Professional Documents
Culture Documents
Final Eces 2023
Final Eces 2023
(EET 4071)
7th Semester, Section: A
Electrical & Electronics Engineering
D R . D EBADATTA A. G ADANAYAK
Assistant Professor
Department of Electrical & Electronics Engineering
0 Detailed Syllabus 1
i
2.2 Basic source/load relationships . . . . . . . . . . . . . . . . . . . . . . . . 27
2.2.1 Thevenin equivalent circuit model of a power system . . . . . . . 27
2.2.2 Fault level and circuit-breaker ratings . . . . . . . . . . . . . . . . 27
2.2.3 Loads and phasor diagrams . . . . . . . . . . . . . . . . . . . . . . 28
2.2.4 The symmetrical system . . . . . . . . . . . . . . . . . . . . . . . . 29
2.3 Complex power, apparent power, real and reactive power . . . . . . . . 30
2.4 Leading and lagging loads . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
2.5 Power factor correction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
2.6 Compensation and voltage control . . . . . . . . . . . . . . . . . . . . . . 34
2.6.1 System load line . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
2.7 Control of power and frequency . . . . . . . . . . . . . . . . . . . . . . . 37
2.8 Relationships between power, reactive power, voltage levels and load
angle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
2.9 Three phase systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
2.9.1 Advantages of three phase systems . . . . . . . . . . . . . . . . . 39
2.9.2 Development of three phase systems . . . . . . . . . . . . . . . . . 40
2.9.3 The wye-delta transformation . . . . . . . . . . . . . . . . . . . . . 41
2.10 Power flow and measurement . . . . . . . . . . . . . . . . . . . . . . . . . 43
2.10.1 Single phase . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
2.10.2 Three phase . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
2.10.3 Two phase . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
2.11 Three phase power measurement . . . . . . . . . . . . . . . . . . . . . . . 45
2.11.1 Three watt-meter method . . . . . . . . . . . . . . . . . . . . . . . 45
2.11.2 Two watt-meter method . . . . . . . . . . . . . . . . . . . . . . . . 46
2.12 Transformers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
2.12.1 Uses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
2.12.2 Parallel operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
2.12.3 Zero sequence effects in three phase transformer . . . . . . . . . . 49
2.13 Harmonics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
2.13.1 Harmonics fundamentals . . . . . . . . . . . . . . . . . . . . . . . 50
2.13.2 Main sources of harmonics in power system . . . . . . . . . . . . 52
2.13.3 Main undesirable effects of harmonics in power system . . . . . . 52
ii
2.13.4 Harmonic power . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
2.13.5 RMS values in presence of harmonics . . . . . . . . . . . . . . . . 54
2.13.6 Phase sequence of harmonics in balanced three-phase systems . . 54
2.14 Review of per-unit system . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
2.14.1 Advantages of per unit system . . . . . . . . . . . . . . . . . . . . 56
iii
Chapter 0
Detailed Syllabus
1. Introduction.
(a) Generation.
(b) Transmission.
(c) Distribution.
(d) Utilization.
1
Chapter 0. Detailed Syllabus Dr. D. A. Gadanayak
8. Relationship between power, reactive power, voltage level and load angle.
11. Transformer.
(b) Function.
12. Harmonics.
(d) Basic operating control schemes for GCSC, TSSC, and TCSC.
1. Introduction.
(a) Diode.
(b) Thyristor.
3. Power modules.
4. Passive components.
5. Ancillary equipment.
6. Cooling systems.
7. Component layout.
Laboratory Work
1.1 Introduction
• constant frequency.
• balanced phases.
• lack of interruptions.
8
Chapter 1. Electrical Power Systems - An Overview Dr. D. A. Gadanayak
1. Generation
2. Transmission
3. Distribution
4. Utilization
7th Semester (EEE), Section: A 9
Chapter 1. Electrical Power Systems - An Overview Dr. D. A. Gadanayak
1.2.1 Generation
• Three-phase and single-phase static generators are used in fuel cells and
photovoltaic arrays.
3-phase supply
output DC input
Armature Winding
Rotor
Rotor with
Field Winding
Rotor slots
with
excitation
winding
Round rotor machine Salient pole machine
Synchronous machines can be divided into two categories, according to their rotor
structure.
1. Salient pole machines: A salient pole rotor consists of poles projecting out from
the surface of the rotor core. Salient pole alternators have large number of poles
and operate at lower speeds. It has comparatively a larger diameter and a short
axial length. They are used in hydrogenerators.
2. Round rotor machines: Round rotor or cylindrical rotor has smooth cylindrical
construction without projected poles. In about two-third of the rotor periphery,
slots are cut at regular intervals to house distributed field windings. The
unslotted portion forms the pole faces. They are operated in high speed
generators driven by steam or gas turbines because of their better mechanical
strength and balanced dynamics. Therefore they are also called turboalternators
or turbogenerators.
The turbine-generator set has three main control systems to generate desired power
at desired voltage. They are:
Excitation
σ Firing σ Governor σ System
Control
1.2.2 Transmission
• Transmission networks operate at high voltage levels such as 400 kV and 275
kV, because the transmission of large blocks of energy is more efficient at high
voltages.
carried out with mechanically controlled shunt and series banks of capacitors
and non-linear reactors. However, when there is an economic and technical
justification, the reactive power support is provided by electronic means as
opposed to mechanical means, enabling near instantaneous control of reactive
power, voltage magnitude and transmission line impedance at the point of
compensation. FACTS devices such as TCR, TSC, STATCOM, GCSC, TCSC are
used for this purpose.
1.2.3 Distribution
• Custom power is the low voltage counterpart of the more widely known FACTS
technology. FACTS controllers are aimed at the transmission level whereas
Custom Power controllers are aimed at the distribution level. The STATCOM
and the DVR are the best known Custom Power equipments. The STATCOM is
a shunt connected device which may include the functions of voltage control,
active filtering and reactive power control. The DVR is a series connected device
which precisely compensates for waveform distortion and disturbances in the
neighbourhood of one or more sensitive loads.
1.2.4 Utilization
3. Types of load:
(a) Some loads draw constant current from the power system and their
operation may be affected by supply voltage and frequency variations.
• induction motors
• synchronous motors
• DC motors
(b) Some loads are less susceptible to voltage and frequency variations and
exhibit a constant resistance characteristic:
• incandescent lighting
• heating instruments
(c) Some loads are based on power electronics technology and are capable of
injecting significant harmonic currents back into the network.
• colour TV sets
• microwave ovens
• computer equipment
4. Electric energy storage is an area of great research activity. However, even now,
for the purpose of practical industrial applications, apart from pumped hydro
storage, there is very little energy storage in the system. Thus, at any time the
following basic relation must be met:
So as power engineers have no direct control over the electricity demand only
load shedding is the only way to deal with the generation and demand
imbalances.
(a) connection and disconnection of both large and small loads in any part of
the network.
(c) phase conductors coming into direct contact with each other.
3. For dynamic analysis purposes the power network has traditionally been
subdivided as follows:
(e) loads.
4. The model used for power system dynamic study must consider the time scales
for which the study is intended and the time constants of the plant components.
For example:
(b) The long term dynamics associated with load frequency control and load
shedding involve the dynamic response of the boiler and turbine-governor
set and do not require a detailed representation of the transmission system.
1. Transient stability studies are the most popular dynamic studies. Their main
objective is to determine the synchronous generator’s ability to remain stable
after the occurrence of a fault or following a major change in the network such
as the loss of an important generator or a large load.
3. Transient stability studies are time-based studies and involve solving the
differential equations of the generators and their controls, together with the
algebraic equations representing the transmission power network.
Pe
Pmax
E
A D F
Pm
B C
0 0 C max
2
F IGUREequal
Fig. 2.4: Swing curve to demonstrate 1.5:area
Swing curve
criterion
imbalance in input and output power will lead to rotor gaining kinetic energy and the
From (2.48)
rotor starts and (2.49) it
accelerating. can be understood
Hence, that thepoint
the operating energystarts
gained moving
during acceleration
from point B on
(Area ABCD) should be exactly equal to the energy lost during deceleration (Area
the P − δ curve along the δ − axis towards infinity. If the fault is cleared say at point
DEF) for the system to be stable. Hence, we can write
C, which corresponds to an angle δc , then since electrical power output is not zero but
it is Pmax sinof(δPc ) thecurve
Area operating point moves
during acceleration toduring
= Area pointdeceleration
E on the swing curve.
(2.50) It can be
observed that at point E the electrical power output is greater than the mechanical
Because of (2.50) we call this method of assessing the stability as equal area criterion.
power input and hence the rotor starts decelerating. Since, rotor has finite inertia it
Now the basic idea is that we have to clear the fault below a critical clearing angle c
cannot change its speed suddenly and hence the rotor acceleration will decrease slows
2.18
due to which angle will swing from point E to point F. The rotor angle will increase
until the rotor kinetic energy gained during the fault period is exhausted. Once, the
rotor exhausts the kinetic energy gained during fault period it will swing back from
point F and will move towards the point A. It can be understood that the energy
gained during acceleration (Area ABCD) should be exactly equal to the energy lost
during deceleration (Area DEF) for the system to be stable. Hence, we can write the
stability criteria:
Area of P − δ curve during acceleration = Area during deceleration.
We call this method of assessing the stability as equal area criterion. So the basic task
is to clear the fault below a critical clearing angle δc .
1. The analysis tool used to assess the steady state operation of the power system is
known as Load Flow or Power Flow studie. It has the following objectives:
(a) to determine the nodal voltage magnitudes and angles throughout the
network.
(b) to determine the active and reactive power flows in all branches of the
network.
(c) to determine the active and reactive power contributed by each generator.
(d) to determine active and reactive power losses in each component of the
network.
2. In steady state operation, the plant components of the network are described by
their impedances and loads are normally recorded in MW and MVAr. Ohm’s
law and Kirchhoff’s laws are used to model the power network as a single entity
where the nodal voltage magnitude and angle are the state variables.
3. The power flow is a non-linear problem because, at a given node, the power
injection is related to the load impedance by the square of the nodal voltage,
which itself is not known at the beginning of the study. Thus, the solution has to
7th Semester (EEE), Section: A 18
Chapter 1. Electrical Power Systems - An Overview Dr. D. A. Gadanayak
4. The generators are represented as nodal power injections because in the steady
state the prime mover is assumed to drive the generator at a constant speed and
the AVR is assumed to keep the nodal voltage magnitude at a specified value.
3. Traditionally, the constraint equations include the network equations, active and
reactive power consumed at the load points, limits on active and reactive power
generation, stability and thermal limits on transmission lines and transformers.
4. Optimal power flow studies provide an effective tool for reactive power
management and for assessing the effectiveness of FACTS equipment.
1. Faults are unpredictable events that may occur anywhere in the power network.
Given that faults are unforeseen events, strategies for dealing with them must be
decided well in advance. For the above reason, to create appropriate protection
strategies, fault studies are required.
2. Fault creates large currents flowing from the generators to the point of fault and
the voltage drop to extremely low values. The greatest voltage drop takes place at
the point of fault, but neighbouring locations are also affected to varying degrees.
3. Faults can be divided into two categories shunt faults and series faults.
• Shunt faults:
• Series faults:
1. The system load varies continuously with time in a random fashion. Significant
changes occur from hour to hour, day to day, month to month and year to year.
2. The random nature of system load must be included in power flow studies and
this finds useful applications in planning studies.
3. Some possible approaches for modelling random loads within a power flow
study are:
(b) future load is forecast by means of time series analysis based on historic
values, then normal power flow studies are performed for each forecast
point.
(c) future load is forecast by means of Neural Networks, then normal power
flow studies are performed.
1. Loads can be divided into two categories, linear loads and non-linear loads.
Linear load is a load where current waveform follows the voltage waveform
exactly i.e. if sinusoidal voltage is applied to it the resulting current is also
purely sinusoidal. Examples are, resistive, inductive or capacitive loads.
Similarly, non-linear load is a load in which the current waveform doesn’t
follow the voltage waveform exactly i.e. for a sinusoidal voltage input, the
resulting current is non-sinusoidal.
1. Energy control centres have the objective to monitor and control the electrical
network in real-time so that secure and economic operation is achieved round
the clock, with a minimum of operator intervention.
3. The main power systems softwares used for the real-time control of the network
are:
(c) Directly interact with devices such as sensors, valves, pumps, motors, and
more through human-machine interface (HMI) software.
2. Write two examples each from normal and abnormal dynamic conditions in
electrical power networks.
7. With example explain, why the model used for power system dynamic study
must consider the time scales for which the study is intended?
9. Write different approaches for modelling random loads in a power flow study.
10. Write a short note on energy control center explaining its purpose, equipment
and software.
12. What are the parameters which measure the quality of electricity?
13. Explain briefly with block diagram the main controls of the turbine-generator
sets to generate desired power at desired voltage level.
2. when the focus is on reactive power flow in the transmission line, it is termed as
transmission system compensation.
25
Chapter 2. Power System Engineering - Fundamental Concepts Dr. D. A. Gadanayak
(c) load balancing: Most AC power systems are three-phase, and are designed
for balanced operation. Unbalanced operation gives rise to undesirable
negative and zero sequence components. Such components can have
adverse effects such as additional losses in motors and generating units,
oscillating torque in AC machines, increased ripple in rectifiers,
malfunction of several types of equipment, saturation of transformers, and
excessive triplen harmonics and neutral currents.
(a) It must supply the exact reactive power requirement of the load.
At any point where a load is connected to the power system, the power system can
be represented by a Thevenin equivalent circuit having an open circuit voltage E and
an internal impedance Zs = Rs + jXs . Usually Xs is much bigger than Rs , hence Zs is
approximated as Zs = jXs .
jXS
• The fault level (sometimes called short-circuit level) is a term used to describe
the ’strength’ of a power supply: that is, its ability to provide both current and
voltage. It is defined as:
Fault level = Open-circuit voltage × Short-circuit current.
• Circuit-breakers must interrupt fault currents to separate the healthy circuit from
the faulty one. When the contacts of the circuit-breaker are separating, there is an
arc which must be extinguished. The difficulty of extinguishing the arc depends
on both the current and the system voltage. So it is convenient to take the product
of these as a measure of the size or ’power’ of the circuit-breaker that is needed.
• The rating of a circuit-breaker should always exceed the fault level at the point
where the circuit-breaker is connected otherwise the circuit-breaker might not be
capable of interrupting the fault current.
jXS
E
jXSI
E V R
V
I
jXS
E
E V jXL
V jXSI
jXS
V
E V
-jXC
E jXSI
The symmetrical system is the simple model of a power system that comprises two
synchronous machines coupled by a transmission line modelled by a simple inductive
impedance jXs .
jX
I I
jXI
ES
I
ER
ES S
R
ER
Es ER
P= sin(δ) (2.1)
X
7th Semester (EEE), Section: A 29
Chapter 2. Power System Engineering - Fundamental Concepts Dr. D. A. Gadanayak
• P is the real power averaged over one cycle. It is expressed in W, kW, MW, etc.
• Q is the reactive power averaged over one cycle. It is expressed in VAr, kVAr,
MVAr, etc.
• S is the apparent power equals to the magnitude of the complex power. S = |S|.
It is expressed in VA, kVA, MVA, etc.
S
Q
• In inductive loads reactive power is positive. In other words they absorb VArs.
• Capacitive loads absorb negative reactive power. In other words capacitive loads
generate VArs.
jXS
E
jXSI
E V R
V
I
jXS
jXSI
E V
R+jXL
V
jXS
E
jXSI
I
E V
R-jXC
• For leading power factor load, | E| can be greater than, equals to or less than |V |.
• Only in leading power factor load perfect voltage regulation i.e. | E| = |V | can be
achieved.
IS
I IY
IY
V -jXC IR
V
Z
IX
jXL
I
where Z s = Rs + jXs .
Also we know complex power S = V I ∗ = P + jQ ⇒ V I = P − jQ
P − jQ
I= (2.3)
V
P − jQ Xs P − R s Q
R s P + Xs Q
∆V = ( Rs + jXs ) = +j = ∆VR + j∆VX (2.4)
V V V
R s P + Xs Q Xs P − R s Q
E = V + ∆V = V + +j (2.5)
V V
Magnitude wise,
F:/PEC/REVISES_10-11-01/075065126-CH002.3D ± 46 ± [31±81/51] 17.11.2001 9:49AM
2 2
Xs P − R s Q
2 R s P + Xs Q
| E| = V + + (2.6)
V V
To find the value of total reactive power Qs for zero voltage drop equation 2.6 can be
solved for Q by putting V = | E|.
46 Power systems
Now theengineering ± fundamental
net compensating concepts
reactive power would be QY = Qs − Q.
Iγ
E jX s I s
Is
∆V
RsIs
V
I
Load
Fig. 2.15 Phasor diagram, compensated for constant voltage.
F IGURE 2.13: Phasor diagram of the system with the compensator
voltage V. Equation (2.13) always has a solution for Qs , implying that: A purely
• For complete power factor correction Q in equation (2.4) is zero,
reactive compensator can eliminate voltage variations caused by changes in both the real
and the reactive
Hence power of the load.
Provided that the reactive∆Vpower Rs P of X s P compensator P
= + j the = ( Rs + jXs ) Qg can be controlled
(2.7)
V V V
smoothly over a sufficiently wide range (both lagging and leading), and at an
adequate rate, the compensator can perform as an ideal voltage regulator.
• For a finite value of active power P, equation (2.7) can’t be zero. It implies A
We have seen that a compensator can be used for power-factor correction. For
example,purely reactivefactor
if the power compensator cannot
is corrected to maintain
unity, Qs both unity
0 and Qgpower
Q. factor
Then and
constant voltage.
P
V (Rs jXs ) (2:14)
V
which is independent of Q and therefore not under the control of the compensator.
Thus:
7th A purely (EEE),
Semester reactive compensator
Section: A cannot maintain both constant voltage and unity
35
power factor at the same time.
The only exception is when P 0, but this is not of practical interest.
Chapter 2. Power System Engineering - Fundamental Concepts Dr. D. A. Gadanayak
In the figure 2.2 we can see that ∆VX only rotates the vector E and the change in voltage
E2
magnitude is mainly due to ∆VR . Also the short circuit MVA S = Xs , which can be
E2 V2
approximated as S = Xs ≈ Xs .
Now equation 2.2 becomes
R s P + Xs Q
∆V = ∆VR = (2.8)
V
Xs Q ∆V Xs Q Q
∆V = ⇒ = 2 ≈ (2.9)
V V V S
Q
∆V ≈ V (2.10)
S
Q Q
E−V ≈ V ≈E (2.11)
//SYS21/F:/PEC/REVISES_10-11-01/075065126-CH002.3D ± 45 ± [31±81/51] 17.11.2001 9:49AM S S
Q
V ≈ E 1− (2.12)
S
Now the relationship between Q and V is a straight line and it is called the system load
line. Power electronic control in electrical systems 45
Fig. 2.14 System load line. F IGURE 2.14: The system load line
The `load' can be measured by its current I, but in power systems parlance it is the
reactive volt-amperes Q of the load that is held chiefly responsible for the voltage
drop. From Figures 2.12 and 2.13,
V E V Zs I (2:10)
where I is the load current. The complex power of the load (per phase) is defined by
equation (2.2), so
7th Semester (EEE), Section: A P jQ
36
I (2:11)
V
and if V V j0 is taken as the reference phasor we can write
Chapter 2. Power System Engineering - Fundamental Concepts Dr. D. A. Gadanayak
• The power supplied to the system by the generator Pin is determined by the prime
mover(s).
• However, the power system operator has no control over power taken from the
system Pout , since it depends upon the amount of loading.
• In the short term (i.e. over a period of a fraction of a second), the frequency
control ensures that Pin = Pout , and this control is effected by maintaining the
speed of the generators extremely close to the nominal value. Suppose the power
system is in a steady state and Pin = Pout . Suppose that the load increases so that
more power is taken from the system, tending to make Pin < Pout . The prime
mover and the generator will tend to slow down. Therefore the prime mover has
a governor (i.e. a valve controller) that increases Pin when the frequency is below
the rated value, and decreases Pin when the frequency is above the rated value.
• The large generating stations are usually best operated at constant power for
long periods, without varying their contribution to Pin . Apart from the
economics, one reason for this is that if the power is varied, the temperature
distribution in the turbine, boiler, and generator will be affected, and ’thermal
cycling’ is considered undesirable in these very large machines. So these
generators have a relatively steep or insensitive governor characteristic, such
that the frequency would have to change by quite a large amount to change the
contribution to Pin . Elsewhere in the power system, or sometimes in the same
power station, there are special generators assigned to the task of frequency
control. These generators have very flat governor characteristics such that a tiny
change in frequency will cause a large swing in power. They are usually gas
turbine powered, up to 20 MW. However, some very large rapid-response
generators are sometimes built into hydro-electric pumped-storage schemes.
jX
I I
jXI
ES
I
ER
ES S
R
ER
Let
E R = Er ̸ 0o = Er ; ES = Es ̸ δ (2.13)
Now current
Es ̸ δ − Er ̸ 0o
I= (2.14)
Xs ̸ 90o
∗
E2
Er Es ̸
= δ − 90o − r ̸ −90o
Xs Xs
Er Es ̸ E2
= 90o − δ − r ̸ 90o
Xs Xs
Er Es Er Es E2 E2
= cos(90o − δ) + j sin(90o − δ) − r cos(90o ) − j r sin(90o )
Xs Xs Xs Xs
Er Es Er Es E2
= sin(δ) + j cos(δ) − j r
Xs Xs Xs
E2
Er Es Er Es
= sin(δ) + j cos(δ) − r = P + jQ
Xs Xs Xs
So
Er Es Er Es E2
P= sin(δ) and Q= cos(δ) − r (2.15)
Xs Xs Xs
Similarly, analysing sending end complex power we can get,
Er Es Es2 Er Es
P= sin(δ) and Q= − cos(δ) (2.16)
Xs Xs Xs
2. Three phase power transmission systems are economical. Better utilization of the
transmission line material, insulation, transformers, etc.
5. Three phase induction motors are robust, relatively cheap, smaller, have
self-starting property, provide steady output (uniform torque), requires least
maintenance, and are more efficient than single phase motors.
Fig. 2.22 Three-phase connection with delta-connected load and phasor diagram.
F IGURE 2.17: Three phase delta-connection and phasor diagram
Advantages of wye-connection
1. A star connected alternator requires less number of turns than delta connected
alternator for the same output voltage.
2. For the same line voltage a wye-connected alternator requires less insulation.
3. A three phase four wire system allows use of two voltage levels (phase and line
voltage).
4. When the neutral point is earthed the insulators have to bear less line voltage
during a line-to-ground fault.
Advantages of delta-connection
1. Delta connection has higher reliability. If one of the three primary windings of a
delta-connected transformer fails, the secondary will still produce full voltage on
all three phases.
2. In delta connection, the triplen harmonics are allowed to flow locally without
entering the external circuit.
//SYS21/F:/PEC/REVISES_10-11-01/075065126-CH002.3D ± 54 ± [31±81/51] 17.11.2001 9:49AM
3. Normally three phase motor windings are connected in delta, so that full line
voltage can be utilized for torque production.
current in each phase tends to become distorted, and the triplen harmonics are
allowed to flow
1. Delta-wye locally in a delta-connected winding without entering the external
transformation:
circuit. In electric motors a delta winding permits the use of a larger number of turns
of smaller-gauge wire, because the phase voltage is increased while the phase current
is decreased, Z AB ZCA with the wye connection.
compared ZBC Z AB ZCA ZBC
ZA = ; ZB = ; ZC =
Z AB + ZBC + ZCA Z AB + ZBC + ZCA Z AB + ZBC + ZCA
(2.17)
2.9.2 The wye±delta transformation
A wye-connected load can be represented by a virtual load connected in delta, and
7th vice-versa,
Semester Figure
(EEE), 2.23. To
Section: Atransform the delta connection into a wye connection, 41
ZAB ZCA ZBC ZAB ZCA ZBC
ZA ; ZB ; ZC (2:27)
Z Z Z
Chapter 2. Power System Engineering - Fundamental Concepts Dr. D. A. Gadanayak
2. Wye-delta transformation:
YA YB YB YC YC YA
YAB = ; YBC = ; YCA = (2.18)
YA + YB + YC YA + YB + YC YA + YB + YC
2.10.1 2.10phase
Single Power flow and measurement
2.10.1 Single-phase
Let v = Vm cos(ωt) and i = Im cos(ωt − Φ),
Suppose we have a single-phase load as in Figure 2.7 supplied with a sinusoidal p
voltage whose instantaneous
Now the instantaneous power value is u Vm cos ot. The RMS value is V Vm / 2
and the phasor value is V. If the load is linear (i.e. its impedance is constant and does
not depend on the current or voltage), the current will be sinusoidal too. It leads or
lags the voltage by a phase angle f, depending on whether the load is capacitive or
p = vi = Im cos(ωt
Vminductive. )cosa (lagging
With Φ)
ωt − (inductive) load, i Im cos(ot f); see Figure 2.29.
The instantaneous power is given by p ui, so
V m Im
p Vm Im cos ot cos(ot f) [ cos f cos(2ot f)] (2:30)
2
Vm Im
= (Φ) expression
[cosThis + cos(2ωt has−aΦconstant
)] term and a second term that oscillates at double
2 frequency. The constant term represents the average power P: we can write this as
Vm Im
P p p cos f VI cos f (2:31)
2 2
p
Vm Im P is equal
Vm Ito
p m the product of the rms voltage V Vm / 2, the RMS current
= cos(IΦ) I+ cos(2ωt − Φ)
m / 2, and the power factor cos f. The amplitude of the oscillatory term is
(2.19)
2 2
fixed: i.e. it does not depend on the power factor. It shows that the instantaneous
power p varies from 0 to Vm Im to Vm Im and back to 0 twice every cycle. Since the
Vm Im
It indicates, an average power of 2 with a peak-peak power fluctuation of 200%
at double frequency. The oscillation of power in single-phase circuits contributes to
lamp flicker and causes vibration in motors and transformers, producing undesirable
acoustic noise.
Let
v a = Vm cos(ωt), i a = Im cos(ωt − ϕ) ;
7th Semester (EEE), Section: A 43
Chapter 2. Power System Engineering - Fundamental Concepts Dr. D. A. Gadanayak
2π
vb = Vm cos(ωt − 3 ), i b = Im cos(ωt − 2π
3 − ϕ) ;
2π
vc = Vm cos(ωt + 3 ), i c = Im cos(ωt + 2π
3 − ϕ) ;
Now the instantaneous power
p = v a i a + vb ib + vc ic
2π 2π
= Vm Im [cos(ωt)cos(ωt − ϕ) + cos(ωt − )cos(ωt − − ϕ)
3 3
2π 2π
+ cos(ωt + )cos(ωt + − ϕ)]
3 3
Vm Im 4π
= [cos(ϕ) + cos(2ωt − ϕ) + cos(ϕ) + cos(2ωt − − ϕ)
2 6
4π
+ cos(ϕ) + cos(2ωt − − ϕ)]
3
Vm Im 4π 4π
= [cos(ϕ) + cos(2ωt − ϕ) + cos(ϕ) + cos(2ωt − ϕ)cos( ) + sin(2ωt − ϕ)sin( )
2 6 6
4π 4π
+ cos(2ωt − ϕ)cos( ) + sin(2ωt − ϕ)sin( )]
3 3
√
Vm Im −1 3
= [cos(ϕ) + cos(2ωt − ϕ) + cos(ϕ) + cos(2ωt − ϕ) + sin(2ωt − ϕ)
2 2 2√
−1 − 3
+ cos(2ωt − ϕ) + sin(2ωt − ϕ) ]
2 2
3Vm Im Vm Im
⇒p= cos(ϕ) = 3 √ √ cos(ϕ) = 3V Icos(ϕ) (2.20)
2 2 2
Let
v a = Vm cos(ωt), i a = Im cos(ωt − ϕ) ;
vb = Vm cos(ωt − π2 ), ib = Im cos(ωt − π
2 − ϕ) ;
p = v a i a + vb ib
π π
= Vm Im [cos(ωt)cos(ωt − ϕ) + cos(ωt − )cos(ωt − − ϕ)]
2 2
= Vm Im [cos(ωt − ωt + ϕ)]
//SYS21/F:/PEC/REVISES_10-11-01/075065126-CH002.3D ± 62 ± [31±81/51] 17.11.2001 9:49AM
Vm Im
⇒ p = Vm Im cos(ϕ) = 2 √ √ cos(ϕ) = 2V Icos(ϕ) (2.21)
2 2 ± fundamental concepts
62 Power systems engineering
Ia + Ib + Ic = 0 ⇒ Ic = − Ia − Ib
2.12 Transformers
2.12.1 Uses
3. Impedance matching.
4. Create a neutral point remote from power station (grounding transformers with
zigzag winding configuration).
• Load connection.
⇒ I1 Z1 = I2 Z2 (2.24)
1
I Z Z1 Y1
⇒ 1 = 2 = 1
= (2.25)
I2 Z1 Z2
Y2
I1 Z1 = I2 Z2
⇒ I1 Z1 = ( I − I1 ) Z2 = IZ2 − I1 Z2
⇒ I1 ( Z1 + Z2 ) = IZ2
1
!
Z2 Z1 Y1
⇒ I1 = I= 1 1
I= I (2.26)
Z1 + Z2 Z2 + Z1
Y1 + Y2
Similarly,
Z1 Y2
I2 = I= I (2.27)
Z1 + Z2 Y1 + Y2
Complex power
Complex power through transformer-1
∗ ∗ ∗
Y1 Y1 Y1
S1 = V I1∗ =V I = ∗
VI = S (2.28)
Y1 + Y2 Y1 + Y2 Y1 + Y2
so
S1 Y1∗ Z2∗
= ∗ = ∗ (2.30)
S2 Y2 Z1
Z1 Z [S ]
z1 = = 12 = Z1 1 b2 (2.31)
[ Z1 ]b [V1 ]b [V1 ]b
[ S1 ] b
Similarly,
Z2 Z [S ]
z2 = = 22 = Z2 2 b2 (2.32)
[ Z2 ]b [V2 ]b [V2 ]b
[ S2 ] b
s1 z∗
= 2∗ (2.34)
s2 z1
It indicates that, when the transformers are loaded proportional to their ratings i.e
S1 ∝ [S1 ]b and S2 ∝ [S2 ]b , then z1 = z2 i.e. p.u. impedances must be same.
𝜱1 𝜱2 𝜱3
Ia + Ib + Ic = 0,
Va + Vb + Vc = 0,
ϕa + ϕb + ϕc = 0,
Ia + Ib + Ic = I0 ,
Va + Vb + Vc = V0 ,
ϕa + ϕb + ϕc = ϕ0 ,
Hence,
• ϕ0 doesn’t get a return path and must find a return path outside the three limbs
resulting in leakage flux.
Remedy
1. Five limb core. Extra two limbs provide a return path for the ϕ0 .
3. Tertiary winding.
2.13 Harmonics
cosine waveforms. Let the periodic non-sinusoidal waveform is v(t). Then according
to Fourier series it can be represented as,
∞ ∞
v(ωt) = v0 + ∑ am cos(mωt) + ∑ bm sin(mωt) (2.35)
m =1 m =1
where
Z 2π
1
v0 = v(ωt)d(ωt)
2π 0
Z 2π
1
am = v(ωt)cos(ωt)d(ωt)
π 0
Z 2π
1
bm = v(ωt)sin(ωt)d(ωt).
π 0
∞
v(ωt) = v0 + ∑ [ am cos(mωt) + bm sin(mωt)] (2.36)
m =1
∞
" #
am bm
q
= v0 + ∑ a2m + bm
2 p
a2m + bm
2
cos(mωt) + p
a2m + bm
2
sin(mωt)
m =1
Lets take
am bm −1 am
sin(ϕm ) = p ⇒ cos(ϕm ) = p and ϕm = tan .
a2m + bm
2 a2m + bm
2 bm
q
v p,m = a2m + bm
2.
∞
v(ωt) = v0 + ∑ v p,m [sin(ϕm )cos(mωt) + cos(ϕm )sin(mωt)]
m =1
∞
v(ωt) = v0 + ∑ v p,m sin(mωt + ϕm ) (2.37)
m =1
Now v p,1 is called the magnitude (or the peak value) of fundamental component, v p,2
is called the magnitude of second harmonic component, v p,3 is called the magnitude of
third harmonic component, and so on.
If V1 ,V2 ,...,Vm are the RMS values of fundamental, second harmonics, ..., mth harmonics,
v p,1 v p,2 v p,m
i.e. V1 = √ ,V2 = √ , Vm = √ , then equation (2.37) can be written as,
2 2 2
∞ √
v(ωt) = v0 + ∑ 2Vm sin(mωt + ϕm ) (2.38)
m =1
Generally, in steady state, power system voltage and current waveforms are
symmetrical and having no DC components. Hence in steady state analysis we
neglect v0 and hence equation (2.38) is represented as,
√ ∞
v(ωt) = 2 ∑ Vm sin(mωt + ϕm ) (2.39)
m =1
√ ∞
v(ωt) = 2 ∑ Vm sin(mωt)
m =1
√ ∞
i (ωt) = 2 ∑ In sin(nωt + ϕn )
n =1
Average power:
Z 2π
1
Pavg = p(ωt)d(ωt)
2π 0
Z 2π √ ∞ √ ∞
1
=
2π 0
2 ∑ Vm sin(mωt) 2 ∑ In sin(nωt + ϕn )d(ωt)
m =1 n =1
Z 2π ∞
1
=
2π 0
∑ 2Vm sin(mωt) In sin(nωt + ϕn )d(ωt)
m=1,n=1
Z 2π ∞
1
=
2π 0
∑ Vm In {cos [(m + n)ωt + ϕn ] + cos [(m − n)ωt − ϕn ]}d(ωt) (2.40)
m=1,n=1
R 2π
When p ̸= 0 0 cos( pθ + ϕ)dθ = 0 Hence
Z 2π
1
Vm In cos [(m + n)ωt + ϕn ] d(ωt) = 0 always
2π 0
Z 2π
1
Vm In cos [(m − n)ωt − ϕn ] d(ωt) = 0 only when m ̸= n
2π 0
For m = n
Z 2π
1 1
Vm In cos [(m − n)ωt − ϕn ] d(ωt) = Vm Im cos(−ϕn )(2π ) = Vm Im cos(ϕm )
2π 0 2π
∞
1
Pavg =
2π ∑ Vm Im cos(ϕm ) (2.41)
m =1
2π 2π 2π 2π
vbn = V1 cos(ωt − ) + V2 cos2(ωt − ) + V3 cos3(ωt − ) + V4 cos4(ωt − )
3 3 3 3
2π 2π
+ V5 cos5(ωt − ) + V6 cos6(ωt − ) + ...
3 3
2π 2π 2π 2π
vcn = V1 cos(ωt + ) + V2 cos2(ωt + ) + V3 cos3(ωt + ) + V4 cos4(ωt + )
3 3 3 3
2π 2π
+ V5 cos5(ωt + ) + V6 cos6(ωt + ) + ...
3 3
Now harmonic terms in vbn and vcn can be further simplified, for example
2π 4π 2π
V2 cos2(ωt − ) = V2 cos(2ωt − ) = V2 cos (2ωt + ) − 2π
3 3 3
2π 2π
= V2 cos 2π − (2ωt + ) = V2 cos(2ωt + )
3 3
2π
V3 cos3(ωt + ) = V3 cos(3ωt + 2π ) = V3 cos(3ωt)
3
In the similar fashion if we reduce all terms in vbn and vcn , we get
2π 2π 2π
vbn = V1 cos(ωt − ) + V2 cos(2ωt + ) + V3 cos(3ωt) + V4 cos(4ωt − )
3 3 3
2π
+ V5 cos(5ωt + ) + V6 cos(6ωt) + ...
3
2π 2π 2π
vcn = V1 cos(ωt + ) + V2 cos(2ωt − ) + V3 cos(3ωt) + V4 cos(4ωt + )
3 3 3
2π
+ V5 cos(5ωt − ) + V6 cos(6ωt) + ...
3
Per-unit quantities are quantities that have been normalized to a base quantity.
Conventionally, [ MVA]b and [kV ]b are taken as the primary base quantities and other
[kV ]2b
[ Z ]b = (2.44)
[ MVA]b
• Voltage, current, and impedance expressed in pu do not change when they are
referred from one side of the transformer to the other side.
• As the pu values lie within narrow range, they are suitable for digital calculation.
I(x)
Is Ir
Es V(x) Vr
x
a
Lossless transmission line: Series resistances and shunt conductances are neglected.
Voltage and current equations of of a long, lossless transmission line are given by:
Vr
I (x) = j sinβ( a − x ) + Ir cosβ( a − x ) (3.2)
Z0
57
Chapter 3. Transmission system compensation Dr. D. A. Gadanayak
1
u = √ : propagation velocity (in km/s).
lc
u
λ= : wavelength (in km).
f
θ = βa : electrical length of the transmission line (in radian).
2
Vr,L −L
P0 = (3.3)
Z0
Power electronic control in electrical systems 87
Fig. 3.3 Voltage profiles along a long, lossless symmetrical transmission line.
F IGURE 3.2: Voltage profiles along the long lossless transmission line for
important with very long lines when there are no intermediate substations at which
different cases of power with respect to the surge impedance loading
the voltage level can be controlled. Evidently it is desirable to operate such lines as
close as possible to the SIL, to maintain a flat voltage profile. Shorter lines (typically
those less than 50±100 km) do not have such a problem with the variation of the
voltage profile with load, and the power transmission through them is more likely to
3.2 The uncompensated line on open-circuit
be limited by other factors, such as the fault level or the current-carrying capacity of
the conductors (which is thermally limited).
3.2.3 The
For open-circuit uncompensated
(without load) Ir = 0. line on open-circuit
So equation 3.1 and 3.2 will become:
A lossless line that is energized by generators at the sending end and is open-circuited
at the receiving end is described by equation (3.2) with Ir 0, so that
V ( x ) = Vr cosβ( a − x ) (3.4)
V(x) Vr cos b(a x) (3:6)
and
Vr
I(x) j sin b(a x) (3:7)
Z0
7th Semester (EEE), Section: A 58
The voltage and current at the sending end are given by these equations with x 0.
Es Vr cos y (3:8)
Chapter 3. Transmission system compensation Dr. D. A. Gadanayak
Vr
I (x) = j sinβ( a − x ) (3.5)
Z0
Es
Es = Vr cosβa = Vr cosθ ⇒ Vr = (3.6)
cosθ
Vr
Is = j sinθ (3.7)
Z0
Replacing the value of Vr from equation 3.6 into 3.4 and 3.5, we have,
Es cosβ( a − x )
V (x) = (3.8)
cosθ
Es sinβ( a − x )
I (x) = j (3.9)
Z0 cosθ
To realize the voltage and current profiles, let’s take the example of an unloaded 300
km transmission line. Let’s β = 6o per 100km. Now a = 300 km, θ = βa = 18o . As line
is not loaded, I ( a) = Ir = 0.
From equation 3.8,
//SYS21/F:/PEC/REVISES_10-11-01/075065126-CH003.3D ± 88 ± [82±105/24] 17.11.2001 9:53AM
Es Es
V ( a) = Vr = = = 1.05Es = 1.05 pu.
cosθ cos18o
88 Transmission system compensation
Es sinβa Es sinθ Es Es Es
Is = I (0) = j =j = j tanθ = j tan18o = j0.325 = 0.325 pu.
Z0 cosθ Z0 cosθ Z0 Z0 Z0
Fig. 3.4 Phasor diagram of uncompensated line on open-circuit.
Fig. 3.5 Voltage and current profiles for a 300-km line at no load (open-circuit).
F IGURE 3.3: Voltage and current profiles for a transmission line at no load
The general forms of these profiles are shown in Figure 3.5. For a line 300 km in
5
7th Semester (EEE), length at 50 Hz, b 360 f /3 10 6 per 100 km, so y 6 3 18 . Then
Section: A
Vr Es / cos y 1:05Es and Is (Es /Z0 ) tan y 0:329 p:u: based on the SIL. The
59
voltage rise on open-circuit is called the Ferranti effect.
Although the voltage rise of 5% seems small, the `charging' current is appreciable
and in such a line it must all be supplied by the generator, which is forced to run at
leading power factor, for which it must be underexcited.1 Note that a line for which
y ba p/2 has a length of l/4 (one quarter-wavelength, i.e. 1500 km at 50 Hz),
Chapter 3. Transmission system compensation Dr. D. A. Gadanayak
IS Ir
ES Vr P
+
jQ
When x = 0
Vr Ir∗ = P + jQ
⇒ Vr∗ Ir = P − jQ
P − jQ
⇒ Ir =
Vr∗
P − jQ
ES = Vr cosθ + jZ0 sinθ (3.11)
Vr∗
If ES is fixed, Q is fixed, for any value of P equation (3.11) will give two solutions to Vr .
3.4 Numericals
(vi) the reactive power at the sending end, expressed as a fraction of the
surge-impedance loading.
Ans:
(i) s r
p XL 0.6
Z0 = X L XC = = = 109.5445Ω
YC 50 × 10−6
(ii) s
XL p
= X L YC = 0.6 × 50 × 10−6 = 5.477 × 10−3 radian
p
β=
XC
180
θ = βa = 5.477 × 10−3 × 54.8 = 0.3 radian = 0.3 × = 17.189o
π
(iii)
ES cosβ( a − x )
V (x) =
cosθ
For x = a
Es Es
V ( a) = = = 1.0468ES = 1.0468 p.u.
cosθ cos17.189o
(iv)
ES sinβ( a − x )
I (x) = ×
Z0 cosθ
√
ES sinβa ES sinθ ES (345 × 103 )/ 3
I (0) = × = × = tanθ = tan(17.189o ) = 562.478A
Z0 cosθ Z0 cosθ Z0 109.5445
√ √
QS = 3VS IS = 3345 × 103 × 0.562478 × 103 = 336.113 MVAr
(i) The sending end voltage when load is 900 MVA with a lagging power factor of
0.88.
(v) Draw phasor diagram showing phase voltage and current of both ends.
Ans:
s r
p XL0.6
Z0 = X L XC = = = 109.5445Ω
50 × 10−6
YC
s
XL p
= X L YC = 0.6 × 50 × 10−6 = 5.477 × 10−3 radian
p
β=
XC
180
θ = βa = 5.477 × 10−3 × 14.8 = 0.0810596 radian = 0.0810596 × = 4.64437o
π
Let’s take per phase receiving end voltage Vr as the reference. Vr = ( 345
√ ) × 103 ̸ 0o V
3
As total power is 900 MVA. Per phase power is 300 MVA.
Also, power factor cosϕ = 0.88.
Per phase active power P = 300 × 106 × cosϕ W and
per phase reactive power is Q = 300 × 106 × sin(ϕ) VAr.
(i)
ES = Vr cosθ + jZ0 Ir sinθ per phase
345
ES = ( √ ) × 103 cos(4.64437o ) + j109.5445(1325.395 − j715.372)sin(4.64437o ) per phase
3
√
Sending end voltage (Line-Line)=205.213 × 103 3 = 355.44 kV.
(iii)
Vr
IS = j sinθ + Ir cosθ
Z0
( 345
√ ) × 103
3
=j sin(4.64437o ) + (1325.395 − j715.372)cos(4.64437o ) A
109.5445
(iv)
h i
PS + jQS = 3ES IS∗ = 3 (204.8768 + j11.756) × 10 3
× [1321.04 + j569.023] VA
ES
3.284o
Vr
o
-23.303
-28.357o
IS
Ir
jX
I I
E1
Ip1 jXI=E1-E2
E2 I
E1
E2
Iq1
Ip1 jXI=E1-E2
E2 I
E1
E2
Iq1
Let’s take the symmetrical system shown in Fig 4.1. The phasor diagram is shown in
Fig 4.2. We know that the sending end active and reactive powers are given as,
Er Es Es2 Er Es
P= sin(δ) and Q= − cos(δ) (4.1)
Xs Xs Xs
65
Chapter 4. Flexible AC Transmission Systems Dr. D. A. Gadanayak
4.1.1 Parameters
1. In Figure 4.3(a), we can see that increase and decrease of the value of X will
increase and decrease the height of the P − δ curves, respectively and hence the
active power can be controlled by controlling X.
3. Current flow and hence power flow can also be changed by injecting voltage in
series with the line. It is seen from Figure 4.3(c) that when the injected voltage
in phase quadrature with the current (which is approximately in phase with the
driving voltage), directly influences the magnitude of the current flow, and hence
the active power flow.
r
,f1
I
&_cos 6
",,. -1:1 sin 6
X E2sin 6 �(E2 - E
�lq, = (E1 - E2COS 6)I......._
(b)4. Flexible AC Transmission Systems
Chapter E1 cost,
Dr. D. A. Gadanayak
lq 2 = (E2- E1 cos 6 )IX
r
E2cos 6) (b)
(c)
f1
......._ E2sin 6
�(E2 - E1 cos 6)
t, °
90" 180
�(E2 - E1 cos 6) Angle 6
t, (d) (A) °
(e)
90"Power 180 (B) Changing
angle Angle
curves6 for voltage E1 .
different values of (e)
(d) X.
- Injected voltage Injected voltage
Injected voltage
- Injected voltage
(f)
• Injecting a voltage in series with the line, and perpendicular to the current flow,
can increase or decrease the magnitude of current flow. Since the current flow
lags the driving voltage by 90 degrees, this means injection of reactive power in
series, (e.g., with static synchronous series compensation) can provide a powerful
means of controlling the line current, and hence the active power when the angle
is not large.
• Injecting voltage in series with the line and with any phase angle with respect to
the driving voltage can control the magnitude and the phase of the line current.
This means that injecting a voltage phasor with variable phase angle can provide
a powerful means of precisely controlling the active and reactive power flow.
• When the angle is not large, controlling the magnitude of one or the other line
voltages (e.g., with a thyristor-controlled voltage regulator) can be a very
cost-effective means for the control of reactive power flow through the
interconnection.
• Combination of the line impedance control with a series Controller and voltage
regulation with a shunt Controller can also provide a cost-effective means to
control both the active and reactive power flow between the two systems.
FACTS definition:
A power electronic based system and other static equipment that provides control of
one or more AC transmission system parameters to enhance controllability and
increase power transfer capability.
In general, FACTS Controllers can be divided into four categories:
(b)
(a) (b)
(a)
(b) (A) (b)Series
(c) (B) Shunt
controllers. controllers. (c)
-e -
(c)
-e -
-e -
(c)
-e -
(e)
(d) (C) Combined (e) (D) Combined
(d) series-series
(e) series-shunt
- e- - e-
controllers. controllers.
(h) (i)
3. Combined series-series Controllers: This could0)be a combination of separate
Storage
seriesFigure 1.4 Basicwhich
controllers, types of are
FACfS Controllers:
controlled
(i)
in (a)
a general symbol for
coordinated FACTS in
manner, Con
a multiline
troller; (b) series Controller; (c) shunt Controller; (d) unified
0) series
series Controller;
transmission system. (e) coordinated
Or it could be a unified and (g)
series Controller.
shunt Controller;
The real(f) unified
power transfer
series-shunt Controller; (g) unified Controller for multiple lines; (h)
capability ofFigure
series
the 1.4 Basic
Controller
unified types of FACfS Controllers:
with storage;Controller,
series-series (i) shunt Controller
(a)with
referred general symbol
to storage; (j)
as Interline for FACTS Con
Power
troller; (b) series Controller;
unified series-shunt Controller with storage. (c) shunt Controller; ( d) unified series
Flow Controller, makes series Controller;
it possible (e) coordinated
to balance both the series
realand shunt
and Controller;
reactive power (f) unified
series-shunt Controller; (g) unified Controller for multiple lines; (h)
flow in the lines and thereby maximize the utilization of the transmission system.
series Controller with storage; (i) shunt Controller with storage; (j)
Storage
frequency cycles) storage needs. In addition, another storage
unified series-shunt Controller with storage. source such as a battery,
superconducting magnet, or any other source of energy can be added in parallel
(i)
7th Semester
through an (EEE), Section:
electronic A
interface ) converter's de storage. Any of the
to replenish0the 69
converter-based, series, shunt, or combined shunt-series Controllers can generally
gure 1.4 Basic accommodate
types frequency
of FACfSstorage,
cycles)such as capacitors,
storage
Controllers: needs.
(a) batteries,
In
general andfor
addition,
symbol superconducting
another
FACTS Conmagnets,
storage source such as a b
which bring an added dimension to FACTS technology (Figures Storage
l.4(h), 1 .4(i), and
Chapter 4. Flexible AC Transmission Systems Dr. D. A. Gadanayak
• Control of power flow as ordered. The use of control of the power flow may be
to follow a contract, meet the utilities’ own needs, ensure optimum power flow,
ride through emergency conditions, or a combination thereof.
• Increase the system security through raising the transient stability limit, limiting
short-circuit currents and overloads, managing cascading blackouts and
damping electromechanical oscillations of power systems and machines.
• Provide secure tie line connections to neighbouring utilities and regions thereby
decreasing overall generation reserve requirements on both sides.
• Upgrade of lines.
• Reduce reactive power flows, thus allowing the lines to carry more active power.