PSV - SIZING

Item Equipment number = PSV-LLA-L-005


Location = LLA - LIMA F/S

Case Case = Thermal


Relief load = 3.13 MMSCFD
= 8980 lb/hr (note 1)

Pipe Design pressure = 2025 psig (note 2)


MAWP = 1825 psig (note 2)
Operating pressure = 630 psig
Operating temperature = 86 deg F
NPS - Nominal Pipe Size = 16
OD - outside diameter = 16 inch
ID - inside diameter = 14.314 inch
Length = 10 meter
= 33 ft
Exposed Area = 137 ft^2

Properties PSV set pressure = 850 psig (note 3)


PSV overpressure = 21%
Relieving pressure = 1028.5 psig
Relieving temperature = 116 deg F (from HYSYS)
Molecular weight = 26.13
Cp/Cv = 1.644
C = 376
Tw - wall temperature = 1100 deg F

Calculation Kd - effective coefficient of discharge = 0.975


F' = 0.034
Relief load = 11720 lb/hr
PSV required area = 0.144 inch^2

Exsting data PSV selested area = 0.11 inch^2 (note 4)

Result PSV OK or NOT? = NOT OK

Notes 1. Total of gas lift is 9.4 MMSCFD. It handles LLA, LLB, LE, LD, LC and LB.
Incoming gas lift to LLA will be delivered to LLA and LLB.
2. It is based on document of 226/ROI-V/SCI/BP/09
3. It is based on HP discharge compressor PSHH setting of LCOM.
4. It is based on LIMA data base.
5. The calculation refers to API 521.

You might also like