Professional Documents
Culture Documents
Mod 3 Book 3 Ac Theory
Mod 3 Book 3 Ac Theory
1
AUTHORITY
For health and safety in the workshop you should follow the
regulations/ Guidelines as specified by the equipment manufacturer,
your company, National safety authorities and national governments.
2
CONTENTS
SUBJECT
PAGE
Alternating voltage & current 1
Series ac circuits 9
Pure inductance in ac circuits 13
Pure capacitance in ac circuits 15
Inductance & resistance in series 18
Capacitance & resistance in series 20
Resistance, inductance & capacitance in series 24
Resistance, inductance & capacitance in parallel 31
Power in ac circuits 35
Three phase systems 38
Transformers 45
Filters 66
Differentiators 72
Integrators 74
3
ALTERNATING VOLTAGE AND CURRENT
From the diagram you can see that the ac passes through a definite
sequence, it rises from zero to maximum in one direction and falls back to
zero, it then reverses and goes to a maximum in the other direction and
then goes back to zero again. This complete sequence A to B is called a
cycle and is repetitive.
-1-
4
The number of cycles occurring in one second is called the FREQUENCY of
the alternating current. This has the symbol f and the unit HERTZ (Hz). The
frequency of most aircraft ac constant frequency systems is 400Hz. In
aircraft radio and radar systems many other frequencies are used ranging
from 3kHz (kilo Hertz) to 3OGHz (Giga Hertz).
The time taken to complete one cycle is known as the periodic time or
period denoted by the symbol T. (see figure 1)
Faradays Law states that when a conductor cuts a magnetic field an emf
(electromotive force) is induced into the conductor. Figure 4 shows the
rotation of the loop through 360°.
-2-
5
Fig. 4 VOLTAGE INDUCED IN A ROTATING LOOP
In position (a) no cutting of the flux lines is taking place as the wire is
moving parallel to the lines of flux so no emf (P) is induced. As the loop
rotates from this position it starts to cut the lines of flux and an emf is
generated which reaches a maximum at (Q) - the coil is cutting the
maximum number of lines of flux hence maximum emf is induced. As it
rotates further the induced emf reduces to zero at (R).
The direction of the induced emf reverses as side A of the loop cuts the flux
lines in an upwards direction, again being a maximum at (S) and then
falling to zero at (T). This waveform produced is known as a sinusoidal
waveform or sine wave (got its name from the fact that if the sine of the
angles is plotted against the angles from 0 to 360° a graph known as a sine
wave is produced). So one complete rotation of the loop gives 'one cycle' of
alternating voltage or current.
-3 -
6
If we assume the maximum emf in this case to be 100 volts (ie the length of
the phasor represents 100 volts). Then the height AB in figure 5 and the
drawing below represents the voltage at (a) on the sine wave, this point is
known as an INSTANTANEOUS VALUE - a voltage at an instant in time.
Instantaneous values are given the symbol e and maximum emf as E max.
hence the name sine wave as the voltage at any point is the maximum value
times the sine of the angle.
-4-
7
radians per second. After an interval of t seconds from the
commencement of rotation the loop has rotated an angle equal to
radians which is radians. The emf at this instant is:
ac Values
The AVERAGE VALUE of an ac waveform over a full cycle is zero as there are
equal positive and negative values. It is usual therefore to use the average
value of half a cycle.
- 5-
8
Measuring the value of the current at each point and adding them together
and dividing by the number of values taken, in the drawing:
The EFFECTIVE or ROOT MEAN SQUARE VALUE (rms) is the value that is
most commonly used.
9
-6-
10
-7-
We can represent these two quantities by phasors, the length of each
representing the rms values.
The voltage rises to its positive peak first and is said to be leading the
current, alternatively the current can be said to be lagging the voltage. The
phase difference is the phase angle 0.
-8-
The phasor diagram below shows this more clearly, (remember phasors
rotate anti-clockwise).
ACTIVITY
4) A voltage waveform has an rms value of 707 volts the peak to peak
value of the waveform is?
SERIES ac CIRCUITS
However, for the purposes of the next few pages we are going to assume
'pure' components as it makes the treatment easier and it is helpful to show
the 'ideal' conditions.
-9 -
PURE RESISTANCE IN ac CIRCUITS
With reference to the graph in figure 10. It can be seen that the voltage and
current are in-phase and the phasor diagram would be as shown below the
graph.
Ohms law and the use of rms values applies at all times to a purely resistive
circuit.
Power
The power is the average value of all the instantaneous values of power for a
complete cycle. To find the instantaneous power at any moment, the
instantaneous values of voltage and current at that moment are multiplied
together.
- 10-
Fig. 11 POWER - CURRENT & VOLTAGE IN-PHASE
If this process is carried out over the complete cycle the power curve is
produced as shown in figure 12. The power is always positive because
current and voltage are in phase and when voltage and current are positive
their product is positive when they are both negative their product is still
positive.
Fig. 12 ac POWER
- 11 -
The average power over a complete cycle is the average value of the power
curve and this is represented by a line halfway between maximum and
minimum values of the curve, since the shaded areas above and below the
line are equal.
The power waveform has twice the frequency of the supply. Therefore in the
diagram the power fluctuates rapidly between zero and 12 watts, but over a
complete cycle, the average power is 6 watts.
We are only interested in average power as the frequency of the supply is
usually high and this is what the device (lamp, electric motor etc) actually
consumes.
The average power will from now be referred to as 'power', is half the peak
power in a resistive circuit, and this peak value is the maximum voltage
multiplied by the maximum current.
- 12 -
PURE INDUCTANCE IN ac CIRCUITS
This back emf opposes the rise of current in the circuit and therefore delays
its rise as can be seen by the waveform diagram. In a pure inductive circuit
V leads I by 90° or I lags V by 90°.
The inductive reactance of a coil depends upon the rate of change of current
(which is dependent on frequency) and the value of the inductance. It is
calculated by the formula:
Power
Similar to the process carried out in the pure resistive circuit where V and I
are multiplied at each point to give a power curve as shown in figure 17.
- 14-
As the voltage and current are 90° out of phase positive and negative powers
are produced. In the purely inductive circuit, the total power is zero, since
positive and negative powers cancel. Positive power is given to the circuit
from the power supply on one half cycle and negative is returned to the
supply source on the other half cycle of power.
Over a complete cycle the net power is zero. It is important to note that
current flows in the circuit but no work is being done when the current is
90° out of phase with the voltage.
ACTIVITY
Voltage exists across the plates of a capacitor only after the current has
flowed to charge the plates. With reference to figure 19 it can be seen that
the current leads the voltage and in a pure capacitive circuit it leads by 90°.
Remember, it can also be stated that voltage lags the current.
- 15 -
Fig. 19 CURRENT & VOLTAGE IN A CAPACITIVE CIRCUIT
where:
You must be able to work out what happens to the current in a purely
capacitive circuit when there is a frequency change.
- 16-
Power
The power curve is produced as previously illustrated in the pure resistive
and pure inductive circuits. Looking at figure 21 (the shaded areas) it can
be seen there are two positive peaks and two negative peaks of power over
one complete cycle so the net power is zero.
ACTIVITY
- 17-
INDUCTANCE AND RESISTANCE IN SERIES
The waveform diagram (figure 23) shows that voltage and current are out of
phase by an angle less than 90° and with current lagging voltage.
To find the supply voltage (V) we cannot just add these voltages together as
you would do in a dc circuit, because they are out of phase with one
another, so by completing the parallelogram (phasor addition) we can find
the supply voltage (V).
- 18-
Fig. 24 PHASOR DIAGRAM - RESISTANCE AND INDUCTANCE
Impedance
The opposition to current flow in this circuit is provided by the resistance of
the resistor and the reactance of the inductor and when there is a
combination like this the opposition to current flow is called IMPEDANCE (Z)
in ohms.
- 19 -
- 20 -
Fig. 25 RESISTANCE &
Once again, to draw the phasor diagram use the current phasor as the
reference, VR is in phase with the current so is drawn on top of I. The
voltage across the capacitor Vc is lagging the current by 90° and is drawn
vertically downwards. The actual supply voltage can again be found by
phasor addition.
The opposition to current flow provided by the capacitive reactance (Xc) and
resistance (R) is called impedance (Z) ohms.
-21 -
SUMMARY
1. The current leads the voltage or voltage lags the current by some
angle between 0 and 90° which depends on the values of C and R.
TanXc R
-22 -
2. Opposition to current flows is impedance (Z) ohms
ACTIVITY
- 23 -
RESISTANCE, INDUCTANCE AND CAPACITANCE IN SERIES
Note. In this circuit as VL is greater than Vc then current lags the voltage and
is therefore more inductive. The opposition to current flow is again
impedance and is:
- 24 -
Fig. 30 GRAPH OF XL & Xc AGAINST FREQUENCY
- 25-
If XL = Xc they are 180° apart (antiphase) so they will cancel leaving just the
resistance of the circuit so Z = R.
Also as VL and Vc are antiphase they also cancel so the applied voltage will
equal the voltage across the resistor VR = V. Current will be in phase with
the supply voltage and the power factor is 1.
At resonance, as the current is high the voltages across L and C are equal
and opposite so that their resultant is zero. However, when considered
alone they can be very high voltages, much greater than the supply and it is
this voltage magnification which will be discussed later.
-26-
Selectivity
The sharpness of response over a range of frequencies near resonance gives
an indication of the SELECTIVITY of the circuit. Selectivity is the property of
a tuned circuit which enables it to respond to a particular signal and
disregard others at different frequencies.
- 27 -
-28-
- 29 -
- 30-
PARALLEL AC CIRCUITS RESISTANCE -
The phasor diagram for the above circuit is shown in figure 37. Note that the
reference phasor is voltage as this is common to all components in a
parallel circuit.
The current in the capacitor (Ic) leads the voltage by 90° and the current in
the inductive circuit lags the voltage by some angle less than 90° due to the
resistance. The total current from the supply is the phasor addition of Ic
and IL.
If the frequency to this circuit was varied then at one particular frequency
XL = Xc, this is when the current taken from the supply is in phase with the
voltage. What is happening in the circuit is that the capacitor is charging
up and then discharging through the inductor, the emf induced in the
inductor will then charge up the capacitor in the reverse direction and this
will continue to circulate a current between the two components.
- 31 -
The circuit is said to be at RESONANCE, so we are now looking at a
PARALLEL RESONANT CIRCUIT. The conditions above would continue
forever but the inductor has resistance and there is a power loss here. In
order to keep the current circulating it is necessary to 'top up' the circuit
from the supply.
At resonance the current drawn from the supply is very small and therefore
the impedance is high (opposite to the series resonant circuit).
It should be noted that the actual current circulating between the inductor
and capacitor is high.
The phasor diagram (figure 39) shows the conditions at resonance with the
supply current in phase with the supply voltage.
- 32 -
Fig. 40 IMPEDANCE/FREQUENCY RESPONSE CURVES
-33 -
Figure 40 shows the impedance - frequency response curve. As for a series
circuit the Q 0 value and selectivity and bandwidth depend on R and the ratio
of L to C.
SUMMARY
One of the main factors determining the use of resonant circuits in radio
circuits is the internal impedance of the supply. Selectivity is best for a
series circuit when the supply source internal impedance is the same or
lower than the impedance at resonance. Similarly the parallel circuit has
better selectivity when the supply source is the same or higher than its
impedance (Zo) at resonance.
The first tuned circuit is normally a series tuned circuit because it is fed
from a low impedance source (the aerial). Voltage magnification takes place
where it is fed to an amplifier. The load' for the amplifier stages would be a
parallel tuned circuit because it is being fed from a high impedance source
(transistor).
Resonant circuits are also used for control of rotary inverter outputs and
some older aircraft generator frequency control circuits.
-34-
POWER IN AC CIRCUITS
a) In a purely resistive circuit, all of the current does work and POWER
is produced.
b) In a purely inductive circuit, the current does no work and NO
POWER is produced.
c) In a purely capacitive circuit, the current does no work and NO
POWER is produced.
It is very important to realise that only one current (I) flows in the circuit
and this is the current that is measured by an ammeter in the circuit.
-35-
The unit of reactive power is VOLT AMPS REACTIVE (VAR).
If the supply voltage is multiplied by the current (I) this will give us the
APPARENT POWER being dissipated, we know that this is apparently
available but because current and voltage are not in phase then that is not
the true power available from the system.
Power Factor
As we have seen we can work out the apparent power of a system in KVA.
What we need to know is how much of this available power is producing
actual work done in a circuit, ie producing True Power. So the ratio of
TRUE POWER
- 36-
So in this case the factor of power being used is 0.75, the generator is
producing 0.75 of its output as True Power ie producing power in the system.
So obviously the higher the power factor the better. Aircraft generation
systems are typically .75 - .9 power factor. A power factor of 1 (unity) would
mean that all of the power produced is being used as true power and the
circuit must be purely resistive.
- 37 -
THREE PHASE SYSTEMS
-38-
Figure 41 shows the basic principles of a single, two and three phase ac
supply.
In (a) the single phase generator has one rotating coil (wound many times)
with one cable going to the consumer units (assuming an earth return via
the airframe).
In (b) there are two coils on the same armature at 90° to each other and
there would be two cables going to the consumer units.
In (c) there are three coils on the same armature at 120° to each other
producing three outputs at 120° phase difference. Three supply cables
would be used - one for each phase, each going to its own bus on the
aircraft.
It is usual to connect the phases together into either a STAR
configuration or DELTA (A) configuration. It is standard practice
to identify each phase in a three phase system as Red (R), Yellow
(Y), and Blue (B). This is their phase sequence or phase rotation.
STAR CONNECTED AC GENERATOR OUTPUT
It can be seen from the diagram that the Line Current and Phase Current
are the same:
-39 -
It can also be seen that Line Voltage is derived from the two phases that are
connected across each pair of lines. Because the phase voltages are 120° out
of phase with each other, the Line voltage is found by multiplying the
Phase Voltage by
(c) If the individual loading across each of the three phases is identical,
the loads are said to be BALANCED. When such a condition exists, no
current will flow along the neutral line to or from the generator. The
neutral line only carries out-of-balance currents in the system.
(Because a three-phase line-to-line load (eg a motor) is bound to be
balanced, no neutral connection need be made to it).
(d) Phase voltage (V?h) is measured between any line and the neutral line.
By reference to the drawing it can be seen that LINE voltage ( VL ) and PHASE
voltage (Vph) is the same.
V L = V Ph
-40 -
Fig. 43 DELTA CONNECTED GENERATOR
It can also be seen that the LINE current is derived from the currents
that are flowing in the two windings that are connected to that particular
line. As the phases are 120° out-of-phase with each other the LINE
current (!L) is found by multiplying PHASE current (Iph) by V3 .
- 41 -
The Three Phase Voltages
As the output windings of the generator are identical, their outputs will be
of equal amplitude. These outputs are represented both graphically and as
phasors in figures 44 and 45.
It can be seen that, if values above the zero are called '+' and those below
zero are called ' - ', the sum of the voltages at any instant in time is always
zero.
A Symmetrical Three-Phase system
This is one in which the phase voltages are of the same magnitude and of
the same phase displacement. (The phase currents may have differing
magnitudes and phase displacements, depending upon the type and
magnitude of the phase loads).
-42 -
A Balanced Three-Phase System.
This is one in which the phase loads are equal and, therefore, the phase
currents are equal in magnitude and are operating at the same phase
angle. The phasor diagram is shown in figure 46.
(As with the voltages on the previous page, the sum of the instantaneous
currents in a BALANCED system always equals zero).
- 43 -
Fig. 49 ADDITION OF PHASORS 2
(a) The three phase voltages are 120° apart from each other.
(b) The three line voltages are 120° apart from each other.
(c) There is a phase angle of 30° between any phase voltage and it's
associated line voltage.
(d) THERE IS A PHASE ANGLE OF 90° BETWEEN ANY PHASE
VOLTAGE AND ITS 'OPPOSITE' LINE VOLTAGE. This last
relationship is often overlooked but is extremely important to
understand as it is widely used in control circuitry.
In the Star and Delta connected loads shown in figure 50, the True Power
in each phase is given by:
- 44 -
It is however, usual to express True Power in terms of line values, in
which case it is given by:
STAR CONNECTED LOAD DELTA CONNECTED LOAD
Fig. 50 POWER IN A BALANCED THREE PHASE SYSTEM
TRANSFORMERS
Principle
A transformer consists of two coils adjacent to each other and an ac
supply is applied to one coil known as the PRIMARY. The other coil is
known as the SECONDARY. The changing current in the primary creates
a fluctuating magnetic field that induces a voltage in the secondary coil
(mutual inductance).
For a transformer to work efficiently, all the lines of flux created by the
current in the primary should link with the secondary, this is not
possible but to try and get close to this on low frequency transformers an
iron core is used. It is suitably laminated to reduce eddy current losses.
Because of its high permeability the iron concentrates, and increase, the
lines of flux, and flux loss is small.
-45-
The principle is shown in figure 52. Each winding in the coil is insulated
and the two coils are insulated from one another and the iron core.
Turns Ratio
If the primary and secondary coils are identical, assuming no losses and
the secondary coil is open circuit, the emf induced in the primary coil will
be almost equal to but opposite in phase to the applied voltage. This
secondary coil will produce a mutually induced voltage which is exactly
the same as the primary back emf.
-46 -
If the number of turns on the secondary is increased its inductance
increases, and hence the induced emf increases. If the secondary has
twice the number of turns of the primary the secondary voltage will be
twice the applied voltage at the primary. With three times as many turns
on the secondary as the primary, the secondary emf will be three times
that in the primary.
Thus, a transformation ratio of 4:1 means that the output voltage will be
four times the input voltage (step-up) and a transformation ratio of 1:3
means that the output voltage will be one-third the input voltage (step-
down) .
-47-
Example
A transformer is wound with 100 turns on the primary and 450 turns on
the secondary. The primary is connected to a 250 volts ac supply. Find
the secondary voltage.
If there are more turns on the secondary than on the primary ie T greater
than 1 the secondary voltage is greater than the primary and we have a
STEP-UP TRANSFORMER.
If there are fewer turns on the secondary than on the primary ie T less
than 1 then the secondary voltage is less than input voltage and we have
a STEP- DOWN TRANSFORMER.
-48 -
Assuming no losses then the input power of a transformer equals the
output power.
Vp Ip = Vs Is
ACTIVITY
-49 -
Transformer Losses
Iron losses are due to two causes, eddy currents and hysteresis. From
book 1 you should appreciate that to reduce eddy current losses we
laminate the core and hysteresis losses are reduced by choosing a
material such as silicon steel, stalloy or permalloy which have low
hysteresis loss.
The resistive losses in the wires are called copper losses, which are due to
I2R losses of passing current through the resistance of the copper wire
forming the windings.
If all the primary flux does not link with the secondary then flux leakage
occurs, these may be reduced by the design of the core.
Transformer on No Load
The primary in figure 58 has a 100 volt ac supply and it's secondary is
open-circuited (no load). The current that flows in the primary will cause
an alternating flux in the core which will induce a voltage of 200 volts ac
in the secondary winding. (Check the turns ratio)
- 50-
The primary alternating flux will also induce a back-emf into the primary
winding in opposition to the applied emf. The effective emf acting on the
primary is therefore very small and only a very small current will flow into
the primary winding. (The foregoing is, of course, a description of
inductive reactance, XL). The very small current that flows in the primary
is that current which is necessary to overcome losses and to magnetise the
core.
Because the circuit is inductive, the off-load primary current will lag
behind the primary voltage. The in-phase component of this current is
overcoming copper losses and the quadrature component is magnetising
the core.
Transformer On Load
- 51 -
The phasor diagram shows how the load current (Is) is transformed
through 180° to become the primary load current (Ip) this is combined
with the off load current (Iou). To give the total primary current (Ip TOTAL) a
phasor drawing as shown below is produced.
Transformer Connections
-52 -
Phasing Dots
The next diagram shows a transformer with three secondary windings. The
dots at the ends of the windings are called phasing dots, they show that
the polarity at those points will be the same at the same moment in time,
ie points A D and E will all be positive together and all negative together.
The centre winding is therefore of opposite polarity to the other two
secondary windings. That is windings 1 and 3 will have a 180° phase shift
from the input while winding 2 will be in phase with the input. It will of
course be wound in the opposite sense.
Efficiency
Iron losses are reasonably constant, but copper losses vary as the square
of the currents flowing. Efficiency is greatest when copper losses are
equal to iron losses.
- 53 -
Regulation
TRANSFORMER TYPES
Core type. The laminations are either U-and I-shaped or L-shaped. They
are staggered when assembled to provide a single magnetic circuit. The
windings can be on one limb or split between the two limbs (see figure
62).
Shell type. The laminations are usually T- and U-shaped and are
staggered when assembled to give a three-limbed former.
This gives two magnetic paths and this type, whilst more expensive to
build, is more suitable for use with large values of current.
- 54 -
Fig. 62 TRANSFORMER TYPES
When used for single-phase work, each limb is allocated to the primary
and secondary windings of one particular phase. (This point is covered
later in these notes).
It should be noted, that af transformers can be used as 'matching'
impedances. (Again, see later in these notes). They may also be used as
isolation transformers when the primary and secondary have the same
number of turns so Vp = Vs. It is a way of isolating electrically one circuit
from another without altering the ac conditions.
- 55-
They are inefficient for power transfer and secondary voltage is no longer
equal to T (turns ratio) times the primary voltage.
rf transformers often have iron dust (ferrite) cores which are used to
adjust the coil inductance or modify the coupling effect between the two
coils. Other rf transformers might have the coils wound on a ferritte rod
to act as an aerial receiving arrangement. In nearly all cases, one or both
of the coils will be tuned by parallel capacitors to be resonant at one
fixed frequency or adjustable over a range of frequencies.
ACTIVITY
a) Vs
b) Is if connected to a 87Q load.
c) Ip with the load connected.
a) Lower frequency.
b) Higher frequency.
- 56-
If an ac supply is applied to the primary terminals, an alternating current
will flow through those coils connected across P1 and P2. This will set up
an alternating flux which will link with all of the turns on the former,
inducing a voltage in each.
The output voltage is therefore that which appears in the coils across
terminals S1 and S2. Loading the secondary will have the same effect as
described for the Power Transformer. If the current flow is considered for
one particular half-cycle, it will be seen that the primary and secondary
currents are opposing each other in the common portion of the winding.
The actual current flow in the common portion is therefore the difference
between the two currents. This means that the cross-section area of the
copper can be decreased in the common portion, bringing about a saving
in weight.
This device was known about for many years but no practical use was
made of it until the advent of constant frequency ac systems in aircraft
with their associated control systems.
A device was required that gave a phase angle of 90° between the current
in one circuit and a signal being put into another circuit. The angle
between the primary current in a quadrature transformer and its
secondary voltage is (for all practical purposes) 90°.
- 57 -
VP
If an air gap is cut in the former of the transformer, more current will be
required to magnetise the core to overcome the increased reluctance. As
the magnetising element of the primary current is at 90° to the applied
voltage, it can be seen that the primary current is increased and at the
same time moved around until it is almost 90° behind the applied
voltage, it also follows that the primary current is almost at 90° ahead of
the secondary emf.
- 58 -
Fig. 67 PHASOR DIAGRAM FOR QUADRATURE TRANSFORMER
The air gap has an optimum size and is usually beneath the windings, so it
looks just like any other small transformer. It is only used to obtain signal
voltages and cannot be loaded to any great extent.
- 59-
Fig. 68 THE CURRENT TRANSFORMER
Operation
When the load passes through the supply cable, it creates a magnetic
field along its whole length which is constantly building-up, collapsing,
reversing, building-up, etc. It is this flux which induces emfs into the
coils of the secondary winding.
As the ring former and secondary coil only take up a very small length of
the primary cable, it is obvious that, whatever happens at the secondary,
the effect on the primary will be virtually nil. The primary, which depends
on the load, may therefore be regarded as a constant current/constant
flux supply.
The voltage in the secondary winding causes a current to flow through its
load and through the secondary winding. This produces a secondary flux
which opposes the primary flux and so keeps the core flux to a very low
level. This is a most important point to remember because, if the primary
is operated with the secondary winding disconnected from its load there
will be no secondary emf to oppose the primary emf.
This will result in a high core flux; increased eddy currents in the core;
increased voltages in the individual secondary coils; and overheating.
The result is that the current transformer will burn out. (Even if the
mistake is realised and the system is switched off before it actually burns
out, the core may be pre-magnetised, or biased, and cannot therefore be
relied upon to be accurate).
- 60-
If it is necessary to operate the primary when the secondary load is
disconnected, short together the secondary terminals. This will cause a
secondary current and flux and so keep the core flux to a minimum.
SUMMARY
1. When fitting a current transformer, GET IT THE RIGHT WAY
ROUND.
2. When connecting the secondary to its load, CONNECT IT
CORRECTLY.
3. NEVER operate the primary circuit with the secondary open-
circuited--------- SHORT IT OUT!
4. NEVER operate a current transformer on anything other than its
DESIGNED LOAD.
5. In some cases, the current transformer and its load are a matched
pair. (They may even carry the same serial numbers). If one is
changed, then the other must also be changed.
6. When they are used in control circuitry, remember that the
secondary output is a supply source proportional to the primary
current flow.
- 61 -
In any circuit:
the Impedance Z = V/I
Therefore, in a transformer, the impedance Zs of the secondary is the ratio
of secondary voltage to secondary current and the impedance Zp of the
primary is the ratio of the primary voltage to the primary current.
The primary and secondary voltages and currents are related to each
other by the Turns Ratio of the transformer and so it follows that the
impedance's must be related also. This relationship is given by:
ZP = Zs/T2
If we have a case where they are not equal and we want maximum power
to be transferred, we can use the impedance matching effect of a
transformer to achieve the necessary conditions. It is not very difficult to
make a load impedance appear to the supply source to be equal to the
supply source's own impedance.
- 62 -
As an example: The 4 ohms impedance shown in figure 70 must be made
to appear to the supply source to be equal to 10,000 ohms. From the
formula ZP = Zs/T2, we need to find T.
Therefore T = 1/50.
This means that a 50:1 step-down transformer will transform the 4 ohms
in the secondary to 10,000 ohms in the primary and maximum power is
then transferred to the load.
- 63 -
There are four combinations for three phase transformers:
* Star-star
* Delta-delta
* Delta-star
* Star-delta
- 64-
Fig. 74 DELTA-DELTA THREE PHASE TRANSFORMER
- 65 -
Fig. 76 DELTA-STAR THREE PHASE TRANSFORMER
FILTERS
We shall consider the simple form of the following filters: low pass; high
pass; band pass; band stop.
- 66-
Low Pass Filter
The simple form of the filter is made up of inductors and capacitors, two
examples are shown in figure 78.
At very high frequencies the capacitor acts almost like a short circuit.
-67-
The impedance of the inductor is low at low frequencies and high at high
frequencies . With a combination of these two different effects
the voltage gain tends to zero as shown in the graph. By using a rc type
filter the voltage drops off more steeply.
Design impedance
And
This is the opposite to the low pass filter and attenuates (blocks) all
frequencies up to the cut-off frequency and passes all frequencies above
this value. It is called a HIGH PASS FILTER. Figure 79 shows the
characteristic graph, and again the shaded area is the ideal and the
curve the practical operation. Simple circuits for this form of filter are
shown in figure 80.
and
- 68 -
T TYPE n TYPE
A filter that passes all frequency components between some low cut-off
frequency f c1, and some high cut-off frequency f C2 and blocks all
frequencies below f c1 and above fC2 is a BAND PASS FILTER.
- 69-
Figure 81 shows the characteristic ideal and practical range. Figure 82
shows a simple circuit for a band pass filter.
-70-
Band Stop Filter
A filter that stops the transmission of frequencies between fc1 and fC2.
Figure 83 shows the characteristics.
The series element this time is parallel resonant circuits and the shunt
element is a series resonant circuit.
As the frequency increases the parallel circuit impedance falls and the
series circuit increases so frequencies are passed again.
- 71 -
Applications
DIFFERENTIATORS
Figure 85 shows a simple differentiator circuit consisting of a resistor (R)
and a capacitor (C).
This circuit could be used as a high pass filter, however, with a square
wave input and a short time constant compared to the input pulse, it can
be used as a differentiating circuit.
Fig. 85 DIFFERENTIATOR
- 72 -
Fig. 86 INPUT/OUPUT GRAPHS - DIFFERENTIATOR
Figure 86 shows the input pulse (V) and the voltages across C (Vc) and R
(VR). Note that:
(b) The output across R consists of two very narrow pulses of opposite
sign, one coinciding with the start, the other with the end of the
pulse.
(c) VR = V0
-73-
INTEGRATORS
If the positions of C and R are changed and we make the time constant
large compared to the input pulse we have an integrating circuit (Figure
87). (Note this basic circuit could be used as a low pass filter). Figure 88
shows the input pulse to a RC circuit with a long time constant and the
resulting output across the capacitor.
Fig. 87 INTEGRATOR
- 74-