A -120.00 ° 50.000 Hz
I L3 0.00 A 120.00 ° 50.000 Hz

Generator Settings

Page 5 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

I L1 5.000A 0.00° +90°

I L1
180° 0°

5.0 A -90°
I L2 0.000A -120.00°
I L3 0.000A 120.00°

Binary Inputs
Name Slope Time
TRIP 0
Overload 0

Comment
CT-01 = 12.016 kA
CT-02 = 0 kA
CT-03 = 0 kA
Title: CT-305/Y
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 0.00 A 0.00 ° 50.000 Hz
I L2 5.000 A -120.00 ° 50.000 Hz
I L3 0.00 A 120.00 ° 50.000 Hz

Generator Settings
I L1 0.000A 0.00° +90°

180° 0°

I L2
5.0 A -90°
I L2 5.000A -120.00°
I L3 0.000A 120.00°

Binary Inputs
Name Slope Time
TRIP 0
Overload 0

Comment
CT-01 = 0 kA
CT-02 = 12.014 kA
CT-03 = 0 kA
Title: CT-305/B
Page 6 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 0.00 A 0.00 ° 50.000 Hz
I L2 0.00 A -120.00 ° 50.000 Hz
I L3 5.000 A 120.00 ° 50.000 Hz

Generator Settings
I L1 0.000A 0.00° +90°
I L3

180° 0°

5.0 A -90°
I L2 0.000A -120.00°
I L3 5.000A 120.00°

Binary Inputs
Name Slope Time
TRIP 0
Overload 0
Comment
CT-01 = 0 kA
CT-02 = 0 kA
CT-03 = 12.025 kA
Title: CT-305/RYB
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 5.000 A 0.00 ° 50.000 Hz
I L2 5.000 A -120.00 ° 50.000 Hz
I L3 5.000 A 120.00 ° 50.000 Hz

Generator Settings
I L1 5.000A 0.00° +90°
I L3

I L1
180° 0°

I L2
5.0 A -90°
I L2 5.000A -120.00°
I L3 5.000A 120.00°

Binary Inputs
Name Slope Time
TRIP 0

Page 7 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

Overload 0
Comment
CT-01 = 12.019 kA
CT-02 = 12.008 kA
CT-03 = 12.025 kA
Title: CT-317/R
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 1.000 A 0.00 ° 50.000 Hz
I L2 0.00 A -120.00 ° 50.000 Hz
I L3 0.00 A 120.00 ° 50.000 Hz

Generator Settings
I L1 1.000A 0.00° +90°

I L1
180° 0°

1.0 A -90°
I L2 0.000A -120.00°
I L3 0.000A 120.00°

Binary Inputs
Name Slope Time
TRIP 0
Overload 0
Comment
CT-01 = 500.7 A
CT-02 = 0 A
CT-03 = 0 A
Title: CT-317/Y
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 0.00 A 0.00 ° 50.000 Hz
I L2 1.000 A -120.00 ° 50.000 Hz
I L3 0.00 A 120.00 ° 50.000 Hz

Generator Settings
I L1 0.000A 0.00° +90°

180° 0°

I L2
1.0 A -90°
I L2 1.000A -120.00°

Page 8 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

I L3 0.000A 120.00°

Binary Inputs
Name Slope Time
TRIP 0
Overload 0
Comment
CT-01 = 0 A
CT-02 = 500.5 A
CT-03 = 0 A
Title: CT-317/B
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 0.00 A 0.00 ° 50.000 Hz
I L2 0.00 A -120.00 ° 50.000 Hz
I L3 1.000 A 120.00 ° 50.000 Hz

Generator Settings
I L1 0.000A 0.00° +90°
I L3

180° 0°

1.0 A -90°
I L2 0.000A -120.00°
I L3 1.000A 120.00°

Binary Inputs
Name Slope Time
TRIP 0
Overload 0
Comment
CT-01 = 0 A
CT-02 = 0 A
CT-03 = 501.2 A
Title: CT-317/RYB
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 1.000 A 0.00 ° 50.000 Hz
I L2 1.000 A -120.00 ° 50.000 Hz
I L3 1.000 A 120.00 ° 50.000 Hz

Generator Settings

Page 9 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

I L1 1.000A 0.00° +90°


I L3

I L1
180° 0°

I L2
1.0 A -90°
I L2 1.000A -120.00°
I L3 1.000A 120.00°

Binary Inputs
Name Slope Time
TRIP 0
Overload 0
Comment
CT-01 = 500.8 A
CT-02 = 500.5 A
CT-03 = 500.2 A
Title: CT-310/R
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 5.000 A 0.00 ° 50.000 Hz
I L2 0.00 A -120.00 ° 50.000 Hz
I L3 0.00 A 120.00 ° 50.000 Hz

Generator Settings
I L1 5.000A 0.00° +90°

I L1
180° 0°

5.0 A -90°
I L2 0.000A -120.00°
I L3 0.000A 120.00°

Binary Inputs
Name Slope Time
TRIP 0
Overload 0
Comment
CT-01 = 12.018 kA
CT-02 = 0 kA
CT-03 = 0 kA
Title: CT-310/Y
.

Page 10 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 0.00 A 0.00 ° 50.000 Hz
I L2 5.000 A -120.00 ° 50.000 Hz
I L3 0.00 A 120.00 ° 50.000 Hz

Generator Settings
I L1 0.000A 0.00° +90°

180° 0°

I L2
5.0 A -90°
I L2 5.000A -120.00°
I L3 0.000A 120.00°

Binary Inputs
Name Slope Time
TRIP 0
Overload 0
Comment
CT-01 = 0 kA
CT-02 = 12.024 kA
CT-03 = 0 kA
Title: CT-310/B
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 0.00 A 0.00 ° 50.000 Hz
I L2 0.00 A -120.00 ° 50.000 Hz
I L3 5.000 A 120.00 ° 50.000 Hz

Generator Settings
I L1 0.000A 0.00° +90°
I L3

180° 0°

5.0 A -90°
I L2 0.000A -120.00°
I L3 5.000A 120.00°

Binary Inputs
Name Slope Time
TRIP 0
Overload 0

Page 11 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

Comment
CT-01 = 0 kA
CT-02 = 0 kA
CT-03 = 12.034 kA
Title: CT-310/RYB
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 5.000 A 0.00 ° 50.000 Hz
I L2 5.000 A -120.00 ° 50.000 Hz
I L3 5.000 A 120.00 ° 50.000 Hz

Generator Settings
I L1 5.000A 0.00° +90°
I L3

I L1
180° 0°

I L2
5.0 A -90°
I L2 5.000A -120.00°
I L3 5.000A 120.00°

Binary Inputs
Name Slope Time
TRIP 0
Overload 0
Comment
CT-01 = 12.022 kA
CT-02 = 12.020 kA
CT-03 = 12.031 kA
Title: CT-303/R
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 5.000 A 0.00 ° 50.000 Hz
I L2 0.00 A -120.00 ° 50.000 Hz
I L3 0.00 A 120.00 ° 50.000 Hz

Generator Settings
I L1 5.000A 0.00° +90°

I L1
180° 0°

5.0 A -90°
I L2 0.000A -120.00°
I L3 0.000A 120.00°

Page 12 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

Binary Inputs
Name Slope Time
TRIP 0
Overload 0
Comment
CT-01 = 12.027 kA
CT-02 = 0 kA
CT-03 = 0 kA
Title: CT-303/Y
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 0.00 A 0.00 ° 50.000 Hz
I L2 5.000 A -120.00 ° 50.000 Hz
I L3 0.00 A 120.00 ° 50.000 Hz

Generator Settings
I L1 0.000A 0.00° +90°

180° 0°

I L2
5.0 A -90°
I L2 5.000A -120.00°
I L3 0.000A 120.00°

Binary Inputs
Name Slope Time
TRIP 0
Overload 0
Comment
CT-01 = 0 kA
CT-02 = 12.031 kA
CT-03 = 0 kA
Title: CT-303/B
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 0.00 A 0.00 ° 50.000 Hz
I L2 0.00 A -120.00 ° 50.000 Hz
I L3 5.000 A 120.00 ° 50.000 Hz

Generator Settings

Page 13 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

I L1 0.000A 0.00° +90°


I L3

180° 0°

5.0 A -90°
I L2 0.000A -120.00°
I L3 5.000A 120.00°

Binary Inputs
Name Slope Time
TRIP 0
Overload 0

Comment
CT-01 = 0 kA
CT-02 = 0 kA
CT-03 = 12.027 kA
Title: CT-303/RYB
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 5.000 A 0.00 ° 50.000 Hz
I L2 5.000 A -120.00 ° 50.000 Hz
I L3 5.000 A 120.00 ° 50.000 Hz

Generator Settings
I L1 5.000A 0.00° +90°
I L3

I L1
180° 0°

I L2
5.0 A -90°
I L2 5.000A -120.00°
I L3 5.000A 120.00°

Binary Inputs
Name Slope Time
TRIP 0
Overload 0
Comment
CT-01 = 12.035 kA
CT-02 = 12.025 kA
CT-03 = 12.027 kA
Title: CT-217/R (CORE-IV)

Page 14 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 1.000 A 0.00 ° 50.000 Hz
I L2 0.00 A -120.00 ° 50.000 Hz
I L3 0.00 A 120.00 ° 50.000 Hz

Generator Settings
I L1 1.000A 0.00° +90°

I L1
180° 0°

1.0 A -90°
I L2 0.000A -120.00°
I L3 0.000A 120.00°

Binary Inputs
Name Slope Time
TRIP 0
Overload 0

Comment
CT-04 = 501.4 A

Title: CT-NGT21
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 1.000 A 0.00 ° 50.000 Hz
I L2 0.00 A -120.00 ° 50.000 Hz
I L3 0.00 A 120.00 ° 50.000 Hz

Generator Settings
I L1 1.000A 0.00° +90°

I L1
180° 0°

1.0 A -90°
I L2 0.000A -120.00°
I L3 0.000A 120.00°

Binary Inputs
Name Slope Time
TRIP 0
Overload 0

Page 15 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

Comment
CT-05 = 500.9 A
Summary
22 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed

Title: VT-3/R
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V(1)-1 63.51 V 0.00 ° 50.000 Hz
V(1)-2 0.00 V -120.00 ° 50.000 Hz
V(1)-3 0.00 V 120.00 ° 50.000 Hz

Generator Settings
V(1)-1 63.509V 0.00° +90°

V(1)-1
180° 0°

80.0 V -90°
V(1)-2 0.000V -120.00°
V(1)-3 0.000V 120.00°

Binary Inputs
Name Slope Time
TRIP 0
Comment
VT-01 = 7.964 kV
VT-02 = 0 kV
VT-03 = 0 kV
Title: VT-3/Y
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V(1)-1 0.00 V 0.00 ° 50.000 Hz
V(1)-2 63.51 V -120.00 ° 50.000 Hz
V(1)-3 0.00 V 120.00 ° 50.000 Hz

Generator Settings
V(1)-1 0.000V 0.00° +90°

180° 0°

V(1)-2

80.0 V -90°

Page 16 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

V(1)-2 63.509V -120.00°


V(1)-3 0.000V 120.00°

Binary Inputs
Name Slope Time
TRIP 0
Comment
VT-01 = 0 kV
VT-02 = 7.965 kV
VT-03 = 0 kV
Title: VT-3/B
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V(1)-1 0.00 V 0.00 ° 50.000 Hz
V(1)-2 0.00 V -120.00 ° 50.000 Hz
V(1)-3 63.51 V 120.00 ° 50.000 Hz

Generator Settings
V(1)-1 0.000V 0.00° +90°

V(1)-3

180° 0°

80.0 V -90°
V(1)-2 0.000V -120.00°
V(1)-3 63.509V 120.00°

Binary Inputs
Name Slope Time
TRIP 0
Comment
VT-01 = 0 kV
VT-02 = 0 kV
VT-03 = 7.963 kV
Title: VT-3/RYB
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V(1)-1 63.51 V 0.00 ° 50.000 Hz
V(1)-2 63.51 V -120.00 ° 50.000 Hz
V(1)-3 63.51 V 120.00 ° 50.000 Hz

Generator Settings

Page 17 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

V(1)-1 63.509V 0.00° +90°

V(1)-3

V(1)-1
180° 0°

V(1)-2

80.0 V -90°
V(1)-2 63.509V -120.00°
V(1)-3 63.509V 120.00°

Binary Inputs
Name Slope Time
TRIP 0
Comment
VT-01 = 7.964 kV
VT-02 = 7.965 kV
VT-03 = 7.962 kV
Title: VT-1/R
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V(1)-1 63.51 V 0.00 ° 50.000 Hz
V(1)-2 0.00 V -120.00 ° 50.000 Hz
V(1)-3 0.00 V 120.00 ° 50.000 Hz

Generator Settings
V(1)-1 63.509V 0.00° +90°

V(1)-1
180° 0°

80.0 V -90°
V(1)-2 0.000V -120.00°
V(1)-3 0.000V 120.00°

Binary Inputs
Name Slope Time
TRIP 0
Comment
VT-04 = 7.967 kV
VT-05 = 0 kV
VT-06 = 0 kV
Title: VT-1/Y
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V(1)-1 0.00 V 0.00 ° 50.000 Hz
Page 18 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

V(1)-2 63.51 V -120.00 ° 50.000 Hz


V(1)-3 0.00 V 120.00 ° 50.000 Hz

Generator Settings
V(1)-1 0.000V 0.00° +90°

180° 0°

V(1)-2

80.0 V -90°
V(1)-2 63.509V -120.00°
V(1)-3 0.000V 120.00°

Binary Inputs
Name Slope Time
TRIP 0
Comment
VT-04 = 0 kV
VT-05 = 7.966 kV
VT-06 = 0 kV
Title: VT-1/B
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V(1)-1 0.00 V 0.00 ° 50.000 Hz
V(1)-2 0.00 V -120.00 ° 50.000 Hz
V(1)-3 63.51 V 120.00 ° 50.000 Hz

Generator Settings
V(1)-1 0.000V 0.00° +90°

V(1)-3

180° 0°

80.0 V -90°
V(1)-2 0.000V -120.00°
V(1)-3 63.509V 120.00°

Binary Inputs
Name Slope Time
TRIP 0
Comment
VT-04 = 0 kV
VT-05 = 0 kV
VT-06 = 7968 kV
Title: VT-1/RYB

Page 19 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V(1)-1 63.51 V 0.00 ° 50.000 Hz
V(1)-2 63.51 V -120.00 ° 50.000 Hz
V(1)-3 63.51 V 120.00 ° 50.000 Hz

Generator Settings
V(1)-1 63.509V 0.00° +90°

V(1)-3

V(1)-1
180° 0°

V(1)-2

80.0 V -90°
V(1)-2 63.509V -120.00°
V(1)-3 63.509V 120.00°

Binary Inputs
Name Slope Time
TRIP 0
Comment
VT-04 = 7.967 kV
VT-05 = 7.966 kV
VT-06 = 7.967 kV
Summary
8 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed

3. Generator Differential Protection (87G)


3.1 Pickup Test
Gen. Neutral Pickup L1:

Test Settings
.
General
No. of ramp states: 1
Total steps per test: 21
Total time per test: 16.800 s
No. of test executions: 1

Input Mode: Direct


Fault Type:

Ramped Quantities
I(1)-1 / Magnitude
.
Page 20 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

Ramp States
Ramp Ramp 1
I L1 0.00 A
0.00 °
50.000 Hz
I L2 0.00 A
-120.00 °
50.000 Hz
I L3 0.00 A
120.00 °
50.000 Hz
I(1)-1 800.0 mA
0.00 °
50.000 Hz
I(1)-2 0.00 A
-120.00 °
50.000 Hz
I(1)-3 0.00 A
120.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 800.0 mA
Sig 1 To 900.0 mA
Sig 1 Delta 5.000 mA
Sig 1 d/dt 6.250 mA/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 800.0 ms
Ramp Steps 21
Ramp Time 16.800s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s

. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 06-Jun-2023 10:09:45 Test End: 06-Jun-2023 10:09:55
User Name: Manager:
Company:

Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 I(1)-1 850.0 mA 850.0 mA 25.50 mA 25.50 mA 0.00 A + 57.70 ms
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed

Gen. Neutral Pickup L2:


Page 21 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

Test Settings
.
General
No. of ramp states: 1
Total steps per test: 21
Total time per test: 16.800 s
No. of test executions: 1

Input Mode: Direct


Fault Type:

Ramped Quantities
I(1)-2 / Magnitude
.
Ramp States
Ramp Ramp 1
I L1 0.00 A
0.00 °
50.000 Hz
I L2 0.00 A
-120.00 °
50.000 Hz
I L3 0.00 A
120.00 °
50.000 Hz
I(1)-1 0.00 A
0.00 °
50.000 Hz
I(1)-2 800.0 mA
-120.00 °
50.000 Hz
I(1)-3 0.00 A
120.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 800.0 mA
Sig 1 To 900.0 mA
Sig 1 Delta 5.000 mA
Sig 1 d/dt 6.250 mA/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 800.0 ms
Ramp Steps 21
Ramp Time 16.800s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s

Page 22 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 06-Jun-2023 10:08:50 Test End: 06-Jun-2023 10:09:00
User Name: Manager:
Company:

Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 I(1)-2 850.0 mA 850.0 mA 25.50 mA 25.50 mA 0.00 A + 35.60 ms
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed

Gen. Neutral Pickup L3:

Test Settings
.
General
No. of ramp states: 1
Total steps per test: 21
Total time per test: 16.800 s
No. of test executions: 1

Input Mode: Direct


Fault Type:

Ramped Quantities
I(1)-3 / Magnitude
.
Ramp States
Ramp Ramp 1
I L1 0.00 A
0.00 °
50.000 Hz
I L2 0.00 A
-120.00 °
50.000 Hz
I L3 0.00 A
120.00 °
50.000 Hz
I(1)-1 0.00 A
0.00 °
50.000 Hz
I(1)-2 0.00 A
-120.00 °
50.000 Hz
I(1)-3 800.0 mA
120.00 °

Page 23 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

50.000 Hz
Force abs. Phases No
Sig 1 From 800.0 mA
Sig 1 To 900.0 mA
Sig 1 Delta 5.000 mA
Sig 1 d/dt 6.250 mA/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 800.0 ms
Ramp Steps 21
Ramp Time 16.800s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s

. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 06-Jun-2023 10:11:35 Test End: 06-Jun-2023 10:11:45
User Name: Manager:
Company:

Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 I(1)-3 850.0 mA 850.0 mA 25.50 mA 25.50 mA 0.00 A + 47.90 ms
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed

Gen. Neutral Pickup L1L2L3:

Test Settings
.
General
No. of ramp states: 1
Total steps per test: 21
Total time per test: 16.800 s
No. of test executions: 1

Input Mode: Direct


Fault Type:

Ramped Quantities
I(1)-1, -2, -3 / Magnitude
.
Ramp States
Ramp Ramp 1
I L1 0.00 A

Page 24 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

0.00 °
50.000 Hz
I L2 0.00 A
-120.00 °
50.000 Hz
I L3 0.00 A
120.00 °
50.000 Hz
I(1)-1 800.0 mA
0.00 °
50.000 Hz
I(1)-2 800.0 mA
-120.00 °
50.000 Hz
I(1)-3 800.0 mA
120.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 800.0 mA
Sig 1 To 900.0 mA
Sig 1 Delta 5.000 mA
Sig 1 d/dt 6.250 mA/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 800.0 ms
Ramp Steps 21
Ramp Time 16.800s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s

. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 06-Jun-2023 10:12:53 Test End: 06-Jun-2023 10:13:03
User Name: Manager:
Company:

Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 I(1)-1, -2, 850.0 mA 850.0 mA 25.50 mA 25.50 mA 0.00 A + 44.30 ms
-3
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed

Gen. Terminal Pickup L1:

Test Settings
Page 25 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

.
General
No. of ramp states: 1
Total steps per test: 21
Total time per test: 16.800 s
No. of test executions: 1

Input Mode: Direct


Fault Type:

Ramped Quantities
I L1 / Magnitude
.
Ramp States
Ramp Ramp 1
I L1 800.0 mA
0.00 °
50.000 Hz
I L2 0.00 A
-120.00 °
50.000 Hz
I L3 0.00 A
120.00 °
50.000 Hz
I(1)-1 0.00 A
0.00 °
50.000 Hz
I(1)-2 0.00 A
-120.00 °
50.000 Hz
I(1)-3 0.00 A
120.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 800.0 mA
Sig 1 To 900.0 mA
Sig 1 Delta 5.000 mA
Sig 1 d/dt 6.250 mA/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 800.0 ms
Ramp Steps 21
Ramp Time 16.800s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s

. .
Test Module
Page 26 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

Name: OMICRON Ramping Version: 4.30


Test Start: 06-Jun-2023 10:14:08 Test End: 06-Jun-2023 10:14:18
User Name: Manager:
Company:

Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 I L1 850.0 mA 850.0 mA 25.50 mA 25.50 mA 0.00 A + 36.30 ms
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed
Gen. Terminal Pickup L2:

Test Settings
.
General
No. of ramp states: 1
Total steps per test: 21
Total time per test: 16.800 s
No. of test executions: 1

Input Mode: Direct


Fault Type:

Ramped Quantities
I L2 / Magnitude
.
Ramp States
Ramp Ramp 1
I L1 0.00 A
0.00 °
50.000 Hz
I L2 800.0 mA
-120.00 °
50.000 Hz
I L3 0.00 A
120.00 °
50.000 Hz
I(1)-1 0.00 A
0.00 °
50.000 Hz
I(1)-2 0.00 A
-120.00 °
50.000 Hz
I(1)-3 0.00 A
120.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 800.0 mA
Sig 1 To 900.0 mA

Page 27 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

Sig 1 Delta 5.000 mA


Sig 1 d/dt 6.250 mA/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 800.0 ms
Ramp Steps 21
Ramp Time 16.800s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s

. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 06-Jun-2023 10:15:19 Test End: 06-Jun-2023 10:15:29
User Name: Manager:
Company:

Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 I L2 850.0 mA 850.0 mA 25.50 mA 25.50 mA 0.00 A + 169.6 ms
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed

Gen. Terminal Pickup L3:

Test Settings
.
General
No. of ramp states: 1
Total steps per test: 21
Total time per test: 16.800 s
No. of test executions: 1

Input Mode: Direct


Fault Type:

Ramped Quantities
I L3 / Magnitude
.
Ramp States
Ramp Ramp 1
I L1 0.00 A
0.00 °
50.000 Hz
I L2 0.00 A
-120.00 °

Page 28 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

50.000 Hz
I L3 800.0 mA
120.00 °
50.000 Hz
I(1)-1 0.00 A
0.00 °
50.000 Hz
I(1)-2 0.00 A
-120.00 °
50.000 Hz
I(1)-3 0.00 A
120.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 800.0 mA
Sig 1 To 900.0 mA
Sig 1 Delta 5.000 mA
Sig 1 d/dt 6.250 mA/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 800.0 ms
Ramp Steps 21
Ramp Time 16.800s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s

. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 06-Jun-2023 10:17:09 Test End: 06-Jun-2023 10:17:19
User Name: Manager:
Company:

Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 I L3 850.0 mA 850.0 mA 25.50 mA 25.50 mA 0.00 A + 39.60 ms
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed

Gen. Terminal Pickup L1L2L3:

Test Settings
.
General
No. of ramp states: 1
Total steps per test: 21

Page 29 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

Total time per test: 16.800 s


No. of test executions: 1

Input Mode: Direct


Fault Type:

Ramped Quantities
I L1, L2, L3 / Magnitude
.
Ramp States
Ramp Ramp 1
I L1 800.0 mA
0.00 °
50.000 Hz
I L2 800.0 mA
-120.00 °
50.000 Hz
I L3 800.0 mA
120.00 °
50.000 Hz
I(1)-1 0.00 A
0.00 °
50.000 Hz
I(1)-2 0.00 A
-120.00 °
50.000 Hz
I(1)-3 0.00 A
120.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 800.0 mA
Sig 1 To 900.0 mA
Sig 1 Delta 5.000 mA
Sig 1 d/dt 6.250 mA/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 800.0 ms
Ramp Steps 21
Ramp Time 16.800s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s

. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 06-Jun-2023 10:19:12 Test End: 06-Jun-2023 10:19:22
User Name: Manager:
Company:

Page 30 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 I L1, L2, 850.0 mA 850.0 mA 25.50 mA 25.50 mA 0.00 A + 36.50 ms
L3
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed

3.2 87G Triptime Test:


. .
Test Module
Name: OMICRON QuickCMC Version: 4.30
Test Start: 06-Jun-2023 10:23:49 Test End: 06-Jun-2023 10:28:37
User Name: Manager:
Company:

Test Results
Title: Gen. Terminal L1
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 1.700 A 0.00 ° 50.000 Hz
I L2 0.00 A -120.00 ° 50.000 Hz
I L3 0.00 A 120.00 ° 50.000 Hz

Generator Settings
I L1 1.700A 0.00° +90°

I L1
180° 0°

2.0 A -90°
I L2 0.000A -120.00°
I L3 0.000A 120.00°
I(1)-1 0.000A 0.00°
I(1)-2 0.000A -120.00°
I(1)-3 0.000A 120.00°

Binary Inputs
Name Slope Time
TRIP 0->1 0.036s
Overload 1->0 n/a
Comment
Actual Trip time = 0 second (Instantaneous trip)

Title: Gen. Terminal L2

Page 31 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 0.00 A 0.00 ° 50.000 Hz
I L2 1.700 A -120.00 ° 50.000 Hz
I L3 0.00 A 120.00 ° 50.000 Hz

Generator Settings
I L1 0.000A 0.00° +90°

180° 0°

I L2

2.0 A -90°
I L2 1.700A -120.00°
I L3 0.000A 120.00°
I(1)-1 0.000A 0.00°
I(1)-2 0.000A -120.00°
I(1)-3 0.000A 120.00°

Binary Inputs
Name Slope Time
TRIP 0->1 0.033s
Overload 1->0 n/a
Comment
Actual Trip time = 0 second (Instantaneous trip)

Title: Gen. Terminal L3


.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 0.00 A 0.00 ° 50.000 Hz
I L2 0.00 A -120.00 ° 50.000 Hz
I L3 1.700 A 120.00 ° 50.000 Hz

Generator Settings
I L1 0.000A 0.00° +90°

I L3

180° 0°

2.0 A -90°
I L2 0.000A -120.00°
I L3 1.700A 120.00°
I(1)-1 0.000A 0.00°
I(1)-2 0.000A -120.00°
I(1)-3 0.000A 120.00°
Page 32 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

Binary Inputs
Name Slope Time
TRIP 0->1 0.036s
Overload 1->0 n/a
Comment
Actual Trip time = 0 second (Instantaneous trip)

Title: Gen. Terminal L123


.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 1.700 A 0.00 ° 50.000 Hz
I L2 1.700 A -120.00 ° 50.000 Hz
I L3 1.700 A 120.00 ° 50.000 Hz

Generator Settings
I L1 1.700A 0.00° +90°

I L3

I L1
180° 0°

I L2

2.0 A -90°
I L2 1.700A -120.00°
I L3 1.700A 120.00°
I(1)-1 0.000A 0.00°
I(1)-2 0.000A -120.00°
I(1)-3 0.000A 120.00°

Binary Inputs
Name Slope Time
TRIP 0->1 0.034s
Overload 1->0 n/a
Comment
Actual Trip time = 0 second (Instantaneous trip)

Title: Gen. Neutral L1


.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 0.00 A 0.00 ° 50.000 Hz
I L2 0.00 A -120.00 ° 50.000 Hz
I L3 0.00 A 120.00 ° 50.000 Hz

Generator Settings

Page 33 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

I L1 0.000A 0.00° +90°

I(1)-1
180° 0°

2.0 A -90°
I L2 0.000A -120.00°
I L3 0.000A 120.00°
I(1)-1 1.700A 0.00°
I(1)-2 0.000A -120.00°
I(1)-3 0.000A 120.00°

Binary Inputs
Name Slope Time
TRIP 0->1 0.036s
Overload 1->0 n/a
Comment
Actual Trip time = 0 second (Instantaneous trip)

Title: Gen. Neutral L2


.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 0.00 A 0.00 ° 50.000 Hz
I L2 0.00 A -120.00 ° 50.000 Hz
I L3 0.00 A 120.00 ° 50.000 Hz

Generator Settings
I L1 0.000A 0.00° +90°

180° 0°

I(1)-2

2.0 A -90°
I L2 0.000A -120.00°
I L3 0.000A 120.00°
I(1)-1 0.000A 0.00°
I(1)-2 1.700A -120.00°
I(1)-3 0.000A 120.00°

Binary Inputs
Name Slope Time
TRIP 0->1 0.033s
Overload 1->0 n/a
Comment

Page 34 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

Actual Trip time = 0 second (Instantaneous trip)

Title: Gen. Neutral L3


.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 0.00 A 0.00 ° 50.000 Hz
I L2 0.00 A -120.00 ° 50.000 Hz
I L3 0.00 A 120.00 ° 50.000 Hz

Generator Settings
I L1 0.000A 0.00° +90°

I(1)-3

180° 0°

2.0 A -90°
I L2 0.000A -120.00°
I L3 0.000A 120.00°
I(1)-1 0.000A 0.00°
I(1)-2 0.000A -120.00°
I(1)-3 1.700A 120.00°

Binary Inputs
Name Slope Time
TRIP 0->1 0.036s
Overload 1->0 n/a
Comment
Actual Trip time = 0 second (Instantaneous trip)

Title: Gen. Neutral L123


.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 0.00 A 0.00 ° 50.000 Hz
I L2 0.00 A -120.00 ° 50.000 Hz
I L3 0.00 A 120.00 ° 50.000 Hz

Generator Settings
I L1 0.000A 0.00° +90°

I(1)-3

I(1)-1
180° 0°

I(1)-2

2.0 A -90°
I L2 0.000A -120.00°
I L3 0.000A 120.00°

Page 35 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

I(1)-1 1.700A 0.00°


I(1)-2 1.700A -120.00°
I(1)-3 1.700A 120.00°

Binary Inputs
Name Slope Time
TRIP 0->1 0.033s
Overload 1->0 n/a
Comment
Actual Trip time = 0 second (Instantaneous trip)
Summary
8 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed
3.3 Stability Test

Stability test-Out zone Fault:


. .
Test Module
Name: OMICRON QuickCMC Version: 4.30
Test Start: 06-Jun-2023 10:29:09 Test End: 06-Jun-2023 10:33:22
User Name: Manager:
Company:

Test Results
Title: Test 1
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 850.0 mA 0.00 ° 50.000 Hz
I L2 850.0 mA -120.00 ° 50.000 Hz
I L3 850.0 mA 120.00 ° 50.000 Hz

Generator Settings
I L1 0.850A 0.00° +90°

I L3 I(1)-2

I(1)-1 I L1
180° 0°

I L2 I(1)-3

1.0 A -90°
I L2 0.850A -120.00°
I L3 0.850A 120.00°
I(1)-1 0.850A 180.00°
I(1)-2 0.850A 60.00°
I(1)-3 0.850A 300.00°

Page 36 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

Binary Inputs
Name Slope Time
TRIP 0
Overload 0
Comment
Id1 = 0.012 kA, Ir1 = 2.046 kA
Id2 = 0.012 kA, Ir2 = 2.042 kA
Id3 = 0.010 kA, Ir3 = 2.045 kA
Therefore, No Trip.
Summary
1 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed

Stability test-In Zone Fault:


. .
Test Module
Name: OMICRON QuickCMC Version: 4.30
Test Start: 06-Jun-2023 10:33:42 Test End: 06-Jun-2023 10:36:00
User Name: Manager:
Company:

Test Results
Title: Test 1
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 850.0 mA 0.00 ° 50.000 Hz
I L2 850.0 mA -120.00 ° 50.000 Hz
I L3 850.0 mA 120.00 ° 50.000 Hz

Generator Settings
I L1 0.850A 0.00° +90°

I(1)-3
I L3

I(1)-1
I L1
180° 0°

I(1)-2
I L2

1.0 A -90°
I L2 0.850A -120.00°
I L3 0.850A 120.00°
I(1)-1 0.850A 0.00°
I(1)-2 0.850A -120.00°
I(1)-3 0.850A 120.00°

Binary Inputs
Name Slope Time
TRIP 1

Page 37 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

Overload 0
Comment
Id1 = 4.088 kA, Ir1 = 2.043 kA
Id2 = 4.085 kA, Ir2 = 2.043 kA
Id3 = 4.091 kA, Ir3 = 2.045 kA
Therefore, Relay Tripped.
Summary
1 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed

4. Generator Transformer Differential Protection (87T)


4.1 Pickup Test

Trans. HV side L1 pickup:

Test Settings
.
General
No. of ramp states: 1
Total steps per test: 61
Total time per test: 6.100 s
No. of test executions: 1

Input Mode: Direct


Fault Type:

Ramped Quantities
I L1 / Magnitude
.
Ramp States
Ramp Ramp 1
I L1 150.0 mA
0.00 °
50.000 Hz
I L2 0.00 A
-120.00 °
50.000 Hz
I L3 0.00 A
120.00 °
50.000 Hz
I(1)-1 0.00 A
0.00 °
50.000 Hz
I(1)-2 0.00 A
-120.00 °
50.000 Hz
I(1)-3 0.00 A

Page 38 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

120.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 150.0 mA
Sig 1 To 210.0 mA
Sig 1 Delta 1.000 mA
Sig 1 d/dt 10.00 mA/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 61
Ramp Time 6.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s

. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 06-Jun-2023 11:51:01 Test End: 06-Jun-2023 11:51:08
User Name: Manager:
Company:

Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 I L1 195.0 mA 196.0 mA 5.850 mA 5.850 mA 1.000 mA + 35.40 ms
Assess: + .. Passed x .. Failed o .. Not assessed

Test State:
Test passed

Trans. HV side L2 pickup:

Test Settings
.
General
No. of ramp states: 1
Total steps per test: 61
Total time per test: 6.100 s
No. of test executions: 1

Input Mode: Direct


Fault Type:

Ramped Quantities
I L2 / Magnitude
.
Ramp States
Page 39 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

Ramp Ramp 1
I L1 0.00 A
0.00 °
50.000 Hz
I L2 150.0 mA
-120.00 °
50.000 Hz
I L3 0.00 A
120.00 °
50.000 Hz
I(1)-1 0.00 A
0.00 °
50.000 Hz
I(1)-2 0.00 A
-120.00 °
50.000 Hz
I(1)-3 0.00 A
120.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 150.0 mA
Sig 1 To 210.0 mA
Sig 1 Delta 1.000 mA
Sig 1 d/dt 10.00 mA/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 61
Ramp Time 6.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s

. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 06-Jun-2023 11:52:58 Test End: 06-Jun-2023 11:53:05
User Name: Manager:
Company:

Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 I L2 195.0 mA 195.0 mA 5.850 mA 5.850 mA 0.00 A + 34.40 ms
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed

Trans. HV side L3 pickup:

Page 40 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

Test Settings
.
General
No. of ramp states: 1
Total steps per test: 61
Total time per test: 6.100 s
No. of test executions: 1

Input Mode: Direct


Fault Type:

Ramped Quantities
I L3 / Magnitude
.
Ramp States
Ramp Ramp 1
I L1 0.00 A
0.00 °
50.000 Hz
I L2 0.00 A
-120.00 °
50.000 Hz
I L3 150.0 mA
120.00 °
50.000 Hz
I(1)-1 0.00 A
0.00 °
50.000 Hz
I(1)-2 0.00 A
-120.00 °
50.000 Hz
I(1)-3 0.00 A
120.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 150.0 mA
Sig 1 To 210.0 mA
Sig 1 Delta 1.000 mA
Sig 1 d/dt 10.00 mA/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 61
Ramp Time 6.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s

. .
Page 41 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 06-Jun-2023 11:54:32 Test End: 06-Jun-2023 11:54:38
User Name: Manager:
Company:

Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 I L3 195.0 mA 194.0 mA 5.850 mA 5.850 mA -1.000 mA + 41.40 ms
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed

Trans. HV side L1L2L3 pickup:

Test Settings
.
General
No. of ramp states: 1
Total steps per test: 21
Total time per test: 21.000 s
No. of test executions: 1

Input Mode: Direct


Fault Type:

Ramped Quantities
I L1, L2, L3 / Magnitude
.
Ramp States
Ramp Ramp 1
I L1 120.0 mA
0.00 °
50.000 Hz
I L2 120.0 mA
-120.00 °
50.000 Hz
I L3 120.0 mA
120.00 °
50.000 Hz
I(1)-1 0.00 A
0.00 °
50.000 Hz
I(1)-2 0.00 A
-120.00 °
50.000 Hz
I(1)-3 0.00 A
120.00 °
50.000 Hz
Force abs. Phases Yes
Page 42 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

Sig 1 From 120.0 mA


Sig 1 To 140.0 mA
Sig 1 Delta 1.000 mA
Sig 1 d/dt 1.000 mA/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 1.000 s
Ramp Steps 21
Ramp Time 21.000s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s

. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 06-Jun-2023 11:56:17 Test End: 06-Jun-2023 11:56:29
User Name: Manager:
Company:

Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 I L1, L2, 130.0 mA 130.0 mA 3.900 mA 3.900 mA 0.00 A + 37.80 ms
L3
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed

Trans.LV side L1 pickup:

Test Settings
.
General
No. of ramp states: 1
Total steps per test: 201
Total time per test: 20.100 s
No. of test executions: 1

Input Mode: Direct


Fault Type:

Ramped Quantities
I(1)-1 / Magnitude
.
Ramp States
Ramp Ramp 1
I L1 0.00 A
0.00 °

Page 43 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

50.000 Hz
I L2 0.00 A
-120.00 °
50.000 Hz
I L3 0.00 A
120.00 °
50.000 Hz
I(1)-1 1.300 A
0.00 °
50.000 Hz
I(1)-2 0.00 A
-120.00 °
50.000 Hz
I(1)-3 0.00 A
120.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 1.300 A
Sig 1 To 1.700 A
Sig 1 Delta 2.000 mA
Sig 1 d/dt 20.00 mA/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 201
Ramp Time 20.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s

. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 06-Jun-2023 11:59:11 Test End: 06-Jun-2023 11:59:21
User Name: Manager:
Company:

Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 I(1)-1 1.482 A 1.446 A 44.40 mA 44.40 mA -36.00 mA + 22.20 ms
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed

Trans.LV side L2 pickup:

Test Settings
.
General
Page 44 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

No. of ramp states: 1


Total steps per test: 201
Total time per test: 20.100 s
No. of test executions: 1

Input Mode: Direct


Fault Type:

Ramped Quantities
I(1)-2 / Magnitude
.
Ramp States
Ramp Ramp 1
I L1 0.00 A
0.00 °
50.000 Hz
I L2 0.00 A
-120.00 °
50.000 Hz
I L3 0.00 A
120.00 °
50.000 Hz
I(1)-1 0.00 A
0.00 °
50.000 Hz
I(1)-2 1.300 A
-120.00 °
50.000 Hz
I(1)-3 0.00 A
120.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 1.300 A
Sig 1 To 1.700 A
Sig 1 Delta 2.000 mA
Sig 1 d/dt 20.00 mA/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 201
Ramp Time 20.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s

. .
Test Module
Name: OMICRON Ramping Version: 4.30

Page 45 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

Test Start: 06-Jun-2023 12:00:28 Test End: 06-Jun-2023 12:00:38


User Name: Manager:
Company:

Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 I(1)-2 1.482 A 1.444 A 44.40 mA 44.40 mA -38.00 mA + 44.90 ms
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed

Trans.LV side L3 pickup:

Test Settings
.
General
No. of ramp states: 1
Total steps per test: 201
Total time per test: 20.100 s
No. of test executions: 1

Input Mode: Direct


Fault Type:

Ramped Quantities
I(1)-3 / Magnitude
.
Ramp States
Ramp Ramp 1
I L1 0.00 A
0.00 °
50.000 Hz
I L2 0.00 A
-120.00 °
50.000 Hz
I L3 0.00 A
120.00 °
50.000 Hz
I(1)-1 0.00 A
0.00 °
50.000 Hz
I(1)-2 0.00 A
-120.00 °
50.000 Hz
I(1)-3 1.300 A
120.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 1.300 A
Sig 1 To 1.700 A

Page 46 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

Sig 1 Delta 2.000 mA


Sig 1 d/dt 20.00 mA/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 201
Ramp Time 20.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s

. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 06-Jun-2023 12:01:34 Test End: 06-Jun-2023 12:01:43
User Name: Manager:
Company:

Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 I(1)-3 1.482 A 1.442 A 44.40 mA 44.40 mA -40.00 mA + 46.70 ms
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed

Trans. LV side L1L2L3:

Test Settings
.
General
No. of ramp states: 1
Total steps per test: 31
Total time per test: 31.000 s
No. of test executions: 1

Input Mode: Direct


Fault Type:

Ramped Quantities
I(1)-1, -2, -3 / Magnitude
.
Ramp States
Ramp Ramp 1
I L1 0.00 A
0.00 °
20.000 Hz
I L2 0.00 A
-120.00 °

Page 47 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

50.000 Hz
I L3 0.00 A
120.00 °
50.000 Hz
I(1)-1 750.0 mA
0.00 °
50.000 Hz
I(1)-2 750.0 mA
-120.00 °
50.000 Hz
I(1)-3 750.0 mA
120.00 °
50.000 Hz
Force abs. Phases Yes
Sig 1 From 750.0 mA
Sig 1 To 1.200 A
Sig 1 Delta 15.00 mA
Sig 1 d/dt 15.00 mA/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 1.000 s
Ramp Steps 31
Ramp Time 31.000s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s

. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 06-Jun-2023 12:05:10 Test End: 06-Jun-2023 12:05:18
User Name: Manager:
Company:

Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 I(1)-1, -2, 856.0 mA 840.0 mA 25.68 mA 25.68 mA -16.00 mA + 37.80 ms
-3
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed

4.2 87GT Triptime Test:


. .
Test Module
Name: OMICRON QuickCMC Version: 4.30
Test Start: 06-Jun-2023 12:15:19 Test End: 06-Jun-2023 12:20:15
User Name: Manager:
Company:
Page 48 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

Test Results
Title: Trans. HV side L1
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 390.0 mA 0.00 ° 50.000 Hz
I L2 0.00 A -120.00 ° 50.000 Hz
I L3 0.00 A 120.00 ° 50.000 Hz

Generator Settings
I L1 0.390A 0.00° +90°

I L1
180° 0°

400.0 mA -90°
I L2 0.000A -120.00°
I L3 0.000A 120.00°
I(1)-1 0.000A 0.00°
I(1)-2 0.000A -120.00°
I(1)-3 0.000A 120.00°

Binary Inputs
Name Slope Time
TRIP 0->1 0.037s
Overload 1->0 n/a
Comment
Actual Triptime = 0 second. (Instantaneous trip)

Title: Trans. HV side L2


.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 0.00 A 0.00 ° 50.000 Hz
I L2 390.0 mA -120.00 ° 50.000 Hz
I L3 0.00 A 120.00 ° 50.000 Hz

Generator Settings
I L1 0.000A 0.00° +90°

180° 0°

I L2
400.0 mA -90°
I L2 0.390A -120.00°

Page 49 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

I L3 0.000A 120.00°
I(1)-1 0.000A 0.00°
I(1)-2 0.000A -120.00°
I(1)-3 0.000A 120.00°

Binary Inputs
Name Slope Time
TRIP 0->1 0.033s
Overload 1->0 n/a
Comment
Actual Triptime = 0 second. (Instantaneous trip)

Title: Trans. HV side L3


.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 0.00 A 0.00 ° 50.000 Hz
I L2 0.00 A -120.00 ° 50.000 Hz
I L3 390.0 mA 120.00 ° 50.000 Hz

Generator Settings
I L1 0.000A 0.00° +90°
I L3

180° 0°

400.0 mA -90°
I L2 0.000A -120.00°
I L3 0.390A 120.00°
I(1)-1 0.000A 0.00°
I(1)-2 0.000A -120.00°
I(1)-3 0.000A 120.00°

Binary Inputs
Name Slope Time
TRIP 0->1 0.037s
Overload 1->0 n/a
Comment
Actual Triptime = 0 second. (Instantaneous trip)

Title: Trans. HV side L123


.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 260.0 mA 0.00 ° 50.000 Hz
I L2 260.0 mA -120.00 ° 50.000 Hz
I L3 260.0 mA 120.00 ° 50.000 Hz

Generator Settings

Page 50 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

I L1 0.260A 0.00° +90°

I L3

I L1
180° 0°

I L2

300.0 mA -90°
I L2 0.260A -120.00°
I L3 0.260A 120.00°
I(1)-1 0.000A 0.00°
I(1)-2 0.000A -120.00°
I(1)-3 0.000A 120.00°

Binary Inputs
Name Slope Time
TRIP 0->1 0.033s
Overload 1->0 n/a
Comment
Actual Triptime = 0 second. (Instantaneous trip)

Title: Trans. LV side L1


.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 0.00 A 0.00 ° 50.000 Hz
I L2 0.00 A -120.00 ° 50.000 Hz
I L3 0.00 A 120.00 ° 50.000 Hz

Generator Settings
I L1 0.000A 0.00° +90°

I(1)-1
180° 0°

3.0 A -90°
I L2 0.000A -120.00°
I L3 0.000A 120.00°
I(1)-1 2.960A 0.00°
I(1)-2 0.000A -120.00°
I(1)-3 0.000A 120.00°

Binary Inputs
Name Slope Time
TRIP 0->1 0.035s
Overload 1->0 n/a
Comment

Page 51 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

Actual Triptime = 0 second. (Instantaneous trip)

Title: Trans. LV side L2


.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 0.00 A 0.00 ° 50.000 Hz
I L2 0.00 A -120.00 ° 50.000 Hz
I L3 0.00 A 120.00 ° 50.000 Hz

Generator Settings
I L1 0.000A 0.00° +90°

180° 0°

I(1)-2
3.0 A -90°
I L2 0.000A -120.00°
I L3 0.000A 120.00°
I(1)-1 0.000A 0.00°
I(1)-2 2.960A -120.00°
I(1)-3 0.000A 120.00°

Binary Inputs
Name Slope Time
TRIP 0->1 0.033s
Overload 1->0 n/a
Comment
Actual Triptime = 0 second. (Instantaneous trip)

Title: Trans. LV side L3


.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 0.00 A 0.00 ° 50.000 Hz
I L2 0.00 A -120.00 ° 50.000 Hz
I L3 0.00 A 120.00 ° 50.000 Hz

Generator Settings
I L1 0.000A 0.00° +90°
I(1)-3

180° 0°

3.0 A -90°
I L2 0.000A -120.00°
I L3 0.000A 120.00°

Page 52 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

I(1)-1 0.000A 0.00°


I(1)-2 0.000A -120.00°
I(1)-3 2.960A 120.00°

Binary Inputs
Name Slope Time
TRIP 0->1 0.038s
Overload 1->0 n/a
Comment
Actual Triptime = 0 second. (Instantaneous trip)

Title: Trans. LV side L123


.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 0.00 A 0.00 ° 50.000 Hz
I L2 0.00 A -120.00 ° 50.000 Hz
I L3 0.00 A 120.00 ° 50.000 Hz

Generator Settings
I L1 0.000A 0.00° +90°

I(1)-3

I(1)-1
180° 0°

I(1)-2

2.0 A -90°
I L2 0.000A -120.00°
I L3 0.000A 120.00°
I(1)-1 1.712A 0.00°
I(1)-2 1.712A -120.00°
I(1)-3 1.712A 120.00°

Binary Inputs
Name Slope Time
TRIP 0->1 0.035s
Overload 1->0 n/a
Comment
Actual Triptime = 0 second. (Instantaneous trip)
Summary
8 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed

3.3 Stability Test

Stability test-In Zone Fault:


. .
Page 53 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

Test Module
Name: OMICRON QuickCMC Version: 4.30
Test Start: 06-Jun-2023 12:07:51 Test End: 06-Jun-2023 12:10:05
User Name: Manager:
Company:

Test Results
Title: Test 1
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 130.0 mA 0.00 ° 50.000 Hz
I L2 130.0 mA -120.00 ° 50.000 Hz
I L3 130.0 mA 120.00 ° 50.000 Hz

Generator Settings
I L1 0.130A 0.00° +90°

I(1)-3

I L1 I(1)-1
I L2
L3
180° 0°

I(1)-2

1.0 A -90°
I L2 0.130A -120.00°
I L3 0.130A 120.00°
I(1)-1 0.856A 0.00°
I(1)-2 0.856A -120.00°
I(1)-3 0.856A 120.00°

Binary Inputs
Name Slope Time
TRIP 1
Overload 0
Comment
Id1 = 127.5 A, Ir1 = 66.7 A
Id2 = 127.4 A, Ir2 = 66.8 A
Id3 = 127.5 A, Ir3 = 66.7 A
Therefore, Relay Tripped.
Summary
1 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed

Stability Out Zone fault:


. .
Test Module
Name: OMICRON QuickCMC Version: 4.30
Test Start: 06-Jun-2023 12:11:35 Test End: 06-Jun-2023 12:13:34

Page 54 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

User Name: Manager:


Company:

Test Results
Title: Test 1
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 130.0 mA 0.00 ° 50.000 Hz
I L2 130.0 mA -120.00 ° 50.000 Hz
I L3 130.0 mA 120.00 ° 50.000 Hz

Generator Settings
I L1 0.130A 0.00° +90°

I(1)-2

I(1)-1 I L1
I L2
L3
180° 0°

I(1)-3

1.0 A -90°
I L2 0.130A -120.00°
I L3 0.130A 120.00°
I(1)-1 0.856A 180.00°
I(1)-2 0.856A 60.00°
I(1)-3 0.856A 300.00°

Binary Inputs
Name Slope Time
TRIP 0
Overload 0
Comment
Id1 = 34.3 A, Ir1 = 66.7 A
Id2 = 34.2 A, Ir2 = 66.7 A
Id3 = 34.4 A, Ir3 = 66.8 A
Therefore, No Trip.
Summary
1 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed

5. Negative Sequence Protection (46G)

5.1 Pickup Test

Pickup L1:

Test Settings
Page 55 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

.
General
No. of ramp states: 1
Total steps per test: 61
Total time per test: 6.100 s
No. of test executions: 1

Input Mode: Direct


Fault Type:

Ramped Quantities
I L1 / Magnitude
.
Ramp States
Ramp Ramp 1
I L1 900.0 mA
0.00 °
50.000 Hz
I L2 0.00 A
-120.00 °
50.000 Hz
I L3 0.00 A
120.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 900.0 mA
Sig 1 To 1.200 A
Sig 1 Delta 5.000 mA
Sig 1 d/dt 50.00 mA/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 61
Ramp Time 6.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s

. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 06-Jun-2023 12:36:04 Test End: 06-Jun-2023 12:36:08
User Name: Manager:
Company:

Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 I L1 1.020 A 1.020 A 30.60 mA 30.60 mA 0.00 A + 48.00 ms
Assess: + .. Passed x .. Failed o .. Not assessed

Page 56 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

Test State:
Test passed

46G Pickup L2:

Test Settings
.
General
No. of ramp states: 1
Total steps per test: 61
Total time per test: 6.100 s
No. of test executions: 1

Input Mode: Direct


Fault Type:

Ramped Quantities
I L2 / Magnitude
.
Ramp States
Ramp Ramp 1
I L1 0.00 A
0.00 °
50.000 Hz
I L2 900.0 mA
-120.00 °
50.000 Hz
I L3 0.00 A
120.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 900.0 mA
Sig 1 To 1.200 A
Sig 1 Delta 5.000 mA
Sig 1 d/dt 50.00 mA/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 61
Ramp Time 6.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s

. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 06-Jun-2023 12:37:34 Test End: 06-Jun-2023 12:37:38

Page 57 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

User Name: Manager:


Company:

Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 I L2 1.020 A 1.020 A 30.60 mA 30.60 mA 0.00 A + 43.60 ms
Assess: + .. Passed x .. Failed o .. Not assessed

Test State:
Test passed

46G Pickup L3:

Test Settings
.
General
No. of ramp states: 1
Total steps per test: 61
Total time per test: 6.100 s
No. of test executions: 1

Input Mode: Direct


Fault Type:

Ramped Quantities
I L3 / Magnitude
.
Ramp States
Ramp Ramp 1
I L1 0.00 A
0.00 °
50.000 Hz
I L2 0.00 A
-120.00 °
50.000 Hz
I L3 900.0 mA
120.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 900.0 mA
Sig 1 To 1.200 A
Sig 1 Delta 5.000 mA
Sig 1 d/dt 50.00 mA/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 61
Ramp Time 6.100s
Trigger Bin
Trigger Logic OR
Page 58 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

TRIP 1
Step back No
Delay Time 0.00 s

. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 06-Jun-2023 12:38:51 Test End: 06-Jun-2023 12:38:55
User Name: Manager:
Company:

Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 I L3 1.020 A 1.015 A 30.60 mA 30.60 mA -5.000 mA + 93.30 ms
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed

5.2 46G Triptime:


. .
Test Module
Name: OMICRON QuickCMC Version: 4.30
Test Start: 06-Jun-2023 12:43:42 Test End: 06-Jun-2023 12:44:28
User Name: Manager:
Company:

Test Results
Title: Triptime L1
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 2.040 A 0.00 ° 50.000 Hz
I L2 0.00 A -120.00 ° 50.000 Hz
I L3 0.00 A 120.00 ° 50.000 Hz

Generator Settings
I L1 2.040A 0.00° +90°

I L1
180° 0°

3.0 A -90°
I L2 0.000A -120.00°
I L3 0.000A 120.00°

Binary Inputs
Name Slope Time

Page 59 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

TRIP 0->1 5.047s


Overload 1->0 n/a
Comment
Actual Triptime = 5 seconds.

Title: Triptime L2
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 0.00 A 0.00 ° 50.000 Hz
I L2 2.040 A -120.00 ° 50.000 Hz
I L3 0.00 A 120.00 ° 50.000 Hz

Generator Settings
I L1 0.000A 0.00° +90°

180° 0°
I L2

3.0 A -90°
I L2 2.040A -120.00°
I L3 0.000A 120.00°

Binary Inputs
Name Slope Time
TRIP 0->1 5.042s
Overload 1->0 n/a
Comment
Actual Triptime = 5 seconds.

Title: Triptime L3
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 0.00 A 0.00 ° 50.000 Hz
I L2 0.00 A -120.00 ° 50.000 Hz
I L3 2.040 A 120.00 ° 50.000 Hz

Generator Settings
I L1 0.000A 0.00° +90°

I L3

180° 0°

3.0 A -90°
I L2 0.000A -120.00°
I L3 2.040A 120.00°

Page 60 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

Binary Inputs
Name Slope Time
TRIP 0->1 5.049s
Overload 1->0 n/a
Comment
Actual Triptime = 5 seconds.
Summary
3 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed

6. Thermal Overload Protecttion (49S)

6.1 Triptime Singlephase:


. .
Test Module
Name: OMICRON QuickCMC Version: 4.30
Test Start: 06-Jun-2023 12:55:34 Test End: 06-Jun-2023 12:55:42
User Name: Manager:
Company:

Test Results
Title: Test 1
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 21.30 A 0.00 ° 50.000 Hz
I L2 0.00 A -120.00 ° 50.000 Hz
I L3 0.00 A 120.00 ° 50.000 Hz

Generator Settings
I L1 21.300A 0.00° +90°

I L1
180° 0°

30.0 A -90°
I L2 0.000A -120.00°
I L3 0.000A 120.00°

Binary Inputs
Name Slope Time
TRIP 0->1 44.705s
Overload 1->0 n/a

Page 61 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

Comment
Actual Triptime = 44.99 seconds.
Summary
1 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed

6.2 49S Triptime L1L2L3:


. .
Test Module
Name: OMICRON QuickCMC Version: 4.30
Test Start: 06-Jun-2023 14:11:04 Test End: 06-Jun-2023 14:11:14
User Name: Manager:
Company:

Test Results
Title: Test 1
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 21.30 A 0.00 ° 50.000 Hz
I L2 21.30 A -120.00 ° 50.000 Hz
I L3 21.30 A 120.00 ° 50.000 Hz

Generator Settings
I L1 21.300A 0.00° +90°

I L3
I L1
180° 0°
I L2

30.0 A -90°
I L2 21.300A -120.00°
I L3 21.300A 120.00°

Binary Inputs
Name Slope Time
TRIP 0->1 44.712s
Overload 1->0 n/a
Comment
Operate Value load = 110 degree celcius
Calculated Triptime = 44.99 seconds
Summary
1 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed

7. Reverse Power Protection (37G1)

Page 62 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

7.1 Pickup Test:


. .
Test Module
Name: OMICRON QuickCMC Version: 4.30
Test Start: 07-Jun-2023 10:11:44 Test End: 07-Jun-2023 10:27:17
User Name: Manager:
Company:

Test Results
Title: Test 1
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V L1-E 63.51 V 0.00 ° 50.000 Hz
V L2-E 63.51 V -120.00 ° 50.000 Hz
V L3-E 63.51 V 120.00 ° 50.000 Hz
I(1)-1 115.0 mA 180.00 ° 50.000 Hz
I(1)-2 115.0 mA 60.00 ° 50.000 Hz
I(1)-3 115.0 mA 300.00 ° 50.000 Hz

Generator Settings
V L1-E 63.510V 0.00° +90°

V L3-E I(1)-2

I(1)-1 V L1-E
180° 0°

V L2-E I(1)-3

80.0 V -90° 150.0 mA


V L2-E 63.510V -120.00°
V L3-E 63.510V 120.00°
I(1)-1 0.115A 180.00°
I(1)-2 0.115A 60.00°
I(1)-3 0.115A 300.00°

Binary Inputs
Name Slope Time
TRIP 0
Overload 0
Comment
Currently, the relay does not trip as the power is:
P = 110V x 0.115 A x 1.732
= 21.9 Watt.
Title: Test 2
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)

Page 63 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

Direct V L1-E 63.51 V 0.00 ° 50.000 Hz


V L2-E 63.51 V -120.00 ° 50.000 Hz
V L3-E 63.51 V 120.00 ° 50.000 Hz
I(1)-1 -115.0 mA 180.00 ° 50.000 Hz
I(1)-2 -115.0 mA 60.00 ° 50.000 Hz
I(1)-3 -115.0 mA 300.00 ° 50.000 Hz

Generator Settings
V L1-E 63.510V 0.00° +90°

V I(1)-3
L3-E

VI(1)-1
L1-E
180° 0°

V I(1)-2
L2-E

80.0 V -90° 150.0 mA


V L2-E 63.510V -120.00°
V L3-E 63.510V 120.00°
I(1)-1 -0.115A 180.00°
I(1)-2 -0.115A 60.00°
I(1)-3 -0.115A 300.00°

Binary Inputs
Name Slope Time
TRIP 0->1 0.061s
Overload 1->0 n/a

Comment
The relay tripped when the power value reached the start value for reverse power i.e., -21.9 Watt
Summary
2 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed

7.2 Reverse Power Triptime:


. .
Test Module
Name: OMICRON QuickCMC Version: 4.30
Test Start: 07-Jun-2023 10:32:02 Test End: 07-Jun-2023 10:35:12
User Name: Manager:
Company:

Test Results
Title: Test 1
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V L1-E 63.51 V 0.00 ° 50.000 Hz
V L2-E 63.51 V -120.00 ° 50.000 Hz

Page 64 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

V L3-E 63.51 V 120.00 ° 50.000 Hz


I(1)-1 -220.0 mA 180.00 ° 50.000 Hz
I(1)-2 -220.0 mA 60.00 ° 50.000 Hz
I(1)-3 -220.0 mA 300.00 ° 50.000 Hz

Generator Settings
V L1-E 63.510V 0.00° +90°

V I(1)-3
L3-E

VI(1)-1
L1-E
180° 0°

V I(1)-2
L2-E

80.0 V -90° 300.0 mA


V L2-E 63.510V -120.00°
V L3-E 63.510V 120.00°
I(1)-1 -0.220A 180.00°
I(1)-2 -0.220A 60.00°
I(1)-3 -0.220A 300.00°

Binary Inputs
Name Slope Time
TRIP 0->1 10.054s
Overload 1->0 n/a

Comment
Actual Operate Time delay = 10 seconds.
Summary
1 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed

8. Overvoltage Protection (59G)

8.1 Pickup Test

Stage1 pickup L1L2:

Test Settings
.
General
No. of ramp states: 1
Total steps per test: 101
Total time per test: 10.100 s
No. of test executions: 1

Page 65 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

Input Mode: Direct


Fault Type:

Ramped Quantities
V L1-E, L2-E / Magnitude
.
Ramp States
Ramp Ramp 1
V L1-E 70.00 V
0.00 °
50.000 Hz
V L2-E 70.00 V
-120.00 °
50.000 Hz
V L3-E 63.50 V
120.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 70.00 V
Sig 1 To 75.00 V
Sig 1 Delta 50.00 mV
Sig 1 d/dt 500.0 mV/s
dt per Step 100.0 ms
Ramp Steps 101
Ramp Time 10.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s

. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 06-Jun-2023 14:30:52 Test End: 06-Jun-2023 14:31:00
User Name: Manager:
Company:

Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 V L1-E, 73.03 V 73.05 V 730.3 mV 730.3 mV 20.00 mV + 55.90 ms
L2-E
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed

59G Stage1 pickup L2L3:

Test Settings
.
General
Page 66 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

No. of ramp states: 1


Total steps per test: 101
Total time per test: 10.100 s
No. of test executions: 1

Input Mode: Direct


Fault Type:

Ramped Quantities
V L2-E, L3-E / Magnitude
.
Ramp States
Ramp Ramp 1
V L1-E 63.51 V
0.00 °
50.000 Hz
V L2-E 70.00 V
-120.00 °
50.000 Hz
V L3-E 70.00 V
120.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 70.00 V
Sig 1 To 75.00 V
Sig 1 Delta 50.00 mV
Sig 1 d/dt 500.0 mV/s
dt per Step 100.0 ms
Ramp Steps 101
Ramp Time 10.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s

. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 06-Jun-2023 14:37:28 Test End: 06-Jun-2023 14:37:36
User Name: Manager:
Company:

Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 V L2-E, 73.03 V 73.10 V 730.3 mV 730.3 mV 70.00 mV + 42.10 ms
L3-E
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed

Page 67 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

59G Stage1 pickup L3L1:

Test Settings
.
General
No. of ramp states: 1
Total steps per test: 101
Total time per test: 10.100 s
No. of test executions: 1

Input Mode: Direct


Fault Type:

Ramped Quantities
V L3-E, L1-E / Magnitude
.
Ramp States
Ramp Ramp 1
V L1-E 70.00 V
0.00 °
50.000 Hz
V L2-E 63.51 V
-120.00 °
50.000 Hz
V L3-E 70.00 V
120.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 70.00 V
Sig 1 To 75.00 V
Sig 1 Delta 50.00 mV
Sig 1 d/dt 500.0 mV/s
dt per Step 100.0 ms
Ramp Steps 101
Ramp Time 10.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s

. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 06-Jun-2023 14:44:10 Test End: 06-Jun-2023 14:44:18
User Name: Manager:
Company:

Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact

Page 68 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

Pick-up Ramp 1 TRIP 0->1 V L3-E, 73.03 V 73.05 V 730.3 mV 730.3 mV 20.00 mV + 57.00 ms
L1-E
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed

59G Stage1 pickup L1L2L3:

Test Settings
.
General
No. of ramp states: 1
Total steps per test: 101
Total time per test: 10.100 s
No. of test executions: 1

Input Mode: Direct


Fault Type:

Ramped Quantities
V L1-E, L2-E, L3-E / Magnitude
.
Ramp States
Ramp Ramp 1
V L1-E 70.00 V
0.00 °
50.000 Hz
V L2-E 70.00 V
-120.00 °
50.000 Hz
V L3-E 70.00 V
120.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 70.00 V
Sig 1 To 75.00 V
Sig 1 Delta 50.00 mV
Sig 1 d/dt 500.0 mV/s
dt per Step 100.0 ms
Ramp Steps 101
Ramp Time 10.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s

. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 06-Jun-2023 14:48:45 Test End: 06-Jun-2023 14:48:53

Page 69 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

User Name: Manager:


Company:

Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 V L1-E, 73.03 V 73.05 V 730.3 mV 730.3 mV 20.00 mV + 48.80 ms
L2-E, L3-
E
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed

8.2 Trip time test

59G Stage1 Triptime:


. .
Test Module
Name: OMICRON QuickCMC Version: 4.30
Test Start: 06-Jun-2023 14:58:14 Test End: 06-Jun-2023 14:59:29
User Name: Manager:
Company:

Test Results
Title: Trip time L1L2
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V L1-E 76.00 V 0.00 ° 50.000 Hz
V L2-E 76.00 V -120.00 ° 50.000 Hz
V L3-E 0.00 V 120.00 ° 50.000 Hz

Generator Settings
V L1-E 76.000V 0.00° +90°

V L1-E
180° 0°

V L2-E

80.0 V -90°
V L2-E 76.000V -120.00°
V L3-E 0.000V 120.00°

Binary Inputs
Name Slope Time
TRIP 0->1 3.051s

.
Page 70 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

Comment
Actual Triptime = 3 seconds.

Title: Trip time L2L3


.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V L1-E 0.00 V 0.00 ° 50.000 Hz
V L2-E 76.00 V -120.00 ° 50.000 Hz
V L3-E 76.00 V 120.00 ° 50.000 Hz

Generator Settings
V L1-E 0.000V 0.00° +90°

V L3-E

180° 0°

V L2-E
80.0 V -90°
V L2-E 76.000V -120.00°
V L3-E 76.000V 120.00°

Binary Inputs
Name Slope Time
TRIP 0->1 3.060s
Comment
Actual Triptime = 3 seconds.

Title: Trip time L1L3


.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V L1-E 76.00 V 0.00 ° 50.000 Hz
V L2-E 0.00 V -120.00 ° 50.000 Hz
V L3-E 76.00 V 120.00 ° 50.000 Hz

Generator Settings
V L1-E 76.000V 0.00° +90°

V L3-E

V L1-E
180° 0°

80.0 V -90°
V L2-E 0.000V -120.00°
V L3-E 76.000V 120.00°

Binary Inputs
Name Slope Time
TRIP 0->1 3.055s
Page 71 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

Comment
Actual Triptime = 3 seconds.

Title: Trip time L1L2L3


.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V L1-E 76.00 V 0.00 ° 50.000 Hz
V L2-E 76.00 V -120.00 ° 50.000 Hz
V L3-E 76.00 V 120.00 ° 50.000 Hz

Generator Settings
V L1-E 76.000V 0.00° +90°

V L3-E

V L1-E
180° 0°

V L2-E

80.0 V -90°
V L2-E 76.000V -120.00°
V L3-E 76.000V 120.00°

Binary Inputs
Name Slope Time
TRIP 0->1 3.059s
Comment
Actual Triptime = 3 seconds.
Summary
4 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed

8.3 59G Stage2 pickup L1L2:

Test Settings
.
General
No. of ramp states: 1
Total steps per test: 31
Total time per test: 3.100 s
No. of test executions: 1

Input Mode: Direct


Fault Type:

Ramped Quantities
V L1-E, L2-E / Magnitude
.
Ramp States
Ramp Ramp 1
Page 72 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

V L1-E 78.00 V
0.00 °
50.000 Hz
V L2-E 78.00 V
-120.00 °
50.000 Hz
V L3-E 63.51 V
120.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 78.00 V
Sig 1 To 81.00 V
Sig 1 Delta 100.0 mV
Sig 1 d/dt 1.000 V/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 31
Ramp Time 3.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s

. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 06-Jun-2023 15:08:33 Test End: 06-Jun-2023 15:08:36
User Name: Manager:
Company:

Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 V L1-E, 79.38 V 79.40 V 793.8 mV 793.8 mV 20.00 mV + 54.80 ms
L2-E
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed

59G Stage2 pickup L2L3:

Test Settings
.
General
No. of ramp states: 1
Total steps per test: 31
Total time per test: 3.100 s
No. of test executions: 1

Page 73 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

Input Mode: Direct


Fault Type:

Ramped Quantities
V L2-E, L3-E / Magnitude
.
Ramp States
Ramp Ramp 1
V L1-E 63.51 V
0.00 °
50.000 Hz
V L2-E 78.00 V
-120.00 °
50.000 Hz
V L3-E 78.00 V
120.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 78.00 V
Sig 1 To 81.00 V
Sig 1 Delta 100.0 mV
Sig 1 d/dt 1.000 V/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 31
Ramp Time 3.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s

. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 06-Jun-2023 15:09:41 Test End: 06-Jun-2023 15:09:45
User Name: Manager:
Company:

Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 V L2-E, 79.38 V 79.50 V 793.8 mV 793.8 mV 120.0 mV + 36.40 ms
L3-E
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed

59G Stage2 pickup L3L1:

Page 74 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

Test Settings
.
General
No. of ramp states: 1
Total steps per test: 31
Total time per test: 3.100 s
No. of test executions: 1

Input Mode: Direct


Fault Type:

Ramped Quantities
V L3-E, L1-E / Magnitude
.
Ramp States
Ramp Ramp 1
V L1-E 78.00 V
0.00 °
50.000 Hz
V L2-E 63.51 V
-120.00 °
50.000 Hz
V L3-E 78.00 V
120.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 78.00 V
Sig 1 To 81.00 V
Sig 1 Delta 100.0 mV
Sig 1 d/dt 1.000 V/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 31
Ramp Time 3.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s

. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 06-Jun-2023 15:10:54 Test End: 06-Jun-2023 15:10:57
User Name: Manager:
Company:

Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 V L3-E, 79.38 V 79.50 V 793.8 mV 793.8 mV 120.0 mV + 5.800 ms

Page 75 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

L1-E
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed

59G Stage2 pickup L1L2L3:

Test Settings
.
General
No. of ramp states: 1
Total steps per test: 31
Total time per test: 3.100 s
No. of test executions: 1

Input Mode: Direct


Fault Type:

Ramped Quantities
V L1-E, L2-E, L3-E / Magnitude
.
Ramp States
Ramp Ramp 1
V L1-E 78.00 V
0.00 °
50.000 Hz
V L2-E 78.00 V
-120.00 °
50.000 Hz
V L3-E 78.00 V
120.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 78.00 V
Sig 1 To 81.00 V
Sig 1 Delta 100.0 mV
Sig 1 d/dt 1.000 V/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 31
Ramp Time 3.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s

. .
Test Module
Page 76 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

Name: OMICRON Ramping Version: 4.30


Test Start: 06-Jun-2023 15:11:43 Test End: 06-Jun-2023 15:11:46
User Name: Manager:
Company:

Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 V L1-E, 79.38 V 79.40 V 793.8 mV 793.8 mV 20.00 mV + 49.30 ms
L2-E, L3-
E
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed

8.4 59G Stage2 Triptime:


. .
Test Module
Name: OMICRON QuickCMC Version: 4.30
Test Start: 06-Jun-2023 15:16:59 Test End: 06-Jun-2023 15:17:02
User Name: Manager:
Company:

Test Results
Title: Triptime L1
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V L1-E 81.00 V 0.00 ° 50.000 Hz
V L2-E 81.00 V -120.00 ° 50.000 Hz
V L3-E 0.00 V 120.00 ° 50.000 Hz

Generator Settings
V L1-E 81.000V 0.00° +90°

V L1-E
180° 0°

V L2-E

100.0 V -90°
V L2-E 81.000V -120.00°
V L3-E 0.000V 120.00°

Binary Inputs
Name Slope Time
TRIP 0->1 1.053s
Comment
Actual Triptime = 1 seconds.

Title: Triptime L2L3


Page 77 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V L1-E 0.00 V 0.00 ° 50.000 Hz
V L2-E 81.00 V -120.00 ° 50.000 Hz
V L3-E 81.00 V 120.00 ° 50.000 Hz

Generator Settings
V L1-E 0.000V 0.00° +90°

V L3-E

180° 0°

V L2-E

100.0 V -90°
V L2-E 81.000V -120.00°
V L3-E 81.000V 120.00°

Binary Inputs
Name Slope Time
TRIP 0->1 1.058s
Comment
Actual Triptime = 1 seconds.

Title: Triptime L1L3


.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V L1-E 81.00 V 0.00 ° 50.000 Hz
V L2-E 0.00 V -120.00 ° 50.000 Hz
V L3-E 81.00 V 120.00 ° 50.000 Hz

Generator Settings
V L1-E 81.000V 0.00° +90°

V L3-E

V L1-E
180° 0°

100.0 V -90°
V L2-E 0.000V -120.00°
V L3-E 81.000V 120.00°

Binary Inputs
Name Slope Time
TRIP 0->1 1.053s
Comment
Actual Triptime = 1 seconds.

Title: Triptime L1L2L3


Page 78 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V L1-E 81.00 V 0.00 ° 50.000 Hz
V L2-E 81.00 V -120.00 ° 50.000 Hz
V L3-E 81.00 V 120.00 ° 50.000 Hz

Generator Settings
V L1-E 81.000V 0.00° +90°

V L3-E

V L1-E
180° 0°

V L2-E

100.0 V -90°
V L2-E 81.000V -120.00°
V L3-E 81.000V 120.00°

Binary Inputs
Name Slope Time
TRIP 0->1 1.054s
Comment
Actual Triptime = 1 seconds.
Summary
4 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed

9. Underfrequency Protection (81U)

9.1 Stage1 pickup Test:

Test Settings
.
General
No. of ramp states: 1
Total steps per test: 201
Total time per test: 20.100 s
No. of test executions: 1

Input Mode: Direct


Fault Type:

Ramped Quantities
V L1-E / Frequency
.
Ramp States
Ramp Ramp 1

Page 79 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

V L1-E 63.51 V
0.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 50.000 Hz
Sig 1 To 48.000 Hz
Sig 1 Delta -10.000 mHz
Sig 1 d/dt -100.0 mHz/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 201
Ramp Time 20.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s

. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 06-Jun-2023 15:32:33 Test End: 06-Jun-2023 15:32:44
User Name: Manager:
Company:

Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 V L1-E 49.000 Hz 48.990 Hz 10.000 mHz 10.000 mHz -10.000 + 90.50 ms
mHz
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed

81U Stage1 overvoltage blocking Test:

Test Settings
.
General
No. of ramp states: 1
Total steps per test: 135
Total time per test: 13.500 s
No. of test executions: 1

Input Mode: Direct


Fault Type:

Ramped Quantities
V L1-E / Magnitude
.
Page 80 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

Ramp States
Ramp Ramp 1
V L1-E 84.00 V
0.00 °
48.990 Hz
Force abs. Phases No
Sig 1 From 84.00 V
Sig 1 To 80.00 V
Sig 1 Delta -30.00 mV
Sig 1 d/dt -300.0 mV/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 135
Ramp Time 13.500s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s

Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 06-Jun-2023 15:38:36 Test End: 06-Jun-2023 15:38:43
User Name: Manager:
Company:

Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 V L1-E 82.56 V 82.59 V 825.0 mV 825.0 mV 30.00 mV + 50.30 ms
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed

81U Stage1 pickup OV blocking:

Test Settings
.
General
No. of ramp states: 1
Total steps per test: 201
Total time per test: 20.100 s
No. of test executions: 1

Input Mode: Direct


Fault Type:

Ramped Quantities
V L1-E / Frequency

Page 81 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

.
Ramp States
Ramp Ramp 1
V L1-E 110.0 V
0.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 50.000 Hz
Sig 1 To 48.000 Hz
Sig 1 Delta -10.000 mHz
Sig 1 d/dt -100.0 mHz/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 201
Ramp Time 20.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s

Comment
At rated frequency, if the Voltage is less than the set blocking undervoltge i.e., 44.45 V then the relay doesnot trip.

Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 06-Jun-2023 15:42:30 Test End: 06-Jun-2023 15:42:52
User Name: Manager:
Company:

Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 V L1-E 49.000 Hz 10.000 mHz 10.000 mHz x
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed (manually assessed)

81U Stage1 undervoltage blocking:

Test Settings
.
General
No. of ramp states: 1
Total steps per test: 201
Total time per test: 20.100 s
No. of test executions: 1

Input Mode: Direct

Page 82 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

Fault Type:

Ramped Quantities
V L1-E / Magnitude
.
Ramp States
Ramp Ramp 1
V L1-E 40.00 V
0.00 °
48.990 Hz
Force abs. Phases No
Sig 1 From 40.00 V
Sig 1 To 46.00 V
Sig 1 Delta 30.00 mV
Sig 1 d/dt 300.0 mV/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 201
Ramp Time 20.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s
Comment
At underfrequency less than 49 Hz, if the Voltage is less than the blocking undervoltage then the relay does not trip.
If the voltage is more than the blocking undervoltage then the relay trips.
. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 06-Jun-2023 15:52:30 Test End: 06-Jun-2023 15:52:47
User Name: Manager:
Company:

Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 V L1-E 44.45 V 44.53 V 444.0 mV 444.0 mV 80.00 mV + 45.10 ms
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed

81U Stage1 pickup UV blocking:

Test Settings
.
General
No. of ramp states: 1
Total steps per test: 201

Page 83 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

Total time per test: 20.100 s


No. of test executions: 1

Input Mode: Direct


Fault Type:

Ramped Quantities
V L1-E / Frequency
.
Ramp States
Ramp Ramp 1
V L1-E 43.00 V
0.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 50.000 Hz
Sig 1 To 48.000 Hz
Sig 1 Delta -10.000 mHz
Sig 1 d/dt -100.0 mHz/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 201
Ramp Time 20.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s

Comment
At rated frequency, if the Voltage is less than the set blocking undervoltge i.e., 44.45 V then the relay doesnot trip.

. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 06-Jun-2023 15:53:34 Test End: 06-Jun-2023 15:53:56
User Name: Manager:
Company:

Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 V L1-E 49.000 Hz 10.000 mHz 10.000 mHz x
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed (manually assessed)

9.2 81U trip time Stage 1:


. .
Page 84 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

Test Module
Name: OMICRON QuickCMC Version: 4.30
Test Start: 06-Jun-2023 15:57:14 Test End: 06-Jun-2023 15:57:18
User Name: Manager:
Company:

Test Results
Title: Test 1
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V L1-E 63.51 V 0.00 ° 48.990 Hz

Generator Settings
V L1-E 63.510V 0.00° +90°

V L1-E
180° 0°

80.0 V -90°

Binary Inputs
Name Slope Time
TRIP 0->1 5.635s
Comment
Operate time delay = 5 seconds.
Summary
1 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed

9.3 81U Stage2 pickup:

Test Settings
.
General
No. of ramp states: 1
Total steps per test: 401
Total time per test: 40.100 s
No. of test executions: 1

Input Mode: Direct


Fault Type:

Ramped Quantities
V L1-E / Frequency

Page 85 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

.
Ramp States
Ramp Ramp 1
V L1-E 63.51 V
0.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 50.000 Hz
Sig 1 To 46.000 Hz
Sig 1 Delta -10.000 mHz
Sig 1 d/dt -100.0 mHz/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 401
Ramp Time 40.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s

. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 06-Jun-2023 16:05:36 Test End: 06-Jun-2023 16:06:03
User Name: Manager:
Company:

Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 V L1-E 47.500 Hz 47.490 Hz 10.000 mHz 10.000 mHz -10.000 + 94.80 ms
mHz
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed
81U Stage2 overvoltage blocking:

Test Settings
.
General
No. of ramp states: 1
Total steps per test: 135
Total time per test: 13.500 s
No. of test executions: 1

Input Mode: Direct


Fault Type:

Ramped Quantities

Page 86 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

V L1-E / Magnitude
.
Ramp States
Ramp Ramp 1
V L1-E 84.00 V
0.00 °
47.000 Hz
Force abs. Phases No
Sig 1 From 84.00 V
Sig 1 To 80.00 V
Sig 1 Delta -30.00 mV
Sig 1 d/dt -300.0 mV/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 135
Ramp Time 13.500s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 06-Jun-2023 16:07:55 Test End: 06-Jun-2023 16:08:01
User Name: Manager:
Company:

Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 V L1-E 82.56 V 82.59 V 825.6 mV 825.6 mV 30.00 mV + 46.60 ms
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed

81U Stage2 pickup OV blocking:

Test Settings
.
General
No. of ramp states: 1
Total steps per test: 301
Total time per test: 30.100 s
No. of test executions: 1

Input Mode: Direct


Fault Type:

Ramped Quantities
V L1-E / Frequency
Page 87 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

.
Ramp States
Ramp Ramp 1
V L1-E 110.0 V
0.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 50.000 Hz
Sig 1 To 47.000 Hz
Sig 1 Delta -10.000 mHz
Sig 1 d/dt -100.0 mHz/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 301
Ramp Time 30.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s

Comment
At rated frequency, if the Voltage is less than the set blocking undervoltge i.e., 44.45 V then the relay doesnot trip.

.
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 06-Jun-2023 16:08:57 Test End: 06-Jun-2023 16:09:29
User Name: Manager:
Company:

Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 V L1-E 47.500 Hz 10.000 mHz 10.000 mHz x
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed (manually assessed)

81U Stage2 undervoltage blocking:

Test Settings
.
General
No. of ramp states: 1
Total steps per test: 201
Total time per test: 20.100 s
No. of test executions: 1

Page 88 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

Input Mode: Direct


Fault Type:

Ramped Quantities
V L1-E / Magnitude
.
Ramp States
Ramp Ramp 1
V L1-E 40.00 V
0.00 °
47.000 Hz
Force abs. Phases No
Sig 1 From 40.00 V
Sig 1 To 46.00 V
Sig 1 Delta 30.00 mV
Sig 1 d/dt 300.0 mV/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 201
Ramp Time 20.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s

Comment
At underfrequency less than 49 Hz, if the Voltage is less than the blocking undervoltage then the relay does not trip.
If the voltage is more than the blocking undervoltage then the relay trips.
. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 06-Jun-2023 16:10:41 Test End: 06-Jun-2023 16:10:58
User Name: Manager:
Company:

Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 V L1-E 44.45 V 44.53 V 444.0 mV 444.0 mV 80.00 mV + 52.60 ms
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed

81U Stage2 pickup UV blocking:

Test Settings
.
General

Page 89 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

No. of ramp states: 1


Total steps per test: 301
Total time per test: 30.100 s
No. of test executions: 1

Input Mode: Direct


Fault Type:

Ramped Quantities
V L1-E / Frequency
.
Ramp States
Ramp Ramp 1
V L1-E 43.00 V
0.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 50.000 Hz
Sig 1 To 47.000 Hz
Sig 1 Delta -10.000 mHz
Sig 1 d/dt -100.0 mHz/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 301
Ramp Time 30.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s

Comment
At rated frequency, if the Voltage is less than the set blocking undervoltge i.e., 44.45 V then the relay doesnot trip.
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 06-Jun-2023 16:11:43 Test End: 06-Jun-2023 16:12:15
User Name: Manager:
Company:

Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 V L1-E 47.500 Hz 10.000 mHz 10.000 mHz x
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed (manually assessed)

9.4 81U trip time Stage 2:


. .
Page 90 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

Test Module
Name: OMICRON QuickCMC Version: 4.30
Test Start: 06-Jun-2023 16:13:17 Test End: 06-Jun-2023 16:14:02
User Name: Manager:
Company:

Test Results
Title: Test 1
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V L1-E 63.51 V 0.00 ° 47.000 Hz

Generator Settings
V L1-E 63.510V 0.00° +90°

V L1-E
180° 0°

80.0 V -90°

Binary Inputs
Name Slope Time
TRIP 0->1 0.485s
Comment
Operate Time delay = 0 second.
Summary
1 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed
10. Overfrequency Protection (81o)

10.1 Stage1 pickup Test:

Test Settings
.
General
No. of ramp states: 1
Total steps per test: 401
Total time per test: 40.100 s
No. of test executions: 1

Input Mode: Direct


Fault Type:

Page 91 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

Ramped Quantities
V L1-E / Frequency
.
Ramp States
Ramp Ramp 1
V L1-E 63.50 V
0.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 50.000 Hz
Sig 1 To 52.000 Hz
Sig 1 Delta 5.0000 mHz
Sig 1 d/dt 50.00 mHz/s
dt per Step 100.0 ms
Ramp Steps 401
Ramp Time 40.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s

. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 07-Jun-2023 09:12:05 Test End: 07-Jun-2023 09:12:27
User Name: Manager:
Company:

Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 V L1-E 51.000 Hz 51.010 Hz 10.000 mHz 10.000 mHz 10.000 mHz + 36.70 ms
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed

81o Stage1 overvoltage blocking:

Test Settings
.
General
No. of ramp states: 1
Total steps per test: 401
Total time per test: 40.100 s
No. of test executions: 1

Input Mode: Direct


Fault Type:

Ramped Quantities
V L1-E / Magnitude

Page 92 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

.
Ramp States
Ramp Ramp 1
V L1-E 84.00 V
0.00 °
51.500 Hz
Force abs. Phases No
Sig 1 From 84.00 V
Sig 1 To 80.00 V
Sig 1 Delta -10.00 mV
Sig 1 d/dt -100.0 mV/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 401
Ramp Time 40.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s

Comment
1. At 81o stage 1, if the voltage is greater than blocking overvoltage then relay does not trip.
2. If the voltage is less than the blocking overvoltage then the relay trips.
. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 07-Jun-2023 09:13:28 Test End: 07-Jun-2023 09:13:44
User Name: Manager:
Company:

Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 V L1-E 82.50 V 82.63 V 825.0 mV 825.0 mV 130.0 mV + 58.00 ms
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed

81o Stage1 pickup OV block:

Test Settings
.
General
No. of ramp states: 1
Total steps per test: 201
Total time per test: 20.100 s
No. of test executions: 1

Page 93 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

Input Mode: Direct


Fault Type:

Ramped Quantities
V L1-E / Frequency
.
Ramp States
Ramp Ramp 1
V L1-E 84.00 V
0.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 50.000 Hz
Sig 1 To 52.000 Hz
Sig 1 Delta 10.000 mHz
Sig 1 d/dt 100.0 mHz/s
dt per Step 100.0 ms
Ramp Steps 201
Ramp Time 20.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s

Comment
If the voltage is more than the blocking overvoltage then the 81o function doesnot take place.
. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 07-Jun-2023 09:14:15 Test End: 07-Jun-2023 09:14:37
User Name: Manager:
Company:

Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 V L1-E 51.000 Hz 10.000 mHz 10.000 mHz x
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed (manually assessed)

81o Stage1 undervoltage blocking:

Test Settings
.
General
No. of ramp states: 1
Total steps per test: 151
Total time per test: 15.100 s
No. of test executions: 1

Page 94 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

Input Mode: Direct


Fault Type:

Ramped Quantities
V L1-E / Magnitude
.
Ramp States
Ramp Ramp 1
V L1-E 43.00 V
0.00 °
51.010 Hz
Force abs. Phases No
Sig 1 From 43.00 V
Sig 1 To 46.00 V
Sig 1 Delta 20.00 mV
Sig 1 d/dt 200.0 mV/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 151
Ramp Time 15.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s

Comment
If the voltage is more than the Blocking undervoltage at Stage 1, then the relay trips.
. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 07-Jun-2023 09:15:56 Test End: 07-Jun-2023 09:16:06
User Name: Manager:
Company:

Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 V L1-E 44.50 V 44.52 V 400.0 mV 400.0 mV 20.00 mV + 50.50 ms
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed

81o Stage1 pick up UV block:

Test Settings
.
General
Page 95 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

No. of ramp states: 1


Total steps per test: 201
Total time per test: 20.100 s
No. of test executions: 1

Input Mode: Direct


Fault Type:

Ramped Quantities
V L1-E / Frequency
.
Ramp States
Ramp Ramp 1
V L1-E 43.00 V
0.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 50.000 Hz
Sig 1 To 52.000 Hz
Sig 1 Delta 10.000 mHz
Sig 1 d/dt 100.0 mHz/s
dt per Step 100.0 ms
Ramp Steps 201
Ramp Time 20.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s

Comment
If the voltage is less than the blocking undervoltage then the 81o function doesnot take place.
. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 07-Jun-2023 09:16:41 Test End: 07-Jun-2023 09:17:03
User Name: Manager:
Company:

Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 V L1-E 51.000 Hz 10.000 mHz 10.000 mHz x
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed (manually assessed)

10.2 81o trip time Stage1:


. .
Test Module
Name: OMICRON QuickCMC Version: 4.30

Page 96 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

Test Start: 07-Jun-2023 09:19:03 Test End: 07-Jun-2023 09:19:07


User Name: Manager:
Company:

Test Results
Title: Test 1
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V L1-E 63.51 V 0.00 ° 52.000 Hz

Generator Settings
V L1-E 63.510V 0.00° +90°

V L1-E
180° 0°

80.0 V -90°

Binary Inputs
Name Slope Time
TRIP 0->1 5.435s
Comment
Operate Time delay = 5 seconds.
Summary
1 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed

10.3 81o Stage2 pickup:

Test Settings
.
General
No. of ramp states: 1
Total steps per test: 601
Total time per test: 60.100 s
No. of test executions: 1

Input Mode: Direct


Fault Type:

Ramped Quantities
V L1-E / Frequency
.
Ramp States

Page 97 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

Ramp Ramp 1
V L1-E 63.50 V
0.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 50.000 Hz
Sig 1 To 53.000 Hz
Sig 1 Delta 5.0000 mHz
Sig 1 d/dt 50.00 mHz/s
dt per Step 100.0 ms
Ramp Steps 601
Ramp Time 60.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s

. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 07-Jun-2023 09:26:20 Test End: 07-Jun-2023 09:27:11
User Name: Manager:
Company:

Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 V L1-E 52.500 Hz 52.510 Hz 10.000 mHz 10.000 mHz 10.000 mHz + 38.20 ms
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed

81o Stage2 overvoltage blocking:

Test Settings
.
General
No. of ramp states: 1
Total steps per test: 401
Total time per test: 40.100 s
No. of test executions: 1

Input Mode: Direct


Fault Type:

Ramped Quantities
V L1-E / Magnitude
.
Ramp States
Ramp Ramp 1
V L1-E 84.00 V
0.00 °

Page 98 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

52.700 Hz
Force abs. Phases No
Sig 1 From 84.00 V
Sig 1 To 80.00 V
Sig 1 Delta -10.00 mV
Sig 1 d/dt -100.0 mV/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 401
Ramp Time 40.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s

Comment
1. At 81o stage 1, if the voltage is greater than blocking overvoltage then relay does not trip.
2. If the voltage is less than the blocking overvoltage then the relay trips.
. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 07-Jun-2023 09:27:55 Test End: 07-Jun-2023 09:28:10
User Name: Manager:
Company:

Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 V L1-E 82.50 V 82.63 V 825.0 mV 825.0 mV 130.0 mV + 54.00 ms
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed

81o Stage2 pickup OV block:

Test Settings
.
General
No. of ramp states: 1
Total steps per test: 301
Total time per test: 30.100 s
No. of test executions: 1

Input Mode: Direct


Fault Type:

Ramped Quantities
V L1-E / Frequency

Page 99 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

.
Ramp States
Ramp Ramp 1
V L1-E 84.00 V
0.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 50.000 Hz
Sig 1 To 53.000 Hz
Sig 1 Delta 10.000 mHz
Sig 1 d/dt 100.0 mHz/s
dt per Step 100.0 ms
Ramp Steps 301
Ramp Time 30.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s

Comment
If the voltage is more than the blocking overvoltage then the 81o function doesnot take place.
. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 07-Jun-2023 09:28:45 Test End: 07-Jun-2023 09:29:17
User Name: Manager:
Company:

Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 V L1-E 52.500 Hz 10.000 mHz 10.000 mHz x
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed (manually assessed)

81o Stage2 undervoltage blocking:

Test Settings
.
General
No. of ramp states: 1
Total steps per test: 151
Total time per test: 15.100 s
No. of test executions: 1

Input Mode: Direct


Fault Type:

Ramped Quantities
Page 100 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

V L1-E / Magnitude
.
Ramp States
Ramp Ramp 1
V L1-E 43.00 V
0.00 °
52.700 Hz
Force abs. Phases No
Sig 1 From 43.00 V
Sig 1 To 46.00 V
Sig 1 Delta 20.00 mV
Sig 1 d/dt 200.0 mV/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 151
Ramp Time 15.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s

Comment
If the voltage is more than the Blocking undervoltage at Stage 1, then the relay trips.
. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 07-Jun-2023 09:29:55 Test End: 07-Jun-2023 09:30:05
User Name: Manager:
Company:

Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 V L1-E 44.50 V 44.50 V 400.0 mV 400.0 mV 0.00 V + 97.10 ms
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed

81o Stage2 pickup UV block:

Test Settings
.
General
No. of ramp states: 1
Total steps per test: 301
Total time per test: 30.100 s
No. of test executions: 1

Page 101 of 146


Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

Input Mode: Direct


Fault Type:

Ramped Quantities
V L1-E / Frequency
.
Ramp States
Ramp Ramp 1
V L1-E 43.00 V
0.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 50.000 Hz
Sig 1 To 53.000 Hz
Sig 1 Delta 10.000 mHz
Sig 1 d/dt 100.0 mHz/s
dt per Step 100.0 ms
Ramp Steps 301
Ramp Time 30.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s

Comment
If the voltage is less than the blocking undervoltage then the 81o function doesnot take place.
. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 07-Jun-2023 09:30:42 Test End: 07-Jun-2023 09:31:14
User Name: Manager:
Company:

Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 V L1-E 52.500 Hz 10.000 mHz 10.000 mHz x
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed (manually assessed)

10.4 81o triptime Stage2:


. .
Test Module
Name: OMICRON QuickCMC Version: 4.30
Test Start: 07-Jun-2023 09:32:23 Test End: 07-Jun-2023 09:32:27
User Name: Manager:
Company:

Test Results
Page 102 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

Title: Test 1
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V L1-E 63.51 V 0.00 ° 52.700 Hz

Generator Settings
V L1-E 63.510V 0.00° +90°

V L1-E
180° 0°

80.0 V -90°

Binary Inputs
Name Slope Time
TRIP 0->1 0.519s
Comment
Operate Time delay = 0 second.
Summary
1 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed

11. Undervoltage Protection (27G)

11.1 Pickup Test:

Stage1 pickup L1L2:

Test Settings
.
General
No. of ramp states: 1
Total steps per test: 85
Total time per test: 8.500 s
No. of test executions: 1

Input Mode: Direct


Fault Type:

Ramped Quantities
V L1-E, L2-E / Magnitude
.
Ramp States
Page 103 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

Ramp Ramp 1
V L1-E 46.19 V
0.00 °
50.000 Hz
V L2-E 46.19 V
-120.00 °
50.000 Hz
V L3-E 63.50 V
120.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 46.19 V
Sig 1 To 42.00 V
Sig 1 Delta -50.00 mV
Sig 1 d/dt -500.0 mV/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 85
Ramp Time 8.500s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s

. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 10-Jun-2023 09:53:40 Test End: 10-Jun-2023 09:53:45
User Name: Manager:
Company:

Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 V L1-E, 44.45 V 44.44 V 444.0 mV 444.0 mV -11.00 mV + 51.60 ms
L2-E
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed

27G Stage1 pickup L2L3:

Test Settings
.
General
No. of ramp states: 1
Total steps per test: 85
Total time per test: 8.500 s
No. of test executions: 1

Page 104 of 146


Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

Input Mode: Direct


Fault Type:

Ramped Quantities
V L2-E, L3-E / Magnitude
.
Ramp States
Ramp Ramp 1
V L1-E 63.50 V
0.00 °
50.000 Hz
V L2-E 46.19 V
-120.00 °
50.000 Hz
V L3-E 46.19 V
120.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 46.19 V
Sig 1 To 42.00 V
Sig 1 Delta -50.00 mV
Sig 1 d/dt -500.0 mV/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 85
Ramp Time 8.500s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s

. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 10-Jun-2023 09:54:39 Test End: 10-Jun-2023 09:54:44
User Name: Manager:
Company:

Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 V L2-E, 44.45 V 44.44 V 444.0 mV 444.0 mV -11.00 mV + 41.30 ms
L3-E
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed

27G Stage1 pickup L3L1:

Test Settings
Page 105 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

.
General
No. of ramp states: 1
Total steps per test: 85
Total time per test: 8.500 s
No. of test executions: 1

Input Mode: Direct


Fault Type:

Ramped Quantities
V L3-E, L1-E / Magnitude
.
Ramp States
Ramp Ramp 1
V L1-E 46.19 V
0.00 °
50.000 Hz
V L2-E 63.50 V
-120.00 °
50.000 Hz
V L3-E 46.19 V
120.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 46.19 V
Sig 1 To 42.00 V
Sig 1 Delta -50.00 mV
Sig 1 d/dt -500.0 mV/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 85
Ramp Time 8.500s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s

. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 10-Jun-2023 09:55:17 Test End: 10-Jun-2023 09:55:23
User Name: Manager:
Company:

Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 V L3-E, 44.45 V 44.44 V 444.0 mV 444.0 mV -11.00 mV + 61.70 ms
L1-E

Page 106 of 146


Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

Assess: + .. Passed x .. Failed o .. Not assessed


Test State:
Test passed

27G Stage1 pickup L1L2L3:

Test Settings
.
General
No. of ramp states: 1
Total steps per test: 85
Total time per test: 8.500 s
No. of test executions: 1

Input Mode: Direct


Fault Type:

Ramped Quantities
V L1-E, L2-E, L3-E / Magnitude
.
Ramp States
Ramp Ramp 1
V L1-E 46.19 V
0.00 °
50.000 Hz
V L2-E 46.19 V
-120.00 °
50.000 Hz
V L3-E 46.19 V
120.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 46.19 V
Sig 1 To 42.00 V
Sig 1 Delta -50.00 mV
Sig 1 d/dt -500.0 mV/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 85
Ramp Time 8.500s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s

. .
Test Module
Name: OMICRON Ramping Version: 4.30

Page 107 of 146


Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

Test Start: 10-Jun-2023 09:55:55 Test End: 10-Jun-2023 09:56:01


User Name: Manager:
Company:

Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 V L1-E, 44.45 V 44.44 V 444.0 mV 444.0 mV -11.00 mV + 49.10 ms
L2-E, L3-
E
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed

10.2 Undervoltage Triptime Test:


. .
Test Module
Name: OMICRON QuickCMC Version: 4.30
Test Start: 10-Jun-2023 10:00:47 Test End: 10-Jun-2023 10:02:44
User Name: Manager:
Company:

Test Results
Title: NO TRIP condition
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V L1-E 63.51 V 0.00 ° 50.000 Hz
V L2-E 63.51 V -120.00 ° 50.000 Hz
V L3-E 63.51 V 120.00 ° 50.000 Hz

Generator Settings
V L1-E 63.509V 0.00° +90°

V L3-E

V L1-E
180° 0°

V L2-E

80.0 V -90°
V L2-E 63.509V -120.00°
V L3-E 63.509V 120.00°

Binary Inputs
Name Slope Time
TRIP 0

Title: TRIP condition


.
Fault Calculator:
Page 108 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

Table Inputmode Parameters (All values are secondary)


Direct V L1-E 43.00 V 0.00 ° 50.000 Hz
V L2-E 43.00 V -120.00 ° 50.000 Hz
V L3-E 43.00 V 120.00 ° 50.000 Hz

Generator Settings
V L1-E 43.000V 0.00° +90°

V L3-E

V L1-E
180° 0°

V L2-E

50.0 V -90°
V L2-E 43.000V -120.00°
V L3-E 43.000V 120.00°

Binary Inputs
Name Slope Time
TRIP 0->1 4.063s

Comment
Firstly, inject nominal voltage i.e., 63.51 V then hold the values and inject values less than the rated undervoltage value.
Then give the feedback and unhold the values.
Summary
2 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed

12. Overexcitation Protection (24G)

12.1 Pickup Test

Stage1 pickup L1:

Test Settings
.
General
No. of ramp states: 1
Total steps per test: 301
Total time per test: 30.100 s
No. of test executions: 1

Input Mode: Direct


Fault Type:

Ramped Quantities

Page 109 of 146


Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

V L1-E / Frequency
.
Ramp States
Ramp Ramp 1
V L1-E 110.0 V
0.00 °
47.000 Hz
Force abs. Phases No
Sig 1 From 47.000 Hz
Sig 1 To 44.000 Hz
Sig 1 Delta -10.000 mHz
Sig 1 d/dt -100.0 mHz/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 301
Ramp Time 30.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s

. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 07-Jun-2023 12:14:10 Test End: 07-Jun-2023 12:14:28
User Name: Manager:
Company:

Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 V L1-E 45.450 Hz 45.450 Hz 454.00 mHz 454.00 mHz 0.000 Hz + 13.00 ms
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed

24G Stage1 pickup L1L2L3:

Test Settings
.
General
No. of ramp states: 1
Total steps per test: 301
Total time per test: 30.100 s
No. of test executions: 1

Input Mode: Direct


Fault Type:

Page 110 of 146


Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

Ramped Quantities
V L1-E, L2-E, L3-E / Frequency
.
Ramp States
Ramp Ramp 1
V L1-E 63.51 V
0.00 °
47.000 Hz
V L2-E 63.51 V
-120.00 °
47.000 Hz
V L3-E 63.51 V
120.00 °
47.000 Hz
Force abs. Phases No
Sig 1 From 47.000 Hz
Sig 1 To 44.000 Hz
Sig 1 Delta -10.000 mHz
Sig 1 d/dt -100.0 mHz/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 301
Ramp Time 30.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s

. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 07-Jun-2023 12:15:14 Test End: 07-Jun-2023 12:15:31
User Name: Manager:
Company:

Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 V L1-E, 45.450 Hz 45.440 Hz 454.00 mHz 454.00 mHz -10.000 + 46.80 ms
L2-E, L3- mHz
E
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed

11.2 24G Stage1 Triptime:


. .
Test Module
Name: OMICRON QuickCMC Version: 4.30
Test Start: 07-Jun-2023 12:18:53 Test End: 07-Jun-2023 12:22:47

Page 111 of 146


Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

User Name: Manager:


Company:

Test Results
Title: Test 1
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V L1-E 63.51 V 0.00 ° 40.000 Hz
V L2-E 63.51 V -120.00 ° 40.000 Hz
V L3-E 63.51 V 120.00 ° 40.000 Hz

Generator Settings
V L1-E 63.510V 0.00° +90°

V L3-E

V L1-E
180° 0°

V L2-E

80.0 V -90°
V L2-E 63.510V -120.00°
V L3-E 63.510V 120.00°

Binary Inputs
Name Slope Time
TRIP 0->1 5.397s

Comment
1. Actual Volts/Hertz = 2.42
2. Operate Time Delay = 5 seconds
Saturation, S = Volts/Hertz
110/40= 2.75
Summary
1 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed

11.3 24G Stage2 pickup L1:

Test Settings
.
General
No. of ramp states: 1
Total steps per test: 121
Total time per test: 12.100 s
No. of test executions: 1

Input Mode: Direct


Fault Type:

Page 112 of 146


Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

Ramped Quantities
V L1-E / Frequency
.
Ramp States
Ramp Ramp 1
V L1-E 110.0 V
0.00 °
47.000 Hz
Force abs. Phases No
Sig 1 From 47.000 Hz
Sig 1 To 35.000 Hz
Sig 1 Delta -100.00 mHz
Sig 1 d/dt -1.000 Hz/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 121
Ramp Time 12.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s

. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 07-Jun-2023 12:28:17 Test End: 07-Jun-2023 12:28:26
User Name: Manager:
Company:

Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 V L1-E 40.000 Hz 39.900 Hz 400.00 mHz 400.00 mHz -100.00 + 77.30 ms
mHz
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed

24G Stage2 pickup L1L2L3:

Test Settings
.
General
No. of ramp states: 1
Total steps per test: 121
Total time per test: 12.100 s
No. of test executions: 1

Page 113 of 146


Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

Input Mode: Direct


Fault Type:

Ramped Quantities
V L1-E, L2-E, L3-E / Frequency
.
Ramp States
Ramp Ramp 1
V L1-E 63.51 V
0.00 °
47.000 Hz
V L2-E 63.51 V
-120.00 °
47.000 Hz
V L3-E 63.51 V
120.00 °
47.000 Hz
Force abs. Phases No
Sig 1 From 47.000 Hz
Sig 1 To 35.000 Hz
Sig 1 Delta -100.00 mHz
Sig 1 d/dt -1.000 Hz/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 121
Ramp Time 12.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s

. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 07-Jun-2023 12:29:39 Test End: 07-Jun-2023 12:29:48
User Name: Manager:
Company:

Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 V L1-E, 40.000 Hz 40.000 Hz 400.00 mHz 400.00 mHz 0.000 Hz + 94.00 ms
L2-E, L3-
E
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed

11.4 24G Stage2 Trip time:


. .
Page 114 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

Test Module
Name: OMICRON QuickCMC Version: 4.30
Test Start: 07-Jun-2023 12:31:45 Test End: 07-Jun-2023 12:31:48
User Name: Manager:
Company:

Test Results
Title: Test 1
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V L1-E 63.51 V 0.00 ° 35.000 Hz
V L2-E 63.51 V -120.00 ° 35.000 Hz
V L3-E 63.51 V 120.00 ° 35.000 Hz

Generator Settings
V L1-E 63.510V 0.00° +90°

V L3-E

V L1-E
180° 0°

V L2-E

80.0 V -90°
V L2-E 63.510V -120.00°
V L3-E 63.510V 120.00°

Binary Inputs
Name Slope Time
TRIP 0->1 0.398s

Comment
1. Actual Volts/Hertz = 2.75
2. Operate Time Delay = 0.3 seconds
Saturation, S = Volts/Hertz
110/40= 2.75
Summary
1 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed

13. Loss of Excitation Protection (40G)

13.1 Pickup Test:


. .
Test Module
Name: OMICRON QuickCMC Version: 4.30
Test Start: 07-Jun-2023 14:55:39 Test End: 07-Jun-2023 14:55:44
User Name: Manager:

Page 115 of 146


Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

Company:

Test Results
Title: Test 1
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V L1-E 0.00 V 0.00 ° 50.000 Hz
V L2-E 63.51 V -120.00 ° 50.000 Hz
V L3-E 63.51 V 120.00 ° 50.000 Hz
I(1)-1 14.00 A 0.00 ° 50.000 Hz
I(1)-2 0.00 A -120.00 ° 50.000 Hz
I(1)-3 0.00 A 120.00 ° 50.000 Hz

Generator Settings
V L1-E 0.000V 0.00° +90°

V L3-E

I(1)-1
180° 0°

V L2-E

80.0 V -90° 15.0 A


V L2-E 63.510V -120.00°
V L3-E 63.510V 120.00°
I(1)-1 14.000A 0.00°
I(1)-2 0.000A -120.00°
I(1)-3 0.000A 120.00°

Binary Inputs
Name Slope Time
TRIP 0->1 0.055s
Overload 1->0 n/a

Comment
1. To find the start value rotor angle i.e., 70 degree, we inject one of the phase current with its opposite phase voltages.
2. Here we ramp either current or the phase angle. (The exact current and exact phase angle to find the rotor angle is not
defined)
Summary
1 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed

12.2 40G Trip time Test:


. .
Test Module
Name: OMICRON QuickCMC Version: 4.30
Test Start: 07-Jun-2023 14:56:05 Test End: 07-Jun-2023 15:04:12
User Name: Manager:
Company:

Page 116 of 146


Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

Test Results
Title: Test 1
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V L1-E 0.00 V 0.00 ° 50.000 Hz
V L2-E 63.51 V -120.00 ° 50.000 Hz
V L3-E 63.51 V 120.00 ° 50.000 Hz
I(1)-1 18.00 A 0.00 ° 50.000 Hz
I(1)-2 0.00 A -120.00 ° 50.000 Hz
I(1)-3 0.00 A 120.00 ° 50.000 Hz

Generator Settings
V L1-E 0.000V 0.00° +90°

V L3-E

I(1)-1
180° 0°

V L2-E

80.0 V -90° 20.0 A


V L2-E 63.510V -120.00°
V L3-E 63.510V 120.00°
I(1)-1 18.000A 0.00°
I(1)-2 0.000A -120.00°
I(1)-3 0.000A 120.00°

Binary Inputs
Name Slope Time
TRIP 0->1 3.057s
Overload 1->0 n/a

Comment
Operate Time Delay = 3 seconds
Summary
1 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed

14. Restricted Earth fault Protection (64RT)

14.1 Transformer Terminal Pickup Current Method:

Test Settings
.
General
No. of ramp states: 1

Page 117 of 146


Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

Total steps per test: 5


Total time per test: 5.000 s
No. of test executions: 1

Input Mode: Direct


Fault Type:
Ramped Quantities
I(1)-1 / Magnitude
.
Ramp States
Ramp Ramp 1
I(1)-1 85.00 mA
0.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 85.00 mA
Sig 1 To 120.0 mA
Sig 1 Delta 10.00 mA
Sig 1 d/dt 10.00 mA/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 1.000 s
Ramp Steps 5
Ramp Time 5.000s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s

. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 07-Jun-2023 15:54:41 Test End: 07-Jun-2023 15:54:45
User Name: Manager:
Company:

Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 I(1)-1 100.0 mA 105.0 mA 6.000 mA 6.000 mA 5.000 mA + 49.60 ms
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed

13.2 Trip time Test:


. .
Test Module
Name: OMICRON QuickCMC Version: 4.30
Test Start: 07-Jun-2023 15:55:56 Test End: 07-Jun-2023 15:57:16
User Name: Manager:

Page 118 of 146


Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

Company:

Test Results
Title: Test 1
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I(1)-1 1.940 A 0.00 ° 50.000 Hz

Generator Settings
I(1)-1 1.940A 0.00° +90°

I(1)-1
180° 0°

2.0 A -90°

Binary Inputs
Name Slope Time
TRIP 0->1 0.043s
Overload 1->0 n/a

Summary
1 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed

15. 95% Stator Earth Fault Protection (64G1)

15.1 Pickup Test:

Test Settings
.
General
No. of ramp states: 1
Total steps per test: 201
Total time per test: 20.100 s
No. of test executions: 1

Input Mode: Direct


Fault Type:

Ramped Quantities
V L1-E / Magnitude
.

Page 119 of 146


Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

Ramp States
Ramp Ramp 1
V L1-E 6.000 V
0.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 6.000 V
Sig 1 To 8.000 V
Sig 1 Delta 10.00 mV
Sig 1 d/dt 100.0 mV/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 201
Ramp Time 20.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s

. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 08-Jun-2023 16:09:43 Test End: 08-Jun-2023 16:09:57
User Name: Manager:
Company:

Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 V L1-E 7.210 V 7.200 V 72.10 mV 72.10 mV -10.00 mV + 56.20 ms
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed

14.2 Triptime:
. .
Test Module
Name: OMICRON QuickCMC Version: 4.30
Test Start: 08-Jun-2023 16:10:21 Test End: 08-Jun-2023 16:11:19
User Name: Manager:
Company:

Test Results
Title: Test 1
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V L1-E 10.00 V 0.00 ° 50.000 Hz

Page 120 of 146


Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

Generator Settings
V L1-E 10.000V 0.00° +90°

V L1-E
180° 0°

10.0 V -90°

Binary Inputs
Name Slope Time
TRIP 0->1 5.055s
Comment
Actual Trip time = 5 seconds
Summary
1 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed

16. Inadvertent Energization Protection

16.1 PickupTest

Pickup L1:

Test Settings
.
General
No. of ramp states: 1
Total steps per test: 31
Total time per test: 3.100 s
No. of test executions: 1

Input Mode: Direct


Fault Type:

Ramped Quantities
I(1)-1 / Magnitude
.
Ramp States
Ramp Ramp 1

Page 121 of 146


Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

V L1-E 43.00 V
0.00 °
50.000 Hz
V L2-E 43.00 V
-120.00 °
50.000 Hz
V L3-E 43.00 V
120.00 °
50.000 Hz
I(1)-1 3.500 A
0.00 °
50.000 Hz
I(1)-2 0.00 A
-120.00 °
50.000 Hz
I(1)-3 0.00 A
120.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 3.500 A
Sig 1 To 5.000 A
Sig 1 Delta 50.00 mA
Sig 1 d/dt 500.0 mA/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 31
Ramp Time 3.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s

. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 08-Jun-2023 09:29:12 Test End: 08-Jun-2023 09:29:15
User Name: Manager:
Company:

Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 I(1)-1 4.110 A 4.150 A 123.0 mA 123.0 mA 40.00 mA + 46.50 ms
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed

Pickup L2:

Test Settings
Page 122 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

.
General
No. of ramp states: 1
Total steps per test: 31
Total time per test: 3.100 s
No. of test executions: 1

Input Mode: Direct


Fault Type:

Ramped Quantities
I(1)-2 / Magnitude
.
Ramp States
Ramp Ramp 1
V L1-E 43.00 V
0.00 °
50.000 Hz
V L2-E 43.00 V
-120.00 °
50.000 Hz
V L3-E 43.00 V
120.00 °
50.000 Hz
I(1)-1 0.00 A
0.00 °
50.000 Hz
I(1)-2 3.500 A
-120.00 °
50.000 Hz
I(1)-3 0.00 A
120.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 3.500 A
Sig 1 To 5.000 A
Sig 1 Delta 50.00 mA
Sig 1 d/dt 500.0 mA/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 31
Ramp Time 3.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s

. .
Test Module
Page 123 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

Name: OMICRON Ramping Version: 4.30


Test Start: 08-Jun-2023 09:31:19 Test End: 08-Jun-2023 09:31:23
User Name: Manager:
Company:

Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 I(1)-2 4.110 A 4.150 A 123.0 mA 123.0 mA 40.00 mA + 38.70 ms
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed

Pickup L3:

Test Settings
.
General
No. of ramp states: 1
Total steps per test: 31
Total time per test: 3.100 s
No. of test executions: 1

Input Mode: Direct


Fault Type:

Ramped Quantities
I(1)-3 / Magnitude
.
Ramp States
Ramp Ramp 1
V L1-E 43.00 V
0.00 °
50.000 Hz
V L2-E 43.00 V
-120.00 °
50.000 Hz
V L3-E 43.00 V
120.00 °
50.000 Hz
I(1)-1 0.00 A
0.00 °
50.000 Hz
I(1)-2 0.00 A
-120.00 °
50.000 Hz
I(1)-3 3.500 A
120.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 3.500 A

Page 124 of 146


Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

Sig 1 To 5.000 A
Sig 1 Delta 50.00 mA
Sig 1 d/dt 500.0 mA/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 31
Ramp Time 3.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s

. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 08-Jun-2023 09:32:19 Test End: 08-Jun-2023 09:32:23
User Name: Manager:
Company:

Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 I(1)-3 4.110 A 4.150 A 123.0 mA 123.0 mA 40.00 mA + 38.40 ms
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed

Pickup L1L2L3:

Test Settings
.
General
No. of ramp states: 1
Total steps per test: 21
Total time per test: 2.100 s
No. of test executions: 1

Input Mode: Direct


Fault Type:

Ramped Quantities
I(1)-1, -2, -3 / Magnitude
.
Ramp States
Ramp Ramp 1
V L1-E 43.00 V
0.00 °
50.000 Hz
V L2-E 43.00 V

Page 125 of 146


Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

-120.00 °
50.000 Hz
V L3-E 43.00 V
120.00 °
50.000 Hz
I(1)-1 4.000 A
0.00 °
50.000 Hz
I(1)-2 4.000 A
-120.00 °
50.000 Hz
I(1)-3 4.000 A
120.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 4.000 A
Sig 1 To 5.000 A
Sig 1 Delta 50.00 mA
Sig 1 d/dt 500.0 mA/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 21
Ramp Time 2.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s

. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 08-Jun-2023 09:33:35 Test End: 08-Jun-2023 09:33:37
User Name: Manager:
Company:

Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 I(1)-1, -2, 4.110 A 4.150 A 123.0 mA 123.0 mA 40.00 mA + 45.30 ms
-3
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed

15.2 Arming Pick Up Test:


.
Test Settings
State pre fault Voltage Energisati
drop on
V L1-E 57.10 V 37.00 V 24.00 V

Page 126 of 146


Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

0.00 ° 0.00 ° 0.00 °


50.000 Hz 50.000 Hz 50.000 Hz
V L2-E 57.10 V 37.00 V 24.00 V
-120.00 ° -120.00 ° -120.00 °
50.000 Hz 50.000 Hz 50.000 Hz
V L3-E 57.10 V 37.00 V 24.00 V
120.00 ° 120.00 ° 120.00 °
50.000 Hz 50.000 Hz 50.000 Hz
I(1)-1 0.00 A 0.00 A 5.000 A
0.00 ° 0.00 ° 0.00 °
50.000 Hz 50.000 Hz 50.000 Hz
I(1)-2 0.00 A 0.00 A 5.000 A
-120.00 ° -120.00 ° -120.00 °
50.000 Hz 50.000 Hz 50.000 Hz
I(1)-3 0.00 A 0.00 A 5.000 A
120.00 ° 120.00 ° 120.00 °
50.000 Hz 50.000 Hz 50.000 Hz

Comment
1. Arming Pickup time = 5 sec
. .
Test Module
Name: OMICRON State Sequencer Version: 4.30
Test Start: 08-Jun-2023 11:06:13 Test End: 08-Jun-2023 11:06:21
User Name: Manager:
Company:

Test Results
.
Time Assessment
Name Ignore Start Stop Tnom Tdev- Tdev+ Tact Tdev Assess
before
Trip Energisatio Energisatio TRIP 0>1 60.00 ms 30.00 ms 30.00 ms 54.40 ms -5.600 ms +
n n
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed

15.3 Arming Pick Up blocking:


.
Test Settings
State pre fault Voltage Energisati Unit
drop on Standstill
V L1-E 57.10 V 37.00 V 24.00 V 0.00 V
0.00 ° 0.00 ° 0.00 ° 0.00 °
50.000 Hz 50.000 Hz 50.000 Hz 50.000 Hz
V L2-E 57.10 V 37.00 V 24.00 V 0.00 V
-120.00 ° -120.00 ° -120.00 ° -120.00 °
50.000 Hz 50.000 Hz 50.000 Hz 50.000 Hz

Page 127 of 146


Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

V L3-E 57.10 V 37.00 V 24.00 V 0.00 V


120.00 ° 120.00 ° 120.00 ° 120.00 °
50.000 Hz 50.000 Hz 50.000 Hz 50.000 Hz
I(1)-1 0.00 A 0.00 A 0.00 A 0.00 A
0.00 ° 0.00 ° 0.00 ° 0.00 °
50.000 Hz 50.000 Hz 50.000 Hz 50.000 Hz
I(1)-2 0.00 A 0.00 A 0.00 A 0.00 A
-120.00 ° -120.00 ° -120.00 ° -120.00 °
50.000 Hz 50.000 Hz 50.000 Hz 50.000 Hz
I(1)-3 0.00 A 0.00 A 0.00 A 0.00 A
120.00 ° 120.00 ° 120.00 ° 120.00 °
50.000 Hz 50.000 Hz 50.000 Hz 50.000 Hz

Comment
1. Arming Pickup time = 5 sec
2. If the CB closes after the Arming pickup time, then the function picks up.
. .
Test Module
Name: OMICRON State Sequencer Version: 4.30
Test Start: 08-Jun-2023 11:09:00 Test End: 08-Jun-2023 11:09:10
User Name: Manager:
Company:

Test Results
.
Time Assessment
Name Ignore Start Stop Tnom Tdev- Tdev+ Tact Tdev Assess
before
Trip Energisatio Energisatio TRIP 0>1 60.00 ms 30.00 ms 30.00 ms x
n n
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed (manually assessed)

15.4 Arming drop off Test:


.
Test Settings
State pre fault Voltage Voltage Energisati
pickup 1 pickup 2 on
V L1-E 0.00 V 24.50 V 50.00 V 57.10 V
0.00 ° 0.00 ° 0.00 ° 0.00 °
50.000 Hz 50.000 Hz 50.000 Hz 50.000 Hz
V L2-E 0.00 V 24.50 V 50.00 V 57.10 V
-120.00 ° -120.00 ° -120.00 ° -120.00 °
50.000 Hz 50.000 Hz 50.000 Hz 50.000 Hz
V L3-E 0.00 V 24.50 V 50.00 V 57.10 V
120.00 ° 120.00 ° 120.00 ° 120.00 °
50.000 Hz 50.000 Hz 50.000 Hz 50.000 Hz
I(1)-1 0.00 A 0.00 A 0.00 A 5.000 A

Page 128 of 146


Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

0.00 ° 0.00 ° 0.00 ° 0.00 °


50.000 Hz 50.000 Hz 50.000 Hz 50.000 Hz
I(1)-2 0.00 A 0.00 A 0.00 A 5.000 A
-120.00 ° -120.00 ° -120.00 ° -120.00 °
50.000 Hz 50.000 Hz 50.000 Hz 50.000 Hz
I(1)-3 0.00 A 0.00 A 0.00 A 5.000 A
120.00 ° 120.00 ° 120.00 ° 120.00 °
50.000 Hz 50.000 Hz 50.000 Hz 50.000 Hz

Comment
1. The Arming Dropoff time = 2 sec
2. If the CB is closed within the arming dropoff time then the function picks up following relay trip.
. .
Test Module
Name: OMICRON State Sequencer Version: 4.30
Test Start: 08-Jun-2023 11:09:53 Test End: 08-Jun-2023 11:10:00
User Name: Manager:
Company:

Test Results
.
Time Assessment
Name Ignore Start Stop Tnom Tdev- Tdev+ Tact Tdev Assess
before
Trip Energisatio Energisatio TRIP 0>1 60.00 ms 30.00 ms 30.00 ms 56.80 ms -3.200 ms +
n n
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed

15.5 Arming drop off blocking Test:


.
Test Settings
State pre fault Voltage Voltage Energisati
pickup pickup on
V L1-E 0.00 V 24.50 V 50.00 V 57.10 V
0.00 ° 0.00 ° 0.00 ° 0.00 °
50.000 Hz 50.000 Hz 50.000 Hz 50.000 Hz
V L2-E 0.00 V 24.50 V 50.00 V 57.10 V
-120.00 ° -120.00 ° -120.00 ° -120.00 °
50.000 Hz 50.000 Hz 50.000 Hz 50.000 Hz
V L3-E 0.00 V 24.50 V 50.00 V 57.10 V
120.00 ° 120.00 ° 120.00 ° 120.00 °
50.000 Hz 50.000 Hz 50.000 Hz 50.000 Hz
I(1)-1 0.00 A 0.00 A 0.00 A 5.000 A
0.00 ° 0.00 ° 0.00 ° 0.00 °
50.000 Hz 50.000 Hz 50.000 Hz 50.000 Hz
I(1)-2 0.00 A 0.00 A 0.00 A 5.000 A
-120.00 ° -120.00 ° -120.00 ° -120.00 °

Page 129 of 146


Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

50.000 Hz 50.000 Hz 50.000 Hz 50.000 Hz


I(1)-3 0.00 A 0.00 A 0.00 A 5.000 A
120.00 ° 120.00 ° 120.00 ° 120.00 °
50.000 Hz 50.000 Hz 50.000 Hz 50.000 Hz

Comment
1. Arming dropoff time = 2 sec
2. If the CB does not closes within the Arming dropoff time then the function does not pick up. Therefore, the Arming dropoff
blocks.
. .
Test Module
Name: OMICRON State Sequencer Version: 4.30
Test Start: 08-Jun-2023 11:10:28 Test End: 08-Jun-2023 11:10:38
User Name: Manager:
Company:

Test Results
.
Time Assessment
Name Ignore Start Stop Tnom Tdev- Tdev+ Tact Tdev Assess
before
Trip Energisatio Energisatio TRIP 0>1 60.00 ms 30.00 ms 30.00 ms x
n n
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed (manually assessed)
17. Generator Transformer Backup Earthfault Protection

17.1 51NGT pickup Test:

Test Settings
.
General
No. of ramp states: 1
Total steps per test: 21
Total time per test: 6.300 s
No. of test executions: 1

Input Mode: Direct


Fault Type:

Ramped Quantities
I(1)-1 / Magnitude
.
Ramp States
Ramp Ramp 1
I(1)-1 150.0 mA
0.00 °

Page 130 of 146


Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

50.000 Hz
Force abs. Phases No
Sig 1 From 150.0 mA
Sig 1 To 250.0 mA
Sig 1 Delta 5.000 mA
Sig 1 d/dt 16.67 mA/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 300.0 ms
Ramp Steps 21
Ramp Time 6.300s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s

. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 07-Jun-2023 10:58:28 Test End: 07-Jun-2023 10:58:33
User Name: Manager:
Company:

Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 I(1)-1 200.0 mA 200.0 mA 6.000 mA 6.000 mA 0.00 A + 54.70 ms
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed

16.2 Triptime Test:


. .
Test Module
Name: OMICRON QuickCMC Version: 4.30
Test Start: 07-Jun-2023 10:59:54 Test End: 07-Jun-2023 11:01:33
User Name: Manager:
Company:

Test Results
Title: Test 1
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I(1)-1 400.0 mA 0.00 ° 50.000 Hz

Generator Settings

Page 131 of 146


Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

I(1)-1 0.400A 0.00° +90°

I(1)-1
180° 0°

400.0 mA -90°

Binary Inputs
Name Slope Time
TRIP 0->1 6.053s
Overload 1->0 n/a

Summary
1 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed

18. Monitoring Voltage 3-phases

18.1 Positive Sequence Pickup:


. .
Test Module
Name: OMICRON QuickCMC Version: 4.30
Test Start: 08-Jun-2023 14:48:07 Test End: 08-Jun-2023 14:50:49
User Name: Manager:
Company:

Test Results
Title: Test 1
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Symmetrical components V1 13.00 V 0.00 ° 50.000 Hz
V2 0.00 V -120.00 ° 50.000 Hz
V0 0.00 V 120.00 ° 50.000 Hz
I1 500.0 mA 0.00 ° 50.000 Hz
I2 0.00 A -120.00 ° 50.000 Hz
I0 0.00 A 120.00 ° 50.000 Hz

Generator Settings

Page 132 of 146


Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

V L1-E 13.000V 0.00° +90°


I(1)-3
V L3-E

V L1-E
I(1)-1
180° 0°

V L2-E
I(1)-2
15.0 V -90° 500.0 mA
V L2-E 13.000V -120.00°
V L3-E 13.000V 120.00°
I(1)-1 0.500A 0.00°
I(1)-2 0.500A -120.00°
I(1)-3 0.500A 120.00°

Binary Inputs
Name Slope Time
TRIP 0
Overload 0
Comment
Positive sequence release current = 0.43 A
Positive sequence voltage start value = 11 V
Title: Test 2
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Symmetrical components V1 9.000 V 0.00 ° 50.000 Hz
V2 0.00 V -120.00 ° 50.000 Hz
V0 0.00 V 120.00 ° 50.000 Hz
I1 500.0 mA 0.00 ° 50.000 Hz
I2 0.00 A -120.00 ° 50.000 Hz
I0 0.00 A 120.00 ° 50.000 Hz

Generator Settings
V L1-E 9.000V 0.00° +90°
I(1)-3
V L3-E

V L1-E
I(1)-1
180° 0°

V L2-E
I(1)-2
10.0 V -90° 500.0 mA
V L2-E 9.000V -120.00°
V L3-E 9.000V 120.00°
I(1)-1 0.500A 0.00°
I(1)-2 0.500A -120.00°
I(1)-3 0.500A 120.00°

Binary Inputs
Name Slope Time

Page 133 of 146


Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

TRIP 0->1 0.061s


Overload 1->0 n/a
Comment
Positive sequence release current = 0.43 A
Positive sequence voltage start value = 11 V
Therefore, the relay trips.
Title: Test 3
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Symmetrical components V1 0.00 V 0.00 ° 50.000 Hz
V2 13.00 V -120.00 ° 50.000 Hz
V0 0.00 V 120.00 ° 50.000 Hz
I1 0.00 A 0.00 ° 50.000 Hz
I2 500.0 mA -120.00 ° 50.000 Hz
I0 0.00 A 120.00 ° 50.000 Hz

Generator Settings
V L1-E 13.000V -120.00° +90°
I(1)-3
V L3-E

V L2-E
I(1)-2
180° 0°

V L1-E
I(1)-1
15.0 V -90° 500.0 mA
V L2-E 13.000V 0.00°
V L3-E 13.000V -240.00°
I(1)-1 0.500A -120.00°
I(1)-2 0.500A 0.00°
I(1)-3 0.500A -240.00°

Binary Inputs
Name Slope Time
TRIP 0
Overload 0
Comment
Negative sequence release current = 0.43 A
Negative sequence voltage start value = 11 V
Relay doesnot trip.
Title: Test 4
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Symmetrical components V1 0.00 V 0.00 ° 50.000 Hz
V2 13.00 V -120.00 ° 50.000 Hz
V0 0.00 V 120.00 ° 50.000 Hz
I1 0.00 A 0.00 ° 50.000 Hz
I2 300.0 mA -120.00 ° 50.000 Hz
I0 0.00 A 120.00 ° 50.000 Hz

Page 134 of 146


Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

Generator Settings
V L1-E 13.000V -120.00° +90°

V L3-E
I(1)-3
V L2-E
I(1)-2
180° 0°

I(1)-1
V L1-E

15.0 V -90° 400.0 mA


V L2-E 13.000V 0.00°
V L3-E 13.000V -240.00°
I(1)-1 0.300A -120.00°
I(1)-2 0.300A 0.00°
I(1)-3 0.300A -240.00°

Binary Inputs
Name Slope Time
TRIP 0->1 0.057s
Overload 1->0 n/a
Comment
Negative sequence release current = 0.43 A
Negative sequence voltage start value = 11 V
Thus, the relay trips.
Summary
4 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed

17.2 Positive Sequence Pickup with Voltage function:

Test Settings
.
General
No. of ramp states: 1
Total steps per test: 71
Total time per test: 7.100 s
No. of test executions: 1

Input Mode: Symmetrical components


Fault Type:

Ramped Quantities
V 1 / Magnitude
.
Ramp States
Ramp Ramp 1
V L1-E 15.00 V
0.00 °
50.000 Hz

Page 135 of 146


Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

V L2-E 15.00 V
-120.00 °
50.000 Hz
V L3-E 15.00 V
120.00 °
50.000 Hz
I(1)-1 450.0 mA
0.00 °
50.000 Hz
I(1)-2 450.0 mA
-120.00 °
50.000 Hz
I(1)-3 450.0 mA
120.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 15.00 V
Sig 1 To 8.000 V
Sig 1 Delta -100.0 mV
Sig 1 d/dt -1.000 V/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 71
Ramp Time 7.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s

. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 08-Jun-2023 14:30:14 Test End: 08-Jun-2023 14:30:20
User Name: Manager:
Company:

Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 V1 11.00 V 11.00 V 330.0 mV 330.0 mV 0.00 V + 63.30 ms
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed

17.3 Triptime Test:


. .
Test Module
Name: OMICRON QuickCMC Version: 4.30
Test Start: 08-Jun-2023 14:54:33 Test End: 08-Jun-2023 14:55:39
User Name: Manager:
Page 136 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

Company:

Test Results
Title: Negative Sequence Condition
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Symmetrical components V1 0.00 V 0.00 ° 50.000 Hz
V2 15.00 V -120.00 ° 50.000 Hz
V0 0.00 V 120.00 ° 50.000 Hz
I1 0.00 A 0.00 ° 50.000 Hz
I2 90.00 mA -120.00 ° 50.000 Hz
I0 0.00 A 120.00 ° 50.000 Hz

Generator Settings
V L1-E 15.000V -120.00° +90°
V L3-E
I(1)-3

I(1)-2
V L2-E
180° 0°

I(1)-1
V L1-E
15.0 V -90° 100.0 mA
V L2-E 15.000V 0.00°
V L3-E 15.000V -240.00°
I(1)-1 0.090A -120.00°
I(1)-2 0.090A 0.00°
I(1)-3 0.090A -240.00°

Binary Inputs
Name Slope Time
TRIP 0->1 5.056s
Overload 1->0 n/a

Title: Positive Sequence Condition


.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Symmetrical components V1 9.000 V 0.00 ° 50.000 Hz
V2 0.00 V -120.00 ° 50.000 Hz
V0 0.00 V 120.00 ° 50.000 Hz
I1 500.0 mA 0.00 ° 50.000 Hz
I2 0.00 A -120.00 ° 50.000 Hz
I0 0.00 A 120.00 ° 50.000 Hz

Generator Settings

Page 137 of 146


Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

V L1-E 9.000V 0.00° +90°


I(1)-3
V L3-E

V L1-E
I(1)-1
180° 0°

V L2-E
I(1)-2
10.0 V -90° 500.0 mA
V L2-E 9.000V -120.00°
V L3-E 9.000V 120.00°
I(1)-1 0.500A 0.00°
I(1)-2 0.500A -120.00°
I(1)-3 0.500A 120.00°

Binary Inputs
Name Slope Time
TRIP 0->1 5.063s
Overload 1->0 n/a

Comment
Actual time delay = 5 seconds.
Summary
2 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed

19. Generator Overcurrent Protection

19.1 Stage-1 Single phase Pickup:

Test Settings
.
General
No. of ramp states: 1
Total steps per test: 51
Total time per test: 5.100 s
No. of test executions: 1

Input Mode: Direct


Fault Type:

Ramped Quantities
I(1)-1 / Magnitude
.
Ramp States
Ramp Ramp 1
I(1)-1 4.000 A
0.00 °

Page 138 of 146


Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

50.000 Hz
I(1)-2 0.00 A
-120.00 °
50.000 Hz
I(1)-3 0.00 A
120.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 4.000 A
Sig 1 To 6.000 A
Sig 1 Delta 40.00 mA
Sig 1 d/dt 400.0 mA/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 51
Ramp Time 5.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s

. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 08-Jun-2023 16:30:22 Test End: 08-Jun-2023 16:30:27
User Name: Manager:
Company:

Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 I(1)-1 5.110 A 5.120 A 153.0 mA 153.0 mA 10.00 mA + 48.70 ms
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed

Stage-1 Three phase Pickup:

Test Settings
.
General
No. of ramp states: 1
Total steps per test: 101
Total time per test: 10.100 s
No. of test executions: 1

Input Mode: Direct


Fault Type:

Page 139 of 146


Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

Ramped Quantities
I(1)-1, -2, -3 / Magnitude
.
Ramp States
Ramp Ramp 1
I(1)-1 4.000 A
0.00 °
50.000 Hz
I(1)-2 4.000 A
-120.00 °
50.000 Hz
I(1)-3 4.000 A
120.00 °
50.000 Hz
Force abs. Phases Yes
Sig 1 From 4.000 A
Sig 1 To 6.000 A
Sig 1 Delta 20.00 mA
Sig 1 d/dt 200.0 mA/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 101
Ramp Time 10.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s

. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 08-Jun-2023 16:34:36 Test End: 08-Jun-2023 16:34:44
User Name: Manager:
Company:

Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 I(1)-1, -2, 5.110 A 5.100 A 153.0 mA 153.0 mA -10.00 mA + 52.30 ms
-3
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed

18.2 Stage-1 Triptime:


. .
Test Module
Name: OMICRON QuickCMC Version: 4.30
Test Start: 08-Jun-2023 16:39:05 Test End: 08-Jun-2023 16:40:21
User Name: Manager:

Page 140 of 146


Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

Company:

Test Results
Title: SIngle phase triptime
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I(1)-1 7.000 A 0.00 ° 50.000 Hz
I(1)-2 0.00 A -120.00 ° 50.000 Hz
I(1)-3 0.00 A 120.00 ° 50.000 Hz

Generator Settings
I(1)-1 7.000A 0.00° +90°

I(1)-1
180° 0°

8.0 A -90°
I(1)-2 0.000A -120.00°
I(1)-3 0.000A 120.00°

Binary Inputs
Name Slope Time
TRIP 0->1 2.058s
Overload 1->0 n/a

.
Comment
Actual triptime = 2 seconds.

Title: Three phase triptime


.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I(1)-1 7.000 A 0.00 ° 50.000 Hz
I(1)-2 7.000 A -120.00 ° 50.000 Hz
I(1)-3 7.000 A 120.00 ° 50.000 Hz

Generator Settings
I(1)-1 7.000A 0.00° +90°

I(1)-3

I(1)-1
180° 0°

I(1)-2

8.0 A -90°
I(1)-2 7.000A -120.00°
I(1)-3 7.000A 120.00°
Page 141 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

Binary Inputs
Name Slope Time
TRIP 0->1 2.058s
Overload 1->0 n/a
Comment
Actual triptime = 2 seconds.
Summary
2 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed

18.3 Stage-2 Single phase Pickup:

Test Settings
.
General
No. of ramp states: 1
Total steps per test: 61
Total time per test: 6.100 s
No. of test executions: 1

Input Mode: Direct


Fault Type:

Ramped Quantities
I(1)-1 / Magnitude
.
Ramp States
Ramp Ramp 1
I(1)-1 20.00 A
0.00 °
50.000 Hz
I(1)-2 0.00 A
-120.00 °
50.000 Hz
I(1)-3 0.00 A
120.00 °
50.000 Hz
Force abs. Phases No
Sig 1 From 20.00 A
Sig 1 To 23.00 A
Sig 1 Delta 50.00 mA
Sig 1 d/dt 500.0 mA/s
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 61
Ramp Time 6.100s
Trigger Bin
Page 142 of 146
Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s

. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 08-Jun-2023 16:44:54 Test End: 08-Jun-2023 16:45:00
User Name: Manager:
Company:

Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 I(1)-1 22.10 A 22.05 A 663.0 mA 663.0 mA -50.00 mA + 62.30 ms
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed

Stage-2 Three phase Pickup:

Test Settings
.
General
No. of ramp states: 1
Total steps per test: 61
Total time per test: 6.100 s
No. of test executions: 1

Input Mode: Direct


Fault Type:

Ramped Quantities
I(1)-1, -2, -3 / Magnitude
.
Ramp States
Ramp Ramp 1
I(1)-1 20.00 A
0.00 °
50.000 Hz
I(1)-2 20.00 A
-120.00 °
50.000 Hz
I(1)-3 20.00 A
120.00 °
50.000 Hz
Force abs. Phases Yes
Sig 1 From 20.00 A
Sig 1 To 23.00 A
Sig 1 Delta 50.00 mA
Sig 1 d/dt 500.0 mA/s

Page 143 of 146


Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
dt per Step 100.0 ms
Ramp Steps 61
Ramp Time 6.100s
Trigger Bin
Trigger Logic OR
TRIP 1
Step back No
Delay Time 0.00 s

. .
Test Module
Name: OMICRON Ramping Version: 4.30
Test Start: 08-Jun-2023 16:50:10 Test End: 08-Jun-2023 16:50:16
User Name: Manager:
Company:

Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up Ramp 1 TRIP 0->1 I(1)-1, -2, 22.10 A 22.05 A 663.0 mA 663.0 mA -50.00 mA + 44.60 ms
-3
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed

18.4 Stage-2 Triptime:


. .
Test Module
Name: OMICRON QuickCMC Version: 4.30
Test Start: 08-Jun-2023 16:51:15 Test End: 08-Jun-2023 16:53:29
User Name: Manager:
Company:

Test Results
Title: Single phase triptime
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I(1)-1 23.00 A 0.00 ° 50.000 Hz
I(1)-2 0.00 A -120.00 ° 50.000 Hz
I(1)-3 0.00 A 120.00 ° 50.000 Hz

Generator Settings

Page 144 of 146


Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

I(1)-1 23.000A 0.00° +90°

I(1)-1
180° 0°

30.0 A -90°
I(1)-2 0.000A -120.00°
I(1)-3 0.000A 120.00°

Binary Inputs
Name Slope Time
TRIP 0->1 0.058s
Overload 1->0 n/a

.
Comment
Actual Triptime = 0 second

Title: Three phase triptime


.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I(1)-1 23.00 A 0.00 ° 50.000 Hz
I(1)-2 23.00 A -120.00 ° 50.000 Hz
I(1)-3 23.00 A 120.00 ° 50.000 Hz

Generator Settings
I(1)-1 23.000A 0.00° +90°

I(1)-3

I(1)-1
180° 0°

I(1)-2

30.0 A -90°
I(1)-2 23.000A -120.00°
I(1)-3 23.000A 120.00°

Binary Inputs
Name Slope Time
TRIP 0->1 0.061s
Overload 1->0 n/a
Comment
Actual Triptime = 0 second
Summary
2 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed

Page 145 of 146


Test Report
Project/Customer: 6*200 MW PHPA-I
Protection Panel: UNIT-3 PRT SYSTEM (Main-I)
Document No: C-012101-600-28 Rev: 00

Page 146 of 146