Professional Documents
Culture Documents
Modbus en 1 14
Modbus en 1 14
Modbus en 1 14
8193 8193 u 16bit High (12bit): part number; Low (4bit):device version
---
HHHH HHHH HHHH LLLL
8228 8228 u 8bit Number of hours of the current day (internal time)
0-23h
8230 8230 u 8bit Minima voltage of the 3 phase network of the current day (internal time)
Voltage = (transferred value) * 4
0-1020V
8231 8231 u 8bit Total underrun undervoltage limit 1 for the current hour internal time
8233 8233 u 8bit Minimum voltage 3 phase AC before 48-72h internal clock
0 ... 1020V in 4V steps
8234 8234 u 8bit Minimum voltage 3 phase AC before 48-72h internal clock
0 … 1020V in 4V stepsk
8235 8235 u 8bit Minimum voltage 3 phase AC before 96-120h internal clock
0 ... 1020V in 4V steps
8236 8236 u 8bit Minimum voltage 3 phase AC before 120- 144h internal clock
0 ... 1020V in 4V steps
8237 8237 u 8bit Minimum voltage 3 phase AC before 144- 168h internal clock
0 ... 1020V in 4V steps
8241 8241 u 8bit Maximum voltage of the 3 phase network of the current day (internal time)
Voltage = (transmitted value) * 4
0-1020V
8242 8242 u 8bit Maximum voltage of the 3-phase network of the last day (current day - 1 day, internal
time)
Voltage = (transmitted value) * 4
0-1020V
8243 8243 u 8bit Maximum voltage of the 3-phase network of the penultimate day (current day - 2 days,
internal time)
Voltage = (transmitted value) * 4
0-1020V
8244 8244 u 8bit Maximum voltage of the 3-phase network of the third last day (current day - 3 days,
internal time)
Voltage = (transmitted value) * 4
0-1020V
8245 8245 u 8bit Maximum voltage of the 3-phase network of the penultimate day (current day - 4 days,
internal time)
Voltage = (transmitted value) * 4
0-1020V
8246 8246 u 8bit Maximum voltage of the 3-phase network of the fifth-to-last day (current day - 5 days,
internal time)
Voltage = (transmitted value) * 4
0-1020V
8247 8247 u 8bit Maximum voltage of the 3 phase network of the sixth last day (current day - 6 days,
internal time)
Voltage = (transmitted value) * 4
0-1020V
8303 8303 u 16bit Sum of shutdowns due to sensor short circuit alarm
8306 8306 u 16bit Sum of shutdowns due to motor temp static alarm
8331 8331 u 16bit Sum of lockouts due to wrong phase sequence alarm
8352 8352 u 8bit Error memory: Error number of the last error
8353 8353 u 8bit Error memory: time difference of the last error to the previous
in the range 0.. .120 = value in minutes
in the 121…238 = value in hours 3..120 h