Conext™ RL Ethernet card

www.schneider-electric.com
B Material List E Installation of Conext RL Ethernet card
Quickstart Guide Item Quantity Description
1. De-energize the inverter. If possible follow the lock-out tag-out procedure.
2. Wait at least five minutes for internal voltages to discharge before doing any of the
Conext RL Ethernet card 1 Ethernet card for local monitoring
following steps.
Note: The module contains static-sensitive circuits, follow suitable handling precautions.
Quick start guide 1 Instructions for installing the Conext RL Ethernet card
3. Remove the existing communication module from the Conext RL expansion socket. (For
Two M3.5 Philips pan-head captive screws detailed instructions, refer to the "Removing the Communication Module" section in the
Set of screws 1
(attached to card) Conext RL Installation and Operation Manual).
4. If an RS485 connection already exists, unplug and disconnect the RS485 connection from
Cable gland 1 MG25A M26x1.5 (attached to card) the existing Conext RL Communication module card.

C Important Physical Features

Device for Photovoltaic Inverter Monitoring and Control


1. Conext RL Ethernet card
3
2. Conext RL communication
A Introduction expansion slot
1 3. DC switch
Conext RL Ethernet card is an add-on accessory for the Conext RL series of PV 2
5 1 10/100 Mbps Ethernet port
inverters. This card extends the monitoring capability of Conext RL Inverters by
2 RS485 port (dual port) 5. Depending on the local network, follow step 6 (Direct connection to computer) or step 7
providing the user with a rich graphical webpage interface. The card has both
3 Screw terminal (Connection through a network switch or router)
10/100 Mbps Ethernet connection and standard RS485-Modbus interface.
4 Cable gland
4 3 1 2 5 Termination resistor 6. Direct connection to computer
DANGER 1. Connect one end of a CAT5 Ethernet cable to the 10/100 Mbps Ethernet port on
the Conext RL Ethernet card (Refer to the figure under Section C for the location
HAZARD OF ELECTRIC SHOCK AND FIRE of Ethernet port).
2. Connect the other end of the Ethernet cable to the laptop or PC.
• All the wiring must be done by qualified personnel to ensure compliance with all
applicable installation codes and regulations. Note: • An old PC or laptop may require an Ethernet cross over cable.
• For use only with Conext RL series PV Inverters.
• The default IP address is: 169.254.1.100.
• Suitable only for connection to Class 2, energy limited, separated extra-low voltage
• Do not connect the Ethernet cable to the Modbus RS485 port, to avoid
circuits (SELV). potential damage to the Ethernet card.
• Follow the installation and safety instructions in the Conext RL Installation and D Pre-requisites
Operation Manual.
• Do not disassemble.
Web browsers:
• Disconnect all the sources of energy before adding or removing the communication
module or the Ethernet card. • Windows Internet Explorer 9.x or later
• Firefox 22.x or later
Failure to follow these instructions will result in death or serious injury.
• Google Chrome 22 or later (recommended)
Exclusion for Documentation
UNLESS SPECIFICALLY AGREED TO IN WRITING, SELLER
• Safari 5.1.7 or later
(A) MAKES NO WARRANTY AS TO THE ACCURACY, SUFFICIENCY OR SUITABILITY OF ANY TECHNICAL OR OTHER INFORMATION PROVIDED IN ITS MANUALS OR OTHER
DOCUMENTATION;
(B) ASSUMES NO RESPONSIBILITY OR LIABILITY FOR LOSSES, DAMAGES, COSTS OR EXPENSES, WHETHER SPECIAL, DIRECT, INDIRECT, CONSEQUENTIAL OR INCIDENTAL, WHICH
MIGHT ARISE OUT OF THE USE OF SUCH INFORMATION. THE USE OF ANY SUCH INFORMATION WILL BE ENTIRELY AT THE USER’S RISK; AND
(C) REMINDS YOU THAT IF THIS MANUAL IS IN ANY LANGUAGE OTHER THAN ENGLISH, ALTHOUGH STEPS HAVE BEEN TAKEN TO MAINTAIN THE ACCURACY OF THE TRANSLATION,
THE ACCURACY CANNOT BE GUARANTEED. APPROVED CONTENT IS CONTAINED WITH THE ENGLISH LANGUAGE VERSION WHICH IS POSTED AT WWW.SCHNEIDER-ELECTRIC.COM.

Contact Information
www.schneider-electric.com
Please contact your local Schneider Electric Sales Representative or visit the Schneider Electric website at:
http://www.schneider-electric.com/sites/corporate/en/support/operations/local-operations/local-operations.page
975-0694-01-01 Rev A
08-2013 1
Conext RL Ethernet card
www.schneider-electric.com PVSCMC1105
E Installation of Conext RL Ethernet card (continued) F Accessing the webpage F
G Accessing the inverter
Monitoring the webpage (continued)
OR 1. Select the preferred language. The Settings screen is displayed as shown below.
2. Login with the username and password.
7. Connection through a network switch or router. 4.Select the Ethernet tab.
• The default username is Owner.
1. Connect one end of the CAT 5 Ethernet Cable to the RJ45 Ethernet port on
• The default password is ConextRL.
the Conext RL Ethernet card.
2. Connect the other end of the CAT5 Ethernet cable to the network router
Ethernet port.
Note: Do not connect the CAT5 Ethernet cable to the MODEM/ WAN port on
the router.

G Specifications
Communication interfaces

Ethernet • Connector: 1 x RJ45, 10/100 Mbps (auto-negotiation)


8. If required, reconnect the RS485 Modbus cables to RS485 Modbus ports. Refer • DHCP / SNTP / DNS / NBNS / HTTP
to the figure under section C for RS485 port locations. (For detailed instructions
On successful login, the Conext RL dashboard is displayed as shown below: • Connector: 2 x RJ45
on connecting cables, refer to the "Connecting Cables to the Communication
RS485 • Modbus slave: 2 Wire Serial
Module" section in the Conext RL Installation and Operation Manual).
• Speed: 9600 bps
Note: Do not connect the Modbus cable to the Ethernet port.
9. Insert the Conext RL Ethernet card into the Conext RL Communication module General specifications
expansion slot and secure the card by tightening the two captive screws on
both sides. Weight 115 g (0.25 lbs)
10. Energize the inverter by connecting all the AC and DC sources that power the
system and wait for the inverter to power-up. Dimensions (H x W x D) 64 mm x 80 mm x 122 mm (2.52 in x 3.15 mm x 4.8 in)
11. Wait for around 60 seconds and navigate to the IP address option on the LCD
display. (Refer to the "Communication Settings" option in the Conext RL Power consumption 1.5 Watt maximum
Installation and Operation Manual for viewing the Ethernet IP address).
12. Open a web browser on your laptop or tablet and type the IP address displayed Interface Golden finger 24 pins
on the LCD display. The Conext RL login webpage will be loaded and displayed
by the web browser. Operating temperature -20° C to 85° C (-4° F to 185 ° F)

Storage temperature -20 ° C to 85° C (-4° F to 185 ° F)

Operating humidity 0 - 90 % Non-condensing


3.To view and edit the network settings, click on the Settings tab. Features

User Interface Integrated Web Server (Internet Browser)

Warranty Two years


Copyright © 2013 Schneider Electric. All Rights Reserved.