Installation contractor to
ensure that short circuiting of
fresh air and discharge air
doesn’t take place.
2 Minimum cooling + combustion air flow + 1,747 M3/Min
20% Fouling Factor for Each Genset
Calculation
a) Cooling Air Flow – 1,355 M 3/Min
b) Combustion Air Flow – 101 M 3/Min
c) Total(a + b) = 1,456 M 3/Min
d) Fouling Factor (20% of c)–291 M 3/Min
e) Total Air Flow(a+b+d)- 1747 M 3/Min