Professional Documents
Culture Documents
Calculul Puterii Cerute PUTEREA ABSORBITA
Calculul Puterii Cerute PUTEREA ABSORBITA
Calculul Puterii Cerute PUTEREA ABSORBITA
𝑃_𝑎=𝑃_𝑖∙𝑘_𝑢∙𝑘_𝑠
Unde:
𝑃_𝑖=𝑝𝑢𝑡𝑒𝑟𝑒𝑎 𝑖𝑛𝑠𝑡𝑎𝑙𝑎𝑡𝑎
𝑘_𝑢=𝑐𝑜𝑒𝑓𝑖𝑐𝑖𝑒𝑛𝑡 𝑑𝑒 𝑢𝑡𝑖𝑙𝑖𝑧𝑎𝑟𝑒, 𝐼7−2011 𝑐𝑎𝑝 3.2.2
𝑘_𝑠=𝑐𝑜𝑒𝑓𝑖𝑐𝑖𝑒𝑛𝑡 𝑑𝑒 𝑠𝑖𝑚𝑢𝑙𝑡𝑎𝑛𝑒𝑖𝑡𝑎𝑡𝑒, 𝐼&−2011, 𝑐𝑎𝑝 3.2.2
PARTER
C1 Iluminat 50 10 0.95 1
C2 Iluminat 50 10 0.95 1
C3 Prize-6P 2000 1 0.80 1
C4 Prize-6P 2000 1 0.80 1
C5 Rezerva 2000 1 0.80 1
TOTAL
ETAJ
C1 Iluminat 50 10 0.95 1
C2 Iluminat 50 10 0.95 1
C3 Iluminat 50 10 0.95 1
C4 Iluminat 50 10 0.95 1
C5 Prize-6P 2000 1 0.80 1
C6 Rezerva 2000 1 0.80 1
TOTAL
TOTAL GENERAL
Puterea activa instalata Coeficient Coeficient de Puterea absorbita
pe circuit incarcare circuit simultaneitate ceruta pe circuit
[kW] Ci ks [kW]
0.50 1 1 0.50
0.50 1 1 0.50
2.00 0.4 1 0.80
2.00 0.4 1 0.80
2.00 0.4 1 0.80
7.00 3.40
0.50 1 1 0.50
0.50 1 1 0.50
0.50 1 1 0.50
0.50 1 1 0.50
2.00 0.4 1 0.80
2.00 0.4 1 0.80
6.00 3.60
13.00 7.00
ILUMINAT SI PRIZE MONOFAZIC APARTAMENTE
Puterea Puterea
Coeficient
Putere activa Coeficient de absorbita
incarcare
Circuit Date de intrare unitara Nr. Buc Cos ϕ η instalata simultaneitate ceruta pe
circuit
[W] pe circuit ks circuit
Ci
[kW] [kW]
PARTER
C1 Iluminat 50 10 0.95 1 0.50 1 1 0.50
C2 Iluminat 50 10 0.95 1 0.50 1 1 0.50
C3 Prize-6P 2000 1 0.80 1 2.00 0.45 1 0.90
C4 Prize-6P 2000 1 0.80 1 2.00 0.45 1 0.90
C5 Rezerva 2000 1 0.80 1 2.00 0.45 1 0.90
C6 Rezerva 2000 1 0.80 1 2.00 0.45 1 0.90
TOTAL 9.00 4.60
ETAJ
C1 Iluminat 50 10 0.95 1 0.50 1 1 0.50
C2 Iluminat 50 10 0.95 1 0.50 1 1 0.50
C3 Iluminat 50 10 0.95 1 0.50 1 1 0.50
C4 Iluminat 50 10 0.95 1 0.50 1 1 0.50
C5 Iluminat 50 10 0.95 1 0.50 1 1 0.50
C6 Prize-6P 2000 1 0.80 1 2.00 0.45 1 0.90
C7 Rezerva 2000 1 0.80 1 2.00 0.45 1 0.90
TOTAL 6.50 4.30
TOTAL GENERAL 15.50 8.90
ILUMINAT SI PRIZE MONOFAZIC APARTAMENT 3 CAMERE
Puterea
Coeficient
Putere activa Coeficient de
incarcare
CircuitDate de intrareunitara Nr. Buc Cos ϕ η instalata simultaneitate
circuit
[W] pe circuit ks
Ci
[kW]
PARTER
C1 Iluminat 150 14 0.95 1 2.10 1 1
C2 Iluminat 150 12 0.95 1 1.80 1 1
C3 Prize-6P 3000 1 0.80 1 3.00 0.45 1
C4 Prize-6P 3000 1 0.80 1 3.00 0.45 1
TOTAL 9.90
𝐼_𝑐= 5700/(230∙0,875)=28,32 𝐴
Puterea
absorbita
Tensiunea Curentul
ceruta pe
[V] [I]
circuit
[kW]
𝐼_𝑐= 5700/(230∙0,875)=28,32 𝐴
Tensiunea Curentul
[V] [I]
230 6.86
230 0.00
230 12.23
230 12.23
31.32
230 6.86
230 2.29
230 3.26
230 3.26
230 3.26
230 3.26
22.20
53.52