Ventilation Re-Commendation C18 - 650 KVA Standby

You might also like

Download as doc, pdf, or txt
Download as doc, pdf, or txt
You are on page 1of 1

Ventilation Re-commendation for Each Cat C18,

650 KVA Standby Rated Diesel Generator Set

Sl.No. Description Re-commendation

1. Direction of air flow Ideally intake and discharge


should be at 180 Deg. Fresh
air intake to be at the rear
side( alternator side) of
genset and hot air discharge
to be in front of the radiator.
Installation contractor to
ensure that short circuiting of
fresh air and discharge air
doesn’t take place.

2. Minimum cooling + combustion


air flow + 20% Fouling Factor
for Each Genset
Calculation 829.20 m3/min
a) Cooling Air Flow – 660 m3/min
b) Combustion Air Flow – 31 m3/min
c) Total(a + b) = 691 m3/min
d) Fouling Factor(20%of’c)- 138.20 m3/min
e) Total Air Flow(a+b+d)- 829.20 m3/min
3. Maximum allowable system 120 Pascals
restriction
4. Maximum allowable air velocity 3-4 Mtr / Sec