0A7450 Rev E 20 Light Annunciator
0A7450 Rev E 20 Light Annunciator
Remote Annunciator
Owner’s Manual
DETAILED SPECIFICATIONS 2. The RS485 cable should not be run in the same
conduit, or in the same grouping as any high volt-
ENVIRONMENTAL SPECS age or other “noisy” electrical conductors.
Temperature -20°C to +50°C 3. Avoid running the RS485 cable through any “high
noise” environments.
Humidity 0 to 95% Non Condensing
INTERFACE WITH OTHER EQUIPMENT
POWER SUPPLY REQUIREMENTS Alarm Relay Output 1 pair N/O Volt-free contacts-
Power Supply Source Generator Battery to comply 100mA, 24V DC
with NFPA
Nominal Supply +12 to +24VDC AGENCY COMPLIANCE
Transient protection Spikes clamped to 40V NFPA-110 Yes
Power Usage 150mA maximum. NFPA-99 Yes
Battery Supply cable 2 wire - DC resistance less
than 7 Ohms per conductor. TRANSPORTATION AND STORAGE
Fuse on front panel 1 Amp Temperature -20°C to +80°C
Humidity 0-95% Non Condensing
COMMUNICATION WITH D/E PANEL PACKAGING AND MOUNTING
Communication link 2 wire RS485 fully isolated. Enclosure type Sheet metal box.
Communication cable 2 wire—twisted pair with Base panel Part #A6985/A7437
overall screen.
Front panel Part #A6988/A7443
Cable size 24 AWG 0-250 feet. 18 AWG
0-1,200 feet. Panel overlay Part #A6733
Baud rate 2400/4800/9600 bd Field replacement Physically replaceable with
Auto detect. Model #9556 electrically not
compatible.
NOTE:
Mounting Flush or Wall.
1. Ensure the generator control panel is set to the
proper protocol. Weight requirements None
Manuals Yes - Operator guide
2
20 Light Remote Annunciator
3
20 Light Remote Annunciator
5
20 Light Remote Annunciator
6
20 Light Remote Annunciator
E Panel Interconneciton Diagram
TRANSFER SWITCH
(OPTIONAL)
AUXILIARY
CONTACTS
TO CONTACT COMMONS
GROUND CONNECT
J1 INSIDE
REMOTE ANNUNCIATOR
CONNECT THE
SCREEN ON
THIS END ONLY.
INSIDE
TYPICAL
E-PANEL
7
8
E/PANEL TERMINAL BLOCK
(5 POSITIONS) D & E REMOTE ANNUNCIATOR BOARD
C2688
485+
S C
RM
485-
L
LA
RM
N
N
R
LA
LA
SP Y) REE
O
SCREEN
D O CT
4V
HO
LA
(C
/P
N-
P
NA ARE
A
EN NNE
2/2
M
RN
0V
R
+12/24V
J1 J
1 2
D/PANEL TERMINAL BLOCK
(20 POSITIONS)
20 Light Remote Annunciator
0 BATT -
0 BATT -
0
0 BATT - RS485+ 520
RESET
0 BATT -
CONNECT TO RS485- 328
0 BATT - TERMINAL BLOCK
SCREEN
13A BATT +
INSIDE THE 327
Electrical Schematic – Drawing No. 0A7169-B
12/24 V
"D" OR "E"
RA-1 RS485 +
325
PANEL
OV 326
RA-2 RS485 -
RA-3 RS485
SHIELD
CONNECT THE SCREEN ON THIS END
RA-4 LINE PWR (INSIDE GENERATOR CONTROL PANEL)
FUSE I/P
1 RESET RE-ARM HORN TEST
RA-5 GEN PWR HORN
RA-6 C/A NO 1 1 1
RA-7 C/A NC 329 2 521 2 2 TEST
2 N/O
FUSE O/P N/O
RA-8 C/A COM 0 0
3 3 3 0V OP
RA-9 A/A NO
EXTERNAL ALARM
RA-10 A/A NC FUSE 1.0A
RA-11 A/A COM
EXT.
RA-12 A/C CHRG
ALARM
FAIL
POWER
RA-13 SPARE I/P
SUPPLY
C8474
2, 004280-0, 004280-1, 004280-2, 004281-0, 004281-1, 004281-2
For Models: 000984-0, 000984-1, 000984-2 000985-0, 000985-1, 000985-
20 Light Remote Annunciator
Electrical Schematic – Drawing No. 0C5770-B
For Models: 004391-0, 004391-1, 004392-0, 004392-1
9
20 Light Remote Annunciator
10
20 Light Remote Annunciator
NOTE:
Model 004280-0 DOES NOT work in a “D” panel application.
Model 004280-1 & 004280-2 DOES work in a “D” panel application.
ITEM PART NO. QTY. DESCRIPTION ITEM PART NO. QTY. DESCRIPTION
12
20 Light Remote Annunciator
NOTE:
Model 004281-0 DOES NOT work in a “D” panel application.
Model 004281-1 & 004281-2 DOES work in a “D” panel application.
ITEM PART NO. QTY. DESCRIPTION ITEM PART NO. QTY. DESCRIPTION
13
20 Light Remote Annunciator
NOTE:
This is the Time Multiplexed version to be used with the “E” Panel only.
ITEM PART NO. QTY. DESCRIPTION ITEM PART NO. QTY. DESCRIPTION
NOTE:
This is the Time Multiplexed version to be used with the “E” Panel only.
ITEM PART NO. QTY. DESCRIPTION ITEM PART NO. QTY. DESCRIPTION
15
20 Light Remote Annunciator
TROUBLESHOOTING GUIDE
No LEDs are lit. 1. Check for proper battery supply at J1 pins 3 and 4.
• J1 pin 3 should be + Battery (12 or 24 volts).
• J1 pin 4 should be – Battery.
• Refer to the “power supply requirements” section at the
beginning of the manual for cable specifications.
2. Check the 1 Amp panel fuse, replace if necessary.
The “Communication OK” 1. Does the RS485 communications cable meet specifications.
LED is flashing at the rate: Refer to the “Communication with D/E panel” section at the
one sec on/one sec off beginning of the manual.
2. Check that the RS485 connections are connected properly.
• RS485+ connected to J1 pin 1.
• RS485– connected to J1 pin 2.
• Shield is connected correctly. Refer to the wiring schematic-
for your particular model located in this manual. Note the
screen should be connected on one end only.
3. Check that the generator control panel protocol is set correctly.
Refer to the generator’s control panel manual for instructions.
4. “E” Panel application: Check the communications switch on the
back of the “E” panel master control box. This switch needs
to be set for RS485 communications. The “E” Panel must be
“power cycled” after the switch is set. This can be done by
removing/replacing the front panel fuse.
5. Check for proper installation of the RS485 cable between the
annunciator and the generator’s control panel. Is this cable
sharing a conduit or running next to any high voltage or other
“noisy” electrical lines?
The “Communication OK” 1. Does the RS485 communications cable meet specifications?
LED is flashing at the rate: Refer to the “Communication with D/E Panel” section at the
0.5 sec on/two sec off beginning of the manual.
2. Is the cable shield connected correctly? Refer to the wiring sche-
matic for your particular model located in this manual. Note
that the screen should be connected on one end only.
3. Check for proper installation of the RS485 cable between the
annunciator and the generator’s control panel. Is this cable
sharing a conduit or running next to any high voltage or other
“noisy” electrical lines?