MINUTES OF MEETING BETWEEN M/S GALLANTT METAL LTD & M/S AKSHAR LEEPANT at Smakhyali,

on dated 13/6/2023

M/S GALLANTT METAL LTD M/S AKSHAR LEEPANT


Mr. B.THIRUMAL Mr. Dharmesh Prajapati
Mr. Sunil Raval

Testing team reached at site 12/06/2023 .The following work has been carried at 18MW Generator
Relay Panel

1.0 Metering CT & PT Secondary Injection check at load 100%, 75%, 50% and 25% has been tested

successfully.

(Check: MW, MVAR, PF, FREQUENCY, VOLTAGE, CURRENT, MVA, GOVERNER RELAY)

2.0 Relay Siemens Make 7UM62 at GRP panel following protection check successfully

1) current and voltage Measurement has been checking successfully.

2) All Input check ok

3) Diff protection, o/c protection, thermal, NPS, Reverse power, under & over voltage
under & over frequency, under excitation, Impedance all protection check.

Note: Testing team leave at side due to Siemens OEM leave for Cyclone Red Alert.

M/S GALLANTT METAL LTD M/S AKSHAR LEEPANT


Mr. B. THIRUMAL Mr. Dharmesh Prajapati