Sistema de Fire&Gas

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 96

Commissioning Operating & Maintenance Handbook

Mechanical Carbon Dioxide Skid


(Hazardous Area Application)

PDVSA
NA0209-01 – 021
Reassigned to NA0426 Ocensa Paez
64/91002563/030103
64/91002563/70/72
64/91002552/8

P.O. 4500088975-01 - 021

DOCUMENT No. GT1005068-04 Rev. 0


06.08.10

Hazop (2000) Twin Shot Fire and Gas


Protection System

TYCO FIRE & INTEGRATED SOLUTIONS


HILLCREST BUSINESS PARK
CINDERBANK
DUDLEY
WEST MIDLANDS

TEL. No: 01384 458993


FAX No: 01384 458981
EMAIL: (tfis.power.uk@tycoint.com)
CONTENTS

CHAPTER 1 COMMISSIONING
SECTION 1.0 INTRODUCTION
SECTION 1.1 PRELIMINARY EQUIPMENT CONNECTIONS
SECTION 1.2 FUNCTIONAL TESTING
SECTION 1.3 ARMING THE SYSTEM
SECTION 1.4 COMMISSIONING CHECK LIST

CHAPTER 2 OPERATION
SECTION 2.0 INTRODUCTION
SECTION 2.1 THE SYSTEM
SECTION 2.2 SYSTEM OPERATION
SECTION 2.3 PROTECTION EQUIPMENT SCHEDULE
SECTION 2.4 RESETTING DEVICES
SECTION 2.5 DEVICE OPERATION TABLE
SECTION 2.6 REFERENCE DOCUMENTS

CHAPTER 3 MAINTENANCE
SECTION 3.0 INTRODUCTION
SECTION 3.1 PRECONDITIONS
SECTION 3.2 ADDITIONAL NOTES RELATING TO
MAINTENANCE ACTIVITIES
SECTION 3.3 MAINTENANCE SCHEDULE

APPENDIX A CARBON DIOXIDE CYLINDER REMOVAL


AND FILLING INSTRUCTIONS

APPENDIX B CYLINDER WEIGHING DEVICE


SETTING INSTRUCTIONS

APPENDIX C COSHH SHEETS

APPENDIX D CHECK LIST FORMS

APPENDIX E CYLINDER HANDLING

APPENDIX F RECOMMENDED SPARE PARTS LIST

APPENDIX G EQUIPMENT DATA SHEETS


CHAPTER 1

COMMISSIONING
Section 1.0 – Introduction

The first chapter describes the methods for the successful commissioning of the fire
protection skid.

The commissioning is carried out in four separate phases described below.

• Preliminary Connections

• Functional Testing

• Visual Inspection

• Arming the system


1.0.1 Receiving Equipment

The equipment is supplied in a “safe” condition to prevent carbon dioxide cylinder operation
during transit. As a result, additional work is required such as final connections to make the
equipment ready for operation.

The following measures are taken to achieve safety during transit.

• The cylinders are secured in position with transport racking.


• Cylinders are lowered to the base of the cabinet.
• The cylinder discharge outlet port is fitted with an anti-recoil cap.
• The flexible discharge hose is disconnected from the cylinder valve.
• The cylinder weighing device counter weight is lowered to its operated position.
• The solenoid actuator is removed.

Note: Cable ties will secure disconnected devices; these will need to be removed during
commissioning works.

Note: ALL EQUIPMENT SHOULD BE HANDLED WITH CARE, AS HIGH PRESSURE


CARBON DIOXIDE CYLINDERS ARE INCLUDED IN THE INSTALLATION.

The carbon dioxide cylinders are at high pressure.

The anti-recoil cap must be fitted to the valve outlet and the protection cap must be fitted
before removing the carbon dioxide cylinders.

Normal pressure vessel handling precautions must be observed.

Safety clothing (footwear, glasses and hard hats) must be worn when carrying out
installation and maintenance.

Should it be necessary to remove a cylinder from the cabinet, suitable lifting


equipment/trolley must be used.

Each cylinder’s weight monitoring device has a counter weight that is cable tied for transit
purposes. Care should be taken on removal, as a falling weight will cause injury.
Figure 1

When the protection cap is removed the recessed actuating pin will be exposed. Care should
be taken to ensure the pin is not pressed.

Never use the cylinder valve to turn or move the cylinder.

Never fit any release device to a cylinder valve until it is secured in its final location and
connected to the discharge pipework.

1.0.2 Loose Equipment

The skid is provided with the following loose materials, which do not form part of the
system operation.

Cylinder transport protection caps. These will be required in the event of cylinder re-filling.
It should be noted that carriers would refuse to transport cylinders without the necessary
protection.

Cylinder valve solenoid port protection caps, which should be retained for transit.
CO2 Cabinet Assembly – Weather Protected – Figure 2
Section 1.1 – Preliminary Equipment Connections
The following instructions are laid out in the order in which the tasks should be completed to
maintain safety. Reference should be made to Chapter 2 of this manual concerning hazards
and safety.

1.1.1. Preconditions
The following conditions/work shall be completed prior to skid commissioning.

• Turbine shut down.


• Control/Monitoring System Commissioned, see Operating and Maintenance Handbook for
Controls Systems.
• Field devices commissioned with the exception of extinguishant actuator circuits.
• Control panel is in quiescent mode with extinguishant actuator circuits disconnected.
• Pipework installation completed and a purge test carried out.
• The extinguishant isolate ball valve should be closed to prevent accidental operation of
carbon dioxide into the risk during preliminary works.

1.1.2 Procedure for setting the cylinder in position.


1.1.2.1 Move cylinder front securing strap to its operational position.

Figure 3
Typical plan view of cylinder racking inside skid.
1.1.2.2 Raise the cylinder into its operational position by turning the M12 nut on the top of the
weigh beam. The cylinder should be raised until the top of the weight monitoring unit body
is approx 10mm from the underside of the weigh beam (See figures 4 & 4a). Cylinder should
be approximately 10 mm from the floor.

Figure 4

Figure 4a
1.1.2.3 Remove the anti recoil cap and connect the discharge hose to the cylinder valve outlet.
(Store the anti recoil cap in safe place for future transit use). Adjust the height of the
cylinder as necessary using the M12 nut on the weigh beam to ensure the discharge hose is
under no strain. The discharge hose is already connected into the manifold. Check the
manifold connection is tightened.
Important: Check Co2 cylinders are positioned as shown in figure 5a. Position ensures
solenoid assembly, vent valves and hose do not clash with weight monitoring hanger rods.

Figure 5

Figure 5a
1.1.2.4 Raise the weighing device counter balance weight to its monitoring position. The weight will
be retained in the upper position as the counter balance weight is set to its correct monitoring
position prior to dispatch.

Figure 6

Note: In the event of difficulty a full procedure for setting the weighing device is
included in Appendix ‘B’
Section 1.2 – Functional Testing

Note: Functional testing is carried out by Tyco Fire prior to delivery of the extinguishant
cabinet.

Functional testing shall be carried out to prove:

• Weight monitoring operation.


• Discharge pressure switch signal operation.
• Actuator circuit operation.

1.2.1 Weight Monitoring Circuits

There are two weight-monitoring circuits (Initial/Reserve)


Each weight-monitoring unit should be tested to prove a signal is received at the
Control/Monitoring System. The weight monitoring mechanism (See Figure 6) should be
manually lowered to its operated position, note that a signal is received at the
Control/Monitoring System. Return the mechanism to its monitoring position and repeat on
all other cylinders.

1.2.2 Discharge Pressure Switches (Initial/Reserve)


The pressure switches are factory set to operate at 4 bar rising. The test procedure is
therefore by simulation only. For ongoing maintenance see Chapter 3. To simulate the
switch operation, gently lift the microswitch (See Figure 7) and the switch contact will be
made. Check the Control/Monitoring System for the following conditions.

Initial Discharge Pressure Switch

a. System discharge LED on


b. Alarm LED on

Reserve discharge pressure switch

a. System reserve LED on


b. Alarm LED on
Figure 7
1.2.3 Actuator Circuit Test

Note: The solenoid operation is confirmed during system discharge test (if required) or
enclosure integrity test.
This test will entail operating both initial and reserve actuator circuits simultaneously. The
logic of the actuator circuits and time delay should have already been proven in the
Control/Monitoring System commissioning.
Note: To carry out this test all discharge hoses (Initial/Reserve) shall be removed from
their cylinder valves and anti-recoil caps fitted.

1.2.3.1 Test Procedure (Refer to Figure 8)


a) Ensure that the safety pins are installed in all cylinder valves and mechanical release
lever is fitted to the solenoid operated cylinder valve assembly.
b) Disconnect discharge hose from the cylinder valve of each cylinder on the cylinder bank
to be tested.
c) Fit a new or unused hexagonal valve anti-recoil cap to each cylinder valve outlet and
tighten the cap securely (torque setting 20 to 50 Nm).
Note: a hexagonal valve outlet cap is supplied with each CO2 cylinder assembly.
d) Check the solenoid pilot hose connections are tightened down.
e) Check pilot vent valve is installed on each valve assembly.
f) Fit the actuator solenoid (Initial/Reserve) and secure with locking nut.
g) Simulate a fire condition by using manual release test key. This will cause operation of
the pilot operating circuits initial solenoid after 30 seconds and reserve solenoid after a
further 5 seconds.
h) Reset the Control/Monitoring System, 60 seconds after simulating fire condition.
i) At the carbon dioxide skid, check each solenoid cylinder valve has operated. The pistons
on each valve should be seen to protrude approximately 25mm. The safety lock off pins
will inhibit final stage of valve opening.
j) Remove the actuator solenoid (Initial/Reserve) by removing the locking nut and sliding
actuator off the solenoid assembly pin.
k) Depress the bleed button on the pilot vent to relieve carbon dioxide pressure in the pilot
circuit.
l) Using the mechanical release lever, reset the CO2 cylinder valves to the set (armed)
position.
m) Carefully unscrew the anti-recoil cap from the CO2 cylinder valve outlet. There should
be no pressure behind the caps.
n) Reconnect the discharge hose to the CO2 cylinder valves.
o) Fit the actuator solenoid (Initial/Reserve) and secure with locking nut.
p) When all the discharge hoses have been reconnected to all CO2 cylinder valves, remove
the safety pin from each CO2 cylinder valve. Warning: With the safety pins removed
the CO2 cylinders are armed.

WARNING: Checking the operation of the CO2 cylinder valve & solenoid assemblies
should only be carried out by a suitable qualified engineer.
Figure 8

Note: The solenoid-operated valve is intentionally left installed at all times. Removal of the
solenoid valve may cause damage or loss of the ‘O’ ring seal. For removal instructions
refer to Appendix ‘A’ Cylinder Removal.
1.2.3.2 Resetting Procedure
Note: The solenoid actuator is a non-latching device, resetting the Control/Monitoring
System will reset the solenoid actuation.

• Ensure the Control/Monitoring System is reset.

• Remove the actuator solenoid-locking nut and detach the solenoid from the solenoid-
operated valve. This will close off the pilot supply.

• Depress the bleed button on the pilot vent to relieve carbon dioxide pressure in the pilot
circuit.

• Using the mechanical release lever, reset the CO2 cylinder valves to the set (armed)
position.

• Carefully unscrew the anti-recoil cap from the CO2 cylinder valve outlet. There should
be no pressure behind the cap.

• Reconnect the discharge hose to the CO2 cylinder valves.

Section 1.3 - Arming the System

All parties should be made aware and access to the protected area should be restricted.

Refitting the actuator solenoid.

Fit the actuator solenoid after firstly ensuring that the Control/Monitoring System is fully
reset.

Each skid assembly is fitted with two pilot circuits to operate initial/reserve cylinders.

Check that the weight monitoring device is in its monitored position (See Figure 6).

Remove safety lock off pins (See Figure 9) from all the CO2 cylinder valves.

Important – with safety lock pins in place the system will not operate.

Open system isolate valves located on extinguishant pipe work to risk area.

Notify key personnel that the CO2 system is operational.


Note: Should the piston not return to it’s set position either the pilot line has not been fully
vented or the solenoid valve has not re-seated properly. Manually vent the line using pilot vent
and refer back to resetting instruction 1.2.3.2

Figure 9

Note: Each cylinder valve is fitted with a pilot vent.


Section 1.4 – Commissioning Check List

Preliminary Connections Refer to Section Tick List

Preconditions:-
Turbine Shutdown 1.1

Control/Monitoring System Commissioned 1.1

Field Devices Commissioned 1.1

Actuator Circuits Disconnected 1.1

Pipework installation and testing completed 1.1

Isolate ball valve closed 1.1

Equipment set up:


Cylinder straps removed 1.1.2.1

Locating Carbon Dioxide cylinders 1.1.2.2

Fit discharge hose to valve. Check discharge hose manifold 1.1.2.3


connection
Set the weighing device 1.1.2.4

Functional testing:
Check weight monitoring signals to Control/Monitoring System 1.2.1

Check pressure switch signals 1.2.2

Check actuator circuit and pilot circuit 1.2.3

Resetting on completion of commission 1.2.3.2

Arming system: -
Fit actuator solenoids 1.3

Ensure all safety pins are removed from each cylinder valve 1.3
CHAPTER 2

OPERATION
Section 2.0 - Introduction

2.0.1 An extinguishant system is provided comprising of the following equipment:


• An extinguishant skid complete with bottles, weight monitoring, valves and
actuation/monitoring electrical equipment.
• Piping with isolation valve and position switches.
• Discharge nozzles (positioned within the acoustic enclosure).

2.0.2 The extinguishant equipment is for emergency use. Its correct operation requires the
apparatus to be in perfect working condition at all times. Regular routine
maintenance should be carried out to ensure the system remains functional at all
times.

2.0.3 All extinguishant hardware is skid mounted to suit the client’s requirements. Each
electrical device located within the extinguishant assembly is fully monitored on
input/output circuits via the fire and gas control and monitoring system.

2.0.4 The extinguishant agent used for this application is Carbon Dioxide.
At atmospheric pressure carbon dioxide is a colourless, odourless and an electrically
non-conducting inert gas, which is almost 1.5 times as dense as air. It is stored as a
liquid under pressure, and 1Kg of liquid carbon dioxide expanded to atmospheric
pressure will produce approximately 0.52m³ of free gas at a temperature of 10°C.

2.0.5 Carbon dioxide extinguishes fire by reducing the oxygen content of the atmosphere
to a point where it will not support combustion. Reducing the oxygen content from
the normal 21% in air to 15% will extinguish most surface fires. In some
applications the cooling effect of carbon dioxide may also assist extinction.
Typically for turbine application the oxygen levels will be reduced to below 12%.

2.0.6 Carbon dioxide provides its own pressure for discharging through valves, pipework
and nozzles, penetrating into otherwise inaccessible locations.
Section 2.1 – The System

2.1.1 System Detail

Extinguishant Agent : Carbon Dioxide


Type of System : Total Flooding
Actuation Method at the Skid : a) Electrical Solenoid Actuator
b) Cylinder Manual Lever Actuator.
c) Also refer to electrical operating
instructions covering the field devices
and control system.

System Operating Pressure : 51 Bar g at 20 deg. C


Risk : Lube Oil/Natural Gas and or Liquid Fuel.
Extinguishant Quantity : 45 Kg capacity per cylinder.
2 Initial cylinders + 2 Reserve cylinders

2.1.2 General System Description

The extinguishant skid assembly houses extinguishant equipment in accordance with


the contract requirements.

Each cylinder is connected to an overhead manifold using flexible discharge hoses,


each manifold port is fitted with a check valve. The check valve is installed to allow
for cylinder removal whilst maintaining operation.

The manifold incorporates further check valves (100% redundancy) to allow for
positive differentiation between initial and reserve discharge signals. Flexible pilot
loops are connected from the manifold to the relevant discharge pressure switch
(initial/reserve).

The manifold is connected to a network of discharge pipework and nozzles, with


pipe diameters and nozzle orifices sized to achieve the required rates of application.
Connections are provided off the carbon dioxide pipework to operate dampers.

An isolation ball valve is installed within the discharge pipework outside the
protected area at an accessible level. This device allows the carbon dioxide supply to
be manually isolated. The ball valve is supplied with limit switches to provide
electrical confirmation of operation (open and closed) back to the turbine
Control/Monitoring System.
2.1.3. Type of System (Total Flood)

The system is designed to achieve an extinguishing concentration of 37% carbon


dioxide within one minute and maintain a minimum 50% concentration for 20
minutes to allow cool down of surface temperatures and avoid re-ignition.

2.1.4 Hazards to Personnel

The reduction of oxygen content in the air, caused by a carbon dioxide concentration
sufficient to extinguish fire, will create atmospheres that will not sustain life.

Carbon dioxide is normally colourless but when discharged from a storage cylinder
under pressure it resembles a cloud of steam. Large volume discharges of carbon
dioxide may seriously interfere with visibility during and immediately after the
discharge period.

The rapid release of a large quantity of carbon dioxide results in a substantial


localised cooling of the discharge pipework and the area surrounding the point of
discharge. This can present a frostburn hazard. During the process of carbon dioxide
being released, frosting of the discharge pipework and cylinders will occur.
Personnel must not touch the pipework and cylinders, hazard notices are provided to
warn of this danger.

The removal of cylinders should be carried out using suitable lifting and transport
equipment.

When working on a cylinder the weight monitoring counter balance weight should be
temporarily tied in position, a falling weight will cause injury.
2.1.5 Safety Summary

The discharge of large amounts of carbon dioxide used to fight fires may cause
hazards to personnel as described in section 2.1.4 above.

Exposure to atmospheres containing about 5% carbon dioxide leads to shortness of


breath and causes slight headaches. At 10% headaches, visual disturbance, ringing in
the ears (tinnitus) and tremors are caused, followed by the loss of consciousness.

The fire extinguishing concentration of carbon dioxide in the turbine enclosure is in


excess of 30% and carries the risk of almost immediate asphyxiation.

The gas is also denser than air and will drift and accumulate in low spaces.
Thorough ventilation of discharged carbon dioxide should be carried out and the area
declared safe prior to re-entry. Consideration should also be given as to where the
carbon dioxide would be vented to and if this would result in accumulation in other
areas.

Since the turbine enclosure area is not normally occupied, the carbon dioxide system
may be left on fully automatic control i.e. release of the carbon dioxide system is
initiated by automatic fire detection equipment.

The system may be set to manual-only operation, by using a keyswitch located at the
Control/Monitoring System if required.

Prior to entry into an enclosure where carbon dioxide has been present the ventilation
system should be run for 5 minutes and it is recommended a portable carbon dioxide
‘sniffer’ should be used.

Entry to the turbine enclosure/protected area should only be permitted after closing
the carbon dioxide supply isolate ball valve located on the discharge pipework that is
adjacent to the extinguishing system skid and putting the discharge system into
manual via the control system. Switch contacts on the ball valve are used to provide
a signal to the turbine Control/Monitoring System.

Enclosure door warning notices are positioned on the turbine enclosure to warn of
the dangers of entering the enclosure with the carbon dioxide system active.
Section 2.2– System Operation

2.2.1 Automatic (Electrical) Operation

The fire detection Control/Monitoring System provides a 24V signal to the solenoid
actuator assembly. Operation of the solenoid causes a pilot valve to open and the
master cylinder pressure is allowed to enter the pilot circuit. Operation of the
cylinder actuator(s) causes the cylinder discharge valve(s) to open and the carbon
dioxide is discharged into the system via the flexible discharge hose. The pilot circuit
consists of small bore interconnecting pilot loops connecting each cylinder valve
actuator to achieve simultaneous discharge. Each cylinder valve is fitted with a pilot
vent that is normally open to allow for possible fluctuations in pressure and safeguard
against unwanted discharge. On operation of the pilot valve the pilot vent will close
in order to maintain pilot operating pressure for the discharge duration. (See figure
10)

Figure 10 – Solenoid Actuator Assembly


2.2.2 Emergency Manual Operation.

System operation via manual lever actuator.

This mechanical release facility is only intended for use in the event of automatic or
electrical manual release failure.

Note: Operation of the individual cylinder actuators are available at all times
and is not inhibited by auto inhibit.

Manual release of carbon dioxide is achieved by operation of the lever actuator,


fitted to the pneumatic actuator, actuator through its complete 90 degrees movement
causes the firing piston to release the cylinder valve-actuating pin. This action would
result in releasing the extinguishant agent from the cylinder. (See Figure 10a)

Figure 10a
2.2.3 Extinguishant Discharge Manifold and Pipework.

As previously described the manifold consists of three sections of pipe with the use
of check valves i.e. initial/reserve manifolds feeding into a common manifold.

Flexible hoses are provided to allow free movement of cylinders for the weight
monitoring system and to facilitate ease of disconnection.

Flexible hoses are connected to check valves. The check valves allow removal of a
cylinder whilst retaining protection.
(See Figure 11)

Figure 11– Discharge/Pilot Hoses and Check Valve Arrangements


A directional check valve is fitted between the initial and reserve cylinder
manifolds. This additional check valve is fitted to provide protection against
unwanted operation of the reserve ‘Gas Released’ pressure switch from the initial
system discharge.
(See Figure 12)

Figure 12 – Gas Released Pressure Switches

2.2.4 Manifold Burst Disc Assembly

Should the system be discharged with the risk isolation ball valve closed then the
manifold and flexible discharge hoses would be pressurised to full system pressure.
As a safety measure the manifold is fitted with a burst disc assembly so that if the
pressure in the manifold should rise above 190 bar (as a result of high temperature)
the disc would rupture and allow a controlled release of the carbon dioxide within the
cabinet.

Figure 13– Manifold Burst Disc Assembly


2.2.5 Cylinder Weight Monitoring Equipment

The weight monitoring mechanism is a device used to automatically monitor the


weight of a fixed fire extinguishant cylinder. The system operates by suspending the
cylinder approximately 10mm above the skid base and uses a counterbalance weight
system. When correctly adjusted the counterbalance weight is held up by the weight
of the extinguishant cylinder. If the cylinder weight falls by a pre-determined
amount, typically 10%, the counterbalance weight drops, operating a micro-switch
and sends a warning signal to the monitoring control system.

Each cylinder weight monitoring assembly is pre-set during assembly of the


extinguishing skid.

If cylinders are removed and replaced, it is essential that the weight monitoring
system is adjusted in accordance with maintenance procedures to accommodate the
new cylinders

Figure 14 – Weight Monitoring Assembly


Section 2.3 – Protection Equipment Schedule

Description Part No.

45Kg CO2 Extinguishant Cylinder c/w SL94002ex


Solenoid Actuating Valve
45Kg CO2 Extinguishant Standard SL93532
Cylinder
Direct Actuating Solenoid Assembly
SL94003ex
Weight Monitoring Assembly
50-20-007
Flexible Discharge Hose C02012

Pilot Loop – Long C02013/650

Manual Pilot Vent Bleed SL93866

Manual Pilot Vent Bleed Adaptor SL93521

Safety Manual Burst Disc SL93864

Gas Gone Pressure Switch


HS24OGEA02F
(Set at 4 bar rising)

Discharge Manifold Purpose built


Section 2.4 – Resetting devices

Note:
ENSURE THE EXTINGUISHANT SYSTEM DISCHARGE SEQUENCE IS
FULLY COMPLETED PRIOR TO ANY MAINTENANCE OR
DISASSEMBLY OF ANY SYSTEM COMPONENTS, THIS INCLUDES
REFILLING OF CYLINDERS.

2.4.1 Silence and reset the fire detection system Control/Monitoring System.

2.4.2 To reset the solenoid actuator refer to clause 1.2.3.2

Section 2.5 - Device Operation Table

Device Function

1. Slave Extinguishant Cylinder Vessel designed to store extinguishant under


pressure which can be pressure/manually
operated when fitted with item 4
2. Master Extinguishant Cylinder As above, but including electrical operation
facility when fitted with items 3 & 4. Also
providing pilot pressure for simultaneous
operation of slave cylinder(s)
3. Solenoid Actuator Control/Monitoring System electrical interface
to cause discharge.
4. Lever Actuator Manual and pneumatically operated device to
release extinguishant from individual cylinders
and provide pilot line interconnection points.

5. Flexible Discharge Hose Convey carbon dioxide to the discharge


manifold and facilitate weighing and removal of
cylinders.

6. Gas Discharge Pressure Switch Confirm carbon dioxide discharge.

7. Pilot Line (Loops) Convey pilot operating pressure.

8. Manual Pilot Vent Bleed Provides facility to manually vent pilot lines
after discharge and compensate for pressure
fluctuations in the pilot circuit.
Device Function

9. Extinguishant Cylinder Weight Each cylinder is suspended approx. 20mm above


Monitoring the enclosure floor. A counter weight is set to
drop and operate an infra-red light switch,
should the cylinder lose approx. 10% in content
weight.

Cylinder low content is monitored at the


Control/Monitoring System.

10. Manual Isolation Valve Device allows discharge pipework to be isolated


to ensure extinguishant cannot enter the risk
during times of maintenance etc.

11. Safety Burst Disc Safety rupture disc is located within the
manifold before the isolation valve.

Should the isolation valve be closed and a


system discharge occurs. The rupture disc will
burst when the pressure within the closed section
of pipework increases to an unsafe level
(dependent on temp.) venting extinguishant to
atmosphere.
CHAPTER 3

MAINTENANCE
Section 3.0 - Maintenance
3.0.1 This part of the manual describes procedures that will enable a proficient Service
Engineer to undertake the regular inspection and testing of fire protection equipment
safely.
3.0.2 Prior to attending site, the Service Engineer should obtain the relevant details and
drawings of the systems to be serviced, and refer to reports of previous service visits
and fault “call outs” since the last service.
3.0.3 The Engineer’s signature on the service report and record card on completion of
work is confirmation that the system, on that day, was in complete operational order.
3.0.4 On arrival at site, the service engineer should report to the customer’s representative
to determine if there are any specific instructions with which to comply.
3.0.5 Obtain permit to work from the customer if necessary.
3.0.6 Ask if any particular problems have arisen since the last service visit.
3.0.7 Ask if any fires have occurred and how the system performed.
3.0.8 All fires, faults or accidental operation of systems should be recorded with reasons.
3.0.9 If it is necessary to take further action, which may cause inconvenience to the
customer, ask his permission first.
3.0.10 Notify all concerned that the fire protection system is being maintained and may be
inoperative.
3.0.11 Work systematically in a clean, tidy and professional manner.
3.0.12 Consider the possibility of a genuine fire alarm occurring while you are working on
the system and make appropriate arrangements.
3.0.13 Prepare a service report, submitting a copy to the Client, the Customer Service
Manager and retain a copy. (See checklist Appendix D)
3.0.14 Where faulty parts are removed and the fault requires further investigation,
arrangements should be made to return the parts to the supplier.

Section 3.1 - Pre-conditions

• Maintenance should be carried out during planned shutdown periods.

• The carbon dioxide isolate valve should be closed to protect against accidental
operation.

• Inhibit F & G system.


Section 3.2 - Additional reference notes relating to maintenance activities

3.2.1 To obtain the overall weight of the carbon dioxide cylinder assembly, the counter
balance weight position can be measured to obtain a reasonably accurate assembly
weight.

The object of the exercise is to identify any cylinder showing a loss of 10% nett
contents. (i.e. cylinder fill 45kg therefore 4.5 kg loss) Any cylinder showing this loss
should be removed and refilled.

Proceed as follows: -

• Read the tare weight stamped on the cylinder


• Take dimension ‘A’
• Refer to chart below

Figure 15

Cylinder Tare Weight (kg) Dimensions A (mm)

70 245.9
71 247.7
72 249.5
73 251.3
74 253.1
75 254.9
76 256.7
77 258.5
78 260.3

Note: 1 Kg weight difference = 1.8mm movement


3.2.2 Gas Gone Pressure Switch

The pressure setting shall be tested using a suitable pressure source, regulator and
calibrated gauge. The switch set point is set at 4 bar rising, the pressure switch has a
¼” N.P.T. female process connection,

Also inspect all terminals for tightness and that cables are in good condition. Check
for internal condensation and rectify is necessary.

Figure 16

To adjust the set point, slacken off the set point lock screw and rotate the set point
adjuster to suit. (Clockwise to increase, counter clockwise to decrease)
Lock the set point lock
Re-check the set point is 4 bar rising
3.2.3 Carbon Dioxide Cylinder(s)

An inspection of the carbon dioxide cylinder(s) should be carried out annually.


Deterioration of cylinder paintwork should be repaired.

A full inspection and test for all cylinders should be carried out after a 10 year period
from the date stamped on the cylinder. This should include re-hydro testing and
should be carried out by a competent Organisation.

A full external inspection should be carried out by a competent engineer to check for
mechanical damage, excessive corrosion and loss of gross mass with all results
recorded appropriately.

Any cylinder showing signs of mechanical damage, excessive corrosion or loss of


gross mass exceeding 3% shall be withdrawn from service and submitted to a full
periodic inspection and test.

3.2.4 Enclosure Integrity Test


An enclosure integrity test shall be carried out yearly to establish if any sealing work
is required.
The efficiency of the fire fighting system depends on achieving and maintaining
concentrations to a required level. Therefore, leakage above the original design
criteria will affect the performance of the fire protection.
Section 3.3 - Maintenance Schedule
Activity 6 Months Visual Yearly 5 Year
Inspection by Maintenance Maintenance
Operator Schedule and at Schedule
Commissioning
Close isolate ball valve in feed pipe and
verify a signal is received at the T.C.M. √ √
Check all manual controls are accessible
√ √
Check all warning/instruction labels are
in place and clearly visible √ √
Check discharge nozzles are unobstructed
and adequately secured √ √
Check the system pipework is adequately
bracketed, inspect pipework for signs of √ √
corrosion
Check pilot circuit, pilot loop and vents
are secure √ √
Check weight-monitoring circuits (See
1.2.1.) √
Check discharge pressure switches
operation (See 1.2.2) √
Check actuator circuits operation (See
1.2.3.) √
Check cylinder weights (See 3.2.1)

Check discharge pressure switch setting
point (See 3.2.2). √
Check condition of Carbon Dioxide
cylinder (See 3.2.3) √
Enclosure integrity testing (See 3.2.4) √

All flexible hoses including pilot loops


shall be visually inspected for damage √
and if necessary replaced.
All flexible hoses including pilot loops √
shall be pressure tested to 190 bar and
tagged
APPENDIX A

CARBON DIOXIDE
CYLINDER REMOVAL AND FILLING
INSTRUCTION
Cylinder Removal Instruction

Note: If cylinders are being removed after a discharge ensure resetting is


complete. (See Section 2.4)

a) Where applicable. Remove lever actuators from cylinder valves.

b) Where applicable. Remove the actuator solenoid and retain locking nut in a safe
place for re-installation.

c) Where applicable. Remove the solenoid valve assembly (See Figure 8).

Removal of solenoid-operated valve may result in damage to the ‘O’ ring seal. Carefully
check the seal before reusing.

Slowly unscrew the solenoid operated valve assembly, a short discharge of gas may be
audible.

Fully remove the actuator assembly. (Retaining the ‘O’ ring seal.)

To protect the valve sealing face immediately assemble the protection cap to the
valve.

d) Disconnect the discharge hose at the valve outlet position (See Figure 9) do not
disconnect the discharge hose from the manifold. Retain any sealing washers and
store in a safe place for re-installation.

e) Before attempting to move the cylinder, install the anti recoil cap on the
discharge valve outlet (See Figure 9).

f) Lower cylinder to cabinet floor using the M12 nut on the top of the weigh beam (See
Figure 14).

g) Disconnect the hanger rods from the neck collar and remove the neck collar (See
Figure 14) retain all parts for re-installation.

h) Fit the cylinder transport protection cap. (See Figure 1)

i) Remove the cylinder(s) from the cabinets if necessary lay the cylinders on the floor
ready for transport (See Appendix E).
Cylinder Filling Instructions

To replace a discharged cylinder bank, the following action should be taken:

• Notify key personnel that work is being carried out

• Ensure the manual isolation valve is closed and the pilot circuit has been
vented via the vent valves located on the carbon dioxide cylinder valve

• Where applicable disconnect the flexible pilot loops

• Disconnect flexible hoses from the cylinder valves, taking care to retain the
sealing washers

• Where applicable remove the pilot solenoid and solenoid hose

• Fit transport caps, valve outlet caps and lock off pins onto cylinders to be
recharged

• Remove cylinders from weight monitoring cylinder hangers and remove from
frame

• Where applicable remove pilot cylinder assembly and disconnect from


actuators

• The cylinders will need to be re-connected when recharged

Refer to Section 3 for instructions on re-connecting the cylinders


APPENDIX B

CYLINDER WEIGHING DEVICE


SETTING INSTRUCTIONS
Tyco Fire Limited Document 2072-046
Hillcrest Business Park Date 02.07.99
Rev O
Cinderbank, Dudley, West Midlands DY2 9AP Page 1 of 2
Tel 01384 458993 Fax 01384 458981

CARBON DIOXIDE WEIGHT MONITORING DEVICE


1.1 General

The Weight Indicator Mechanism (Part No. E8731-402) is a device used to automatically
monitor the contents of fixed fire carbon dioxide cylinder. When the contents of the
cylinder fall by a predetermined amount, typically 10%, the weight drops.

The components of the weight indicator mechanism are shown below. The device is
supplied in a kit form, for assembly onto the mounting frame, and comprises: the body, two
hanger rods, neck collar, weight, four off M10 nuts and washers, and one off M12 nut and
washer.

1.2 Operation

When the weight indicator mechanism is set up, the downward force of the cylinder is
greater than the leverage provided by the weight on the weight rod.

As the contents of the cylinder drops through a pre-determined amount, the downward force
of the cylinder becomes less than the leverage of the weight, therefore the weight rod drops.

All screws and steel fittings are zinc plated.


Tyco Fire Limited Document 2072-46
Hillcrest Business Park Date 02.07.99
Rev O
Cinderbank, Dudley, West Midlands DY2 9AP Page 2 of 2
Tel 01384 458993 Fax 01384 458981

Setting Instruction

1. Position the weight on the hanger rod so that the carbon dioxide cylinder weight holds the
weight in its upper position, i.e. moving the weight slightly away from the cylinder will
cause the weight will fall.

2. On achieving the balance position the nut located between the weight and the cylinder
should be turned five full rotations.

3. Accordingly the weight should be rotated back to the cylinder by five rotations.

4. The front securing nut should be tightened down onto the weight. This position will monitor
for a 10% loss in liquid contents.
APPENDIX C

COSHH SHEETS
APPENDIX D

CHECKLIST FORMS
Commissioning Check List

Preliminary Connections Refer to Section Tick List

Preconditions:-
Turbine Shutdown 1.1

Control/Monitoring System Commissioned 1.1

Field Devices Commissioned 1.1

Actuator Circuits Disconnected 1.1

Pipework installation and testing completed 1.1

Isolate ball valve closed 1.1

Equipment set up:


Cylinder straps removed 1.1.2.1

Locating Carbon Dioxide cylinders 1.1.2.2

Fit discharge hose to valve. Check discharge hose manifold 1.1.2.3


connection
Set the weighing device 1.1.2.4

Functional testing:
Check weight monitoring signals to Control/Monitoring System 1.2.1

Check pressure switch signals 1.2.2

Check actuator circuit and pilot circuit 1.2.3

Resetting on completion of commission 1.2.3.2

Arming system: -
Fit actuator solenoids 1.3

Ensure all safety pins are removed from each cylinder valve 1.3

DATE SIGNATURE
Maintenance Schedule
Activity 6 Months Visual Yearly 3 Year
Inspection by Maintenance Maintenance
Operator Schedule and at Schedule
Commissioning
Close isolate ball valve in feed pipe and
verify a signal is received at the T.C.M.
Check all manual controls are accessible

Check all warning/instruction labels are


in place and clearly visible
Check discharge nozzles are unobstructed
and adequately secured
Check the system pipework is adequately
bracketed, inspect pipework for signs of
corrosion
Check pilot circuit, pilot loop and vents
are secure
Check weight-monitoring circuits (See
1.2.1.)
Check discharge pressure switches
operation (See 1.2.2)
Check actuator circuits operation (See
1.2.3.)
Check cylinder weights (See 3.2.1)

Check discharge pressure switch setting


point (See 3.2.2).
Check condition of Carbon Dioxide
cylinder (See 3.2.3)
Enclosure integrity testing (See 3.2.4)

All flexible hoses including pilot loops


shall be visually inspected for damage
and if necessary replaced.
All flexible hoses including pilot loops
shall be pressure tested to 190 bar and
tagged

DATE SIGNATURE
APPENDIX E
CYLINDER HANDLING
APPENDIX F

RECOMMENDED SPARE PARTS


LIST
QTY DESCRIPTION PART NO MANUFACTURER

1 45Kg CO2 Extinguishant


Cylinder c/w Solenoid SL94002ex TYCO
Actuating Valve

1 45Kg CO2 Extinguishant Standard


Cylinder SL93532 TYCO

1 Direct Actuating Solenoid Assembly


SL94003ex TYCO

1 Weight Monitoring Assembly


50-20-007 TYCO
4 Flexible Discharge Hose
C02012 TYCO
4 Pilot Loop – Long
C02013/650 TYCO
2 Manual Pilot Vent Bleed
SL93866 TYCO
2 Manual Pilot Vent Bleed Adaptor
SL93521 TYCO
1 Safety Manual Burst Disc
SL93864 TYCO
1 Gas Gone Pressure Switch
(Set at 4 bar rising) HS24OGEA03F DELTA
APPENDIX G

EQUIPMENT DATA SHEETS


APPENDX G EQUIPMENT DATA SHEETS - CONTENTS:

01. SL9003ex SOLENOID ASSEMBLY.

02. SL95005 45Kg CO2 CYLINDER.

03. C02012 DISCHARGE HOSE.

04. C02013/650 PILOT HOSE.

05. C02015 CHECK VALVE c/w PILOT OUTLET.

06. SL96866 BLEED/VENT VALVE.

07. SL93864 SAFETY OUTLET BURST DISC.

08. 50-20-007 WEIGHT MONITORING UNIT G.A.

09. HS240GEA02F PRESSURE SWITCH.

10. ISOLATION BALL VALVE c/w SWITCH BOX


1. SL9003ex SOLENOID ASSEMBLY.
Baureihe 52 - Type 52
2/2 - Wege Magnetventil
2/2 - way solenoid valve

Standardtype
Ventil in Ruhestellung durch Federkraft geschlossen-(NC).
Der erregte Magnet zieht den Magnetanker entgegen der
Kraftwirkung der Feder an den Gegenkern. Das Ventil öffnet.
Ventile dieser Bauart benötigen keinen Differenzdruck. Beachten
Sie bitte, daß der max. angegebene Betriebsdruck nicht
überschritten wird.

Standard type
Valve non-energised closed by spring power - NC. When
energised, the solenoid lifts the seal of the seat (orifice) directly. A
pressure differential (Dp) is not required for the operation.

Steuerungsart: direktgesteuert metall. Innenteile: Messing und Edelstahl 1.4104


type of control: direct acting metallic internals: brass and stainless steel (AISI 430F)

Konstruktion: Sitzventil mit Nippeldichtung Dichtung: FKM


construction: piston design seal: FKM

Anschluß: G1/8-G1/2, DIN ISO 228 Einbaulage: beliebig


connection: G1/8-G1/2, DIN ISO 228 installation: actuator in any position

Druck: 0-350 bar (s. Tabelle) Anschlußspannung: AC: 24,42,110,230V 50 bzw. 60 Hz


pressure: 0-350 bar ( see table) supply voltage: DC: 24, 110 V=

Durchflußmedium: neutrale, gasförmige u. flüssige Medien Spannungstoleranz: +5% / -10%


medium: neutral, gaseous and liquid medium voltage tolerance: +5% / -10%

Viskosität: 22mm²/s Leistungsaufnahme: 1182=6,8 Watt 0182=14,5/10,5 VA


viscosity: 22mm²/s power-consumption: 1032=11 Watt 0032=24/15 VA
1012=18,5 Watt 0012=43/24 VA
1147=10 Watt 0147=9 VA
Mediumtemperatur: -10 bis +80°C 1322/3322= 30 Watt
medium temperature: -10 up to +80°C 5327=23 Watt

Umgebungstemperatur: +35°C Schutzart: IP65 nach DIN 43650


ambient temperature: +35°C enclosure: IP65 according to DIN 43650

Ventilgehäuse: ../10../.. = Messing / brass Einschaltdauer: 100% ED-VDE 0580


body material: ../06../.. = Edelstahl 1.4305 / st. steel (AISI 303) operating factor: 100% ED-VDE 0580

Kabelanschluß: Gerätestecker DIN 43650


electric connection: DIN 43650 - plug

Sitz Kv-Wert Standardtype max. Druck bei Magnettype


G orifice flow-rate standard type max. pressure regarding solenoid type
Æmm m³/h EEX mII T4 EEXemII T4
.182 .032 .012 .012-NO .692-NO .147 .322 .327
1/8 1,0 0,06 A5230/..02/.... 0-50 0-90(150) 0-90(150) 0-90 0-90 0-90 0-350 0-280
1/8 1,5 0,09 A5231/..02/.... 0-30 0-85 0-90(120) 0-40 0-80 0-90 0-330 0-120
1/8 2,0 0,13 A5232/..02/.... 0-15 0-40 0-90 0-22 0-40 0-55 0-180 0-90
1/8 2,5 0,16 A5233/..02/.... 0-8 0-22 0-45 0-14 0-28 0-28 0-110 0-60
1/8 3,0 0,20 A5234/..02/.... - 0-15 0-30 0-10 0-20 0-20 0-80 0-40
1/8 4,0 0,35 A5235/..02/.... - 0-8 0-16 - 0-12 0-10 0-40 0-25
1/8 5,0 0,50 A5236/..02/.... - 0-5 0-10 - 0-6 0-6 0-28 0-12
1/8 6,0 0,75 A5237/..02/.... - 0-4 0-8 - 0-4 0-5 0-20 0-10

1/4 DN 1,0 - DN 6,0 A5240/.. - A5247/.. technische Daten wie oben


3/8 DN 1,0 - DN 6,0 A5250/.. - A5257/.. technical informations see above
1/2 DN 1,0 - DN 6,0 A5260/.. - A5267/..

Druckwerte in Klammern nur bei Dichtwerkstoff PTFE möglich! / Pressure nominal only with PTFE sealing available!

Stand: 01/2001
DB-52-GSR-MK-ML Irrtum und Änderungen vorbehalten
Maßzeichnung Standardausfürung Schaltfunktion/function:
A
dimensional drawing of standard type in Ruhestellung gesperrt - NC.
normally closed - NC.
T
P
D

A Schaltfunktion/function:
in Ruhestellung geöffnet - NO.

A
normally open - NO.
P

Anschlußplan / connection diagramm

Für Wechsel- und


Gleichspannung.
AC,DC For AC and DC.

Erdung oder Schutzschaltung nach Vorschrift des zuständigen EVU.


Grounding or earthing of the protective circuit in accor-dance with
regulations of the responsible electric supply company.
Absicherung entsprechend der Stromaufnahme vorsehen.
Appropiate protection according to the power-consumption.

Magnet
solenoid .182 .032/ .012/ .147/ .012-NO .692-NO .322/.327
Type A523. A524. A523. A524. A525. A526. A523. A524. A525. A526. A523.-5. A526.
G 1/8 1/4 1/8 1/4 3/8 1/2 1/8 1/4 3/8 1/2
A 15 20 25 25 30 30 25 25 30 30
B 30x30 30x30 35x32 35x32 35x32 35x32 35x35 35x35 35x35 35x35
C 53 53 58 58 58 58 66 66 66 66
D - M5 M6 M6 M6 M6 M6 M6 M6 M6
H 55 60 80 80 85 90 95 95 100 105
K 47,5 52,5 67,5 67,5 70 70 82,5 82,5 85 90
L 32 40 40 40 50 60 40 40 50 60
M 30 30 40 40 40 40 50 50 50 50
N 5 5 10 10 10 10 10 10 10 10
T - - 15,5 15,5 15,5 15,5 15,5 15,5 15,5 15,5
U - 11 15,5 15,5 15,5 15,5 15,5 15,5 15,5 15,5
Pg 11 11 11 11 11 11 11 11 11 11
kg 0,3 0,35 0,55 0,6 0,65 0,75 0,8 0,9 1,0 1,2

Alle Angaben sind freibleibend und unverbindlich / all technical specifications are without obligation!

Weitere Ventilausführungen / optional extras

stromlos geöffnet= NO Handbetätigung= HA


non energised open= NO manual override= HA

Dichtung= EPDM, PTFE Öl- und fettfrei= OF


seal= EPDM, PTFE free of oil and grease= OF (for oxygen applications)

andere Durchflußmedien und Viskositäten buntmetallfrei= BF


varying medium and viscosity ranges free of brass and bronze= BF

abweichende Temperaturen und Drücke P-Sammelleisten


varying temperature and pressure ranges maniflold system

Ventilgehäuse= Rotguß Ex-Schutz= EEx mII T4, EEx dII cT6


body material= bronze explosion proof= EEx mII T4, EEx dII cT6
Stückliste - parts list Baureihe / type 52-NC

K1.1 Armatur / valve body 7.1


K5.1 Magnethülse, komplett / solenoid sleeve
K5.4 6-kt. Mutter / hexagon nut
K5.5 Scheibe / disk 5.4
K6.1 Magnet / solenoid
K7.1 Stecker / plug
5.5

6.1

5.1

1.1

Stückliste - parts list Baureihe / type 52-NO

K1.1 Armatur / valve body


5.8
K3.1 Verschraubung / screw joint
*K3.2 Spindel / stem
*K3.3 Dichtung / seal 5.7
*K3.4 O-Ring / o-ring
K3.5 6-kt. Mutter / hexagon nut 5.6
K5.0 Magnethülse / solenoid sleeve
K5.4 Scheibe / disk 3.5
K5.6 Druckstück / pressure part
K5.7 Scheibe / disk 5.4
K5.8 6-kt. Mutter / hexagon nut
K6.1 Magnet / solenoid
K7.1 Stecker / plug
7.1
3.2
6.1
3.1
5.0
3.3
3.4
1.1

Stückliste - parts list Baureihe / type 52-NO


Koaxialventil / coax valve Koax / coax

K1.1 Armatur / valve body 7.1


K3.2 O-Ring / o-ring
K3.1 Kopfmuffe / connection part
K5.1 Magnethülse, komplett / solenoid sleeve 3.1
K5.5 Scheibe / disk
K5.10 Ankerfeder / plunger sping
K6.1 Magnet / solenoid 5.5
K7.1 Stecker / plug

6.1
*= Bestandteil des Ersatzteilpäckchens
(je nach Ausführung freibleibend)
*= all components of spare parts and service 3.2
sets are variable in reference to different
versions and executions. (These specifications
are without obligation). 5.1

5.10

1.1
Ventiloptionen / optional extras

Handbetätigung-HA
manual operation-HA

K1.1 Armatur / valve body


3.65 K3.62 Spindel / stem
K3.65 O-RIng / o-ring

3.62
(Nur für Magnet .032+.012!)
(only solenoid .032+.012!)

1.1

P-Anschluß beidseitig Verteilerleisten


P-connection both ways manifold

mit Hohlschraube und Dichtung


incl. hollow bolt and seal

Baureihe Anschluß Baulänge


type connection length

2/079-2-.. 2-fach 77 mm
2/079-3-.. 3-fach 114 mm
2/079-4-.. 4-fach 151 mm
2/079-5-.. 5-fach 188 mm
2/079-6-.. 6-fach 225 mm
2/079-7-.. 7-fach 262 mm

Nur in Messing lieferbar!


only availbale in brass (brass-nickle plated)!

GSR Ventiltechnik GmbH & Co. KG


Postfach 2060 Ÿ D-32595 Vlotho Ÿ Im Meisenfeld 1 Ÿ D-32602 Vlotho
Telefon (05228) 779-0 Ÿ Telefax (05228) 779-90
E-mail: info@ventiltechnik.de Homepage: http://www.ventiltechnik.de
2. SL95005 45Kg CO2 CYLINDER.
3. C02012 DISCHARGE HOSE.
4. C02013/650 PILOT HOSE.
5. C02015 CHECK VALVE c/w PILOT OUTLET.
6. SL96866 BLEED/VENT VALVE.
7. SL93864 SAFETY OUTLET BURST DISC.
8. 50-20-007 WEIGHT MONITORING UNIT G.A.
9. HS240GEA02F PRESSURE SWITCH.
ISO 9001

FM 720

INSTRUMENTATION SOLUTIONS FOR INDUSTRY

SOVEREIGN SERIES
S21/2/4
DIAPHRAGM OPERATED
ISSUE G.1
PRESSURE SWITCHES
▲ Ranges available up to 700 bar
(10,000 psi)

▲ Maximum working pressure up to


1000 bar (15,000 psi).

▲ Epoxy coated die cast and natural


stainless steel weatherproof
enclosures NEMA 4, 4X, IP66 and
Explosionproof NEMA 4, 4X, 7,9.

▲ Safety vented design as standard.

▲ Field set point adjustment against


a reference scale.

▲ SPDT or DPDT switching and


optional gold alloy contacts. LISTED

▲ Terminal block for easy field wiring. LISTED

▲ Hermetically sealed microswitch BASEEFA


options.
CENELEC
▲ 316 stainless steel wetted parts.
✽ JAPANESE APPROVAL
▲ NACE MR-01-75 compatibility.

HOW TO ORDER
The Sovereign Series S20 Pressure
When ordering, please state the
Switches are designed as compact, cost
effective solutions to meet a variety of relevant product code for each
applications in the oil, gas and chemical instrument, made up as follows:
industries.
Enclosure. See Table l.
The sensing element consists of a
diaphragm sealed piston providing high Model. See Table 2.
integrity, sensitivity and overload
protection. Electrical Entry. See Table 3.

The Sovereign Series continues to offer Material of Wetted Parts. See Table 4.
the high standard of performance and
Range. See Table 5.
service so long the hallmark of Delta
Controls.
Switching Options. See Table 6.

Process Connection. See Table 7.

Options. See Table 8.

Special Engineering.
By consultation with our engineers. See Table 9.
ENCLOSURES TABLE 1
INTRINSIC SAFETY EXPLOSIONPROOF ENCLOSURES DIVISION 1 (ZONE 1) Code
Pressure switches neither store nor
generate electricity and are therefore Aluminium Alloy EExd IIC T6(-60 to +65ºC), T5(-60 to +80ºC)
normally usable in intrinsically safe Gravity die-cast enclosure In aluminium-silicon alloy, epoxy painted
circuits without further certification internally and externally. BASEEFA certified to CENELEC EN 50 014 H
provided that the power source of the and EN 50 018. Weatherproof to NEMA type 4, 4X, IP66. See Note.
circuit is certified Exi and the installation
is in accordance with the relevant For Aggressive Atmospheres EExd IIC T6(-60 to +65ºC)
codes of practice (e.g. ANSI/ISA 12.6 or T5(-60 to +80ºC) Investment cast enclosure In austenitic stainless steel.
BS 5345 Part 4, 1977). Because of the BASEEFA certified to CENELEC EN 50 014 and EN 50 018. R
low voltages and currents of I.S. circuits, Weatherproof to NEMA type 4X, IP66.
we recommend using gold and/or
sealed contacts. Aluminium Alloy NEC 500, NEMA 7,9
Temperatures in Table 1 refer to Gravity die-cast enclosure in aluminium-silicon alloy, epoxy painted
limitations for certified enclosures. See internally and externally. Class 1, Groups C and D, Class II, T
TECHNICAL DATA. Groups E, F and G, Div. 1&2.Weatherproof to NEMA type 4, 4X, IP66.
See Note.
NOTE: Codes T and U - to increase gas
class see Table 6. For Aggressive Atmospheres NEC 500, NEMA 7,9
NOTE: Codes H, T for 4X Investment cast enclosure in austenitic stainless steel.
Aluminium Enclosure protected by Class 1, Groups C and D, Class II, Groups E, F and G, Div. 1 & 2. U
quality epoxy paint system. Weatherproof to NEMA type 4X, IP66.
Performance of enclosure requires
careful installation and sealing of cable SAFE AREA ENCLOSURES
gland connection in situ.
Assembly requires to be built for Marine General Purpose Weatherproof
use, See Table 8, Code 02. The basic enclosure is pressure die-cast in zinc alloy, epoxy painted, W
with weather protection not less than NEMA type 4, IP66.
JAPANESE APPROVAL ✽
Weatherproof For Aggressive Atmospheres
An enclosure Code `B' is available that
Investment cast enclosure In austenitic stainless steel with A
meets the requirements of Japanese
weather protection not less than NEMA type 4X, IP66.
industrial standards for use in hazardous
areas. Details on application.

MODELS TABLE 2
S21/2 Code
For applications up to 100 bar (1500 psi).
Maximum working pressure 155 bar Fixed Switching Differential.
SPDT & DPDT options available. See Table 6. S21
(2250 psi).
Adjustable Switching Differential. (Limited Span)
S24 Achieved by special microswitch with built in adjuster. SPDT only S22
For applications up to 700 bar See Table 6.
(10,000 psi). Maximum working pressure Fixed Switching Differential.
1000 bar (15,000 psi). S24
SPDT & DPDT options available. See Table 6.

ELECTRICAL ENTRY TABLE 3


Adaptors are available for other popular Code
thread sizes.
Enclosure W: 22mm dia (0.86 in) entry. 1
Enclosure W: M20 x 1.5 elbow adaptor to suit. 0
Enclosure W: 3/4-NPT INT. elbow adaptor to suit. 3

Enclosures H, R & A: M20 x 1.5 ISO thread. 0

Enclosures H, R & A: M20 x 1.5 ISO thread, dual entry. 5

Enclosures H, R, T & U: 3/ -NPT INT. 3


4

Enclosures H, R, T & U: 3/4-NPT INT. dual entry 6

SEE APPROVALS
MATERIAL OF TABLE 4
WETTED PARTS
Code
316 stainless steel diaphragm, process connection and viton
WELDED CONSTRUCTION
O-ring seal. A
Code S and T.
316 stainless steel diaphragm, process connection and nitrile
For reduced risk against leakage O-ring seal. G
under extreme or unusual conditions Stainless steel process connection, Polyimide (Kapton)
the diaphragm may be welded directly diaphragm and nitrile O-ring seal. H
to the process connection, eliminating
the O-ring. Nickel Alloy (Monel) diaphragm, 316 stainless steel process
connection and Viton O-ring seal, for application as laid K
Welded construction not available on down in NACE MR-01-75.
ranges CC to CE (CW to CK). (See Table Nickel Alloy (Monel) diaphragm, 316 stainless steel process
5.) Ranges CC to G3 (CW to GK) connection and nitrile O-ring seal. P
available with metallic diaphragm only.
316 stainless steel diaphragm and process connection. All
(See Table 5.)
welded construction. S
Nickel Alloy (Monel) welded diaphragm and process
connection. (Suitable for NACE MR-01-75) T
APPLIES TO ALL MATERIALS IN THE TABLE ABOVE AND AVAILABLE IN A VARIETY OF
COMBINATIONS

SETTING RANGES TABLE 5


When ordering, please state units Pmax RANGE
required. Range and set point will be in bar psi Model bar mbar Code psi in.Hg in.H2O Code
units of preference. S21 12 to 250 CC 5 to 100 CW
S21 -120 to +120 CD -50 to +50 CH
1 bar = 100kPa = 14.5 psi 15 217 S21 100 to 600 CE 1.5 to 8.5 CK
1 mbar = 100Pa = 0.39 in.H2O S21 -1000 to 0 AO -30 to 0 AB
Pmax = maximum working pressure S21 -1 to +1.5 G3 -14.5 to 20 GK

NOTE: Codes may differ for other units.


S21/2 0.25 to 1.6 DB 4 to 25 DK
27 400 S21/2 0.4 to 2.5 DC 6 to 40 DP
S21/2 1 to 6 DE 16 to 100 DZ

S21/2 1.6 to 10 EA 25 to 160 EH


70 1000 S21/2 2.5 to 16 EB 40 to 250 EM

S21/2 4 to 25 EC 60 to 400 ER
110 1600 S21/2 10 to 40 ED 160 to 600 EW
S21/2 16 to 75 EF 250 to 1000 EE

155 2250 S21/2 10 to 100 FA 160 to 1500 F6


APPLIES TO ALL RANGES IN THE TABLE ABOVE

Pmax RANGE
bar psi Model bar Code psi Code

S24 0.4 to 2.5 DC 6 to 40 DP


S24 1 to 6 DE 16 to 100 DZ

S24 1.6 to 10 EA 25 to 160 EH


-1 -30”Hg S24 2.5 to 16 EB 40 to 250 EM
to to
600 8700 S24 4 to 25 EC 60 to 400 ER
S24 10 to 40 ED 160 to 600 EW
S24 16 to 75 EF 250 to 1000 EE

S24 10 to 100 FA 160 to 1500 F6

S24 7 to 160 U7 100 to 2300 UK

1000 15000 S24 25 to 250 V7 350 to 3500 VC


S24 50 to 400 W7 800 to 6000 W9
S24 100 to 700 Y4 1600 to 10000 YF

APPLIES TO ALL RANGES IN THE TABLE ABOVE SEE APPROVALS


SWITCHING OPTIONS TABLE 6
Model S21/4
IEC 947-5-1/EN 60947-5-1 RATING
UL/CSA RATING Designation & Rated operational current Ie VA rating Contact Code
(RESISTIVE) Utilization (A) at rated operational Ui Uimp
§SEE NOTE Category voltage Ue Make Break
5 Amps @ 110/250V AC AC14 D300 0.6/0.3A @ 120/240V AC AC 432 72 SPDT 00
250V 0.8kV
Light Duty for AC only DC13 R300 0.22/0.1A @ 125/250V DC DC 28 28 DPDT 01
5 Amps @ 110/250V AC and
AC14 D300 0.6/0.3A @ 120/240V AC 250V 0.8kV AC 432 72 SPDT 02
2 Amps @ 30V DC
General purpose precision DC13 R300 0.22/0.1A @ 125/250V DC DC 28 28 DPDT 03

1 Amp @ 125V AC and


SPDT 04
§100 mA @ 30V DC gold alloy 1A @ 125 VAC RESISTIVE (IEC 1058-1/EN 61058-1)
DPDT 05
contacts for low voltage switching
§5 Amps @ 110/250V AC and
5 Amps @ 30V DC AC14 D300 0.6/0.3A @ 120/240V AC 250V 0.5kV AC 432 72 SPDT* 08
Environmentally sealed DC13 R300 0.22/0.1A @ 125/250V DC DC 28 28 DPDT* 09

§1 Amp @ 30V AC and


30V DC Environmentally sealed AC14 E150 0.3A @ 120V AC 125V 0.5kV AC 216 36 SPDT* 0G
with gold contacts DPDT* 0H

5 Amps @250V AC and


AC14 D300 0.6/0.3A @ 120/240V AC 250V 0.5kV AC 432 72 SPDTt H2
2 Amps @ 30V DC Hermetically
DC13 R300 0.22/0.1A @ 125/250V DC DC 28 28 DPDTt H3†, H66‡
sealed. Gold plated silver contacts
†2 Single pole, double throw. simultaneous falling under pressure.
‡2 Single pole, double throw, simultaneous rising under pressure.
Model S22
5 Amps @ 110/250V AC
Adjustable for AC only AC14 D300 0.6/0.3A @ 120/240V AC 250V 0.8kV AC 432 72 SPDT 0C

5 Amps @ 110/250V AC and AC14 D300 0.6/0.3A @ 120/240V AC AC 432 72


2 Amps @ 30V DC Adjustable DC13 R300 0.22/0.1A @ 125/250V DC 250V 0.8kV DC 28 28 SPDT 0D

NOTE: Enclosure Codes T and U. Enclosure Codes H and R.


Microswitch Codes 02 and 03. Microswitch Codes 02 and 03.
UL/CSA rating as follows:- UL/CSA Rating as follows:-
110/150V AC 5A 250V/125V DC 0.25/0.5A 110/250V AC 5A 250V/125/30V DC 0.25/0.5/2A

NOTE: Using Codes H2, H3, H6 increases the Gas Class to:
Class 1, Groups A, B, C and D, Div 2., for Enclosures T and U.

UL recognised component for use in hazardous areas. CSA accepted component for use in hazardous
Class 1, Div 2, Groups A,B,C and D. Class II Groups F areas Class 1, Div 2, Groups A,B,C and D.
and G. When used in enclosures T and U. When used in enclosures T and U.

The electrical rating is dependent on the microswitch fitted to the instrument. The electrical ratings defined by each approval that the micro
switch complies with and is shown on the product nameplate, ie UL/CSA, or IEC. It should be noted that the instrument must be used within the
electrical rating specified from the approval you require. This table lists the actual IEC ratings against the Designation& Utilization Category
marked on the nameplates. In the absence of any verification by UL/CSA the microswitch §manufacturer's rating is stated in italics and bold.
If in doubt seek guidance from the factory.

PROCESS TABLE 7
CONNECTION
Code
Other thread specifications and sizes Rc 1/4 (1/4 BSP tr INT) to BS21 (ISO 7/1) A
are available without using adaptors.
1/ -18NPT INT F
4
Adaptors are available for applications 1/ -14NPT INT H
2
where their use is permitted.
1/ -14NPT EXT J
2
OPTIONS AND TABLE 8
TREATMENTS Code
Tropicalisation High humidity environment. 01
Combinations available, apply for details. Marine and Offshore Saline atmosphere or salt spray. 02
Ammonia Process (wetted) parts and construction suitable 03
for atmospheric ammonia.
Oxygen Service 2: Process (wetted) parts are cleaned for oxygen. 04
Oxygen Service 3: Process and non process parts are
cleaned for use with oxygen. 05
Stainless Steel Pipe Mounting Bracket Permits local 2" pipework to
be utilised for mounting the instrument. 10
APPLY FOR
Tagging - Variety of tagging methods are available DETAILS
Applies when - no option is required and selection is
made from special engineering 00

APPLIES TO ALL OPTIONS AND TREATMENTS IN TABLE ABOVE


SEE APPROVALS

SPECIAL ENGINEERING TABLE 9


To your individual requirements, where FEATURE Code
specified. For your convenience, enter
your special listing in space provided.

PERFORMANCE DATA TABLE 10


TABLES 10A, 10B, 10C, 10D. Figures given in Table 10 are typical higher at the top of the range. Should
MODELS S21, S24 maxima for mid-range setting and are the differential be critical for specific
FIXED SWITCHING DIFFERENTIAL for guidance only. Values will vary across applications our engineers should be
the range, i.e. lower at the bottom and consulted prior to ordering.

MODEL S21 PSI UNITS TABLE 10A MODEL S21 SI UNITS TABLE 10B
SWITCHING OPTIONS. SWITCHING OPTIONS.
RANGE Pmax SWITCHING DIFFERENTIAL in H2O/inHg/PSI RANGE Pmax SWITCHING DIFFERENTIAL mbar
Code H2O/inHg/PSI PSI 00 01 02 03 04 05 08/0G 09/0H H2 H3/6 Code mbar/bar bar 00 01 02 03 04 05 08/0G 09/0H H2 H3/6
CW 5 to 100 218 2 3.1 3.5 5.5 2 2.4 3.1 6 11.7 11.7 CC 12 to 250 16 5 8 6 8 5 6 8 15 30 30
CH -50 to +50 218 3.1 5.5 3.1 9 3.1 3.1 5.5 7 8 8 CD -120 to 120 16 8 14 8 23 8 8 14 18 20 20
CK 1.5 to 8.5 218 3.1 5.5 6 9 3.1 4.7 5.5 7 18 18 CE 100 to 600 16 8 14 15 23 8 12 14 18 45 45
AB -30 to 0 218 0.6 0.8 1.3 1.7 0.5 0.5 0.8 1 3 3 A0 -1000 to 0 16 21 27 45 60 18 18 30 36 105 105
GK -14.5 to +20 218 0.3 0.6 0.7 1.5 0.3 0.4 0.5 0.7 2.2 2.2 G3 -1 to +1.5 16 21 40 48 100 24 30 36 45 150 150
DK 4 to 25 400 0.4 0.7 1.0 1.5 1.0 1.5 2.6 3.5 1.2 2.3 DB 0.25 to 1.6 27 30 45 70 100 70 100 180 240 80 160
DP 6 to 40 400 0.4 0.7 1.0 1.5 1.0 1.5 2.6 3.5 1.2 2.3 DC 0.4 to 2.5 27 30 45 70 100 70 100 180 240 80 160
DZ 16 to 100 400 0.6 0.9 1.7 2.0 1.5 2.2 3.5 1.6 2.9 5.8 DE 1 to 6 27 40 60 120 140 100 150 240 320 200 400
EH 25 to 160 1000 1.5 2.2 3.6 6.5 2.2 3.3 11.6 14.5 6 11.6 EA 1.6 to 10 70 100 150 250 450 150 230 800 100 400 800
EM 40 to 250 1000 2.2 4.0 5.1 9.9 3.6 5.8 13.1 17.4 7.5 14.5 EB 2.5 to 16 70 150 275 350 680 250 400 900 1200 500 1000
ER 60 to 400 1500 4.4 6.5 15.2 19.6 7.3 10.2 26 35 26 52 EC 4 to 25 112 300 450 1050 1350 500 700 1800 2400 1800 3600
EW 160 to 600 1500 7.3 11.6 20 26 11.6 17.4 44 46 31 61 ED 10 to 40 112 500 800 1400 1800 800 1200 3000 3200 2100 4200
EE 250 to 1000 1500 9.4 14.5 25 33 14.5 22 44 58 51 102 EF 16 to 75 112 650 1000 1750 2250 1000 1500 3000 4000 3500 7000
F6 160 to 1500 2250 14.5 22 51 65 29 44 87 116 73 145 FA 10 to 100 155 1000 1500 3500 4500 2000 3000 6000 8000 5000 10000

MODEL S24 TABLE 10C MODEL S24 TABLE 10D


SWITCHING OPTIONS. SWITCHING OPTIONS.
RANGE Pmax SWITCHING DIFFERENTIAL PSI RANGE Pmax SWITCHING DIFFERENTIAL mbar
Code PSI PSI 00 01 02 03 04 05 08/0G 09/0H H2 H3/6 Code bar bar 00 01 02 03 04 05 08/0G 09/0H H2 H3/6
DP 6 to 40 8700 3.2 4.8 5.8 5.8 4.4 4.4 6.5 7.4 6 11.6 DC 0.4 to 2.5 600 220 330 400 400 300 300 450 510 400 800
DZ 16 to 100 8700 3.5 5.8 8.7 11.6 7.3 10.2 8.7 9.4 12 23 DE 1 to 6 600 240 400 600 800 500 700 600 650 800 1600
EH 25 to 160 8700 5.5 10.2 11.6 17.4 8.7 13 8.7 11 18 35 EA 1.6 to 10 600 380 700 800 1200 600 900 600 750 1200 2400
EM 40 to 250 8700 6.7 11.5 11.6 17.4 8.7 13 11.6 17.4 18 35 EB 2.5 to 16 600 480 790 800 1200 600 900 800 1200 1200 2400
ER 60 to 400 8700 12.5 20 17.4 23 11.6 17.4 20 22 34 67 EC 4 to 25 600 860 1400 1200 1600 800 1200 1350 1500 2300 4600
EW 160 to 600 8700 14.5 23 29 44 22 36 29 44 51 102 ED 10 to 40 600 1000 1600 2000 3000 1500 2500 2000 3000 3500 7000
EE 250 to 1000 8700 22 28 36 73 22 58 44 58 58 116 EF 16 to 75 600 1500 1900 2500 5000 1500 4000 3000 4000 4000 8000
F6 160 to 1500 8700 29 36 65 87 51 73 58 73 73 145 FA 10 to 100 600 2000 2500 4500 6000 3500 5000 4000 5000 5000 10000
UK 100 to 2300 15000 49 80 99 145 58 77 73 90 150 290 U7 7 to 160 1000 3400 5500 6800 10000 4000 5300 5000 6200 10000 20000
VC 350 to 3500 15000 81 162 145 244 122 203 725 870 370 725 V7 25 to 250 1000 5600 11200 10000 16800 8400 14000 50000 60000 35000 50000
W9 800 to 6000 15000 128 255 255 574 192 319 1160 1160 600 1160 W7 50 to 400 1000 8800 17600 17600 39600 13200 22000 80000 80000 40000 80000
YF 1600 to 10000 15000 218 435 290 653 326 486 1450 1450 750 1450 Y4 100 to 700 1000 15000 30000 20000 45000 22500 33500 100000 100000 50000 100000

TABLES 10E, 10F. MODEL S22 ADJUSTABLE SWITCHING DIFFERENTIAL


MODELS S22 TABLE 10E MODEL S22 TABLE 10F
SWITCHING OPTIONS. SWITCHING OPTIONS.
RANGE Pmax SWITCHING DIFFERENTIAL PSI RANGE Pmax SWITCHING DIFFERENTIAL mbar
Code PSI PSI MIN OC MAX MIN OD MAX Code bar bar MIN OC MAX MIN OD MAX
DK 4 to 25 400 0.2 1.1 1.0 2.9 DB 0.25 to 1.6 27 11 78 66 200
DP 6 to 40 400 0.3 1.2 1.3 3.0 DC 0.4 to 2.5 27 22 82 88 210
DZ 16 to 100 400 0.5 2.8 2.5 7.3 DE 1 to 6 27 33 190 170 500
EH 25 to 160 1000 1.9 6.2 6.4 16 EA 1.6 to 10 70 132 430 440 1100
EM 40 to 250 1000 3.2 9.1 9.6 23 EB 2.5 to 16 70 220 630 660 1600
ER 60 to 400 1500 9.6 35 41 88 EC 4 to 25 112 660 2400 2800 6100
EW 160 to 100 1500 13 61 57 125 ED 10 to 40 112 880 3300 3900 8600
EE 250 to 1000 1500 16 62 80 160 EF 16 to 75 112 1100 4300 5500 11000
F6 160 to 1500 2250 25 83 96 212 FA 10 to 100 155 1700 5700 6600 14600
TECHNICAL DATA

ACCURACY ELECTRICAL CONNECTIONS OPTIONAL EXTRAS


Set point repeatability ±1% of span at
20ºC ambient. Terminal block Chemical Seals
AMBIENT TEMPERATURE RANGE Cable entry is to a non-pinching Chemical seals of our own or proprietary
All models are suitable for operating terminal block made of a non- manufacture can be fitted when
within a range of -25 to +60ºC (-13 to hygroscopic thermosetting plastic, required.
+140ºF). Enclosures A, H, R, T, U, on suitable for cables up to
Models S21 and S24 with ranges CC to 2.5mm2/14AWG.
FA may be used intermittently down to
-60 and up to +80ºC (-76 to +176ºF). Earthing/Grounding
For continuous use below -25ºC (-13ºF) An earthing facility is provided.
we recommend using only enclosures
H, R, T, U and A with special gaskets Dielectric Strength
and limited switching. The electrical assembly is capable of
MAXIMUM PROCESS TEMPERATURE withstanding *2kV between live parts
Subject to appropriate installation and earth/ground and 500V between
practice, the component parts open contacts.
withstand up to +60ºC (+140ºF). For
process temperatures up to +120ºC *1.2kV for microswitch Codes H2, H3
(+248ºF), order WETTED PARTS Code A and H6. Refer to Table 6.
(Table 4), and for higher temperatures,
refer to SPECIAL ENGINEERING. Electrical Entry
Standard options are listed In Table 3.
CAUTION: Pg, and ET threads can be
Moving parts have been treated with a accommodated by adaptors. Dual
water repelling lubricant before leaving entry available in some enclosures. See
factory. Table 3.
Occasional inspection and the
application of a water repelling
lubricant Is recommended to ensure
moving parts remain free under all UNIT WEIGHTS (Approx)
conditions. RANGE AND MODEL
WARNING: Does not apply to Oxygen S21/2 S24
Services, see Table 8. Enclosures CC ALL
CD OTHER ALL
CE RANGES RANGES
B, H & T 3.5kg/7.7lb 2.7kg/5.9lb 2.8kg/6.1lb
U&R 6.6kg/14.5lb 5.8kg/12.8lb 5.9kb/13lb
W 3.1kg/6.8lb 2.6kg/5.7lb 2.9kg/6.4lb
A 4.2kg/9.2lb 3.8kg/8.4lb 4kg/8.8lb

OPERATION/
INSTALLATION
TYPICAL INTERNAL ARRANGEMENT
Mounting Position/Location/
Installation
Vertical as shown, taking care to
avoid siting in locations that transmit
excessive shock or vibration. For
further advice contact our
engineers.
APPROVALS
CENELEC/BASEEFA

BASEEFA certified to CENELEC EN50 014 and EN50 018.


for use in Zone 1 hazardous areas.

Enclosure Codes H and R and all models.


BASEEFA No. Ex 89C 1374

CANADIAN STANDARDS ASSOCIATION

Switches - Automatic - Pressure Type - For hazardous locations


Enclosure codes T & U

Class 1 Groups C & D, Class II Groups E F and G


LR 94185-2

UNDERWRITERS LABORATORIES INC.

NOWT
Float - and Pressure - Operated Motor Controller
For Use in Hazardous Locations.

E134197(N)
Enclosure codes T & U

Class 1. Groups C and D, Class II, Groups E, F and G.

JAPANESE APPROVAL ✽
BASEEFA certified to CENELEC EN50 014 and EN50 018
for use in Zone 1 hazardous areas.

Enclosure Code B.
JAPANESE APPROVAL No. C11348.
DIMENSIONS
‘B’, ‘H’, ‘R’, ‘T’, ‘U’ ENCLOSURE 'W' ENCLOSURE

ALL DIMENSIONS mm (inches) ALL DIMENSIONS mm (inches)

'A' ENCLOSURE MODEL S21/2 ALL RANGES CC, CD, CE

ALL DIMENSIONS mm (inches) ALL DIMENSIONS mm (inches)

MODEL S21/2 RANGES CC, CD, CE MODEL S24 ALL RANGES

ALL DIMENSIONS mm (inches) ALL DIMENSIONS mm (inches)

In the interest of development and improvement Delta Controls Ltd, reserve the right to amend, without notice, details contained in this publication.
No legal liability will be accepted by Delta Controls Ltd for any errors, omissions or amendments.

DELTA CONTROLS LIMITED, ISLAND FARM AVENUE, WEST MOLESEY, SURREY KT8 2UZ
TEL: +44 (0)20 8939 3500 FAX: +44 (0)20 8783 1163
E-MAIL: sales@delta-controls.com WEB SITE: www.delta-controls.com
Registered Office Registered in England No. 486464
STOCK NO: 002521/S20 - Nov '00
10. ISOLATION BALL VALVE c/w SWITCH BOX
C O M M U N I C A T I N G W I T H V A L V E S

IP.67
Polycarbonate
Valve Position Monitor

Type SLR

The type SLR valve position monitor has Features and Benefits

been designed to reduce installation costs Enclosure manufactured in polycarbonate for improved
chemical and mechanical resistive properties.
and space requirements but at the same
Versions available providing compatibility for hazardous
time offering rugged reliability in the most area applications including EEx ia intrinsic safety.

testing environments. A lockable part-turn quick access cover ensures fast


access for speedy start-up.

Utilising a corrosion resistant polycarbonate High visibility position indicator with different colouring
options providing clear local indication of the current
enclosure for added protection, the SLR valve position.

monitor incorporates a number of distinct Using a stainless steel drive shaft that eliminates the
problems associated with plastic shaft assemblies thus
features that allow plant personnel to install, allowing precise switch setting.

monitor and maintain the valve assembly IP67 ingress protection.

with the minimum of fuss. Quick setting switch cams that are set without the need
for additional tools allow fast and simple switch adjustments.

Switch termination via. European approved terminal blocks.

Compact design provides considerable space saving


over similar equipment without compromising the ease
of installation or maintenance.

Simplified mounting arrangements allow quick and secure


mounting to pneumatic actuators with VDI/VDE.3845 topworks
as well as other actuators with non-standard topworks.

Different electrical functions available including mechanical


switches, reed type proximity switches and inductive
proximity sensors.

C O M M U N I C A T I N G W I T H V A L V E S
C O M M U N I C A T I N G W I T H V A L V E S

IP.67
Polycarbonate
Valve Position Monitor

Type SLR

Materials of Construction
Housing Polycarbonate (Black) Cover Polycarbonate (Clear)
Shaft 300 Stainless Steel Seals Nitrile (Optional – Viton)

Enclosure
Type Weatherproof Ingress Protection IP.67
Conduit Entries 2 x M20 (Optional – PG13.5 and 1⁄2 " NPT)

Visual Indication
Type R Red Closed/Green Open (Optional – Blue Closed/White Open, Navy Closed/Yellow Open)

Electrical Functions*
16 (2) SPDT V3 Mechanical 10 A @ 125/250 VAC, 0.5 A @ 125 VDC
17 (2) SPDT V3 Mechanical ‘Gold Plated’ Contacts 1 A @ 125 VAC, 0.5 A @ 30VDC
40 (2) SPST Reed Type Proximity 0.15 A @ 30 VDC
42 (2) V3 Namur Type Inductive Proximity EEx ia On I <1mA, Off I >3mA, 8 VDC Nominal
(2) V3 Inductive Proximity 3-Wire On Request
43 (2) Cylindrical & Slotted Namur Inductive Proximity EEx ia On I <1mA, Off I >3mA, 8 VDC Nominal
(2) Cylindrical Inductive Proximity 3-Wire On Request
96 AS-Interface Communication Model 4 Inputs Open & Closed / 2 Power Outputs
25 to 30 VDC, 4 Watts

Hazardous Area Classification


Functions 16, 42, 43 and 96 Non-Hazardous
Functions 17, 40, 42 (2-Wire Namur) and 43 (2-Wire Namur) ATEX II 2 G / EEx ia IIB T6 Intrinsic Safety
*Note – Other models available on request

Imtex Controls Limited


Unit 5a Valley Industries Hadlow RoadTonbridge Kent TN11 0AH UK
Tel +44 (0)1732-850360 Fax +44 (0)1732-852133
Email sales@imtex-controls.com
www.imtex-controls.com C O M M U N I C A T I N G W I T H V A L V E S
This page is intentionally blank

You might also like