Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

HOPPECKE

Installation instructions
for stationary batteries
(Batteries / stands / cabinets)

Observe the operating instructions! 1. Requirements and preparations 1.2. Check deliveries for completeness and
Work on batteries only under instruc- for installation damage. If necessary, clean all parts before
tion of skilled personnel only, obser- assembling.
ving commissioning instructions and 1.1. Before installation ensure that the bat- 1.3. Observe all documentation included
instructions for use! tery room is clean and dry and is furnished with the delivery (e.g. battery-, rack-,
with a lockable door. The battery room must cabinet-assembly drawings).
When working on batteries wear be set out and marked with warning marks 1.4. Before renewing old batteries ensure
protective glasses and clothing! according to EN 50272-2. Particular atten- that all electric loads are switched off (sepa-
Observe the accident prevention tion must be paid to the following: rator, fuses, switches). This must be carried
rules as well as EN 50272-2, out by qualified personnel.
VDE 0105 part 1! - floor load-carrying capacity and nature
(conveying paths and battery room)
Smoking prohibited! Do not expose
- electrolyte resistance of battery installation CAUTION: Do not carry out un-
the battery to open flame, glowing
surface authorised switching!
embers or sparks as explosion and
- no ignitable sources (e.g. open flame,
fire hazard exists!
glowing objects, electric switches) near the 1.5. Open-circuit voltage measurements
Acid splashes in the eyes or on the cell openings (500 mm ”safety distance”) of individual cells or block batteries. Ensure
skin must be washed out or off with - ventilation conditions correct polarity. With unfilled and charged
plenty of water. Then consult a doc- batteries these measurements can only be
tor immediately. Clothing contami- To ensure smooth operation, coordination carried out after start-up. Fully charged
nated with acid should be washed between other persons working in the same cells have the following listed open circuit
with water! room is necessary. voltages at an electrolyte temperature of
20°C:
Explosion and fire hazard, avoid
short circuits! Caution! Metal parts of
the batteries are always live, do not
place tools or other objects on the OPzS cells DIN 40736 P1 (2.08 ± 0.01) V/C
battery! OPzS bloc batteries DIN 40737 P3 (2.08 ± 0.01) V/C
Electrolyte is strongly corrosive. max.power cells DIN 40736 P2 (2.08 ± 0.01) V/C
Under normal operating conditions solar.power cells (2.08 ± 0.01) V/C
exposure to electrolyte is impossible. GroE cells DIN 40738 (2.06 ± 0.01) V/C
Should the casing be destroyed, the
OGi cells DIN 40734 (2.08 ± 0.01) V/C
released fixed electrolyte is as corro-
sive as liquid electrolyte. OGi bloc batteries DIN 40739 (2.08 ± 0.01) V/C
OSP cells (2.11 ± 0.01) V/C
Block batteries and cells are
OSP.HC cells (2.08 ± 0.01) V/C
extremely heavy!
Ensure secure installation! USV bloc batteries (2.13 ± 0.01) V/C
Only use suitable handling OPzV cells DIN 40742 (2.08 - 2.14) V/C
equipment, tools and measuring OPzV bloc batteries DIN 40744 (2.08 - 2.14) V/C
equipment!
power.com SB / power.com HC (2.08 - 2.14) V/C
Dangerous voltage ! net.power (2.08 - 2.14) V/C
The open-circuit voltages of a battery’s indi- 2.4. Place each cell or block battery onto - If necessary, number the cells or block bat-
vidual cells must not deviate from each the rack with the correct polarity. With large teries visibly (from the battery’s positive
other more than 0.02 V. cells it is recommended that cell installation terminal to the negative terminal).
The following maximum open-circuit voltage should commence from the middle of the - Affix polarity labels for the battery
deviations for block batteries apply: rack. connectors.
4 V block batteries 0.03 V/block - Arrange cells or batteries plumb and level - After assembly completion affix nameplate
6 V block batteries 0.04 V/block with the correct polarity. integrated in operating instructions.
12 V block batteries 0.05 V/block - Distance between the cells should be approx. - Affix safety marking sign and operating
10 mm or according to the length of the instructions visibly.
Higher temperatures decrease, lower tem- connectors supplied. The batteries must not be cleaned with fea-
peratures increase the open-circuit voltage. - If necessary clean the contact surface of ther dusters or dry cloths, this could cause
With a deviation of 15 K from the nominal the terminals and connectors. electrostatic charge (explosion hazard).
temperature the open-circuit voltage - With screwed connectors:
changes by 0.01 V/cell. Should greater · Remove protective caps from terminals 3. Cabinets
deviations occur, consult the supplier. · Check
· that the terminal surfaces are properly 3.1. Cabinets with built-in battery:
2. Racks greased with neutraliser and protected - The battery cabinet is assembled on site
by means of red or blue terminal cover (observing the relevant accident preven-
2.1. Align the racks according to the instal- rings, tion rules).
lation drawing. Should an installation draw- · that the O-ring or grease groove is - Take into account additional space needed
ing be missing, the following minimum di- completely filled with neutraliser and between wall and cabinet for possible or
stances must be observed: the O-ring is seated, as specified, on planned cable entries.
the grease pad, - Remove any transport safety devices from
- To the wall: 100 mm on all sides for the · that the threaded insert is sufficiently full the built-in cells or block batteries.
cell or block container, or 50 mm for the rack. of neutraliser and the terminal contact - Check cells or block batteries for correct
- 1.5 metres by a nominal or component surface is greased. position and mechanical damage.
voltage > 120 V between non-insulated - Fit cell or block connectors and tighten
terminals or connectors and earthed parts with an insulated torque wrench 3.2. Cabinets with separately deli-
(e.g. water pipes) or between the battery’s (20 Nm  1 Nm). Caution: Screws are vered cells or block batteries:
end terminals. approved for single use.
During installation it must be ensured that - Fit row, step, tier connectors and tighten - Only filled and charged cells or block
DIN VDE 0510, Part 2, EN 50272-2 is observing the specified torques. batteries (vented or sealed) are built into
adhered to (e.g. - After fitting, the welded connectors of the cabinets.
cover electrically conductive parts with individual cells GroE/OGi/OPzS/ - Assemble cabinet, place in designated
insulating mats). OSP.HC/max.power must be aligned and location and align (observing the relevant
- To ignitable sources: For distance from the welded to the terminals as specified. accident prevention rules).
nearest cell vent see EN 50272-2. Observe the specifications under VBG 15. - Place cells or block batteries into the cabi-
- To passageways: 1.5 x cell width (in- - If necessary, fit insulating caps onto cell/ net according to assembly plan and spa-
stallation depth) but not less than 50 cm. block connectors and end terminals. cing specified, connect them and mark
- Ensure short-circuit proof installation work. (see item 2.4).
2.2. Align racks horizontally using the le- Wiring with a dielectric strength and a de-
velling parts or adjustable insulators provi- signed operating voltage above the maxi- 4. CE marking
ded. The distances of the support profiles mum possible battery system voltage must
must correspond with the cell or block bat- be used, or a distance of approx. 10 mm Since 01.01.97 an EC declaration of con-
tery size. Check rack stability and ensure between wiring and electrically conductive formity under the low voltage regulation is
that all screw and clamp connectors are parts must be kept or the connectors must required for batteries from 75 V to 1500 V
firmly seated. If stipulated, earth the rack or be furnished with additional insulation. nominal voltage with the corresponding CE
Teil-Nr. 7140203191/03.02/07.02/1 H Printed in Germany

parts thereof. Protect screw connectors from Avoid mechanical stress on the cell/ labelling on the battery. The battery installer
corrosion. battery terminals. of the battery plant is responsible for issuing
Please note that when using wooden racks - If applicable, remove transport plugs and the declaration and affixing the CE label on
a flexible connector must be fitted between replace with sealing plugs. or next to the battery’s nameplate.
each rack joint. - Check electrolyte level (observe operating
2.3. Check that cells or block batteries are instructions/commissioning instructions). CAUTION!
sound (visually, polarity). - Measure the total voltage which should Before connecting to the charger
equal the total open circuit voltages of the ensure that all assembly work has
individual cells/block batteries. been duly completed!

HOPPECKE HOPPECKE Batterien GmbH & Co. KG, Brilon


P.O.Box 1140
Phone (0 29 63) 61-0 · Fax (0 29 63) 61-4 49
http://www.HOPPECKE.de
Batterien D-59914 Brilon e-Mail: hoppecke.IOt-online.de

You might also like