Disconnecting Means For Motor

You might also like

Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 9

Disconnecting Means for Motor and

Air-conditioning Equipment

Michael JohnstonJanuary 16, 2003Electrical InspectionsJanuary/February 2003

The purpose of electrical codes is practical safe guarding of persons and property from the hazards
associated with electricity. Numerous prescriptive requirements address safety from the minimum
standpoint. Codes and standards are the minimum rules for electrical safety, so one can easily
surmise that for electrical safety one must do at least what is required by the codes.

Many rules in the codes require installation of protective devices and equipment to be in place for the
user and occupant long after the final electrical inspection and certificate of occupancy (C of O) is
issued. One type of protective equipment for use by the occupant and by service personnel is the
disconnecting means required for electric motors and air-conditioning or refrigeration equipment.
There are also rules for service disconnects, disconnects for appliances, electric signs, and other
equipment throughout electrical codes. This article takes a close look at the minimum requirements
for locations of safety disconnects for motors and air-conditioning equipment as specified in NEC
Articles 430 and 440.

Photo 1

The primary purpose of the Code is safety. Compliance with minimum Code rules will generally
result in an electrical installation that is essentially safe and free from hazards to persons and
property. More specific to motors and air-conditioning equipment, the Code requires a necessary
safety disconnecting device for workers and building occupants to remove the electrical power
during service operations and also to be able to disconnect the equipment in emergency conditions,
such as electrical fires or explosions associated with the equipment. With electrical events or
problems, such as explosions or mechanical failures, the natural reaction is to disconnect the power
as soon as possible. The disconnecting means required for motors and equipment falling under the
scope of Articles 430 and 440 are safety disconnects. In the interest of safety for anyone who may
need to react swiftly to adverse conditions or situations, electrical design and installation should not
take the location of disconnects lightly. In the electrical field it is vital that safety be first priority,
always.

Disconnect Locations for Motor Controllers

Figure 1

Article 430 includes the minimum requirements for electrical motors. Provisions for locations of
motor disconnects are included in 430.102. There are two components of Section 430.102, the
controller in 430.102(A) and the motor in 430.102(B). Let’s look at the controller first. Section
430.102(A) requires a disconnect in sight from the controller and it must disconnect to be located in
sight from the controller and it shall disconnect the controller from the source. A closer look at the
definition of the term in sight from is in order here; by definition, it means that one component can
be seen from the other and the distance between must not exceed 15 m (50 ft). The disconnecting
means must be visible from the motor and equipment. Visible through a glass partition or window
does not meet the requirements of this section (see figure 1).

Section 430.81 indicates clearly that the controller is the device that starts and stops the motor, by
making nd breaking the motor-circuit current. An example of a controller is a combination magnetic
motor starter. Controllers require servicing from time to time and the required disconnect is a means
of safety for the worker performing those service operations. The disconnect also serves to allow
compliance with the general provisions in OSHA 1910.333, one of which requires electrical
equipment to be worked on while de-energized. Of course during some troubleshooting and testing
procedures, the equipment will be required to be worked while energized, and the qualified service
person then must wear the appropriate personal protective equipment to provide a reasonable level of
protection should an arc flash or arc blast event occur (see OSHA 1910.335 for additional
information about personal protective equipment). Some requirements for disconnecting means
locations in the OSHA Standards also are similar to what is required in NEC 430.102 and 440.14 (see
OSHA 1910.333) for information about lockout and tagging procedures for safety). This article
focuses primarily on the rules of the NEC, but compliance with installation rules found in the Code
often results in conformance to OSHA provisions also. Knowledge of all possible applicable
standards results in increased safety relative to the electrical installation and also assists with worker
safety.

The disconnect ahead of the controller allows safe replacement of overloads, fuses, worn contacts,
and so forth. Most individual combination magnetic motor starters or starters that are part of a motor
control center include both the controller and the disconnect within the same enclosure. Compliance
with 430.102(A) is inherent to these types of combination controllers that include both the disconnect
and the controller as an assembly. Disconnects and motor controllers can also be installed as
individual units and must be located with respect to the provisions of 430.102(A).

Disconnect for Motor(s) and Driven Machinery

Figure 2

Requirements for the motor and driven machinery disconnect(s) are found in 430.102(B), which
stipulates that the disconnecting means to be located within sight from the motor and driven
machinery location (see photo 1). The disconnect that is provided to meet the requirements of
430.102(A) can also serve as the disconnect for the motor if it is located within sight from and not at
a distance greater than 15 m (50 ft) from the motor and equipment. At least one of these disconnects
is required to be readily accessible in accordance with 430.107 (see figure 2).

This disconnect is a safety device and provides reasonable protection for personnel that may be
servicing the motor or the equipment driven by the motor. Service personnel are able to visually
monitor the safety disconnect when it is located in accordance within the limits of the in-sight-from
rule.

Two exceptions permit the motor disconnect required in 430.102(B) to be located out of sight from
the motor and driven machinery location. These provisions are worth a closer look as this alternative
is limited and has become even more restrictive by recent changes to NEC 2002.
The first exception allows the disconnect to be located remote (out of sight) from the motor and
equipment in installations or systems where locating the disconnect in sight from the motor is
impracticable or introduces additional increased hazards to persons or property. Although this is
generally in the judgment of the AHJ, the revision in this section gives a clearer indication of what is
intended by the rule in the first place. Some examples are also provided of situations where the
location would be impracticable. This information is helpful to designers as well as installers.

Figure 3

The second exception to this disconnect rule is intended to be applied to industrial installations under
controlled conditions: (1) that qualified persons service the installation, and (2) written safety
procedures are in place. Another fine print note provides guidance and direction to NFPA 70 E
(Standard for Electrical Safety Requirements for Employee Workplaces), which includes information
about acceptable lockout/tag out procedures. If the installation can meet the restricted conditions set
forth in this exception, the disconnects can be remotely located but must be individually capable of
being locked in the open position. The provisions for the locking means must be permanently
installed on or at the switch or circuit breaker used as the disconnecting means. Portable types of
lockout devices are no longer acceptable under this provision (see figure 3).

Air-conditioning and Refrigeration Disconnecting Means


Photo 2

Requirements for air-conditioning equipment disconnecting means are found in 440.14 and 440.13.
The requirements and reasons for the disconnects at air-conditioning and refrigeration equipment are
basically the same. The decision whether or not to use the rules in Article 440 rather than Article 430
is related to the type of motor employed within the equipment.

Basically, if the motor or equipment incorporates a hermetic refrigerant motor compressor, then the
rules in 440.14 apply. Both types of motors are used with air-conditioning and refrigeration
equipment and systems, so it is important to establish which Code article and rules apply for a given
installation (see photos 2 and 3).

Photo 3

If the air-conditioning equipment incorporates or is driven by a standard motor, meaning a motor that
is not hermetically sealed, then the rules in 430.102 have to be applied. It is helpful to visit the
definitions in 440.2 for additional clarification on hermetic refrigerant motor compressors. Section
440.3(A) clearly indicates that if the equipment does not have a hermetic refrigerant motor
compressor, then 440 does not apply and reference is made back to Articles 422, 424, or 430 as
applicable. An example of refrigeration equipment falling under the scope of Article 430 is the
typical fan coil unit installed in a walk-in refrigerator or freezer. The disconnecting means would
need to be provided for such equipment in accordance with 430.102 (see photo 4).

Photo 4

If the air-conditioning or refrigeration unit falls under the scope of Article 440, the disconnecting
means location requirements of 440.13 or 440.14 would apply.

Cord and Plugs as Disconnects

Section 440.13 includes the disconnect provision for room air-conditioners and similar utilization
equipment where cord and plug connection can serve as the required means of disconnect. Section
440.63 places a within-sight-from requirement for the disconnecting means for room air-
conditioners, and also requires it to be readily accessible from the unit. Section 440.64 also places
length limitations on cords of room air-conditioners that are related to the voltage rating of the unit
(see figure 4). For 120-volt room air-conditioners, the length of cord must not be longer than 3.0 m
(10 ft); and for 208- or 240-volt rated room air-conditioners, the length of cord is limited to not
longer than 1.8 m (6 ft).
Figure 4

Section 440.14 includes the disconnect location requirements for air-conditioning and refrigeration
equipment in types other than those that are cord- and plug-connected.

The requirements are relatively straight-forward and simple. The disconnecting means must be
located within sight from and also readily accessible from the equipment it supplies (see figure 5).
Readily accessible is defined in Article 100 as “Capable of being reached quickly for operation,
renewal, or inspections without requiring those to whom ready access is requisite to climb over or
remove obstacles or to resort to portable ladders, and so forth.”

Figure 5

It should be clarified that the wording in 440.14 requires ready access from the equipment. This is
slightly different and more restrictive than the rules in 430.102. The disconnect is permitted to be
located adjacent to the equipment. Generally, disconnect switches have a height limit of not greater
than 2.0 m (6 ft 7 in.) above the floor or working platform as indicated in 404.8(A). Exception 2 to
404.8(A) relaxes this requirement and allows greater heights to meet the provisions of 440.14 for
these types of equipment. Examples of applications using the exception to the height limitations are
heat pumps installed in hollow spaces above suspended ceilings. The disconnect is permitted to be
installed on or within the equipment; and where it is installed on the equipment, it must not obstruct
access panels that are removable for servicing (see photo 5).

Photo 5

Two alternatives are allowed by exception to this basic rule in 440.14. One exception refers to the
cord- and plug-connected equipment as specified in 440.13, and the other exception is applicable to
controlled conditions in industrial applications. In order to qualify for the alternatives in the
exception, the refrigerating or air-conditioning equipment must be essential to an industrial process
in a facility that includes conditions of maintenance, and the supervision available to ensure that only
qualified persons service the equipment. In these cases, a disconnecting means within sight from the
equipment shall not be required. Where the disconnecting means normally required by 440.14 is
located remotely from the equipment in accordance with the provisions of the exception, it must
capable of being locked in the open position (see figure 6).

Summary

Figure 6
It is best in electrical design to start with the rules and not the exceptions. It seems as though over
several code cycles, the alternatives allowed by the exception to the required disconnecting means for
motors and air-conditioning equipment have been incorporated into design. These disconnects ensure
safety for personnel and property, and should not be eliminated for reasons other than those
specifically included by the exception to the main rule. Some requirements in the OSHA Standards
also are similar to what is required in NEC 430.102 and 440.14 [see OSHA 1910.333 for additional
information]. Always consult the local AHJ if there are any doubts or if there are any local codes or
regulations that require clarification.

You might also like