NOTES:

1. LOCATION: AT PENTHOUSE LEVEL, EXTERIOR CONDITION


2. SCOPE OF WORK IS LIMITED TO DUCT SUPPORT FOR GRAVITY, WIND, AND SEISMIC
LONGITUDINAL LOADS (TRANSVERSE LOAD SHALL BE SUPPORTED AT THE OTHER LOCATIONS)
3. ALL STEEL MEMBERS & FASTENERS EXPOSED TO EXTERIOR CONDITIONS SHALL BE TREATED
FOR CORROSION RESISTANCE PER PROJECT SPECIFICATION.
4. TENSILE STRENGTH OF WELD ELECTRODE SHALL BE NOT LESS THAN 70 KSI CONFORMING TO
AWS D1.1
5. THE INTEGRITY OF THE THERMO-DUCT TO SUPPORT ITS OWN WEIGHT, WIND AND SEISMIC
LOADS IS OUTSIDE OF ISAT SOPE

N
A. MAX LONGITUDINAL SUPPORT TRIBUTARY LENGTH = 24 FT.
B. MAX LATERAL SUPPORT TRIBUTARY LENGTH = 12 FT.
C. MAX VERTICAL LOAD TRIBUTARY LENGTH = 6 FT.

O
D. PENETRATION OF SCREWS THROUGH SUPPORTING MATERIAL SHOULD BE MIN 3 EXPOSED
THREADS

TI
MIN 18 Ga THK x MIN 3"

C
MAX 54'' Ø THERMO-DUCT THERMO-DUCT PROVIDED WIDE A653 Gr.33 STL STRAP
BY OTHERS STL. EARRING STRAP @ XX FT SPACING, TYP.
MAX WEIGHT = 15.2 Plf

U
R
ST
DUCT RUN

N
O
C
R
FO
BOLTED CONNECTION AT
ISAT BRACE ASSEMBLY (E) STUCTURAL STEEL BEAM STUCTURAL STEEL BEAM
C38IJ04WS - TYP. AND ITS CONNECTION TO
NOT TO SCALE
STRUCTURE, BY OTHERS Approval From Engineer of Record
ELEVATION VIEW OKAY TO HAVE THE STEEL Required Prior To Installation
T

1 SCALE: NTS
BEAM @ DIFFERENT
ORIENTATION
O
N

PROJECT SHEET TITLE REV # DETAIL NUMBER


STIA NORTH MAIN TERMINAL 0
5113 Pacific Highway East, #3, Fife, WA 98424
253-926-2250 253-926-2463 (fax)
www.isatsb.com
CONTRACTOR
REDEVELOPMENT
PRE-LIM LONGITUDINAL SUPPORT
SIESMIC AND WIND ANCHORAGE DESIGN
DATE
1/15/2024 SK1
HERMANSON COMPANY DRAWN BY TASK NUMBER
CB 238780