Professional Documents
Culture Documents
Calculos Hidraulicos 1
Calculos Hidraulicos 1
MEDELLIN
Address 2 AHJ
INGESED SAS
Address 3 Job Site/Building
System
Density Area of Application
0.150gpm/ft² 139.35m² (Actual 211.75m²)
Most Demanding Sprinkler Data Hose Streams
PROYECTO MONTREAL
Address 1 AHJ
MEDELLIN
Address 2 Job Site/Building
INGESED SAS
Address 3 Drawing Name
MONTREAL
System Remote Area(s)
Most Demanding Sprinkler Data Occupancy Job Suffix
250.00
System Flow Demand Total Water Required (Including Hose Allowance)
346.93 596.93
Maximum Pressure Unbalance In Loops
0.000
Maximum Velocity Above Ground
20.41 between nodes 8 and 7
Maximum Velocity Under Ground
568.05gal
Supplies
Hose Flow Static Residual Flow Available Total Demand Required Safety Margin
@ @
Node Name (gpm) (psi) (psi) (gpm) (psi) (gpm) (psi) (psi)
10 Water Supply 250.00 175.000 165.000 750.00 168.445 596.93 82.026 86.419
Contractor
Contractor Number Contact Name Contact Title
Address 1 FAX
Address 2 E-mail
Address 3 Web-Site
Hydraulic Graph
175.000 178.983
Residual: Pressure
165.000 @ 750.00
Available Pressure at Time of Test
168.445 @ 596.93
System Demand
82.026 @ 346.93
System Demand (Including Hose Allowance at Source)
82.026 @ 596.93
• • • • • Route 2 • • • • •
SP 1.0490 49.06 18.21 120 2.245164 0.14m Pf 3.746
202 15.09m 49.06 11.2 19.185 Sprinkler, 1.52m Pe 0.205
11 14.95m 23.136 mecT(1.52m) 1.67m Pv
BL 1.4420 49.06 9.64 120 0.476721 1.03m Pf 1.572
11 14.95m 23.136 2.27m Pe
12 14.95m 24.708 mecT(2.27m) 3.30m Pv
CM 2.6350 146.40 8.61 120 0.191294 5.50m Pf 1.052
12 14.95m 43.54 24.708 Flow (q) from Route 4 Pe
13 14.95m 25.760 5.50m Pv
CM 2.6350 159.22 9.37 120 0.223414 5.50m Pf 1.229
13 14.95m 12.81 25.760 Flow (q) from Route 7 Pe
14 14.95m 26.989 5.50m Pv
CM 2.6350 126.15 7.42 120 0.145244 32.31m Pf 5.665
14 14.95m 26.989 6.70m Pe
7 14.95m 32.654 LtE(1.67m), T(5.02m) 39.01m Pv
• • • • • Route 3 • • • • •
SP 1.0490 49.26 18.29 120 2.262630 0.14m Pf 3.775
203 15.09m 49.26 11.2 19.346 Sprinkler, 1.52m Pe 0.205
15 14.95m 23.327 mecT(1.52m) 1.67m Pv
CM 1.6820 44.85 6.48 120 0.190834 7.87m Pf 2.077
15 14.95m 23.327 3.02m Pe
3 14.95m 25.403 mecT(3.02m) 10.88m Pv
• • • • • Route 4 • • • • •
SP 1.0490 49.28 18.29 120 2.263947 0.14m Pf 3.777
204 15.09m 49.28 11.2 19.358 Sprinkler, 1.52m Pe 0.205
16 14.95m 23.341 mecT(1.52m) 1.67m Pv
CM 1.6820 53.69 7.75 120 0.266161 1.72m Pf 1.260
16 14.95m 4.41 23.341 Flow (q) from Route 8 3.02m Pe
2 14.95m 24.601 mecT(3.02m) 4.74m Pv
CM 2.6350 43.54 2.56 120 0.020296 5.24m Pf 0.106
2 14.95m 24.601 Pe
12 14.95m 24.708 5.24m Pv
• • • • • Route 5 • • • • •
SP 1.0490 49.37 18.33 120 2.271914 0.14m Pf 3.791
205 15.09m 49.37 11.2 19.432 Sprinkler, 1.52m Pe 0.205
17 14.95m 23.428 mecT(1.52m) 1.67m Pv
© M.E.P.CAD, Inc. AutoSPRINK® VR11 v11.0.30.0 03/05/2021 20:57:42 Page 6
Hydraulic Analysis Job Number: 03052021
Report Description: Ordinary Group I
Pipe Type Diameter Flow Velocity HWC Friction Loss Length Pressure
Downstream Elevation Discharge K-Factor Pt Pn Fittings Eq. Length Summary
Upstream Total Length
CM 1.6820 4.42 0.64 120 0.002621 5.50m Pf 0.014
17 14.95m 23.428 Pe
18 14.95m 23.442 5.50m Pv
CM 1.6820 53.80 7.77 120 0.267226 1.72m Pf 1.265
18 14.95m 49.39 23.442 Flow (q) from Route 6 3.02m Pe
12 14.95m 24.708 mecT(3.02m) 4.74m Pv
• • • • • Route 6 • • • • •
SP 1.0490 49.39 18.33 120 2.273235 0.14m Pf 3.793
206 15.09m 49.39 11.2 19.444 Sprinkler, 1.52m Pe 0.205
18 14.95m 23.442 mecT(1.52m) 1.67m Pv
• • • • • Route 7 • • • • •
SP 1.0490 51.62 19.16 120 2.467378 0.14m Pf 4.117
207 15.09m 51.62 11.2 21.245 Sprinkler, 1.52m Pe 0.205
19 14.95m 25.568 mecT(1.52m) 1.67m Pv
CM 1.6820 12.81 1.85 120 0.018794 7.22m Pf 0.192
19 14.95m 25.568 3.02m Pe
13 14.95m 25.760 mecT(3.02m) 10.24m Pv
• • • • • Route 8 • • • • •
CM 1.6820 4.41 0.64 120 0.002613 5.50m Pf 0.014
15 14.95m 23.327 Pe
16 14.95m 23.341 5.50m Pv
• • • • • Route 9 • • • • •
CM 1.6820 44.95 6.49 120 0.191641 20.09m Pf 4.428
17 14.95m 23.428 3.02m Pe
4 14.95m 27.856 mecT(3.02m) 23.11m Pv
• • • • • Route 10 • • • • •
CM 1.6820 38.81 5.60 120 0.146025 20.09m Pf 3.374
19 14.95m 25.568 3.02m Pe
5 14.95m 28.942 mecT(3.02m) 23.11m Pv
• • • • • Route 11 • • • • •
CM 1.6820 33.06 4.77 120 0.108552 27.31m Pf 3.619
14 14.95m 26.989 mecT(3.02m) 6.03m Pe
6 14.95m 30.608 mecT(3.02m) 33.34m Pv
Equivalent Pipe Lengths of Valves and Fittings (C=120 only) C Value Multiplier
4.87