Download as pdf or txt
Download as pdf or txt
You are on page 1of 15

Fire Hose Cabinet (FHC)

Standpipe System
Components of FHC

1. Cabinet

2. Hose

3. Angle Valve

4. Discharge Nozzle

5. Fire Extinguisher (Optional)


Cabinet
Location of FHC

90 : 150 cm
Fire Hose
Hose Arrangement Inside Cabinet
1- Hose reel type

2- Hose rack type


Classes of Standpipe System
• Class 1
• Class 2
• Class 3
Item Class 1 Class 2 Class 3

Hose Size 2.5 ” 1 ” or 1.5 “ 2.5 “ or 1 ”

Min. Press. 6.9 bar 4.5 bar 6.9 bar for 2.5”
and 4.5 bar for 1.5 ”

Min. Flow Rate 250 gpm 100 gpm 250 gpm

Pmax 12 bar 6.9 bar 6.9 bar

Diam. Of Pipe 2.5 “ 1 “ or 1.5 “ 2.5 “ or 3 ” for 2.5 ”


1 ” for 1.5 “

Description ………………………. …………………. ………………………………

Travel Distance 45.7 m 39.7 m for 30 m


1.5 “
36.6 m for 1 “
Restricted Valve
Basement Ramp
‫ساللم الهروب‬
Fire Rated Wall
Building

Through Out Partially

Pump 250 250 500 Pump 250 250 250 500

1250 gpm
1000 gpm
Through Out

500 1000 750

Pump 500 250 250 500 250 500

Partially
500 1250 750

Pump 500 250 250 250 500 250 500


Z.C.V

Riser
SPKs
FHC

Tank Pump