Rainfall Details
0 4 0.100 4 8 0.095
Tank/Pond Details
Depth Area Depth Area Depth Area Depth Area Depth Area
(m) (m²) (m) (m²) (m) (m²) (m) (m²) (m) (m²)
0.00 151.5 0.60 265.0 1.20 285.9 1.80 285.9 2.40 285.9
0.10 169.0 0.70 285.9 1.30 285.9 1.90 285.9 2.50 285.9
0.20 187.0 0.80 285.9 1.40 285.9 2.00 285.9
0.30 205.6 0.90 285.9 1.50 285.9 2.10 285.9
0.40 224.8 1.00 285.9 1.60 285.9 2.20 285.9
0.50 244.6 1.10 285.9 1.70 285.9 2.30 285.9
Design Head (m) 0.450 Hydro-Brake Type MD5 Invert Level (m) 68.250
Design Flow (l/s) 5.0 Diameter (mm) 108
Depth Flow Depth Flow Depth Flow Depth Flow Depth Flow
(m) (l/s) (m) (l/s) (m) (l/s) (m) (l/s) (m) (l/s)
0.10 3.3 0.80 6.3 2.00 10.0 4.00 14.1 7.00 18.7
0.20 4.8 1.00 7.1 2.20 10.5 4.50 15.0 7.50 19.3
0.30 4.8 1.20 7.7 2.40 10.9 5.00 15.8 8.00 20.0
0.40 4.9 1.40 8.4 2.60 11.4 5.50 16.6 8.50 20.6
0.50 5.1 1.60 8.9 3.00 12.2 6.00 17.3 9.00 21.2
0.60 5.5 1.80 9.5 3.50 13.2 6.50 18.0 9.50 21.8
Storm
Rain Time-Peak
Duration
(mm/hr) (mins)
(mins)
15 Summer 98.68 21
30 Summer 64.79 35
60 Summer 40.51 62
120 Summer 24.46 116
180 Summer 17.96 144
240 Summer 14.34 176
360 Summer 10.42 244
480 Summer 8.30 312
600 Summer 6.96 380
720 Summer 6.02 444
960 Summer 4.78 572
1440 Summer 3.46 808
2160 Summer 2.49 1164
2880 Summer 1.98 1524
4320 Summer 1.42 2208
5760 Summer 1.12 2944
7200 Summer 0.94 3672
8640 Summer 0.81 4408
10080 Summer 0.71 0
15 Winter 98.68 21
30 Winter 64.79 35
60 Winter 40.51 62
120 Winter 24.46 118
180 Winter 17.96 164
240 Winter 14.34 188
Storm
Rain Time-Peak
Duration
(mm/hr) (mins)
(mins)
Rainfall Details
0 4 0.100 4 8 0.095
Tank/Pond Details
Depth Area Depth Area Depth Area Depth Area Depth Area
(m) (m²) (m) (m²) (m) (m²) (m) (m²) (m) (m²)
0.00 151.5 0.60 265.0 1.20 285.9 1.80 285.9 2.40 285.9
0.10 169.0 0.70 285.9 1.30 285.9 1.90 285.9 2.50 285.9
0.20 187.0 0.80 285.9 1.40 285.9 2.00 285.9
0.30 205.6 0.90 285.9 1.50 285.9 2.10 285.9
0.40 224.8 1.00 285.9 1.60 285.9 2.20 285.9
0.50 244.6 1.10 285.9 1.70 285.9 2.30 285.9
Design Head (m) 0.450 Hydro-Brake Type MD5 Invert Level (m) 68.250
Design Flow (l/s) 5.0 Diameter (mm) 108
Depth Flow Depth Flow Depth Flow Depth Flow Depth Flow
(m) (l/s) (m) (l/s) (m) (l/s) (m) (l/s) (m) (l/s)
0.10 3.3 0.80 6.3 2.00 10.0 4.00 14.1 7.00 18.7
0.20 4.8 1.00 7.1 2.20 10.5 4.50 15.0 7.50 19.3
0.30 4.8 1.20 7.7 2.40 10.9 5.00 15.8 8.00 20.0
0.40 4.9 1.40 8.4 2.60 11.4 5.50 16.6 8.50 20.6
0.50 5.1 1.60 8.9 3.00 12.2 6.00 17.3 9.00 21.2
0.60 5.5 1.80 9.5 3.50 13.2 6.50 18.0 9.50 21.8
Hydrological region: 6 6
(3) Is SPR/SPRHOST ≤ 0.3?
Growth curve factor 1 year: 0.85 0.85
Growth curve factor 30 years: 2.3 2.3 Where groundwater levels are low enough the use of
soakaways to avoid discharge offsite would normally be
Growth curve factor 100 years: 3.19 3.19 preferred for disposal of surface water runoff.
Growth curve factor 200 years: 3.74 3.74
This report was produced using the greenfield runoff tool developed by HR Wallingford and available at www.uksuds.com. The use of
this tool is subject to the UK SuDS terms and conditions and licence agreement , which can both be found at www.uksuds.com/terms-
and-conditions.htm. The outputs from this tool are estimates of greenfield runoff rates. The use of these results is the responsibility of
the users of this tool. No liability will be accepted by HR Wallingford, the Environment Agency, CEH, Hydrosolutions or any other
organisation for the use of this data in the design or operational characteristics of any drainage scheme.
Skimmingdish Lane, Bicester Drainage Strategy
S T O R M WAT E R
2
Compliance
Premier Tech Aqua’s range of Conder Oil Separators full conform to both the Environment Agency’s latest PPG
guidelines and European standard BSEN-858-1-2 and are proven to effectively separate oil and water. Under test, the
Conder Bypass performed to less than 1 mg/L and in doing so guarantees minimal environmental impact and ensures
public safety.
Classes of Separators
There are two classes of separators which are defined by performance.
Class 1 Class 2*
Class 1 Separators are designed to achieve a Class 2 Separators are designed to achieve a
concentration of less than 5 mg/L of oil under standard concentration of less than 100 mg/L oil under standard
test conditions. These conditions are required for test conditions and are suitable for dealing with
discharges to surface water drains and the water discharges where a lower quality requirement applies,
environment. such as discharges to the foul sewer.
*Class 2 available in forecourt separators only.
• Bypass Separator If you’re unsure of what type of Conder Oil Separator you require, please use
• Full Retention Separator the chart below to help you identify the most suitable product for your project.
• Forecourt Separator The guidance given is for the use of separators in surface water drainage
• Wash Down and Silt Separators systems that discharge to rivers and soakways.
Risk of infrequent Risk of regular Risk of regular Fuel oils are delivered Very low risk of oil
light contamination contamination of Drainage will also to and dispensed on contamination e.g.
and potential for small surface water run off contain dissolved site e.g. retail fuel roofwater.
spills only e.g. car with oil and/or risk oils, detergents or forecourts.
park. of larger spills e.g. degreasers such as
vehicle maintenance vehicle wash water
area, goods vehicle and trade effluents
YES parking or vehicle e.g. industrial sites. YES
manoeuvring.
Source control SUDS Separator not
must be considered required.
and incorporated
where suitable.
By-pass separator Full retention separator Trade effluents must Full retention forecourt Clean water should
with alarm required. with alarm required. be directed to the separator with alarm not be passed through
Class 1 if discharge to Class 1 if discharge to foul sewer. It may required. Class 1 if the separator unless
surface water. Class surface water. Class need to pass through discharge to surface the size of the unit is
2 if discharge to foul 2 if discharge to foul a separator before water. Class 2 if increased accordingly.
sewer. sewer. discharge to sewer to discharge to foul
remove. sewer.
The use of SUDS should be considered at all sites and they should be incorporated where suitable. Source control SUDS
SUDS can be used to polish the effluent from these separators before it enters the environment. should be considered
where possible.
Separator Alarms
All oil separators are required by legislation to be fitted with an oil level alarm system with recommendations that the
alarm is installed, tested, commissioned and regularly serviced by a qualified technician.
The alarm indicates when the separator is in need of immediate maintenance in order for it to continue to work
effectively. Premier Tech Aqua can offer a full technical and service package for a variety of alarm options.
3
Conder Bypass Separators
Premier Tech Aqua’s range of Conder Bypass Separators are used to fully treat all flows generated by rainfall rates
of up to 6.5 mm/hr. Conder Bypass Separators are used when it is considered an acceptable risk not to provide full
treatment for high flows, for example where only small spillages occur and the risk of spillage is small.
Typical Applications
• Car parks
• Roadways and major trunk roads
• Light industrial and goods yards
How it Works
Step 1 Step 2 Step 3
During the early part of a rain All of the oil then proceeds to the As the rainstorm builds up to
storm, which is a time of high separation chamber where it is its maximum and the level of oil
oil contamination, all of the separated to the Class 1 standard of contamination reduces significantly,
contaminated water flow passes 5 mg/L and safely trapped. the nominal size flow continues
through the sediment collection to pass through the separation
chamber and enters the separation chamber and any excess flow of
chamber through a patented oil virtually clean water is allowed to
skimming and filter device. bypass directly to the outlet.
4
Conder Full Retention Separators
Premier Tech Aqua’s range of Conder Full Retention Separators are designed to treat the full flow that can be delivered
by a drainage system, which is normally equivalent to the flow generated by a rainfall intensity of 65 mm/hr. Full Retention
Separators are used where there is a risk of regular contamination with oil and a foreseeable risk of significant spillages.
Typical Applications
• Sites with a high-risk of oil contamination
• Fuel storage depots
• Refuelling facilities
• Petrol forecourts
• Vehicle maintenance areas/workshops
• Where discharge is to a sensitive environment
How it Works
Step 1 Step 2 Step 3
Contaminated water enters the The decontaminated water then Retained pollutants must be
separator where the liquid is passes through the coalescing filter emptied from the separator once
retained for a sufficient period to before it is safely discharged from the level of oil is reached, or the
ensure that the lighter than water the separator, with the remaining oil level alarm is activated. This
pollutants (such as oil, petrol) pollutants being retained in the waste should be removed from
separate and rise to the surface of separator. the separator under the terms of
the water. The Waste Management Code of
Practice.
5
Conder Forecourt Separators
Conder Forecourt Separators have been designed for specific use in petrol filling stations and other similar applications.
The size of this separator has been specifically increased in order to retain the possible loss of the contents from one
compartment of a road tanker, which could be up to 7,600 litres.
Forecourt Separators are an essential infrastructure requirement for all forecourts so as to ensure compliance with both
health and safety and environmental legislation.
Typical Applications
• Petrol forecourts
• Refuelling facilities
• Fuel storage depot
Performance
All Conder Forecourt Separators have an automatic closure device
(ACD) fitted as standard. This is compulsory for all PPG3 compliant
Full Retention Separators and prevents accumulated pollutants
flowing through the unit when maximum storage level is reached.
How it Works
Step 1
Contaminated water enters the separator where the liquid is retained for a sufficient period to ensure that the lighter
than water pollutants (such as oil, petrol) separate and rise to the surface of the water.
Step 2
The decontaminated water then passes through the coalescing filter before it is safely discharged from the separator,
with the remaining pollutants being retained in the separator.
Step 3
Retained pollutants must be emptied from the separator once the level of oil is reached, or the oil level alarm is activated.
This waste should be removed from the separator under the terms of The Waste Management Code of Practice.
Specifications
Tank Code Volume Length Diameter Height Base to Base to Access
(L) (mm) (mm) (mm) Inlet Outlet (mm)
(mm) (mm)
6
Conder Washdown and Silt Separators
Premier Tech Aqua’s range of Conder Washdown and Silt Separators are for use in areas such as car washes,
pressure wash facilities or other cleaning facilities and must be discharged to the foul water drainage system in
accordance with PPG13.
Typical Applications
• Car wash facilities
• Tool hire depots
• Pressure washer facilities
Performance
The Environment Agency’s PPG13 requires that discharge from pressure
washers must discharge to a foul drainage system. Where there is no foul
drainage available, the effluent must be contained within a sealed drainage
system or catchpit for disposal by a licenced waste contractor.
Silt build-up is the primary concern with washdown facilities and so our range of
Conder Washdown and Silt Separators are used to remove the silt and will allow some separation of hydrocarbons.
Detergents that are used in wash down areas will break down and disperse hydrocarbons (hindering the separation
process). Therefore, it is important to remember the main function of wash down separators is to remove silt.
How it Works
Step 1 Step 2 Step 3
Contaminated wash down water The lighter liquids, hydrocarbons, Treated water will exit the separator
enters the unit where the heavier will rise to the surface and be via the dipped outlet.
solids, silts and settle to the bottom retained within the tank.
of the tank.
Specifications
Although it is recognised that single stage separators give the most efficient separation, 2 and 3 chamber Conder
Washdown and Silt Separators are available on request.
Tank Code Capacity Silt Storage Diameter Length Access Base to Inlet Base to Outlet
(L) (mm) (mm) Diameter Invert Invert
(mm) (mm) (mm)
Peripherals
Features and Benefits Coalescing Filters
• Option for installation at a remote supervisory point The Conder Coalescing Filter is designed to separate
residual oil in already separated oil/water and ensures a
• Audible and visual discharge quality of less than 5 mg/L of oil in water.
• Eliminates unnecessary waste management visits Features and Benefits
• Easy installation • Handle for easy removal and cleaning
• Audible, visual and text message alert alarm systems • Flashing beacons (with option of siren kit)
available • Kiosks
• Probe brackets
• Bas 1000 intrinsically safe junction box
Mains Powered System • High level probe
• Silt level probe
Mains powered alarm systems are best suited to
new build situations or sites where installation of the • Oil level probe
necessary cabling and ducting is straight forward and
economical. The probe located in the separator will,
when surrounded by floating hydrocarbons, activate an
alarm condition on the remote panel to advise that the
Servicing
unit requires emptying. The Environmental Agency’s PPG3 guidelines
stipulate that every 6 months, and in accordance with
manufacturer’s instructions, experienced personnel
should carry out maintenance to both the separator
and alarm.
Premier Tech Aqua and our service partners can offer a
full technical and service package including separator
and alarm installation, commissioning, oil and silt removal
and route service contracts.
2 Whitehouse Way, South West Industrial Estate, Peterlee, Co Durham, SR8 2RA UNITED KINGDOM.
+44 (0) 8702 640004 | +44 (0) 8702 640005 | ptauk-sales@premiertech.com
PREMIERTECHAQUA.CO.UK
6.7 SPEL Grease Separators
REV 06.20 © SPEL Products, Lancaster Road, Shrewsbury, Shropshire, SY1 3NQ, England. T. +44 (0)1743 445200 F. +44 (0)1743 465442 E. info@spelproducts.co.uk
SPEL Grease Separators 6.8
© SPEL Products, Lancaster Road, Shrewsbury, Shropshire, SY1 3NQ, England. T. +44 (0)1743 445200 F. +44 (0)1743 465442 E. info@spelproducts.co.uk REV 06.20
WATER MANAGEMENT
AquaCell systems
Product and installation manual
Contents
2 Wavin AquaCell Systems PIM Customer Services: 0844 856 5152 Technical Advice: 0844 856 5165
Introduction to SuDS
Continuing urban development, a changing climate and Which SuDS components are best?
the consequences of increased rainfall are all increasingly
prominent issues on the political and environmental agenda SuDS should help maximise amenity and biodiversity, whilst
and all drive the need to actively manage excessive rainfall also delivering key objectives to manage flood risk and
across new and existing developments through the use of water quality For any given site, SuDS should be considered
Sustainable Drainage Systems (SuDS). as sequence of components designed to efficiently drain
Designed correctly drainage systems can assist in delivering surface water whilst minimising pollution.
sustainable development whilst improving the spaces where Selection of which SuDS components is best for each
we live, work and play. development is dependent on the site specific requirements.
The SuDS approach to managing water takes account not
just of how water quantity is managed but also considers How can Wavin help with SuDS projects?
how improvements to water quality can be delivered as
well as the creation of habitats promoting biodiversity and Wavin is well qualified to advise on how to comply with
amenity for the community. current and emerging regulation. We can aid specifiers,
Good SuDS aim to mimic nature and manage rainfall close developers and contractors in responding to legislative
to where it falls. They are designed to move and attenuate demands as they pertain to flooding, sewage, urban drainage
water within the development before it is released into water and sustainable resources use.
courses. Water is stored within the development where In particular, the proven qualities and performance of
is allowed to infiltrate into the ground or is released at a AquaCell systems not only support the achievement of
controlled rate to prevent issues downstream. SuDS, they can also help reinforce and enhance planning
The CIRIA SuDS Manual gives guidance on all areas of applications and enable development to proceed.
SuDS and focuses on the cost-effective planning, design,
construction, operation and maintenance of SuDS.
SuDS Design
Amenity Biodiversity
Create and sustain Create and sustain
better places for people better places for nature
3 Wavin AquaCell Systems PIM Customer Services: 0844 856 5152 Technical Advice: 0844 856 5165
Keeping you on top of legislation
Flood and Water Management Act 2010 The EU Water Framework Directive
The Flood and Water Management Act was designed to reduce Nearly half the EU population lives in ‘water-stressed’ countries,
the risk of flooding and its consequences by providing for better, caused by high extraction from freshwater sources, and
more comprehensive and co-ordinated water management, demand is growing all the time. The EU Water Framework
embracing groundwater, surface water and coastal erosion Directive introduces a new legislative approach designed to
risk. Schedule 3 of the act gives DEFRA responsibility for better manage and protect water resources, based not on
establishing national standards for sustainable drainage national orpolitical boundaries but on the natural catchment
and empowers local authorities to manage local flood risk of river basins.
by adopting and maintaining sustainable drainage schemes.
In January 2019 Schedule 3 was implemented by the Welsh Building Regulation Part H (Drainage and Waste Disposal)
Government. This legislation effectively makes the use of SuDS
mandatory on new developments with the aim of reducing Building Regulation Part H embraces the guidelines for
flood risk and improving water quality. The new standards drainage and waste disposal that must be met in the UK.
for Wales support the ‘four pillars’ of SuDS. Although Part H extends to rainwater drainage and solid
waste storage, waste drainage issues are to the fore. The
Sewers for Adoption Building Regulations are designed to ensure that all foul
water is properly disposed of to maintain a decent level
In England the framework for the delivery of SuDS in the of sanitation, promoting both personal and environmental
absence of Schedule 3 is through a revision to Sewers for health. The regulations also highlight the importance of
Adoption to include some SuDS components as adoptable by pollution prevention, working sewage infrastructure and
the Water and Sewage Companies. The document, currently sewage maintenance. With regards to stormwater, Building
with Ofwat for approval, is expected to be introduced early Regulations Approved Document H3 stipulates that adequate
2020. When it comes into force it will be the only guide to the provision should be made for rainwater to be carried from the
standards that sewers must meet if they are to be adoptable roof of a building to either a soakaway, water course or sewer.
by WaSCs in England. The new document will, for the first
time, offer guidance on SuDS components (although not all) National Planning Policy Framework
that can be adopted by Water and Sewerage Companies with
standards on the flood risk performance that is expected. Section 14 of the National Planning Policy Framework sets
out policy to ensure that flood risk is taken into account at
The Water Environment and Water Services (WEWS) all stages of the planning process and that inappropriate
(Scotland) Act 2003 development in areas at risk of flooding is avoided. The policy
directs development away from areas of highest risk and
In Scotland WEWS makes Scottish Water responsible for SuDS where new development is, exceptionally necessary in such
that deal with the run-off from roofs and any paved ground areas, aims to make it safe without creating an increase in
surface within the property boundary. In order to deliver this flood risk elsewhere and, where possible, reduce flood risk
SuDS need to be designed to Scottish Water’s specifications overall. It also states developments should only be allowed
as set out in their manual, Sewers for Scotland v4.0. In addition, in an area of flood risk if it incorporates sustainable drainage
the law makes the use of SuDS obligatory when dealing with systems, unless there is clear evidence that these would
surface water drainage from all new developments. be inappropriate.
4 Wavin AquaCell Systems PIM Customer Services: 0844 856 5152 Technical Advice: 0844 856 5165
Overview
The AquaCell range of geocellular systems are a fully tried The AquaCell range
and tested, BBA approved, modular technique for managing
excessive rainfall. There are three types of AquaCell unit. Each can be used as
a standalone system or different unit types can be mixed and
Applications matched together in layers to value engineer the most cost
effective solution.
The AquaCell range can be used as either a temporary
storage tank or as a soakaway, and is suitable for All AquaCell units have identical dimensions (1m x 0.5m x 0.4m),
applications including: but they are manufactured to perform differently. The type of
Landscaped areas unit, or combination of units required will depend on factors
Parks such as the load application, overall installation depth and
Domestic gardens site conditions.
Residential developments
Car parks & roads Features and benefits
Industrial/commercial areas
The following are applicable to all AquaCell units:
BBA Approved – certificate No. 03/4018
Modular, lightweight and versatile
Easy to handle and quick to install
Proven clip and peg connection system
95% void (each unit holds 190 litres of water)
Can be brick-bonded for extra stability
Units can be mixed and matched
together for optimum performance
Full range of ancillaries
Can be used as integral part of a SuDS scheme
Environmental benefits
5 Wavin AquaCell Systems PIM Customer Services: 0844 856 5152 Technical Advice: 0844 856 5165
Eco AquaCell
Configurator
Tool
Core-R
Optimise tank and soakaway designs with
the AquaCell Configurator Tool
The tool generates a PDF of the design for easy download and
can store the data online for future reference. To start using the
tool or to learn more visit: myportal.wavin.co.uk/tools
Core-R has been designed for use in deep applications,
subject to both regular and heavy traffic loadings, such as
cars and HGV’s.
Plus-R
6 Wavin AquaCell Systems PIM Customer Services: 0844 856 5152 Technical Advice: 0844 856 5165
AquaCell Eco
Application
H
on site, including mechanical equipment, must be avoided.
The width of an AquaCell Eco installation should not exceed Nominal Part Dimensions (mm)
size (mm) number W H L
12 metres to allow for mechanical backfilling without loading.
160 6LB025 500 400 1000
There is no limit to the length of the installation.
(1) These values relate to installations where the groundwater is a minimum of one metre below the base of the excavation.
(2) AquaCell Eco units should not be used where groundwater is present.
(3) 0.5m cover is required where a ride-on mower may be used.
Assumptions made: Ground surface is horizontal
Shear planes or other weaknesses are not present within the structure of the soil.
Source: BBA
7 Wavin AquaCell Systems PIM Customer Services: 0844 856 5152 Technical Advice: 0844 856 5165
AquaCell Core-R
Application
H
Suitable for regular and heavy traffic loadings
L W
Proven vertical loading capacity of: 66.9 tonnes/m² (669 kN/m²)
Proven lateral loading capacity of: 12.3 tonnes/m² (123kN/m²)
BBA approved – Certificate No 03/4018
Ideal for all types of shallow and deep projects including Nominal Part Dimensions (mm)
size (mm) number W H L
major attenuation and infiltration schemes
160 6LB150 500 400 1000
67 tonnes/m2
(1) Without groundwater present below base of units – AquaCell Core-R may be used where groundwater is present, contact
Wavin for technical advice.
(2) Loosening of dense sand or softening of clay by water can occur during installation. The designer should allow for any such
likely effects when choosing an appropriate value of φ.
(3) The design is very sensitive to small changes in the assumed value of φ, therefore, it should be confirmed by a chartered
geotechnical engineer. In clay soils, it may be possible to utilise cohesion in some cases.
(4) Applicable for car parks or other areas trafficked only by cars or occasional refuse collection trucks or similar vehicles
(typically one per week).
(5) This category should be used when considering landscaped areas that may be trafficked by ride on mowers.
Assumptions made: Ground surface is horizontal
Shear planes or other weaknesses are not present within the structure of the soil.
Source: BBA
8 Wavin AquaCell Systems PIM Customer Services: 0844 856 5152 Technical Advice: 0844 856 5165
AquaCell Plus-R
Application
H
Typically for use down to depths of 7.82m in landscaped
areas (7.57m trafficked by cars and 7.3m trafficked by
L W
HGV’s) to the base of the units from ground level, in best soil
conditions. Trafficking by heavy construction plant on site,
Material: Polypropylene
including mechanical equipment, must be avoided until the
minimum cover depth of 1.30 metres is in place. Nominal Part Dimensions (mm)
size (mm) number W H L
Features and benefits 160 6LB200 500 400 1000
(1) Without groundwater present below base of units – AquaCell Plus-R may be used where groundwater is present, contact
Wavin for technical advice.
(2) Loosening of dense sand or softening of clay by water can occur during installation. The designer should allow for any such
likely effects when choosing an appropriate value of φ.
(3) The design is very sensitive to small changes in the assumed value of φ, therefore, it should be confirmed by a chartered
geotechnical engineer. In clay soils, it may be possible to utilise cohesion in some cases.
(4) Applicable for car parks or other areas trafficked only by cars or occasional refuse collection trucks or similar vehicles
(typically one per week).
(5) This category should be used when considering landscaped areas that may be trafficked by ride on mowers.
Assumptions made: Ground surface is horizontal
Shear planes or other weaknesses are not present within the structure of the soil.
9 Wavin AquaCell Systems PIM Customer Services: 0844 856 5152 Technical Advice: 0844 856 5165
AquaCell Plus-R: for inspectability Inspectability scenarios
By aligning AquaCell Plus-R units end-to-end, full length AquaCell Plus-R viewing channel
viewing channels can be created – allowing for CCTV
inspection if required. These are created in the bottom layer
of an AquaCell tank installation.
Inspection chambers
AquaCell viewing
For off-line installations: channels
— Manhole with in-built flow control
10 Wavin AquaCell Systems PIM Customer Services: 0844 856 5152 Technical Advice: 0844 856 5165
Design guidance
Infiltration or attenuation? Large scale AquaCell Core-R storage tank
Ground conditions may be established According to the principals of SuDS, A storage tank may be designed to be
as part of a geotechnical assessment. wherever possible stormwater should online or offline (see pages 26-31 for
This may include tests for infiltration be drained back into the ground via typical details). However, if the site is
and ground water level. a soakaway as the first priority. A site subject to groundwater or a high water
must meet BOTH of the following table, it is important to ensure that
If there is no confirmation that such criteria for infiltration to be possible: the tank is not vulnerable to flotation.
assessments have been conducted, or The underlying soil surrounding the Sufficient weight from soil, or other
resulting conclusions are unavailable, a proposed installation is sufficiently covering placed over the AquaCell
trial pit will be required in accordance permeable units, must be sufficient to counter any
with BRE 365. The seasonally high water table is a buoyancy uplift force from the rising
minimum of 1 metre below the base groundwater level.
For further information and guidance, of the proposed installation
please contact the Wavin Technical
Design Team. If either of these criteria is not met, or
cannot be confirmed for any reason, a
soakaway system may not be suitable
for the application, in which case a
storage tank must be used.
11 Wavin AquaCell Systems PIM Customer Services: 0844 856 5152 Technical Advice: 0844 856 5165
Important design considerations for A: Non-trafficked B: Trafficked
geocellular structures
5
Rising rainfall levels and increased focus on SuDS
compliance, have led to an increase in the use of modular 3 3
units to create underground structures for infiltration or the
temporary storage of stormwater.
12 Wavin AquaCell Systems PIM Customer Services: 0844 856 5152 Technical Advice: 0844 856 5165
Design guidance
Hydraulic design Typical minimum cover depths and maximum installation depths
(1) For specific advice on cover depths for heavier loadings/HGV applications,
Each AquaCell unit has been designed
contact Wavin Technical Design on 0844 856 5165.
to have specific loading capacities
(2) 0.30m is minimum depth for AquaCell in landscaped applications. 0.5m cover is
(see pages 8-10) that define the
recommended in applications where ride-on mowers may be used. If construction
maximum depth parameters for which
plant is to be used on site, extra protection may be needed.
they are suitable.
(3) Allowable maximum depth to base of bottom layer of units is dependent on soil
type, angle of shearing resistance, loadings, and groundwater level. The above
Minimum depth of cover varies
depths are based on 38° angle of shearing resistance and no groundwater.
according to whether or not the
installation will be subject to trafficking
by cars/HGVs.
However, in some situations, In trafficked applications it is recommended that the height of any tank
should not exceed 2m (5 units). If you require a tank that exceeds this,
installations may have to be located
please contact Wavin Technical Design for guidance:
with greater cover depths. Reasons
may include: T: 0844 856 5165 E: technical.design@wavin.co.uk
Deep-running drainage network
Other buried services running above
tank location
Installation into banked/ sloping
ground
Upper layer of clay preventing
infiltration
13 Wavin AquaCell Systems PIM Customer Services: 0844 856 5152 Technical Advice: 0844 856 5165
Minimum cover and maximum installation depths to base of units from ground level, in best soil conditions
This chart shows how deep each unit can be used for different applications in best soil conditions.
0m
Minimum cover
Minimum cover
0.3m 0.3m 0.3m
0.6m
0.69m
Minimum cover
1m 1.1m
1.3m
NB: The height of any tank should not exceed 2m (5 units)
2m
2.7m
Maximum installation depth
3m
4m
5m
6m
6.2m
6.4m
6.7m
7m
7.3m
7.6m
7.8m
8m
Note: The AquaCell units can also be used in combination with each other, see page 16 for details.
14 Wavin AquaCell Systems PIM Customer Services: 0844 856 5152 Technical Advice: 0844 856 5165
Design guidance
Mix and match Brick bonding – for extra stability
Although all AquaCell units have identical dimensions, and When assembling a geocellular structure that comprises two
a high nominal void ratio of 95%, they are manufactured to or more layers, it is recommended that AquaCell units are
perform at a range of depths, dependent on soil type, angle placed in a ‘brick-bonded’ configuration for extra stability.
of shearing resistance, loading and ground water levels.
For optimum performance the units can be mixed and matched This helps minimise continuous vertical joints in the
(in layers) to value engineer the most effective design (in cost assembly, and gives the structure extra stability.
and performance terms) for each installation. For example,
in a landscaped application if you needed to install a tank or A significant advantage of AquaCell unit design is that brick
soakaway that is deeper than 2.7m, you could install layers bonding placement does not require extra connectors.
of AquaCell Core-R underneath the AquaCell Eco. See below
illustrations showing examples of how the AquaCell units can All three AquaCell units may be placed in this way, unless
be mix and matched together. For advice on how to optimise inspection channels and cleaning access are required using
a tank or soakaway design using more than one type of AquaCell Plus-R.
AquaCell please contact Wavin Technical Design.
AquaCell Plus-R units incorporate integral inspection
Note: AquaCell Eco cannot be used directly with AquaCell channels. These are designed for combined alignment to
Plus-R therefore there must be a layer of AquaCell Core-R create viewing tunnels at the base of an assembled structure
between them. (see page 11).
15 Wavin AquaCell Systems PIM Customer Services: 0844 856 5152 Technical Advice: 0844 856 5165
Installation guidance
Manual assembly
16 Wavin AquaCell Systems PIM Customer Services: 0844 856 5152 Technical Advice: 0844 856 5165
Installation
1. Excavate the trench to the required depth ensuring that the 6. In order to prevent silt from entering the tank, clogging
plan area is slightly greater than that of the AquaCell units. inlet pipework and reducing storage capacity, it is
2. Lay 100mm bed of coarse sand or non angular granular recommended that the Domestic Silt Trap (6LB300) or
material, level and compact. one of the standard Silt Traps (6LB600, 6LB625, 6LB630)
3. Lay the geotextile* over the base and up the sides of is installed prior to the inlet pipework – see page 24 for
the trench. installation guidelines.
4. Lay the AquaCell units parallel with each other. In multiple 7. Wrap and overlap the geotextile covering the entire
layer applications, wherever possible, continuous vertical AquaCell structure.
joints should be avoided. AquaCell units can be laid in 8. Lay 100mm of coarse sand or non angular granular
a ‘brick bonded’ formation (i.e. to overlap the joints material between the trench walls and the AquaCell
below) – see page 16. For single layer applications use the structure and compact.
AquaCell Clips and for multi layers use the AquaCell Clips 9. Lay 100mm of coarse sand or non angular granular
and the AquaCell Shear Connectors (vertical rods). material over the geotextile and compact.
5. Fix the Adaptors to the AquaCell units as required and 10. Backfill with suitable material.
connect pipework. 11. Rainwater from roof areas may discharge directly into the
soakaway but rainwater from carparks must discharge
through a catchpit manhole and/or a petrol interceptor.
AquaCell Units
100mm
Pre-formed socket
Permeable geotextile*
100mm
Coarse sand or non angular granular material base and surround 100mm
Example shows the use of AquaCell Eco. However, a *The geotextile should be selected according to specific site conditions. Specialist
advice should be sought if surrounding soil characteristics exhibit a high degree
soakaway can also be installed as shown using either of of fines/low infiltration capacity and/or there is a high risk of damage from ground
the other versions of AquaCell units (Core-R or Plus-R) contaminants.
as appropriate.
17 Wavin AquaCell Systems PIM Customer Services: 0844 856 5152 Technical Advice: 0844 856 5165
Typical storage tank installation method
Typical installation procedure 7. If side connections into the AquaCell units is required,
(other than the preformed socket), use the appropriate
1. Excavate the trench to the required depth ensuring that the Flange Adaptor (6LB104 or 6LB106). Fix the flange adaptor
plan area is slightly greater than that of the AquaCell units. to the unit using self-tapping screws. Drill a hole through
2. Lay 100mm bed of coarse sand or non-angular granular the Flange Adaptor and connect the pipework. (6LB106
material, level and compact. should not be used with AquaCell Eco).
3. Lay the geotextile1 over the base and up the sides of 8. In order to prevent silt from entering the tank, clogging
the trench. inlet pipework and reducing storage capacity, it is
4. Lay the geomembrane2 on top of the geotextile over the recommended that the Domestic Silt Trap (6LB300) or the
base and up the sides of the trench. standard Silt Trap (6LB600) is installed prior to the inlet
5. Lay the AquaCell units parallel with each other. In multiple pipework – see page 20 for installation guidelines.
layer applications, wherever possible, continuous vertical 9. Wrap and overlap the geotextile covering the entire
joints should be avoided. AquaCell units can be laid in a AquaCell structure, to protect the geomembrane.
‘brick bonded’ formation (i.e. to overlap the joints below) – 10. Lay 100mm of coarse sand or non angular granular
see page 16. For single layer applications use the AquaCell material between the trench walls and the AquaCell
Clips and for multi layers use the AquaCell Clips and the structure and compact.
AquaCell Shear Connectors (vertical rods). 11. Lay 100mm of coarse sand or non angular granular
6. Wrap the geomembrane around the AquaCell structure material over the geotextile/geomembrane and compact.
and seal to manufacturers recommendations.* 12. Backfill with suitable material.
AquaCell Units
100mm
Suitable impermeable
geomembrane
Suitable protective
geotextile layer
Pre-formed socket
100mm
Coarse sand or non angular granular material base and surround 100mm
Example shows the use of AquaCell Core-R. However, 1. For protective geotextiles CIRIA C753 – The SuDS Manual recommends a geotextile
of at least 2mm thick and 300gsm.
a storage tank can also be installed as shown using any of
2. The geomembrane should be designed to survive the rigours of construction,
the other versions of AquaCell units (Eco, Core-R or Plus-R) this is typically at least 0.5mm thick. Joints should be sealed using proprietary
as appropriate. welding techniques.
18 Wavin AquaCell Systems PIM Customer Services: 0844 856 5152 Technical Advice: 0844 856 5165
Installation
Ventilation box
150mm
concrete plinth
110mm Ø
Vent
6D205 160mm
OsmaDrain
AquaCell Units
NOTE: It is recommended that all connections and air vent NOTE: It is recommended that one vent pipe, 110mm in
installations in storage applications (using geomembrane) are diameter, is provided per 7,500 square meters of impermeable
made using a Flange Adaptor. catchment area on a site. Please contact Wavin Technical
Design for further details.
Adhesive or double sided tape should be used between the
geomembrane and the flange plate to ensure a watertight seal.
19 Wavin AquaCell Systems PIM Customer Services: 0844 856 5152 Technical Advice: 0844 856 5165
Connections
Geomembrane wrap
AquaCell Units
Geomembrane wrap
20 Wavin AquaCell Systems PIM Customer Services: 0844 856 5152 Technical Advice: 0844 856 5165
Connections
AquaCell Units Permeable Geotextile Wrap Jubilee clip
Connections to AquaCell units
Connection for soakaway application using either the
pre-formed socket (as shown below) or standard adaptors
into pre-formed socket*.
Installation procedure
21 Wavin AquaCell Systems PIM Customer Services: 0844 856 5152 Technical Advice: 0844 856 5165
Connection configurations
The connections shown here in schematic form, are the
typical options used to connect AquaCell units to control
chambers. They provide a controlled feed into and out of
the AquaCell units, and are used for either infiltration or
attenuation schemes.
AquaCell unit assembly
150mm/225mm
UltraRib/SuperSleve
Pipe
Sump
NOTE: The configuration of pipes in a manifold arrangement will vary to suit site conditions
and aniticipated stormwater intensity. See pages 27 and 30 for this option in context.
Pipe
Sump
Central pipe connection Cover and frame 14mm – 20mm single size granular bedding AquaCell unit assembly
/ backfill material
Pipe
Sump
22 Wavin AquaCell Systems PIM Customer Services: 0844 856 5152 Technical Advice: 0844 856 5165
Soakaways
Min depth*
Installation
depth*
110/100mm Domestic
OsmaDrain or Silt Trap AquaCell Units
SuperSleve pipe (6LB300)
+ adaptor
Trench soakaway
Ground level AquaCell Units
Min depth*
Installation
depth*
Notes S
1. Soakaways should be sited at least 5m away from the building
(Ref BS EN 752-4).
2. The exact size and shape of the soakaways are to be determined
once all the necessary calculations have been produced.
*For information regarding cover depths and installation depths, Key S
see page 15. S = AquaCell units soakaway (See note 2)
= 250mm Dia Silt Trap
23 Wavin AquaCell Systems PIM Customer Services: 0844 856 5152 Technical Advice: 0844 856 5165
Soakaway – traffic loading
Soakaway
Ground level
160mm OsmaDrain
or 150mm UltraRIb/
Supersleve via
appropriate adaptor
24 Wavin AquaCell Systems PIM Customer Services: 0844 856 5152 Technical Advice: 0844 856 5165
On-line storage
Ventilation box
Flow control
Sump Sump
A
Plan
Upstream control chamber AquaCell unit assembly Downstream control chamber
Sump