Hydraulic Overview Job Number: 03052021

Report Description: Ordinary Group I


Job
Job Number Design Engineer
03052021 Gino Montoya
Job Name: Phone FAX

PROYECTO MONTREAL 3044003430


Address 1 State Certification/License Number

MEDELLIN
Address 2 AHJ

INGESED SAS
Address 3 Job Site/Building

System
Density Area of Application
0.150gpm/ft² 139.35m² (Actual 211.75m²)
Most Demanding Sprinkler Data Hose Streams

11.2 K-Factor 48.95 at 19.100 250.00


Coverage Per Sprinkler Number Of Sprinklers Calculated
30.25m² 7
System Pressure Demand System Flow Demand
82.026 346.93
Total Demand Pressure Result

596.93 @ 82.026 +86.419 (51.3%)


Supplies Check Point Gauges
Node Name Flow(gpm) Hose Flow(gpm) Static(psi) Residual(psi) Identifier Pressure(psi) K-Factor(K) Flow(gpm)
10 Water Supply 750.00 250.00 175.000 165.000

MONTREAL Water Supply at Node 10 (750.00, 250.00, 175.000, 165.000)

© M.E.P.CAD, Inc. AutoSPRINK® VR11 v11.0.30.0 03/05/2021 20:56:40 Page 1


Hydraulic Summary Job Number: 03052021
Report Description: Ordinary Group I
Job
Job Number Design Engineer
03052021 Gino Montoya
Job Name: State Certification/License Number

PROYECTO MONTREAL
Address 1 AHJ

MEDELLIN
Address 2 Job Site/Building

INGESED SAS
Address 3 Drawing Name

MONTREAL
System Remote Area(s)
Most Demanding Sprinkler Data Occupancy Job Suffix

11.2 K-Factor 48.95 at 19.100 Ordinary Group I


Hose Allowance At Source Density Area of Application

250.00 0.150gpm/ft² 139.35m² (Actual 211.75m²)


Additional Hose Supplies Number Of Sprinklers Calculated Coverage Per Sprinkler

Node Flow(gpm) 7 30.25m²


AutoPeak Results: Pressure For Remote Area(s) Adjacent To Most Remote Area

Total Hose Streams

250.00
System Flow Demand Total Water Required (Including Hose Allowance)

346.93 596.93
Maximum Pressure Unbalance In Loops

0.000
Maximum Velocity Above Ground
20.41 between nodes 8 and 7
Maximum Velocity Under Ground

Volume capacity of Wet Pipes Volume capacity of Dry Pipes

568.05gal
Supplies
Hose Flow Static Residual Flow Available Total Demand Required Safety Margin
@ @
Node Name (gpm) (psi) (psi) (gpm) (psi) (gpm) (psi) (psi)
10 Water Supply 250.00 175.000 165.000 750.00 168.445 596.93 82.026 86.419

Contractor
Contractor Number Contact Name Contact Title

Name of Contractor: Phone Extension

Address 1 FAX

Address 2 E-mail

Address 3 Web-Site

© M.E.P.CAD, Inc. AutoSPRINK® VR11 v11.0.30.0 03/05/2021 20:56:53 Page 2


Hydraulic Graph Job Number: 03052021
Report Description: Ordinary Group I

Water Supply at Node 10

Hydraulic Graph

Water Supply at Node 10


Static: Pressure Elevation + Static: Pressure

175.000 178.983
Residual: Pressure

165.000 @ 750.00
Available Pressure at Time of Test
168.445 @ 596.93
System Demand

82.026 @ 346.93
System Demand (Including Hose Allowance at Source)

82.026 @ 596.93

© M.E.P.CAD, Inc. AutoSPRINK® VR11 v11.0.30.0 03/05/2021 20:57:05 Page 3


Summary Of Outflowing Devices Job Number: 03052021
Report Description: Ordinary Group I
Actual Flow Minimum Flow K-Factor Pressure
Device (gpm) (gpm) (K) (psi)
Sprinkler 201 48.95 48.95 11.2 19.100
Sprinkler 202 49.06 48.95 11.2 19.185
Sprinkler 203 49.26 48.95 11.2 19.346
Sprinkler 204 49.28 48.95 11.2 19.358
Sprinkler 205 49.37 48.95 11.2 19.432
Sprinkler 206 49.39 48.95 11.2 19.444
Sprinkler 207 51.62 48.95 11.2 21.245
Most Demanding Sprinkler Data

© M.E.P.CAD, Inc. AutoSPRINK® VR11 v11.0.30.0 03/05/2021 20:57:18 Page 4


Node Analysis Job Number: 03052021
Report Description: Ordinary Group I
Node Elevation(Meter) Fittings Pressure(psi) Discharge(gpm)
10 2.80m S 82.026 346.93
201 15.09m Spr(-19.100) 19.100 48.95
202 15.09m Spr(-19.185) 19.185 49.06
203 15.09m Spr(-19.346) 19.346 49.26
204 15.09m Spr(-19.358) 19.358 49.28
205 15.09m Spr(-19.432) 19.432 49.37
206 15.09m Spr(-19.444) 19.444 49.39
207 15.09m Spr(-21.245) 21.245 51.62
1 14.95m mecT(1.52m) 23.036
2 14.95m mecT(2.27m) 24.601
3 14.95m mecT(3.02m) 25.403
4 14.95m mecT(3.02m) 27.856
5 14.95m mecT(3.02m) 28.942
6 14.95m mecT(3.02m) 30.608
7 14.95m T(5.02m) 32.654
8 14.95m mecT(5.02m) 63.209
9 2.80m E(4.01m) 81.960
11 14.95m mecT(1.52m) 23.136
12 14.95m mecT(2.27m) 24.708
13 14.95m mecT(2.27m) 25.760
14 14.95m mecT(2.27m) 26.989
15 14.95m mecT(1.52m) 23.327
16 14.95m mecT(1.52m) 23.341
17 14.95m mecT(1.52m) 23.428
18 14.95m mecT(1.52m) 23.442
19 14.95m mecT(1.52m) 25.568

© M.E.P.CAD, Inc. AutoSPRINK® VR11 v11.0.30.0 03/05/2021 20:57:29 Page 5


Hydraulic Analysis Job Number: 03052021
Report Description: Ordinary Group I
Pipe Type Diameter Flow Velocity HWC Friction Loss Length Pressure
Downstream Elevation Discharge K-Factor Pt Pn Fittings Eq. Length Summary
Upstream Total Length
• • • • • Route 1 • • • • •
SP 1.0490 48.95 18.17 120 2.235995 0.14m Pf 3.731
201 15.09m 48.95 11.2 19.100 Sprinkler, 1.52m Pe 0.205
1 14.95m 23.036 mecT(1.52m) 1.67m Pv
BL 1.4420 48.95 9.62 120 0.474774 1.03m Pf 1.565
1 14.95m 23.036 2.27m Pe
2 14.95m 24.601 mecT(2.27m) 3.30m Pv
CM 2.6350 59.09 3.48 120 0.035711 19.11m Pf 0.802
2 14.95m 24.601 3.35m Pe
3 14.95m 25.403 2LtE(1.67m) 22.46m Pv
CM 2.6350 103.95 6.12 120 0.101516 17.47m Pf 2.453
3 14.95m 44.85 25.403 Flow (q) from Route 3 6.70m Pe
4 14.95m 27.856 LtE(1.67m), T(5.02m) 24.16m Pv
CM 2.6350 148.90 8.76 120 0.197376 5.50m Pf 1.086
4 14.95m 44.95 27.856 Flow (q) from Route 9 Pe
5 14.95m 28.942 5.50m Pv
CM 2.6350 187.71 11.04 120 0.302966 5.50m Pf 1.666
5 14.95m 38.81 28.942 Flow (q) from Route 10 Pe
6 14.95m 30.608 5.50m Pv
CM 2.6350 220.77 12.99 120 0.409015 5.00m Pf 2.046
6 14.95m 33.06 30.608 Flow (q) from Route 11 Pe
7 14.95m 32.654 5.00m Pv
CM 2.6350 346.93 20.41 120 0.943792 13.54m Pf 30.555
7 14.95m 126.15 32.654 Flow (q) from Route 2 18.83m Pe
8 14.95m 63.209 T(5.02m), 2f(-0.000), CV(5.86m), 32.37m Pv
BV(2.93m), mecT(5.02m)
FR 4.2600 346.93 7.81 120 0.090961 12.15m Pf 1.470
8 14.95m 63.209 4.01m Pe 17.281
9 2.80m 81.960 E(4.01m) 16.16m Pv
CM 4.2600 346.93 7.81 120 0.090961 0.72m Pf 0.066
9 2.80m 81.960 Pe
10 2.80m 82.026 Water Supply 0.72m Pv
250.00 Hose Allowance At Source
10 596.93

• • • • • Route 2 • • • • •
SP 1.0490 49.06 18.21 120 2.245164 0.14m Pf 3.746
202 15.09m 49.06 11.2 19.185 Sprinkler, 1.52m Pe 0.205
11 14.95m 23.136 mecT(1.52m) 1.67m Pv
BL 1.4420 49.06 9.64 120 0.476721 1.03m Pf 1.572
11 14.95m 23.136 2.27m Pe
12 14.95m 24.708 mecT(2.27m) 3.30m Pv
CM 2.6350 146.40 8.61 120 0.191294 5.50m Pf 1.052
12 14.95m 43.54 24.708 Flow (q) from Route 4 Pe
13 14.95m 25.760 5.50m Pv
CM 2.6350 159.22 9.37 120 0.223414 5.50m Pf 1.229
13 14.95m 12.81 25.760 Flow (q) from Route 7 Pe
14 14.95m 26.989 5.50m Pv
CM 2.6350 126.15 7.42 120 0.145244 32.31m Pf 5.665
14 14.95m 26.989 6.70m Pe
7 14.95m 32.654 LtE(1.67m), T(5.02m) 39.01m Pv
• • • • • Route 3 • • • • •
SP 1.0490 49.26 18.29 120 2.262630 0.14m Pf 3.775
203 15.09m 49.26 11.2 19.346 Sprinkler, 1.52m Pe 0.205
15 14.95m 23.327 mecT(1.52m) 1.67m Pv
CM 1.6820 44.85 6.48 120 0.190834 7.87m Pf 2.077
15 14.95m 23.327 3.02m Pe
3 14.95m 25.403 mecT(3.02m) 10.88m Pv
• • • • • Route 4 • • • • •
SP 1.0490 49.28 18.29 120 2.263947 0.14m Pf 3.777
204 15.09m 49.28 11.2 19.358 Sprinkler, 1.52m Pe 0.205
16 14.95m 23.341 mecT(1.52m) 1.67m Pv
CM 1.6820 53.69 7.75 120 0.266161 1.72m Pf 1.260
16 14.95m 4.41 23.341 Flow (q) from Route 8 3.02m Pe
2 14.95m 24.601 mecT(3.02m) 4.74m Pv
CM 2.6350 43.54 2.56 120 0.020296 5.24m Pf 0.106
2 14.95m 24.601 Pe
12 14.95m 24.708 5.24m Pv
• • • • • Route 5 • • • • •
SP 1.0490 49.37 18.33 120 2.271914 0.14m Pf 3.791
205 15.09m 49.37 11.2 19.432 Sprinkler, 1.52m Pe 0.205
17 14.95m 23.428 mecT(1.52m) 1.67m Pv
© M.E.P.CAD, Inc. AutoSPRINK® VR11 v11.0.30.0 03/05/2021 20:57:42 Page 6
Hydraulic Analysis Job Number: 03052021
Report Description: Ordinary Group I
Pipe Type Diameter Flow Velocity HWC Friction Loss Length Pressure
Downstream Elevation Discharge K-Factor Pt Pn Fittings Eq. Length Summary
Upstream Total Length
CM 1.6820 4.42 0.64 120 0.002621 5.50m Pf 0.014
17 14.95m 23.428 Pe
18 14.95m 23.442 5.50m Pv
CM 1.6820 53.80 7.77 120 0.267226 1.72m Pf 1.265
18 14.95m 49.39 23.442 Flow (q) from Route 6 3.02m Pe
12 14.95m 24.708 mecT(3.02m) 4.74m Pv
• • • • • Route 6 • • • • •
SP 1.0490 49.39 18.33 120 2.273235 0.14m Pf 3.793
206 15.09m 49.39 11.2 19.444 Sprinkler, 1.52m Pe 0.205
18 14.95m 23.442 mecT(1.52m) 1.67m Pv
• • • • • Route 7 • • • • •
SP 1.0490 51.62 19.16 120 2.467378 0.14m Pf 4.117
207 15.09m 51.62 11.2 21.245 Sprinkler, 1.52m Pe 0.205
19 14.95m 25.568 mecT(1.52m) 1.67m Pv
CM 1.6820 12.81 1.85 120 0.018794 7.22m Pf 0.192
19 14.95m 25.568 3.02m Pe
13 14.95m 25.760 mecT(3.02m) 10.24m Pv
• • • • • Route 8 • • • • •
CM 1.6820 4.41 0.64 120 0.002613 5.50m Pf 0.014
15 14.95m 23.327 Pe
16 14.95m 23.341 5.50m Pv
• • • • • Route 9 • • • • •
CM 1.6820 44.95 6.49 120 0.191641 20.09m Pf 4.428
17 14.95m 23.428 3.02m Pe
4 14.95m 27.856 mecT(3.02m) 23.11m Pv
• • • • • Route 10 • • • • •
CM 1.6820 38.81 5.60 120 0.146025 20.09m Pf 3.374
19 14.95m 25.568 3.02m Pe
5 14.95m 28.942 mecT(3.02m) 23.11m Pv
• • • • • Route 11 • • • • •
CM 1.6820 33.06 4.77 120 0.108552 27.31m Pf 3.619
14 14.95m 26.989 mecT(3.02m) 6.03m Pe
6 14.95m 30.608 mecT(3.02m) 33.34m Pv

Equivalent Pipe Lengths of Valves and Fittings (C=120 only) C Value Multiplier
4.87

( Actual Inside Diameter


Schedule 40 Steel Pipe Inside Diameter ) = Factor
Value Of C
Multiplying Factor
100
0.713
130
1.16
140
1.33
150
1.51

© M.E.P.CAD, Inc. AutoSPRINK® VR11 v11.0.30.0 03/05/2021 20:57:42 Page 7


Hydraulic Analysis Job Number: 03052021
Report Description: Ordinary Group I
Pipe Type Diameter Flow Velocity HWC Friction Loss Length Pressure
Downstream Elevation Discharge K-Factor Pt Pn Fittings Eq. Length Summary
Upstream Total Length
Pipe Type Legend Units Legend Fittings Legend
AO Arm-Over Diameter Inch ALV Alarm Valve
BL Branch Line Elevation Meter AngV Angle Valve
CM Cross Main Flow gpm b Bushing
DN Drain Discharge gpm BalV Ball Valve
DR Drop BFP Backflow Preventer
Velocity fps
DY Dynamic BV Butterfly Valve
FM Feed Main Pressure psi
C Cross Flow Turn 90°
FR Feed Riser Length Meter cplg Coupling
MS Miscellaneous Friction Loss psi/Meter Cr Cross Run
OR Outrigger HWC Hazen-Williams Constant CV Check Valve
RN Riser Nipple Pt Total pressure at a point in a pipe DelV Deluge Valve
SP Sprig Pn Normal pressure at a point in a pipe DPV Dry Pipe Valve
ST Stand Pipe Pf Pressure loss due to friction between points E 90° Elbow
UG Underground Pe Pressure due to elevation difference between indicated EE 45° Elbow
Ee1 11¼° Elbow
points
Ee2 22½° Elbow
Pv Velocity pressure at a point in a pipe f Flow Device
fd Flex Drop
FDC Fire Department Connection
fE 90° FireLock(TM) Elbow
fEE 45° FireLock(TM) Elbow
flg Flange
FN Floating Node
fT FireLock(TM) Tee
g Gauge
GloV Globe Valve
GV Gate Valve
Ho Hose
Hose Hose
HV Hose Valve
Hyd Hydrant
LtE Long Turn Elbow
mecT Mechanical Tee
Noz Nozzle
P1 Pump In
P2 Pump Out
PIV Post Indicating Valve
PO Pipe Outlet
PRV Pressure Reducing Valve
PrV Pressure Relief Valve
red Reducer/Adapter
S Supply
sCV Swing Check Valve
Spr Sprinkler
St Strainer
T Tee Flow Turn 90°
Tr Tee Run
U Union
WirF Wirsbo
WMV Water Meter Valve
Z Cap

© M.E.P.CAD, Inc. AutoSPRINK® VR11 v11.0.30.0 03/05/2021 20:57:42 Page 8