1 2 3 4 5 6 7

NOTES:

1. This drawing is to be read in conjunction with the following Drawings:


START OF TANK Detail A Detail B
MANUFACTURER'S 5521/CE/010 OHAMAREMBA BPS SITE LAYOUT
PIPEWORK Outlet to Booster 5521/CE/013 BT FOUNDATION RING DETAILS
Pump Station 5521/ME/003 WATER METER MANHOLE

400
A Water Level A 2. Setting out of pipework according to coordinates E and H.
Level Indicator
Access Ladders 3. All underground GMS pipework, DCI fittings and valves to be DENSO
wrapped.
Reinforced Concrete Manhole
4. Tank Manufacturer to design, supply and install all pipework, fittings and
Foundation Ring valves between "Start- and End of Tank Manufacturer's Pipework" as
OVERFLOW & shown in drawing.

INLET PIPE SCOUR PIPE 84


°

°
Future Outlet as per

96
Detail D with additional Overflow &
Blank Flange supplied by Center Point Scour Outlet
Tank Manufacturer Coordinate E

4775
Ground Level Balancing Tank
B ND150 GMS Pipework. Volume 450 m³ B
Design and supply by Ø 10.982 m
Tank Manufacturer Height 4.775 m
ND100 GMS Pipework as
per Drawing 5521/ME/003 Ø 10982 for 450 m³ Tank
and supplied by Contractor

Inlet from Water


ND150 PN10 Flanged
Meter Manhole
resilient seated Gate Valve
supplied by Tank Manufacturer
SCHEMATIC LAYOUT OF PIPEWORK SCALE 1 : 200
Detail C
FL ±1075.60
60

450
150

C C
NGL NGL
END OF TANK MANUFACTURER'S PIPEWORK
FOR CONSTRUCTION
700

400

700
ND150 GMS Pipework with Valve
600 Detail D as per Drawing 5521/ME/003 and
supplied by Contractor
Reinforced Concrete Foundation Ring 1 Changes to Schematic Layout of Pipework FK 10.02.2023
NGL
Ø 110 uPVC Class 6 Pipe Ø 160mm uPVC Class 6 Pipe to Scour Manhole No. REVISIONS APP. DATE

150
200 223
from Water Meter Manhole

750
Flange Adaptor Ø 160mm/ND150 CLIENT
Flange Adaptor Ø 110mm/ND100 END OF TANK MANUFACTURER'S PIPEWORK

Kunene
D D
TANK PIPEWORK DETAILS SCALE 1 : 50 Ø 160mm uPVC Class 6 Pipe Regional
to Booster Pump Station
260 Council
PO BOX 502 TEL: (065) 27 3950, FAX: (065) 27 3077
TANK OUTLET PIPEWORK SCALE 1 : 50 OPUWO, NAMIBIA EMAIL: info@kunenerc.com.na

ND100 GMS Pipe TO BOOSTER PUMP STATION APPROVED DATE

Flanges SANS1123 COPYRIGHT RESERVED


Roof Roof
Table 1000/3
CONSULTANTS
PROJECT ENGINEERS
ND150 GMS Pipe 150 150
Roof Structure/Beams Flange SANS1123 PCE POWERCONSULT ENGINEERS
225

Table 1000/3 PO BOX 3628 TEL: (65) 231 997, FAX: (065) 231 980
275

E E ONGWEDIVA, NAMIBIA EMAIL: antindi@powerconsult.com.na


Shell Panel
CIVIL ENGINEER
Shell Panel
ND150 GMS Pipe KUCHLING CONSULTING ENGINEERS
Flange SANS1123 PO BOX 801 TEL: (061) 305 420, FAX: (061) 305 418
ND150 GMS Pipe Table 1000/3
WINDHOEK, NAMIBIA fkuchling@iway.na

Flange SANS1123
PROJECT
ND100 Bend Table 1000/3

200
Shell Panel OKANGUATI WATER SUPPLY PROJECT

150
Support bracket affixed to roof structure.
Shell Panel Tank Membrane Tank Membrane
Design and Supply by Tank Manufacturer.
DRAWING TITLE
100 ND100 GMS Pipe 3.0 m long with ND100 Bend
Channel Ring Channel Ring OHAMAREMBA SITE
supplied by Tank Manufacturer
450 m3 BALANCING TANK
200 3000 150
F F
PIPEWORK DETAILS
Foundation Ring Foundation Ring
CIVIL INSTALLATION

CONSULTANT PROJECT NO.:


DETAIL A: TANK INLET DETAIL B: TANK OVERFLOW DETAIL C: TANK SCOUR OUTLET DETAIL D: TANK OUTLET DESIGNED: DRAWN: CHECKED:
SCALE 1 : 10 SCALE 1 : 10 SCALE 1 : 10 SCALE 1 : 10
SCALE: DATE:

DRAWING NO.: VO.:


1 2 3 4 5 6 7