Engine Starting

You might also like

Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 1

Operating Procedure (PERKINS)

1. Pre-Start Checks:
a. Visual Inspection: - Check for any visible damage, leaks, or loose connections.
- Inspect the fuel and coolant levels.
b. Fluid Levels:
- Ensure there is sufficient fuel and coolant in the respective tanks.
c. Battery:
- Check the battery terminals for corrosion.
- Ensure the battery is fully charged.
d. Oil Level:
- Check the oil level and top up if necessary.
2. Start-up Procedure:
a. Switch Off Electrical Loads:
- Disconnect all electrical loads from the genset before starting.
- Set the selector switch to Genset
- Set the ATS to standby mode
b. Control Panel:
- Turn on the control panel and verify that all indicators are normal.
c. Start the Genset:
- Turn on the breaker of Genset
- Turn the start key and press the start button
- Monitor for any abnormal noises or vibrations during startup.
e. Monitor Gauges:
- Watch the gauges for oil pressure, coolant temperature, and voltage. Ensure they stabilize within normal
ranges.
3. During Operation:
a. Load Connection:
- Gradually connect electrical loads to the generator. - Avoid sudden or heavy loads that could damage
the genset.
b. Monitor Gauges and Indicators:
- Regularly check gauges for oil pressure, coolant temperature, voltage, and frequency. - Respond
promptly to any abnormal readings.
c. Fuel Levels:
- Keep an eye on the fuel level and refill as needed to prevent the generator from running out of fuel.
4. Shutting Down:
a. Unload the Generator:
- Disconnect electrical loads before shutting down the genset.
c. Shut Down:
- Turn off the generator using the designated controls.
d. Post-Operation Checks:
- Perform a visual inspection for any leaks or abnormalities. - Check fluid levels and top up if necessary.
5. Emergency Shutdown:
In case of any emergencies or abnormal conditions, use the emergency shutdown

You might also like