Professional Documents
Culture Documents
351S Transfer Scheme Paper
351S Transfer Scheme Paper
20080317
Factory Assistance
We appreciate your interest in SEL products and services. If you have questions or comments, please
contact us at:
Schweitzer Engineering Laboratories, Inc.
2350 NE Hopkins Court
Pullman, WA USA 99163-5603
Telephone: +1.509.332.1890
Fax: +1.509.332.7990
Internet: www.selinc.com
© 2008 by Schweitzer Engineering Laboratories, Inc. All rights reserved. All brand or product names appearing in this document are the trademark or registered
trademark of their respective holders. No SEL trademarks may be used without written permission. SEL products appearing in this document may be covered by US and
Foreign patents.
Troubleshooting .......................................................................................................... 33
Cross References for Settings, Equations, and Variables..............................................................................33
Summary of Logic and I/O Usage.................................................................................................................44
Logic Descriptions and Diagrams .................................................................................................................46
Main Breaker Overall Trip Logic .........................................................................................................47
Manual Trip and Protection Trip..................................................................................................47
Tie Breaker Failure Backup Trip .................................................................................................48
Automatic Transfer Trip (SV10T) ...............................................................................................48
Main Breaker Close Logic ....................................................................................................................49
Manual Close ...............................................................................................................................49
Automatic Close...........................................................................................................................49
Tie Breaker Overall Trip Logic ............................................................................................................50
Manual Trip and Protection Trip..................................................................................................51
Automatic Open ...........................................................................................................................51
Tie Breaker Close Logic .......................................................................................................................52
Tie Breaker Manual Close Logic .................................................................................................52
Tie Breaker Automatic Close Logic.............................................................................................53
Automatic Transfer Enable Logic.........................................................................................................54
Automatic Retransfer Enable Logic......................................................................................................55
Breaker Trip and Close Failure Logic ..................................................................................................56
Main Breaker Trip Failure............................................................................................................56
Tie Breaker Trip Failure...............................................................................................................57
Tie Breaker Close Failure ............................................................................................................57
Automatic Scheme Lockout Logic .......................................................................................................57
Preferred/Alternate Source Logic .........................................................................................................58
Open Transition Enable ........................................................................................................................59
Scheme Alarm Logic ............................................................................................................................60
Other Logic...........................................................................................................................................61
Automatic Transfer Block (SV13T).............................................................................................61
Tie Breaker Trip/Close Pushbutton Logic....................................................................................62
Flow Chart ............................................................................................................................................63
Relay Settings................................................................................................................................................64
Main Breaker 1 Settings .......................................................................................................................64
Main Breaker 2 Settings .......................................................................................................................68
Figures
Figure 1 Relay Connections With Nonparallel CT Connections ...............................................................................4
Figure 2 Parallel CT Connections ..............................................................................................................................4
Figure 3 SEL-351S Main Breaker Front-Panel Operator Interface............................................................................5
Figure 4 Overall Main Trip Logic............................................................................................................................47
Figure 5 Main Pushbutton/Serial Trip......................................................................................................................48
Figure 6 Protection Trip Logic.................................................................................................................................48
Figure 7 Overall Main Close Logic..........................................................................................................................50
Figure 8 Overall Tie Breaker Trip Logic .................................................................................................................52
Figure 9 Overall Tie Breaker Close Logic ...............................................................................................................54
Figure 10 Automatic Transfer Enable Logic..............................................................................................................55
Figure 11 Automatic Retransfer Enable.....................................................................................................................56
Figure 12 Main Breaker Trip Failure .........................................................................................................................56
Figure 13 Tie Breaker Trip Failure ............................................................................................................................57
Figure 14 Tie Breaker Close Failure ..........................................................................................................................57
Figure 15 Scheme Lockout ........................................................................................................................................58
Figure 16 Preferred/Alternate Source Selection.........................................................................................................59
Figure 17 Open Transition Enable .............................................................................................................................60
Figure 18 Alarm Output Contact................................................................................................................................61
Figure 19 Automatic Transfer Block Logic ...............................................................................................................62
Figure 20 Tie Breaker Trip and Close Pushbutton Logic...........................................................................................62
Figure 21 Scheme Flowchart .....................................................................................................................................63
Figure 22 Design Template Structure ........................................................................................................................74
Figure 23 Open a Design Template............................................................................................................................74
Figure 24 Select Show Settings With Design Templates ...........................................................................................75
Figure 25 Design Template View in ACSELERATOR QuickSet Software ..................................................................75
Figure 26 Configuring the Part Number in ACSELERATOR QuickSet Software ........................................................76
Figure 27 Design Template Manager Directory Tree ................................................................................................77
Figure 28 Sending Settings From the Design Template View ...................................................................................77
Figure 29 Viewing and Printing Design Template Reports .......................................................................................78
Figure 30 Design Report Options ..............................................................................................................................79
Figure 31 Merge Dialog Box in ACSELERATOR QuickSet Software .........................................................................79
Figure 32 Final Step in Merging Settings and Design Template ...............................................................................80
Preface
A common power system configuration for industrial and power generation facilities consists of two
switchgear lineups with separate power sources. In normal operation, main breakers supplying the
switchgear are closed and supply power separately to each switchgear. When one of the two sources fails,
an automatic transfer scheme can trip the main breaker and close a tie breaker, allowing the remaining main
breaker to supply both switchgear lineups.
The SEL-351S Protection and Breaker Control Relay, with its configurable front-panel pushbuttons and
LEDs, significant logic capability, synchronism-check elements, and ability to communicate with other
relays using MIRRORED BITS® communications, is ideal for controlling automatic transfer schemes. In
addition, using an ACSELERATOR® QuickSet Designer™ SEL-5031 Software Design Template, a user can
easily configure such a scheme with a small number of settings. A Design Template is a combination of a
settings interface with custom variables and equations for calculating the actual relay settings and custom
logic in the relay settings file that would normally remain unchanged. The custom settings interface is
developed using ACSELERATOR QuickSet Designer software.
SEL has developed a Design Template that can be used to easily configure SEL-351S Relays for use in a
two-relay main-tie-main automatic transfer scheme. To use this Design Template, you need a copy of
™
ACSELERATOR QuickSet SEL-5030 Software. The ACSELERATOR QuickSet Designer software is only
required if you wish to modify the Design Template or develop new Design Templates for other products.
Refer to the Using Design Templates section at the end of this Design Template Guide for detailed
instructions on using Design Templates.
The SEL-351S Two-Relay Main-Tie-Main Automatic Transfer Scheme Design Template allows easy
configuration of the following features:
• Overcurrent protection
• Transfer initiate voltages
• Transfer time delays
• Synchronism-check parameters
• Local control interface
• Voltage, sag, swell, and interrupt (VSSI) report parameters
The following information is provided in this QuickSet Design Template Guide:
• Introduction provides a brief description of the Design Template purpose and features.
– Relay Selection and Connections describes the basic connections required for the scheme and
the requirements for relay selection.
– Front-Panel Quick Reference describes the functions of the SEL-351S front-panel LEDs and
operator control pushbuttons when the SEL-351S is programmed with this Design Template.
• Description of Operations provides an overview of how the scheme works.
• Design Settings Descriptions and Settings Sheets describes the purpose of each application
setting and contains blank settings sheets.
MIRRORED BITS
Communications
SEL-351S SEL-351S
(2 or 3) (2 or 3)
Port Port
3 3 (3)
(3) IN103 IN103
Transfer Transfer
L.O. L.O.
(1) (1)
TRIP 52A
CLOSE
52/TOC
Bus 1 Bus 2
Tie
(Normally Open)
Load Load
Notes:
1. Connect alarm output on each relay to supervised location for relay monitoring .
2. OUT107 on each relay is programmed for optional scheme alarm .
3. Transfer scheme is disabled on rising edge of IN 104.
(3)
Main 1 Main 2
(Normally (Normally
Closed) Closed)
Bus 1 Bus 2
Tie
(Normally Open)
Load Load
AUTO
RETRANSFER TIE CLOSE
ENABLE
PREFERRED/
ALTERNATE TIE TRIP
SELECT
OPEN
COMM SCHEME
TRANSITION MAIN CLOSE
TST MODE ERROR LO OVERLOAD 50/51 81 ENABLE
MAIN
READY TIE FAIL LOP MAIN TRIP
FAIL
z
Operator
Target Opening Control
LED Labels
Label
Manual Operation
General Manual Breaker Operation
Either main breaker can be manually closed using the {MAIN CLOSE} front-panel pushbutton, or via a serial
communications CLOSE command. Front-panel breaker closing is provided with an optional time delay to
allow the operator to move away from the breaker after pressing the {MAIN CLOSE} pushbutton and is operable
when the front panel is not locked. The MAIN CLOSE LED flashes as the close logic is timing and will
illuminate steadily when the breaker is closed. The main breaker is not permitted to close if the two sources
are not in synchronism while the remote main and tie breakers are closed.
The tie breaker can be manually closed using the {TIE CLOSE} front-panel pushbutton. Front-panel breaker
closing is provided with an optional time delay to allow the operator to move away from the breaker after
pressing the {TIE CLOSE} pushbutton and is operable when the front panel is not locked. The TIE CLOSE LED
does not flash as the close logic is timing. The tie breaker is not permitted to close if both main breakers
are in the close position.
The main breakers can be manually opened using the {MAIN TRIP} front-panel pushbutton, or via
communications. Front-panel breaker tripping is provided with an optional time delay to allow the operator
to move away from the breaker after the {MAIN TRIP} pushbutton is pushed. The MAIN TRIP LED flashes as the
trip logic is timing and will illuminate once the breaker is open.
The tie breaker can be manually opened using {TIE TRIP} front-panel pushbutton. Front-panel breaker tripping
is provided with an optional time delay to allow the operator to move away from the breaker after the
{TIE TRIP} pushbutton is pushed. The TIE TRIP LED does not flash as the trip logic is timing. The LED will
illuminate once the breaker is open.
Automatic Operation
Automatic Transfer Enable
Automatic transfers will occur only when the automatic transfer scheme is enabled. The transfer scheme
can be enabled and disabled by pressing the {AUTO TRANSFER ENABLE} front-panel pushbutton on either main
breaker relay when the front panel is not locked.
The transfer enabled signal is transmitted to the other main breaker relay using MIRRORED BITS
communications. The AUTO TRANSFER ENABLE LED on each relay will illuminate when the automatic transfer
scheme is enabled.
The automatic transfer scheme can be enabled when all of the following conditions are true—the READY
LED will be on when all of these conditions are present:
• The Source 1 voltage is healthy.
• Main Breaker 1 is closed and racked-in.
• The Source 2 voltage is healthy.
• Main Breaker 2 is closed and racked-in.
• The tie breaker is racked-in.
• The auto scheme lockout is not set.
• MIRRORED BITS communications is operating properly.
Closed Transition
If automatic retransfers are enabled and open transitions are disabled, the scheme will perform a closed
transition transfer of the load from the tie breaker back to the main breaker by allowing the main breaker to
close before the tie breaker opens. The tie breaker is forced to trip when both main breakers and the tie
breaker are closed simultaneously.
The main breaker can automatically close for a retransfer if all of the following conditions are true:
• Automatic retransfer is enabled.
• The main breaker has previously tripped on automatic transfer.
• The voltage on the associated source has been healthy for a user-defined retransfer time delay.
• The tie breaker is closed.
• No faults have been detected on either bus.
• The bus has voltage and is in synchronism with the source.
Once the main breaker has closed, the tie breaker will open and the breakers will be in normal
configuration.
Open Transition
If automatic retransfers are enabled and open transfers are enabled, the scheme will perform an open
transition transfer of the load from the tie breaker back to the main breaker by allowing the tie breaker to
open before the main breaker closes.
The tie breaker can automatically open for a retransfer if all the following conditions are true:
• Automatic retransfer is enabled.
• The main breaker has previously tripped on automatic transfer.
• The voltage on the associated source has been healthy for a user-defined retransfer time delay.
• The tie breaker is closed.
• No faults have been detected on either bus.
After the tie breaker has successfully opened, the main breaker is allowed to close if all the following
conditions are true:
• The bus voltage is below the dead bus threshold.
• The tie breaker is open.
• Both sources are healthy.
After the main breaker closes, the breakers will be in the normal configuration.
Test Mode
A test mode is provided to aid in testing the scheme with voltage sources. In each relay, the test mode can
be entered by setting LB1 from the CNTRL menu of the front panel. The relay will remain in the test mode
until LB1 is cleared via the front panel. While in test mode, the TST MODE LED will be displayed.
In the main breaker relays, testing automatic transfer by reducing the voltage below the transfer initiate
voltage without an accompanying change in current will assert the loss-of-potential logic and block the
transfer. The test mode disables the loss-of-potential supervision for automatic transfer initiate.
Table 28 Tie Breaker Open/Main Breaker Close Delay for Retransfers Setting
Setting Range Default Units Increment
Tie Breaker Open/Main Breaker Close 0.0–100.0 2.0 Seconds 0.1
Delay for Retransfers
Enter an additional time delay for tie open (open transitions), once the healthy source has been detected. Also adds
an additional time delay for main close (close/open transitions) once a healthy source has been detected.
Table 29 Maximum Time Sources Can Be Paralleled In Close Transition Mode Setting
Setting Range Default Units Increment
Maximum Time Sources Can Be 0.00–180.00 5.00 Cycles 0.25
Paralleled In Close Transition Mode
Enter the maximum time delay for tie breaker to open after a main has closed on a closed transition retransfer.
Table 49 Use Neutral Elements Instead of Residual Elements for Ground Protection Setting
Setting Range Default Units Increment
Use Neutral Elements Instead of Y, N N
Residual Elements for Ground
Protection?
If measured neutral (IN) input is used, set to Y. Otherwise, set to N, and the relay will calculate the residual current.
Secondary
Transfer Block Phase Overcurrent Level OFF, 0.25–100.00 [0.25]
Amperes
Secondary
Phase Time-Overcurrent Pickup 0.25–16.00 [0.01], OFF
Amperes
Secondary
Ground Time-Overcurrent Pickup 0.10–16.00 [0.01], OFF
Amperes
Secondary
Phase Time-Overcurrent Pickup 0.25–16.00 [0.01], OFF
Amperes
Secondary
Ground Time-Overcurrent Pickup 0.10–16.00 [0.01], OFF
Amperes
Settings Development
The first step in applying the transfer scheme is to develop the settings. Review the Description of
Operations section, this section, and the Logic Descriptions and Diagrams subsection of the
Troubleshooting section to gain an understanding of how the scheme operates and how each setting affects
the operation. To develop settings, first determine how the system PTs are connected. For open-delta, PT
connections, use the Open Delta template. For four-wire, three-phase PTs connected to ground, use the
Wye template.
Next, determine if any changes to the logic are required or if any additional functions are needed. Modify
the logic and design settings as needed for the specific application. See the Using Design Templates
section to gain an understanding of how to modify Design Templates.
Finally, enter the settings into the Design Template and save the settings. Use the settings sheets provided
in the Design Settings Sheets subsection or print the settings from ACSELERATOR QuickSet software to
maintain a hard copy.
Use the front-panel configurable label template included with this Design Template to create labels for the
relays. Install the labels on the relays.
Physical Connections
Connect the relays as shown in Figure 1 (use Figure 2 to connect main and tie breaker CTs in parallel).
Make any modifications required to support the logic and settings changes made under the Settings
Development subsection above.
Test all the relay inputs and outputs to verify that the connections have been made properly. Verify the
voltage and current metering to ensure the PT and CT connections are correct.
Make the following additional connections as needed:
• Connect an SEL-2800 Fiber-Optic Transceiver to Port 3 of each relay for MIRRORED BITS
communications.
• Connect three current and four voltage inputs according to Figure 1 or Figure 2.
• Connect the main breaker status contact to input IN101 on the appropriate main breaker relay, and
connect the tie breaker status contact to input IN102 of each main breaker relay.
• Connect a lockout contact to either relay’s IN104 (optional). This input disables the transfer
scheme for any external lockout condition.
• The truck-operated contacts (TOC) of all the breakers are brought in series to input IN103 of both
relays. These contacts alert the relay if any breaker is out of service. Refer to the breaker
instruction manual for more connection details.
Commissioning Tests
The following is a partial outline of steps that can be taken to commission the scheme and verify that it is
operating properly. Other steps may be required depending on modifications to the scheme, conditions and
procedures at the facility, and code requirements. Appropriate safety precautions should be taken,
especially if testing is performed with live sources.
Step 1. Using a relay test set, or by closing source breakers, put balanced voltages on the source PT input
(VA, VB, and VC) of both main breakers to simulate healthy source voltages.
Secondary voltage magnitude must be greater than [(Healthy Source Voltage Setting/100)*
(System Voltage/Potential Ratio)] for open-delta voltages, or greater than [(Healthy Source
Voltage Setting/100)*System Voltage/(Potential Ratio*1.73)] for wye voltages.
Step 2. Verify that the metered primary voltage is greater than the (Healthy Source Voltage
Setting/100)*(System Voltage).
Step 3. Close both main breakers using the {MAIN CLOSE} pushbutton.
Step 4. When both breakers are closed, the READY LED on each relay should be lit. If not, verify that the
relays are communicating correctly, there are no breaker trip or close failure conditions, there are
no active trip conditions, both main breakers are closed, all three beakers are racked-in, there is
no lockout, and both sources are above the Healthy Source Voltage setting.
Step 5. Enable automatic transfer using the {AUTO TRANSFER ENABLE} pushbutton on either relay.
Step 6. Verify that the AUTO TRANSFER ENABLE LED on both relays is on.
Step 7. Enable retransfer using the {AUTO RETRANSFER ENABLE} pushbutton on either relay.
Step 8. Verify that the AUTO RETRANSFER ENABLE LED on both relays is on.
Step 9. Place the relay in the TEST mode using LB1 in the main breaker relay front-panel CNTRL menu.
25VHI, 25VLO,
27PP, 27PP2P, 25VHI, 25VLO, 27PP,
27SP, 519S1P, 27PP2P, 27SP, 519S1P,
System Voltage (Open Delta)
59S2P, 59PP, 59S2P, 59PP, 59PP2P,
59PP2P, 59QP, 59QP, VNOM
VNOM
25VHI, 25VLO,
27P1P, 27P2P, 25VHI, 25VLO, 27P1P,
27SP, 59S1P, 27P2P, 27SP, 59S1P,
System Voltage (Wye)
59S2P, 59P1P, 59S2P, 59P1P, 59P2P,
59P2P, 59QP, 59QP, VNOM
VNOM
PTR, 25VHI,
25VLO, 27P1P,
Main 1 Source-Side PT Ratio (Wye) 27P2P, 59P1P,
59P2P,
59QP,VNOM
PTR, 25VHI,
25VLO, 27PP,
Main 1 Source-Side PT Ratio (Open Delta) 27PP2P, 59PP,
59PP2P,
59QP,VNOM
PTRS, 25VHI,
Main 1 Load-Side PT Ratio 25VLO, 27SP,
59S1P, 59S2P
PTRS, 25VHI,
Is Main 1 Load-Side PT Connected Phase-to-
25VLO, 27SP,
Phase?
59S1P, 59S2P
[1^25ANG1] [UV^1_25ANG1]
[1^25SF] [UV^1_25SF]
[UV^M2SourceNomVoltage] *
[1^27PP] (Delta)
[UV^Transfer_Initate_Voltage_Entry] / 100
[UV^M2SourceNomVoltage] *
[1^27P1P] (Wye)
[UV^Transfer_Initate_Voltage_Entry] / 100
[1^50P2P] [UV^1_50P2P]
[1^51G1C] [UV^1_51G1C]
[1^51G1P] [UV^1_51G1P]
[1^51G1TD] [UV^1_51G1TD]
[1^51N1C] [UV^1_51G1C]
[1^51N1P] [UV^1_51G1P]
[1^51N1TD] [UV^1_51G1TD]
[1^51P1C] [UV^1_51P1C]
[1^51P1P] [UV^1_51P1P]
[1^51P1TD] [UV^1_51P1TD]
[UV^M1SourceNomVoltage] *
[1^59PP] (Open Delta)
[UV^Healthy_Source_Voltage_Entry] / 100
[UV^M1SourceNomVoltage] *
[1^59P1P] (Wye)
[UV^Healthy_Source_Voltage_Entry] / 100
[1^CTR] [UV^1_CTR]
[1^CTRN] [UV^1_CTRN]
[1^DMTC] [UV^1_DMTC]
[1^E25] Y
[1^E51G] 1
[1^E51N] 1
[1^E51P] 1
[1^EDEM] [UV^1_EDEM]
[1^ESSI] [UV^1_ESSI]
[1^EVOLT] Y
[1^PTR] [UV^1_PTR]
[1^PTRS] [UV^1_PTRS]
[1^RID] [UV^1_RID]
[1^SV10PU] [UV^Transfer_Initiate_Time_Delay]
[1^SV14DO] [UV^G_PB9D] * 60
[1^SV15DO] [UV^G_PB10D] * 60
[1^SV1PU] [UV^Automatic_Retransfer_Time_Delay]
[1^SV3PU] [UV^Transfer_Time_Close_Delay]
[1^SV4PU] [UV^Tie_Breaker_Open_Time]
[1^SV5PU] [UV^Tie_Breaker_Open_Time]
[1^SV6PU] [UV^Max_Parallel_Time_Entry]
[1^SV7PU] [UV^Tie_Breaker_Open_Time]
[1^SV9PU] [UV^Automatic_Retransfer_Time_Delay]
[1^SYNCP] [UV^1_SYNCP]
[1^TCLOSD] [UV^1_TCLOSD]
[1^TDURD] [UV^1_TDURD]
[1^TID] [UV^1_TID]
[1^VINT] [UV^1_VINT]
[1^VNOM] [UV^M1SourceNomVoltage]
[1^VSAG] [UV^1_VSAG]
[1^VSWELL] [UV^1_VSWELL]
[2^25ANG1] [UV^1_25ANG1]
[2^25SF] [UV^1_25SF]
[UV^M2SourceNomVoltage] *
[2^27PP] (Delta)
[UV^Transfer_Initate_Voltage_Entry] / 100
[UV^M2SourceNomVoltage] *
[2^27P1P] (Wye)
[UV^Transfer_Initate_Voltage_Entry] / 100
!TRGTR SV8
SV8T
52A
SV11T
LT8 (Main BF)
(Lockout) SV10T
Seal-In
LT1 Auto Scheme
(Auto Mode) Trip
SV11T
(Main Trip Failure)
Manual Close
The main breakers can be closed manually via the {MAIN CLOSE} pushbutton if all of the following conditions
are true:
• There is no hot line tag (LT6).
• Automatic transfers are disabled (!LT1).
• Either one of the following are true:
– Both sources are synchronized (25A1).
– The local source is healthy (SV9), and the bus is dead (27S).
• The pushbuttons are not locked (LT5).
Automatic Close
The main breakers can also be closed via two types of retransfers: open transitions (SV7T) or close
transitions (SV5T). When open transitions are selected, the tie breaker opens first on a retransfer, and then
the main closes. This prevents paralleling sources, and a synchronism check is not needed. When close
transitions are selected, the main breaker closes first on retransfers, and then the tie breaker opens. This
allows for no loss of load during retransfers, but the two sources are paralleled for a brief amount of time.
(Auto Mode)
PB9
(Close Main)
CC
(SCADA Close)
25A1
(Synch Check)
SV9
(Loc. Src. Healthy)
27S
(Load Side Dead)
OUT102
Close
Main Breaker
Close
IN102
RMB1A
(Remote 52A) SV12 SV12T 52A
52A
Seal-In SV7T
Main Close
RMB3A
(Remote SV9)
SV7
Seal-In SV7T
LT3 SV7T
(Preferred Source)
27S
(Load Side Dead)
LT2
(Auto Return)
Common Logic
SV7 and SV5
59Q
3P59
SV9 SV9T
LT8
(Lockout) 52A
Seal-In SV5T
Main Close
LT4 (Open
Transition Mode)
25A1 SV5
Seal-In SV5T
(Synch Check) SV5T
Automatic Open
The tie breaker can be opened automatically via two types of retransfers: open retransfers and close
retransfers. In an open retransfer, the tie breaker will open before the main closes. In a close retransfer, the
main closes first and then the tie opens. Two SELOGIC control equation timers accommodate both types of
retransfers.
RMB1A
(Remote 52A)
Parallel Sources Logic IN102
(Tie Status)
SV12
Tie Open
52A
SV6
SV6T
SV8T
(Tie Breaker Seal-In SV6T
Failure Timer)
Seal-In SV6T
LT1 (Auto
Mode)
LT2 (Auto
Return)
SV4
LT4 (Open
Transition Mode)
LT8 OUT103
Tie Open
(Lockout) SV4T
(Tie
RMB3A Breaker
(Remote SV9) Open)
SV1T Seal-In SV6T
59Q SV8T
3P59 IN102
SV9 SV9T Seal-In SV6T
Manual Tie Open
PB8 (Tie
Breaker Open)
S SET Q
SV15T
IN102 R CLR Q
LT11
SV1
IN102
(Remote Healthy)
(Tie Breaker Status)
27S TRGTR SV16
(Local Bus Dead) (Target Reset) SV16T
IN102 LT6
(Tie Breaker Status) (No Hot Line Tag)
52A
RMB3A
(Remote Healthy)
RMB1A SV3 Seal-In
(Remote Status) SV3T
Tie Automatic Close
LT1
(Auto Mode)
ROKA SV3
59Q
3P59
SV9
LT8 SV9T
(Lockout)
RMB5A
(Remote Bus Dead)
LT8
(Lockout)
IN103
(All Breakers Racked-In)
Auto Scheme Ready Logic
SV9T
(Local Source Healthy)
SV1T
(Remote Source Healthy)
IN101
(Local Main Status) SV2
RMB1A
(Remote Main Status) S SET Q
IN102
(Tie Status)
R CLR Q
RBADA
(MB Comm Bad) LT1
PB1
(Auto Transfer En.)
LT5
(FP Unlocked)
RMB2A
(Remote Relay LT1)
LT8
(Lockout)
LT5
(FP Unlocked)
RMB8A
(Remote Relay LT2)
LT8
(Lockout)
IN102
(Tie Breaker Status)
LT1
(Auto Transfer En.)
LT2
S SET Q
(Auto Retransfer En.)
PB2 R CLR Q
(Auto Retransfer En.) LT2
LT5
(FP Unlocked)
LT1
(Auto Transfer En.)
RMB8A
(Remote Relay LT2)
LT8
(Lockout)
TRGTR
(Target Reset PB)
OUT101
(Main Trip) SV11T
52A
(Main Status)
TRGTR
(Target Reset PB)
OUT103
(Tie Trip) SV8T
IN102
(Tie Status)
TRGTR
(Target Reset PB)
OUT104
(Tie Close) SV16T
IN102
(Tie Status)
52A
(Local Main Status)
OUT101
(Main Breaker Trip)
LT1
(Auto Transfer En.)
LT1
(Auto Transfer En.)
S SET Q
IN102
(Tie Breaker Status)
R CLR Q
SV4T
(Auto Retransfer Tie Trip) LT9 S SET Q
R CLR Q
SV6 LT8
(Tie Trip Parallel Sources)
TRGTR
(Target Reset PB)
IN104
(Lockout Input)
SV11T
(Main Trip Failure)
CF
(Main Close Failure)
SV16T
(Tie Close Failure)
Trip
(Protection or Manual Trip)
SV8T
(Tie Trip Failure)
IN104
(Lockout Input)
RMB6A
(Remote Scheme Lockout)
LT1
(Auto Transfer En.)
RMB7A
(Remote LT3 Status)
ROKA
(MB Communications OK)
PB3
(Preferred/Alternate PB)
LT5
(FP Not Locked) S SET Q
R CLR Q
RMB7A
(Remote LT3 Status) LT3
ROKA
(MB Communications OK)
PB3
(Preferred/Alternate PB)
LT5
(FP Not Locked)
PB4
(Open Transition Enable)
LT5
(FP Not Locked)
S SET Q
RMB4A
(Remote LT4)
R CLR Q
LT4 LT4
(Open Transition Enable)
PB4
(Open Transition Enable)
LT5
(FP Not Locked)
RMB4A
(Remote LT4)
LT8
(Scheme Lockout) OUT107
(Alarm)
RBADA
(MB Communications Bad)
LB1
(Test Switch Enable)
LOP
(Loss of Potential)
Other Logic
PB8 LT1
(Tie Breaker Trip PB) (Tie Breaker
Manual Trip)
SV15T
Failed Source = Any phase voltage that drops below the Transfer Initiate Voltage setting
START
Healthy source = All phase voltages are above the Healthy Source Voltage setting
Dead Bus = Load-side voltage is below the Dead Bus Voltage setting
Yes Yes No
Did
Breaker Close?
Yes
Yes No After voltage has been
Open Breaker of healthy for Automatic
Failed Source After Return of Return of Both Retransfer Time, initiate a
Yes No
Transfer Initiate One Source Sources main breaker close (includes
Breaker
Time Delay relay time delay).
Opened?
No Action
No
After voltage has been
healthy for Automatic
Breaker Retransfer Time, initiate a Yes
Wait for Bus
Yes Dead Bus? No tie breaker open (includes
Opened? Voltage to Decay Are Sources
relay time delay).
In Sync?
Yes
Yes
No No
Yes
Main
Yes No Action No Open Source Yes
Healthy?
Breaker Did Breaker
Yes Lockout No
Closed? Open?
No
Global Settings:
PTCONN= WYE VSCONN= VS TGR = 180.00
NFREQ = 60 PHROT = ABC DATE_F= MDY
FP_TO = 15 SCROLD= 2 FPNGD = IG
LER = 15 PRE = 4 DCLOP = OFF DCHIP = OFF
IN101D= 0.50 IN102D= 0.50 IN103D= 0.50 IN104D= 0.50
IN105D= 0.50 IN106D= 0.50
EBMON = Y COSP1 = 10000 COSP2 = 150 COSP3 = 12
KASP1 = 1.20 KASP2 = 8.00 KASP3 = 20.00
LED12L= Y LED13L= N LED14L= N LED15L= N
LED16L= N LED17L= Y LED18L= Y LED19L= N
LED20L= N LED21L= N LED25L= Y LED26L= N
RSTLED= Y
PB9D = 0.00 PB10D = 0.00
Group Settings:
RID =MAIN BREAKER 1 TID =SWITCHGEAR A
CTR = 600 CTRN = 600
PTR = 120.00 PTRS = 120.00 VNOM = 66.47
Z1MAG = 2.14 Z1ANG = 68.86 Z0MAG = 6.38 Z0ANG = 72.47
LL = 4.84
E50P = 2 E50N = N E50G = N E50Q = N
E51P = 1 E51N = 1 E51G = 1 E51Q = N
E32 = N ELOAD = N ESOTF = N EVOLT = Y
E25 = Y EFLOC = N ELOP = N ECOMM = N
E81 = N E79 = N ESV = 16 EDEM = THM
EPWR = N ESSI = Y
50P1P = OFF 50P2P = 6.00
67P1D = 0.00 67P2D = 0.00
50PP1P= OFF 50PP2P= OFF
51P1P = 6.00 51P1C = U3 51P1TD= 3.00 51P1RS= N
51P1CT= 0.00 51P1MR= 0.00
51N1P = 1.500 51N1C = U3 51N1TD= 1.50 51N1RS= N
51N1CT= 0.00 51N1MR= 0.00
51G1P = 1.50 51G1C = U3 51G1TD= 1.50 51G1RS= N
51G1CT= 0.00 51G1MR= 0.00
27P1P = 53.18 27P2P = 59.82 59P1P = 59.82 59P2P = 73.12
59N1P = OFF 59N2P = OFF 59QP = 6.65
59V1P = OFF 27SP = 16.62 59S1P = 73.12 59S2P = 59.82
27PP = OFF 59PP = OFF
25VLO = 59.82 25VHI = 73.12 25SF = 0.042
25ANG1= 10.00 25ANG2= 40.00 SYNCP = VA TCLOSD= 0.00
DMTC = 15
PDEMP = OFF NDEMP = OFF GDEMP = OFF QDEMP = OFF
TDURD = 9.00 CFD = 60.00 3POD = 2.00 50LP = OFF
SV1PU = 600.00 SV1DO = 0.00 SV2PU = 0.00 SV2DO = 0.00
SV3PU = 120.00 SV3DO = 3.00 SV4PU = 120.00 SV4DO = 3.00
SV5PU = 120.00 SV5DO = 3.00 SV6PU = 5.00 SV6DO = 3.00
SV7PU = 120.00 SV7DO = 3.00 SV8PU = 8.00 SV8DO = 0.00
SV9PU = 600.00 SV9DO = 0.00 SV10PU= 300.00 SV10DO= 3.00
SV11PU= 8.00 SV11DO= 0.00 SV12PU= 0.00 SV12DO= 10.00
SV13PU= 0.00 SV13DO= 0.00 SV14PU= 0.00 SV14DO= 0.00
SV15PU= 0.00 SV15DO= 0.00 SV16PU= 60.00 SV16DO= 0.00
VINT = 10.00 VSAG = 90.00 VSWELL= 110.00
Text Labels:
NLB1 =TEST MODE CLB1 =OFF SLB1 =ON PLB1 =
NLB2 = CLB2 = SLB2 = PLB2 =
NLB3 = CLB3 = SLB3 = PLB3 =
NLB4 = CLB4 = SLB4 = PLB4 =
NLB5 = CLB5 = SLB5 = PLB5 =
NLB6 = CLB6 = SLB6 = PLB6 =
NLB7 = CLB7 = SLB7 = PLB7 =
NLB8 = CLB8 = SLB8 = PLB8 =
NLB9 = CLB9 = SLB9 = PLB9 =
NLB10 = CLB10 = SLB10 = PLB10 =
NLB11 = CLB11 = SLB11 = PLB11 =
NLB12 = CLB12 = SLB12 = PLB12 =
NLB13 = CLB13 = SLB13 = PLB13 =
NLB14 = CLB14 = SLB14 = PLB14 =
NLB15 = CLB15 = SLB15 = PLB15 =
NLB16 = CLB16 = SLB16 = PLB16 =
DP1_1 =COMM FAIL DP1_0 =
DP2_1 =ABNORMAL TOC DP2_0 =
DP3_1 =ATS LOCKOUT DP3_0 =
DP4_1 =UNDERVOLTAGE DP4_0 =
DP5_1 =TIE BK CLOSED DP5_0 =TIE BK OPEN
DP6_1 =TST MODE ENBLD DP6_0 =
DP7_1 =CLOSE FAILURE DP7_0 =
DP8_1 =TRIP FAILURE DP8_0 =
DP9_1 = DP9_0 =
DP10_1= DP10_0=
DP11_1= DP11_0=
DP12_1= DP12_0=
DP13_1= DP13_0=
DP14_1= DP14_0=
Port 3
PROTO = MBA
SPEED = 38400 RTSCTS= N RBADPU= 15 CBADPU= 1000
RXID = 1 TXID = 2 RXDFLT=0X1XXX0X
RMB1PU= 1 RMB1DO= 1 RMB2PU= 1 RMB2DO= 1
RMB3PU= 1 RMB3DO= 1 RMB4PU= 1 RMB4DO= 1
RMB5PU= 1 RMB5DO= 1 RMB6PU= 1 RMB6DO= 1
RMB7PU= 1 RMB7DO= 1 RMB8PU= 1 RMB8DO= 1
Group 2
Group Settings:
RID =MAIN BREAKER 2 TID =SWITCHGEAR B
CTR = 600 CTRN = 600
PTR = 120.00 PTRS = 120.00 VNOM = 66.47
Z1MAG = 2.14 Z1ANG = 68.86 Z0MAG = 6.38 Z0ANG = 72.47
LL = 4.84
E50P = 2 E50N = N E50G = N E50Q = N
E51P = 1 E51N = 1 E51G = 1 E51Q = N
E32 = N ELOAD = N ESOTF = N EVOLT = Y
E25 = Y EFLOC = N ELOP = N ECOMM = N
E81 = N E79 = N ESV = 16 EDEM = THM
EPWR = N ESSI = Y
50P1P = OFF 50P2P = 6.00
67P1D = 0.00 67P2D = 0.00
50PP1P= OFF 50PP2P= OFF
51P1P = 6.00 51P1C = U3 51P1TD= 3.00 51P1RS= N
51P1CT= 0.00 51P1MR= 0.00
51N1P = 1.500 51N1C = U3 51N1TD= 1.50 51N1RS= N
51N1CT= 0.00 51N1MR= 0.00
51G1P = 1.50 51G1C = U3 51G1TD= 1.50 51G1RS= N
51G1CT= 0.00 51G1MR= 0.00
SELogic group 2
Text Labels:
NLB1 =TEST MODE CLB1 =OFF SLB1 =ON PLB1 =
NLB2 = CLB2 = SLB2 = PLB2 =
NLB3 = CLB3 = SLB3 = PLB3 =
NLB4 = CLB4 = SLB4 = PLB4 =
NLB5 = CLB5 = SLB5 = PLB5 =
Port 3
PROTO = MBA
SPEED = 38400 RTSCTS= N RBADPU= 15 CBADPU= 1000
RXID = 2 TXID = 1 RXDFLT=0X1XXX0X
RMB1PU= 1 RMB1DO= 1 RMB2PU= 1 RMB2DO= 1
RMB3PU= 1 RMB3DO= 1 RMB4PU= 1 RMB4DO= 1
RMB5PU= 1 RMB5DO= 1 RMB6PU= 1 RMB6DO= 1
RMB7PU= 1 RMB7DO= 1 RMB8PU= 1 RMB8DO= 1
Components
Design Templates consist of the following components:
• Design settings that are entered using a custom settings interface
• A set of design equations that use the design settings and/or constants to derive the device settings
• A device settings file that contains a complete set of the derived device settings
While some device settings are calculated by the equations, others are not affected by the Design Template
(see Figure 22). Generally, these other settings do not require any modification from the default values that
were established when the Design Template was developed.
Derived Settings
Sending Settings
To send the settings to the device, select File > Send… from the toolbar in the Design Template view, as
shown in Figure 28.
*LDG0006-01*