Professional Documents
Culture Documents
AK Grounding Report IFC
AK Grounding Report IFC
ADIRONDACK SUBSTATION
GROUNDING CALCULATION AND REPORT
REV
DATE DOCUMENT NAME PREPARED CHECKED REVIEWED APPROVED
NO.
ADIRONDACK SUBSTATION
0 02/17/2023 GROUNDING CALCULATION AND SN PB JK GP
REPORT
TABLE OF CONTENTS
7.0 RESULTS/CONCLUSIONS.................................................................................................. 5
Page1
The calculation objective is to design a ground grid for Adirondack Substation and confirm
that the ground grid is adequate to ensure that a ground fault will be safe to personnel in
and around the new substation by analyzing the safe touch and step potentials.
Adirondack Substation is a six position 345/115kV breaker and a half substation
arrangement with five transmission lines; two 345kV lines to Haverstock Substation, one
345kV line to Marcy Substation, one 345kV line to Austin Road Substation, one auto
transformer for one 115kV line to Beaver Falls Substation. The additional major electrical
equipment includes the autotransformer’s 13.8kV tertiary for station service, one future
345kV position, two 345kV 140MVAR capacitor banks, and two 345kV 100MVAR shunt
reactor.
2.0 ASSUMMPTIONS
None
3.9. All vertical column (drilled pier) foundations are represented as Steel Re-Bar Concrete
Electrodes and electrically connected to the main ground grid for additional vertical
grounding conductors.
3.10. Ground Enhancement Material (G.E.M) of rod length 100 ft and well diameter of 12 inch
is required. The rod conductor is coupled 10ft ¾ inch copper clad ground rods centered
within the G.E.M for the entire depth of the ground well. The G.E.M. wells are located at
the four corners of the substation, connected to the ground grid perimeter conductor 3
feet outside the substation fence.
3.11. The number of 345kV transmission lines is four (4), 115kV lines is one (1); therefore, the
total number of transmission lines are five (5). The total number of distribution feeders is
zero (0).
3.12. A crush rock surface, with a 2,000 ohm-meter resistivity and thickness of 6 inches, is over
the entire substation and extends 6 feet beyond the substation fence. As shown in
Grading Plan Cross Section Drawing (Attachment #4), a 24 inches of permeable top rock
surface with three layers of different rock types is utilized with infiltration rate of greater
than 0.5 inch/hour. The top surface layer consists of 6 inches of surface course rock,
followed by 8 inches of filter course rock and 10 inches thickness of reservoir course rock.
Between the filter course rock and reservoir course rock is a layer of non-woven filter
fabric material. The entire surface rock is modeled as a single layer of 24 inches of top
rock in the software.
3.13. The ground grid and all substation grounding are in accordance with NYPA’s Design
Criteria and Construction Standards.
3.14. Soil Resistivity and soil characteristics
a. Soil resistivity data was obtained during a soil investigation by Atlantic Testing
Laboratories during November 2021 using the Wenner 4-Point Soil-Resistivity Test
Method. Measurements were performed at two locations along two traverses at
each location in the vicinity of the proposed substation. The exact locations of the
traverses as well as the actual resistivity measurements are included in Attachment
#1. All four traverses (the results from both tests) were entered into WINIGS to
obtain the two-layer soil model shown in Section 7.1
4.1. IEEE Std 80-2013 – IEEE Guide for Safety in AC Substation Grounding
4.2. NYPA Substation Design Guide, Section 9 – Grounding
4.3. NYPA Substation Design Criteria Document, Smart Path Connect, Burns and McDonnel
Consultants, P.C. Rev C
4.4. Atlanta Testing Laboratories, ATL Report No. CD10187E-02-10-21_NYPA Smart Path
Connect –Proposed Adirondack Substation, dated November 02, 2021.
4.5. National Grid stormwater management standard drawing C-101
Page3
5.0 APPROACH/METHODOLOGY
5.1. The resistivity data that was measured in 2021 is included in Attachment #1. The
resistivity data that was measured (four sets of readings) was entered into and used by
WINIGS version 7.7C to compute the Dynamic Model Fit Report and resulting Two-Layer
Soil Model required for the calculation. The two-layer soil model is included in
Attachment #5.
5.2. The soil condition results revealed poor conductivity (highly resistive) which created
difficulty in establishing safe touch potentials within reach of the substation perimeter
fence. An additional grounding conductor 6 feet outside the substation fence (on the edge
of the insulating rock) and four Ground Enhancement Material wells were needed to
lower the touch potentials within a tolerated value.
5.3. The ground grid is optimally designed based on the minimally acceptable grid dimensions.
Several iterations of different size grids were analyzed using the WINIGS computer
program. The minimum-sized grid was determined to be 15-ft x 15-ft. The ground-grid
layout is shown in Attachment #6.
5.4. No Vertical Ground Rod were included in the design due to the poor soil conditions as the
addition of ground rod on the substation (or at transmission line crossing) do not provide
benefits to the grounding system.
5.5. Fault current through the grid:
a. The substation grounding is designed to be safe for a fault current of 19.8kA with a
fault duration of 0.50 seconds as specified in the NYPA Design Criteria.
b. During a ground fault event, the fault current splits through all conductive paths,
including the ground grid, ground/shield wires and the earth. For transmission and
distribution stations, IEEE Std 80-2013 considers the design of a ground grid based on
fault current returning to ground through shield wires on overhead and armor on
underground power lines. As such, part of the fault current is diverted to areas outside
the substation, thereby reducing the amount of fault current injected into the ground
grid.
c. To determine the split factor, the proposed layout of the Adirondack substation
consists of seven (5) transmission lines and zero (0) distribution feeders; the one-line
diagram is included in Attachment #2.
d. Split factor for this study was estimated using the current splits curve extracted from
the IEEE Std 80-2013 Figure C.19 which is included in Attachment #8. It was
determined using the graphical method at a grid resistance of 14.09 ohms obtained
for the design from the WinIGS software. The Rp value intersects the 5/0 interpreted
curve at a split factor of 0.02. A conservative value of 20% split factor was chosen to
model the grounding system. The fault current is multiplied by the split factor to
obtain the current through the ground grid which is calculated as (Fault Current X Split
Factor = 19.8 * 20%) 3.96kA.
Page4
6.0 COMPUTATIONS
Computations were performed using WINIGS Version 7.7C Software. Data input and all
computation results can be found in Attachment #10.
7.0 RESULTS/CONCLUSIONS
7.1 WINIGS was used to calculate the two-layer soil model using the resistivity data shown in
Attachment #1 as described above. Table 7.1 summarizes the resistivity, tolerance, and
thickness of the layers. Further soil model details are included in Attachment #5.
Table 7.1 Two Layer soil model computed by WinIGS
7.2 The design provided use of a Copper 4/0 AWG, 19 strand, annealed, soft drawn, 100%
conductivity. This conductor exceeds the minimum requirement and is an industry
standard size.
7.3 The designed grid (15 ft X 15 ft) as shown in Attachment #6 meets the safety criteria set
out by IEEE 80-2013. Areas where the maximum touch potential exceeds the minimum
safety threshold outside the station is beyond the reach of hazardous surfaces and is also
considered safe.
7.4 Calculated maximum permitted and achieved step and touch values are as follows:
8.0 ATTACHMENTS
Page6
ATL Project No. CD10187 Project: NYPA Smart Path Connect - Adirondack SS
Client: United ECI Test Date/Time: 10/15/2021: 9:02 - 9:53 AM
Weather Condition Cloudy Soil Condition: Agricultural Field, Low-Growth, Wet
Ambient Temperature: 60 ⁰F Test Method: Wenner 4-Pin Soil Resistivity Test
Test Completed by: I. Spelta / K. Jones ASTM G 57 / IEEE 81
Test Instrument: Advanced Geosciences, Inc. - SuperSting R1/IP, Serial No.: SS1812054
DC-Memory Earth Resistivity Meter
700,000
650,000
600,000
550,000
500,000
450,000
400,000
350,000 SRTͲ1[NͲS]
300,000 SRTͲ1[EͲW]
SRTͲ1AVERAGE
250,000
200,000
150,000
100,000
50,000
0
0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85
Probe Spacing 'a', [ft]
ATLANTIC TESTING LABORATORIES, Limited
ATL Project No. CD10187 Project: NYPA Smart Path Connect - Adirondack SS
Client: United ECI Test Date Time: 10/15/2021: 09:56 - 10:48 PM
eather Condition Cloudy Soil Condition: Agricultural Field, Low-Growth, Wet
Ambient Temperature: 60϶F Test ethod: Wenner 4-Pin Soil Resistivity Test
Test Completed by: I. Spelta / K. Jones ASTM G 57 / IEEE 81
Test nstrument: Advanced Geosciences, Inc. - SuperSting R1/IP, Serial No.: SS1812054
DC-Memory Earth Resistivity Meter
500,000
450,000
400,000
350,000
300,000
SRTͲ2[NͲS]
250,000
SRTͲ2[EͲW]
200,000 SRTͲ2AVERAGE
150,000
100,000
50,000
0
0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85
Probe Spacing 'a', [ft]
Attachment #2
One- Line Diagram and General Arrangement
ST. LAWRENCE-FDR POWER PROJECT
MASSENA, NEW YORK
(100-AK) ADIRONDACK SUBSTATION
ST. LAWRENCE-FDR POWER PROJECT
MASSENA, NEW YORK
(100-AK) ADIRONDACK SUBSTATION
LEGEND ST. LAWRENCE-FDR POWER PROJECT
MASSENA, NEW YORK
(100-AK) ADIRONDACK SUBSTATION
ISSUED FOR
CONSTRUCTION
Attachment #3
ASPEN OneLiner Version 14.8 Bus Fault Summary
ASPEN OneLiner Version 14.8 Bus Fault Summary
11
15
109
4
OHW
OHW
OHW
OHW
OHW
OHW
11
OHW
OHW
OHW
OHW
OHW
32
OHW
OHW
OHW
OHW
OHW
OHW OHW
OHW OHW
OHW OHW
OHW OHW
OHW OHW
OHW OHW
OHW OHW
OHW
OHW
OHW
OHW
OHW
OHW
OHW
OHW
OHW
OHW
OHW OHW
OHW OHW
OHW OHW
OHW OHW
OHW OHW
OHW OHW
OHW
OHW
110
OHW
OHW
OHW
0
OHW
OHW
OHW
OHW
OHW
OHW
OHW
OHW
11
OHW
OHW
OHW
OHW
05
1110
11
17
1113
11
20
OHW
OHW
OHW
OHW
OHW
OHW
OHW
OHW
OHW
OHW
OHW
OHW
OHW
OHW
OHW
OHW
OHW OHW
OHW OHW
OHW OHW
OHW OHW
OHW OHW
OHW OHW
OHW
OHW OHW
OHW
OHW
OHW
OHW
OHW
OHW
OHW
OHW
OHW OHW
OHW OHW
OHW OHW
OHW OHW
OHW OHW
OHW OHW
OHW OHW
OHW
OHW
OHW
OHW
OHW
OHW
OHW
OHW
OHW
OHW
OHW
OHW
OHW
OHW
OHW
OHW
1130
1134
1132
1133
11
34
113
5
1134
1130
1130
1135
1137
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
1138
ISSUED FOR
CONSTRUCTION
1140
1137
1140
1137
≥
Soil Resistivity:
Grid Resistance:
Safety Criteria:
Grid Resistance:
Surface Material:
Conductor Size Used:
Touch Voltage:
Step Voltage:
Attachment #11
Optimized Grounding Grid Layout Drawing
·
·
·
·
·