ARTICLE 2 ASME BPVC.

V-2023

ð23Þ Table T-276


IQI Selection
IQI
Source Side Film Side
Nominal Single-Wall Material Thickness Hole-Type Essential Wire-Type Hole-Type Essential Wire-Type
Range, in. (mm) Designation Hole Essential Wire Designation Hole Essential Wire
≤0.25 (≤6.4) 12 2T 5 10 2T 4
>0.25 through 0.375 (>6.4 through 9.5) 15 2T 6 12 2T 5
>0.375 through 0.50 (>9.5 through 12.7) 17 2T 7 15 2T 6
>0.50 through 0.75 (>12.7 through 19.0) 20 2T 8 17 2T 7
>0.75 through 1.00 (>19.0 through 25.4) 25 2T 9 20 2T 8
>1.00 through 1.50 (>25.4 through 38.1) 30 2T 10 25 2T 9
>1.50 through 2.00 (>38.1 through 50.8) 35 2T 11 30 2T 10
>2.00 through 2.50 (>50.8 through 63.5) 40 2T 12 35 2T 11
>2.50 through 4.00 (>63.5 through 101.6) 50 2T 13 40 2T 12
>4.00 through 6.00 (>101.6 through 152.4) 60 2T 14 50 2T 13
>6.00 through 8.00 (>152.4 through 203.2) 80 2T 16 60 2T 14
>8.00 through 10.00 (>203.2 through 254.0) 100 2T 17 80 2T 16
>10.00 through 12.00 (>254.0 through 304.8) 120 2T 18 100 2T 17
>12.00 through 16.00 (>304.8 through 406.4) 160 2T 20 120 2T 18
>16.00 through 20.00 (>406.4 through 508.0) 200 2T 21 160 2T 20

GENERAL NOTE: It is recognized that the required hole-type designation or wire-type essential wire in this table may not achieve an IQI
sensitivity level of 2–2T . This is intentional.

(c) IQI Placement for Welds — Hole IQIs. The IQI(s) may Errata:
(b) Special Cases4
be placed adjacent to or on the weld. The identification Change from "T-292"
(1) For cylindrical to
components where the source is
number(s) and, when used, the lead letter “F,” shall not "T-282"
placed on the axis of the component for a single exposure,
be in the area of interest, except when geometric config- at least three IQIs, spaced approximately 120 deg apart,
uration makes it impractical. are required under the following conditions:
(d) IQI Placement for Welds — Wire IQIs. The IQI(s) (-a) When the complete circumference is radio-
shall be placed on the weld so that the lengths of the wires graphed using one or more film holders, or;
are transverse to the longitudinal axis of the weld. It is not
(-b) When a section or sections of the circumfer-
required for the essential wire to span the full width of
ence, where the length between the ends of the outermost
the weld. However, the essential wire shall span at least
sections span 240 or more deg, is radiographed using one
that portion of the weld representing the nominal single-
or more film holders. Additional film locations may be re-
wall material thickness and reinforcement for which the
quired to obtain necessary IQI spacing.
IQI essential wire was selected. The density requirements
of T-292 and the sensitivity requirements of T-283 shall (2) For cylindrical components where the source is
also be met.. The IQI identification and, when used, the placed on the axis of the component for a single exposure,
lead letter “F,” shall not be in the area of interest, except at least three IQIs, with one placed at each end of the span
when geometric configuration makes it impractical. of the circumference radiographed and one in the approx-
(e) IQI Placement for Materials Other Than Welds. The imate center of the span, are required under the following
IQI(s) with the IQI identification and, when used, the lead conditions:
letter “F,” may be placed in the area of interest. (-a) When a section of the circumference, the
length of which is greater than 120 deg and less than
T-277.2 Number of IQIs. When one or more film
240 deg, is radiographed using just one film holder, or;
holders are used for an exposure, at least one IQI image
(-b) When a section or sections of the circumfer-
shall appear on each radiograph except as outlined in
ence, where the length between the ends of the outermost
(b) below.
sections span less than 240 deg, is radiographed using
(a) Multiple IQIs. If the requirements of T-282 are met
more than one film holder.
by using more than one IQI, one shall be representative
of the lightest area of interest and the other the darkest (3) In (1) and (2) above, where sections of longitudi-
area of interest; the intervening densities on the radio- nal welds adjoining the circumferential weld are radio-
graph shall be considered as having acceptable density. graphed simultaneously with the circumferential weld,
an additional IQI shall be placed on each longitudinal
weld at the end of the section most remote from the junc-
tion with the circumferential weld being radiographed.

40