Manhole Schedule

You might also like

Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 7

Cover Distance to Pipe size Invert Manhole Cover Manhole Class

Maximim weight
Usage
Claculation Mnhole Cover Duty Level next MH. Slope Level Depth size shpe / size Vent GRP seal Tonn
method NO. of MH. Connectin cover
mt mt mm mt mm mm Light Duty (A15) 1.5 Very light duty for pedestrian areas like gardens, patios and driveways
First Manhole MH-01 Medium Duty (C250) 17.98 5.411 200 mm 1 : 120 17.08 0.90 600 X 600 600 X 600 □ Yes Medium Duty (C250) 25 Lightly trafficked roads and small private car parks
Normal Slope MH-02 Medium Duty (C250) 17.72 11.197 200 mm 1 : 120 17.03 0.68 600 X 600 600 X 600 □ Heavy Duty (D400) 40 Main roads, highways and high traffic areas like public car parks
Normal Slope MH-03 Heavy Duty (D400) 17.53 4.553 200 mm 1 : 120 16.94 0.59 600 X 600 600 X 600 □
Revers Slope (Branch) MH-3A Heavy Duty (D400) 17.43 11.502 200 mm 1 : 120 16.98 0.45 600 X 600 600 X 600 □
FIC MH-04(FIC) Heavy Duty (D400) 17.43 200 mm FIC 15.53 0.58/1.9 600 X 600 1000 Օ Yes Yes
DESIGN CALCULATION SHEET
Sump pump calculation
PROJECT
LOCATION AND PLOT NO
CLIENT

DATE YY MM DD REV. NO

MINIMUM PUMP FLOW RATE = 75

TOTAL LENGTH OF PIPES TILL PBM = 100

STATIC HEAD = 10

TOTAL PRESSURE DROP = 1.9

NUMBER OF PUMPS = 2

REQUIRED POWER CALCULATIONS


REQUIRED POWER (EACH PUMP) = 1.8

REQUIRED POWER (DUTY+ASSIST) = 3.6

SUMP PIT VOLUME


TIME REQUIRED TO EMPTY THE PIT WITH ONE = 600
DRAIN PIPE ENTRY LEVEL = -0.3

PIT MINIMUM HEIGHT BELOW PIPE ENTRY = 1.2

MINIMUM REQUIRED VOLUME = 1.42

PIT HEIGHT = 1.5

PIT LENGTH X WIDTH = 1.54

PUMP SCHDEU

Pump configuration Each pump

SN Reference Flow rate Head


Duty & Assist Stand-by
GPM BAR

1 SUMP-01 2 N/A 37.5 1.9


LCULATION SHEET

REV. NO

BASED ON SPRINKLERS ACTIVATING , 60 MINUTES OF FIRE PUMP


GPM OPERATION AND 180 MINUTES OF SUMP PUMP TO REMOVE THE
WATER

MT INPUT THE TOTAL LENGTH OF DICHARGE PIPES

Water Height REMEMBER TO ACCOUNT FOR PIT DEPTH

BAR WITH SAFETY MARGIN 25 %

PUMPS ONE DUTY AND ONE ASSIST / STAND BY

KW

KW

SECONDS
MT

MT

X 1.54

PUMP SCHDEULE

Each pump
Total power
Power Speed Pressure Vessel
VFD
controlled
KW RPM kw Hz

1.8 2900 NO 3.6 50 N/A


63 10.5 42

63 10.5 42

10.5 42

63 10.5 42

63 10.5 42

You might also like