Professional Documents
Culture Documents
Si Fieldbus
Si Fieldbus
Si Fieldbus
2
© 2007 Fieldbus Foundation
Information Pyramid
ERP
MES
DCS
FIELD
3
© 2007 Fieldbus Foundation
Automation Pyramid
Information Quality
HMI
DCS
Information Quantity
PLC
Interfaces
4
© 2007 Fieldbus Foundation
Power Supply and Wiring Block
Topology
HOST Single point HOST
of failure (o.c.)
(s.c.)
5
© 2007 Fieldbus Foundation
Typical IS fieldbus topology in 2000
Fieldbus
ex-i
...
power
supply
6
© 2007 Fieldbus Foundation
Typical IS fieldbus topology in 2004
Fieldbus
power
supply Termination
ex-i
Fieldbusbarrier Fieldbusbarrier Fieldbusbarrier
spurs
7
© 2007 Fieldbus Foundation
Topology Requirements
8
© 2007 Fieldbus Foundation
Fieldbus topology for IS installations
! In general the same arguments apply for IS
installations in regards of grounding; shielding;
protection etc.
! In addition the topology has to provide the IS
isolation between safe areas (e.g. control room) and
hazardous areas (e.g. field).
! As fieldbus devices are low power devices anyhow,
IS is a very appropriate method for fieldbus
installations in hazardous areas.
! Today two different IS installation concepts for
fieldbus are existing:
! “True intrinsic safety“-Concept
! “High Power Trunk“-Concept
9
© 2007 Fieldbus Foundation
“True Intrinsic Safety“-Concept
Trunk:
24V Ex-i FISCO Gas Group IIC…15 V / 100 mA
Ex-i FISCO Gas Group IIB….15 V / 200 mA
H1
Active
FISCO Fieldbus Powersupply Junction Box
Spur:
Ex-i FISCO Gas Group IIC .. >10 V / 30 mA
10
© 2007 Fieldbus Foundation
“High Power Trunk“-Concept
Trunk:
24V Ex-e ……………. < 31 V / 500 mA
H1
Fieldbus
Powersupply Barrier
Spur:
Ex-i FISCO Gas Group IIC .. >10 V / 30 mA
11
© 2007 Fieldbus Foundation
Characteristics
Power
High Power Supply+ 31 V
Ex-e FISCO Fieldbus
YES
Trunk 500 mA2)
Barrier
12
© 2007 Fieldbus Foundation
VISION
13
© 2007 Fieldbus Foundation
VISION
Trunk:
24V Ex-i ……………. > 24 V / 350 mA
T
H1
Spur:
Ex-i FISCO Gas Group IIC .. >10 V / 30 mA
14
© 2007 Fieldbus Foundation
Advantages
15
© 2007 Fieldbus Foundation
24 V / 350 mA
Intrinsically Safe !?
16
© 2007 Fieldbus Foundation
Principle of Intrinsic Safety
“i”
R L
U C
17
© 2007 Fieldbus Foundation
Principle of Intrinsic Safety
18
© 2007 Fieldbus Foundation
Physics of an arc
30 0.6
25 0.5
Funken -
spannung
Spark UF
voltage
20 0.4
U [V]
I [A]
15 0.3
Funken -
SparkIFcurrent
strom
10 0.2
critical
phase
5 initial 0.1
phase
0 0
0 10 20 30 40 50
t [ µs]
di
I dt
R’ l tp
UT UU
24V
10V 12V
500mA
21
© 2007 Fieldbus Foundation
VISION
Trunk:
24V Ex-i ……………. > 24 V / 350 mA
T
H1
DART
DART
Power Supply
Spur:
Ex-i FISCO Gas Group IIC .. >10 V / 30 mA
22
© 2007 Fieldbus Foundation
Conclusion
Power
Trunk Spur Trunk
Isolation Supply
Protection Protection Spec. Redundancy
True 17 V
Power
Intrinsic Ex-i FISCO Supply
NO
Safety 200 mA1)
Power
High Supply+ 31 V
Power Ex-e FISCO YES
Fieldbus 500 mA2)
Trunk
Barrier
Power 24 V
DART Ex-i FISCO
Supply 350 mA
YES
23
© 2007 Fieldbus Foundation