Service Bulletin
No.: 0 2 9 6 - 0 0 2
Date: Feburary 28, 1996
Machine Model: All M-Plus NC Type:
Serial No. Range: Software Version:
Author: Training Center - Tony Mader
Subject: Writing to PLC parameters (R - Registers)

Remarks:

Listed below are three ways of displaying R - Registers on the M-Plus controls.

1. Bit Form (16 bit register) see Method 1 listed below.


2. Short data form (16 bit decimal value) see Method 2 listed below.
3. Long data form (32 bit decimal value) see Method 3 listed below.
* Parameter listing, 1 series of electrical book.

Method 1. (Bit Form) (Starts at R2100).


- Select Diagnos Display
- Select Version
- Select Diagnos Monitor
- Cursor to I/O Monitor Write (Not Memory Monitor)
- Under Adrss Enter Parameter No.
- Cursor right to Hex
- Enter Hex no. for 16 bit reg.
- Power NC OFF/ON

Method 2. (Short Data Form) (Starts at R2110)


- Select Diagnos Monitor.
- Cursor to I/O Monitor Write
- Enter Parameter No.
- Cursor right 2X to Decimal.
- Enter Parameter Value
- Power NC OFF/ON

Method 3. (Long Data Form) (Starts at R2300)


- Select Diagnos Monitor
- Cursor to I/O Monitor Write
- Enter Parameter No.
- Cursor Right 2X to Decimal
- Press Menu Button No. 1 [Long] (pink block covers 2 parameters)
- Enter Parameter Value
- Power NC OFF/ON

* If changes are permanent, do back-up to EEPROM's

Approved By: Page 1 of 1