S.

no TCP Signals PLC


Required

1 ON feedback Softwired

2 Trip feedback Softwired

3 Local/Remote feedback Softwired / Harwired

4 kV feedback Hardwired

5 mA feedback Hardwired

6 Primary current fb Softwired

7 No of Sparks fb Softwired

8 ON Command Hardwired

9 OFF Command Hardwired

10 ESD Trip Command Hardwired

11 kV Set point Softwired

12 mA Set point Softwired

13 Spark set point Softwired

TR Set Signals TCP

1 Oil Temperature High Hardwired

2 Oil Temperature High High Hardwired

3 Pressure Switch Trip Hardwired


4 Oil level switch Hardwired

5 Earth Switch Close Hardwired

7 Humidity Sensor of TR Set

8 Temperature sensor of TR set

9 Humidity Sensor of TCP

10 Temperature sensor of TCP

Common Signals - Required for Hard

Common Signals Signal creation

Alarm from TRCP or RCP with OR


1 ESP Common Alarm
Gate
Either one transformer rectifier set is
2 ESP Rectifier Faulty
fail

3 Electric supply to ESP Fail Both incomers are open

4 Rapper Mechanism Trip Rappel panel trip

5 Outlet Emission High From Dust monitor

6 kV feedback kV Feedback

7 mA feedback mA Feedback
PLC ECS
Actual Required Actual / Possiblity

Softwired - Hardwired

Softwired - Hardwired

Softwired / Harwired NA NA

Hardwired Hardwired Hardwired

Hardwired Hardwired Hardwired

Softwired NA NA

Softwired NA NA

Hardwired NA NA

Hardwired NA NA

Hardwired NA NA

Softwired NA NA

Softwired NA NA

Softwired NA NA

PLC CMS ECS

Via TCP through Modbus Hardwired Softwired

Via TCP through Modbus Hardwired Softwired

Via TCP through Modbus Hardwired Softwired


Via TCP through Modbus Hardwired Softwired

NA Hardwired Softwired

NA Hardwired Softwired

NA Hardwired Softwired

NA Hardwired Softwired

NA Hardwired Softwired

Common Signals - Required for Hardwired to ECS ND Softwired to DCS

Signal orginate PLC DCS

PLC signal orginate Softwired from PLC

PLC signal orginate Softwired from PLC

MCC Softwired from MCC Softwired from PLC

RCP Softwired from RCP Softwired from PLC

Dust Monitor signal orginate Softwired from PLC

TCP Hardwired from TCP Softwired from PLC

TCP Hardwired from TCP Softwired from PLC


Remarks

These signals are not required as per contract, However is Hardwired


can be provided (P&ID request for Softwired)

Depends on TCP Supplier choosen


o DCS

ECS

Hardwired from PLC

Hardwired from PLC

Hardwired from MCC

Hardwired from RCP

Hardwired from Dust Monitor (4-20mA)

Hardwired from TCP

Hardwired from TCP


Song Hau 1 Thermal power plant
Name Designation
Common Mail id General
Mr. Nguyen Anh Tuan Deputy General Director
Mr.Nguyen Minh Hoang C&I Lead
Mr. Nhut Le Khac Deputy manager of operation
power plant
Email id
sh1pp@sh1pp.pvn.vn
tuanna@sh1pp.pvn.vn
hoangnm@sh1pp.pvn.vn
nhutlk@sh1pp.pvn.vn

You might also like