Professional Documents
Culture Documents
AR222S Week 6-9 HVAC System
AR222S Week 6-9 HVAC System
CONDITIONING COOLING
1 METABOLISM
2
Metabolism
HEAT AND MOISTURE IN THE ATMOSPHERE AND HUMAN COMFORT
4
Regulation of the thermal environment
HEAT AND MOISTURE IN THE ATMOSPHERE AND HUMAN COMFORT
B. AIR IN MOTION
Flexibility and imagination are the key qualities in selecting and developing any mechanical or electrical system. In
the years ahead, frequent changes are always expected.
In 1961's the basement began to disappear. Subslab
perimeter systems were popular for basementless
houses. In general, the above features were retained
and air was delivered upward across glass, to be taken
back at high-return grills.
In the 1970's oil and gas became scarse. The adoption of electricity
resulted in numerous changes. Necessities such as combustion,
chimneys and fuel storage became nonessential.
There are no fixed rules about designs. The principles of efficiency,
comfort, cost and conformity to the architectural design are
paramount.
Heat
Cooling
Ventilation
Hot water and steam boilers:
ELECTRIC BOILERS
For hot water heating are of high capacity output. Electric steam boilers are also commonly used in large
buildings.
Hot water and steam boilers:
COAL-FIRED STEAM BOILER
As less polluting use of coal is achieved, a return of this variation of equipment is seen.
Heating cooling ventilation:
HOT WATER HEATING SYSTEMS
Hot water heating systems are built around the premise of radiant heat. Water is heated by a boiler and
circulated throughout a building usually homes, through a series of pipes that heat radiators that give off heat.
The heat transfers to the air in the room.
HOT WATER HEATING SYSTEMS
A. CIRCUIT TYPES
There are four (4} principal methods of arranging the piping for the circulation of hot water to the heating
elements located in the spaces to be heated.
Circuit types
1 . SERIES PERIMETER LOOP
This series loop system usually run at the perimeter of the house. The water flows to and through each
baseboard or in tube in turn. Obviously the water at the end of the circuit is a little cooler. Values at each heating
element are not possible since any value would shut off the entire loop. Adjustment is by a damper at each
baseboard, which reduces the natural convection of air over the fins. For long runs or lengths of water circuit, the
pipe size can be increased.
Circuit types
2. One-Pipe System
This is a very popular choice. Special fittings, act to divert part of the flow into each baseboard. A value may be
used at each one to allow for reduced heat or a complete ~hut-off to conserve energy, an advantage that the loop
system does not provide. However, this one pipe system uses a little more piping and is thus not as economical
to install as the loop system in which piping is minimal.
Circuit types
3. Two-Pipe Reverse-Return
Considered the classic method, though not too often employed and indeed
not always necessary. Water nearly at boiler temperature is supplied to
each baseboard without being cooled by passing through a previous
baseboard as in ( 11 or accepting the cooler return water as in {21 equal
friction, resulting in equal flow, is achieved through all baseboards Nos. 1 to
5, by reversing the return instead of running it directly back to the boiler.
This equality is affected by equal lengths of water flow through any
baseboard together with its lengths of supply and return main. More pipe is
required for this than for system (1) and {2).
Circuit types
4. Two-Pipe. Direct Return
Special fitting for one-pipe systems. Venturi-type jet tee used here. In the return branch connection to the main it
induces flow through the convector by retarding the flow to force water into the supply branch and producing a
jet to reduce the pressure in the main following the return branch.
HOT WATER HEATING SYSTEMS
C. AIR VENTS AND WATER DRAINS
A centrifugal pump is selected to overcome the friction-of-flow in the piping and fittings and to deliver water at a
rate sufficient to offset the hourly heat loss of the house or buildings
FIREPLACES
A home without a fireplace does seem to lack something a certain something, that is the heart of the home.
There is always an element of security in known you could have a fire if necessary. Although fireplaces are no
longer necessary for survival, a working fireplace with a cheerful fire blazing away exudes an atmosphere of
happy congenital living and contributes to the feeling that this ls the good life. The mind always envisions the
image of a crackling fire and enjoys the atmosphere of hospitality. rest and repose that is in the mind's eye. A
fireplace suggests the comfort and contentment of quiet evenings before a blazing hearth.
TYPES OF FIREPLACE:
1 CONVENTIONAL MASONRY FIREPLACE
This is often used where there is wide space and you can afford it. But conventional fireplaces are about 10%
efficient. That is, 90 percent of the fire's heat goes up the flue.
AIR
CONDITIONING
SIGNAL SYSTEM
8. HYDRONIC HEATING DESIGN AND ZONING
Required Flow :
The water flow in gallons per minute to be circulated to make up
the hourly heat loss and the selected drop in the water temperature.
Required Volume of Expansion Tank :
This is related to the volume of water in the system and the over-
all rise in temperature from cold water supply temperature to boiler
water operating temperature.
Pump rating :
The pump size is selected on the basis of the required flow and
the total friction head.
9. ELECTRIC RESISTANCE HEATING
REFRIGERATED COOLING FOR HOUSES
AIR-TO AIR COOLING
Unlike the technique in
large buildings and in district
cooling. where distance
makes tne use of chilled water
most convenient for thermal
transmission. houses are
coolled by a rather simple
arrangement of the
refrigeration cycle.
Cooling/Heating by a combined Hydronic and Air System
This new system combines a perimeter hot water heating pipe with
an overhead airhandling system. A boiler having a tankless coil
supplies domestic hot water. The heat output supplies both the
perimeter loop and a coil in the air-handling unit of the duct system.
The total heating load is met by the combination of radiant heat
generated by the perimeter loop and heated air from the overhead
air-handling system.
CENTRAL-STATION AIR CONDITIONING
COOLING by COMPRESSIVE REFRIGERATION
After discussing the principles of heating. it is now necessary to
consider the means for producing cool air, or the chilled water by which
air may be cooled. Occasionally ground water is obtainable at
temperature low enough for direct use, but generally the use of a
refrigeration machine or other special cooling device is necessary. As
shown in the figure below, the compressive refrigeration cycle is a
scheme for transferring heat from one circulated water system (chilled
water) to another condenser water.
•UNIT OF REFRIGERATION
A ton of refrigeration is the cooling effect obtained when 1 ton of
32 °F 16 melts to water at 32 °F in 24 hrs. Since the latent heat-of-fusion of
16 is 144 Btu/lb, the cooling effect or rate of ton of refrigeration (200 lb)
is'taken as 144 x 2,000 = 288,000 Btu/day of 24 hr. or 12,000 Btuh. The
requisite capacity of a refrigerating machine in tons may therefore be
found by dividing the total heat gain in a building in Btuh by 12,000.
COOLING by ABSORPTION
Another form of water chiller is the refrigeration absorption
machine. Suitable for installations up to 1,000 tons capacity, the external
connections of this device are similar to the centrifugal-refrigeration. It
produces chilled water and has a cycle, of the condensing water that
must be cooled. Its motive power is steam, but instead of driving a
turbine to run a compressor, the steam is used in regenerative process to
strengthen a salt solution.
• PRINCIPLES OF CENTRAL COOLING
In larger buildings and those w ith varied and diverse
occupancy, it is usually preferred to centralize the refrigeration plant.
The condenser is cooled by water circulated to an outdoor cooling
tower and the evaporator produces chilled water. The latter is then
pumped to wherever it is needed in the building.
•CENTRAL STATION CONDITIONING
When heat is needed in winter the air circulated through the room or
other spaces must be heated
The function of the cooling tower is to dispose of the heat carried away
from the condenser. The condenser- cooling water is pumped to the
tower where it is dropped through a rising current of air. This effects a
vaporization of some of the water. Latent heat necessary to this change
of state is drawn from the remaining water, cooling it for reuse in the
condenser. Makeup water must be added to the tower since some of
the water is lost in vapor.
3. PSYCHROMETRY
a. AIR MOISTURE AND HEAT
AIR AND WATER VAPOR ARE THE MEDIA BY WHICH AIR-
CONDITIONING SYSTEMS OPERATE. WATER VAPOR IN VARYING AMOUNTS
ALWAYS EXIST IN AIR, AND THE REGULATION OF THIS MOISTURE CONTENT
AND OF THE TEMPERATURE OF THE VAPOR-AIR MIXTURE IS THE PROBLEM
POSED TO THE DESIGNER OF AIR CONDITIONING.
2. Placement- while a residential HVAC unit is typically placed in the backyard or the sides
of the house, a commercial HVAC system is placed in swamp coolers or on the buildings
roof for the following reasons:
▪ HVAC system that is placed on the roof makes a great space saving solution
▪ It avoids noise pollution in the building
▪ It is a perfect solution for maintenance as none of the activities are disrupted during
repairs and replacements
3. Complexity- HVAC systems also vary in structure as commercial systems need to be more
adaptable depending on the type of building where they are being installed, the number of
occupants and the use of building whether it is periodic or constant
4. Drainage- As residential HVAC units serve a much smaller area, the entire system drains
in a single pan that is placed outside the house while a commercial consists of multiple
pipes and pans for draining purposes o ensure complete evaporation and avoid overflowing
5. Mechanism- the mechanism of a commercial HVAC unit depends on the structure where it is
going to be installed. The manufacturing and installation of commercial HVAC system are modular
(housed together) whereas a residential unit is manufactured as standalone (split between
indoor and outdoor)
6. Equipment- used in smaller residential structures differs as compared to the massive HVAC
systems in commercial establishments. Commercial systems are customized for effective heating
And cooling while residential humidity and temperature dwelling do not vary much
7. Maintenance Cost- the size of the system and the difference in mechanism.
Maintenance cost of a commercial HVAC systems is more than a standalone residential unit
WHILE BOTH SYSTEMS ARE DESIGNED TO ACCOMPLISH THE SAME GOAL, ENSURING A
COMFORTABLE AND HEALTHY SPACE REQUIRES PERIODIC HVAC MAINTENANCEE CHECKUPS BY
TECHNICIANS WHO SPECIALIZE IN THE PARTICULAR SYSTEM YOU OWN
RESIDENTIAL
COMMERCIAL
DUAL DUCT HIGH VELOCITY SYSTEMS
Operate in the same manner as the low-velocity systems except that the supply fan runs at a
high pressure, and each zone requires a mixing box with sound attenuation
This type of system uses 2 sets of duct work for the distribution of heating and cooling.
Like the multi-zone system, the dual duct system mixes hot and cold air to achieve the
required air temperature
Instead of mixing the air at central air handling unit, mixing boxes are dispersed throughout the
building.
The dual duct system creates a high level of thermal comfort and allows for great zoning
flexibility, it is very expensive, requires much building space and its wasteful energy
The duct with the heating coil is known as the hot deck
The duct with the cold coil is known as the cold deck
These constant volume dual-duct systems usually use a single, constant-volume supply fan to
supply the two ducts
Dual Duct systems achieve the zoned temperature control by mixing the hot and cold air
streams in a dual duct box while maintaining constant air flow
Natural Ventilation- is the process of supplying air to and removing air from an indoor space
without using mechanical systems. It refers to the flow of external air to an indoor space as a
result of pressure differences arising from natural forces.
Mechanical ventilation- uses fans to drive the flow of subaerial air into
a building. This may be accomplished by pressurization (in the case of
positively pressurized buildings), or by depressurization (in the case of
exhaust ventilation systems). Many mechanically ventilated buildings use a
combination of both, with the ventilation being integrated into
the HVAC system.
Mixed-mode Ventilation (Hybrid Ventilation)- refers to a hybrid approach to space
conditioning that uses a combination of natural ventilation from operable windows (either
manually or automatically controlled), and mechanical systems that include air distribution
equipment and refrigeration equipment for cooling. A well-designed mixed-mode building
begins with intelligent facade design to minimize cooling loads. It then integrates the use
of air conditioning when and where it is necessary, with the use of natural ventilation
whenever it is feasible or desirable, to maximize comfort while avoiding the
significant energy use and operating costs of year-round air conditioning
Infiltration- is the unintentional or accidental introduction of outside air into a building,
typically through cracks in the building envelope and through use of doors for passage.
Infiltration is sometimes called air leakage. The leakage of room air out of a building,
intentionally or not, is called exfiltration. Infiltration is caused by wind, negative
pressurization of the building, and by air buoyancy forces known commonly as the stack effect.