This document is a review comment sheet for an NDE procedure submitted for a new gathering centre in North Kuwait. The submitted NDE procedure, which included radiographic testing, ultrasonic testing, magnetic particle testing, and penetrant testing, was a standard procedure used by NBTC. However, the review comments note that the contractor needs to clarify which specific project or job order they intend to use this NDE procedure for. The document was prepared by a QNQC engineer, reviewed by a lead QNQC engineer, and approved by another individual.
This document is a review comment sheet for an NDE procedure submitted for a new gathering centre in North Kuwait. The submitted NDE procedure, which included radiographic testing, ultrasonic testing, magnetic particle testing, and penetrant testing, was a standard procedure used by NBTC. However, the review comments note that the contractor needs to clarify which specific project or job order they intend to use this NDE procedure for. The document was prepared by a QNQC engineer, reviewed by a lead QNQC engineer, and approved by another individual.
This document is a review comment sheet for an NDE procedure submitted for a new gathering centre in North Kuwait. The submitted NDE procedure, which included radiographic testing, ultrasonic testing, magnetic particle testing, and penetrant testing, was a standard procedure used by NBTC. However, the review comments note that the contractor needs to clarify which specific project or job order they intend to use this NDE procedure for. The document was prepared by a QNQC engineer, reviewed by a lead QNQC engineer, and approved by another individual.
This document is a review comment sheet for an NDE procedure submitted for a new gathering centre in North Kuwait. The submitted NDE procedure, which included radiographic testing, ultrasonic testing, magnetic particle testing, and penetrant testing, was a standard procedure used by NBTC. However, the review comments note that the contractor needs to clarify which specific project or job order they intend to use this NDE procedure for. The document was prepared by a QNQC engineer, reviewed by a lead QNQC engineer, and approved by another individual.
REVIEW I COMMENT SHEET NEW GATHERING CENTRE, GC-30 IN
NORTH KUWAIT EF1902/GC30/LNT- Date 18-Nov-2015 Date Transmittal No.: 23-Nov-20 15 KOC-D-3784 Issued: Received: Return Document No.: See below Revision: A A Code: Subject: NDE Procedure(RT,UT,MPT,PT)
Reference Company Response
Supplementary Comments 50489-530-450- PR0-2147 General comments: The submitted NDE procedure (RT, UT, MPT & PT) is 50489-530-450- standard NDE procedure by NBTC, Contractor shall elaborate or clarify in PR0-2148 which P.O or job order intend to use the said NOT procedure. 50489-530-450- PR0-2149