To,

Executive Engineer,CAM Division, Date:


SDSTPS, Nelatur (V)
Muthukur(M),
SPSR Nellore (Dist) -524347.
Andhra Pradesh.

From,
BROTHERS ENGINEERIN AND ERECTORS LIMITED.
Ibrahim Patnam,Vijayawada-521456.
Andhra Pradesh.

Sub :- SDSTPS- Nelatur – CAM Division – Emergency work of dismantling, Shifting / lifting, Laying, fit up & Welding of
lifted 300NB Fire water header line to an elevation of 24 mtrs (above pipe racks) near JNT-6 including supports at
different elevations with required fittings, Complete dismantling and replacement of damaged MSRL / MS PU
coated pipe section of length 14 mtrs pertaining to Hot Well Makeup Line at an elevation of 10 mtrs with
Stainless Steel Pipe alongwith required SS fittings including the fabrication, welding, lifting of pipe etc., & Removal
of existing painted names, Painting and legend printing on the walls (both inside & outside) of Deluge Valve
Housings and on the pipe lines inside the deluge Valve housings available at different locations inclusive of all
consumables like paint brushes, paints & required thinner etc., and any other material required for completion of
work during the year 2023-24 – Quotations called for – Reg.

Ref : Enq. No: 04 / 23-24 / EE / CAM / SDSTPS / Nelatur / F. Enq. / D. No. 97 / 2023, Dated: 08.09.2023.

SCHEDULE OF RATERS

Rate
(Excluding
S.
Description of the work Units Qty EPF, GI, ST,
No
etc.,) in
Rs./Mts.

Laying, fit up, Welding & shifting of 300NB Fire water header line near JNT-6 including supports at different elevations
1
with required fittings

Complete Dismantling of present 300NB header line at an elevation of 12 mtrs (inclusive of


a T&P and Consumables like Grinding Machine, Cutting wheels etc. Work shall be as per Mtr 82 230.00
Standard APSS 202

Lifting and laying of removed 300NB Header Pipe Line above the pipe rack Including Handling
b Charges and Required Consumables and T&P as per the Directions of Engineer-in-Charge and Mtr 75 480.00
shall be done as per standards IS 13039:2004, IS2065:1983 and as per approved drawing.

c Laying of 250 NB MS Pipe Line in place of removed damaged Pipe Line Including Handling Mtr 14 410.00
Charges and Required Consumables and T&P as per the Directions of Engineer-in-Charge and
shall be done as per standards IS 13039:2004, IS2065:1983 and as per approved drawing.

Fabrication & Erection of 250 NB GI / MS bends, TEEs, reducers and shall be done as per
d No 9 350.00
standards IS 13039:2004, IS2065:1983 and as per approved drawing

Painting of newly laid pipe lines with one coat Red Oxide Primer and two coats of PO Red
Paint including paint, primer, scaffolding, sundries and consumables etc. Zinc Chrome- Red
e M2 95 320.00
Oxide primer shall conform to IS 2074:2015, Enamel Paint shall conform to IS 2932:2013,
Colour ISC 538-PO Red. Painting shall be as per IS1477 (part-1):1971 & 1477(part-2): 1971.

Laying of Support for the pipe with "C" channel (125 x 65) & Angle (75 x 75) and fixing U
f clamp and bolts to support the pipe and shall be done as per standards IS APSS 1104 and as No 10 550.00
per approved drawing.

Winch Charges / Arrangement for Scaffolding and safety precautions and including height &
g risk allowance for working against high altitude winds M3 115 280.00

Complete dismantling of damaged MSRL / MS PU coated pipe section of Hotwell Makeup Line with Stainless Steel Pipe
2
alongwith required SS fittings.

Complete Dismantling of present MSRL / MS PU coated line pertaining to Hotwell makeup to


a Unit-2 at an elevation of 12 mtrs (inclusive of T&P and Consumables like Grinding Machine, Mtr 13.5 730.00
Cutting wheels etc. Work shall be as per Standard APSS 202

Fitup, welding and laying of new SS pipe line in place of removed MSRL/MS PU coated Pipe
b line at an elevation of 12 mtrs in between pipe racks and shall be done as per standards IS Mtr 13.5 3200.00
13039:2004, IS2065:1983.

Removal of printed names on the Deluge Valve Housing, painting, legend printing on the walls of DV Housing (both
3 inside & outside) and on the pipes lines inside the Deluge Valve Housing for proper identification of equipment
protected, connected pipe lines and valves with location.

Removal of printed names on the Deluge Valve Housing, painting with White & Lemon Yellow
colour (IS-5 Standard Colour Code ISC-355), legend printing on the walls of DV Housing (both
a Job 74 560.00
inside & outside) and on the pipes lines inside the Deluge Valve Housing for proper
identification