Mtech Transducer Catalogue

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 40

Power

Transducers
Table of Contents

Model Page

AC Current Transducers 4

AC Voltage Transducers 7

AC Power Transducers 10
Watt (Active Power)
VAR (Reactive Power)
Q (Reactive Power)
VA (Apparent Power)

AC Energy Transducers 13
Watt/VAR/Q-Hour (Consumed Energy)

Power Factor/Phase Angle Transducers 16

Frequency Transducers 18

RTD/Slidewire Transducers 19

DC Voltage Transducers/Ground Fault Detectors 20

Line Post Sensor Transducers/Fault Alarms 21

Line Post Sensor Transducer System 23

Portable Transducer Calibrator 25

Dimensions 27

Connection Diagrams 29
Before you can control electricity,
you have to measure it.
Whether you are a utility generating and distributing electricity, or an industrial
plant or commercial facility trying to manage and conserve it, optimization of your
processes depends heavily on accurate power measurement. Measurement
Technologies (mTech) has high quality transducers, covering virtually every
electrical variable, and virtually any I/O combination.
Our products are in daily use by hundreds of utilities, industrial plants, and
commercial customers from all over the world. We strive to meet the needs of the
market with more models and more features per model. We offer DIN cases for
high-density mounting, as well as the traditional, surface-mounting, metal
enclosures. All our units are built to the highest quality standards and perform with
exceptional accuracy and reliability.
We offer a range of models within each of the following categories: AC current;
AC voltage; watts; VAR; Q; VA; watt/VAR/Q-Hour; frequency; power factor;
RTD/slidewire; DC voltage/ground fault detection; and line post sensing. We even
have a portable system for testing transducers.
No one is better equipped to help you measure electricity.

THERE’S AN mTech POWER TRANSDUCER FOR EVERY REQUIREMENT


Trans-
Phase Ground former Ambient Watt/ VAR/ Billing DC
Utilities Watts VARs Current Voltage Frequency Angle Faults Temp. Temp. Watt-hour VAR-hour Allocation Voltage
Generating Per generator ● ● ● ● ● ●
Station
General Use ● ● ● ●
Transmission Incoming Line ● ● ● ●
Station
Outgoing Line ● ● ● ●
General ● ● ● ●
Transformer Incoming Line ●
Station
Station Buss ● ● ● ●
Feeder ● ● ●
General ● ● ● ●
Distribution Incoming Line ●
Station
Station Buss ● ● ● ●
Feeder ●
General ● ● ● ●
PROCESS Motors ● ● ● ● ●
USERS
Energy
● ● ●
Management
Uninterruptible
● ● ● ● ● ● ●
Power Systems

3
AC Current Transducers

Current: The electric charge passing through


a circuit per unit of time. Engineering unit is
the Ampere. Measured in series with a source
or load. Can be inductively monitored with a
current transformer.

Standard Features Operating Temperature: -20°C to +70°C


Operating Humidity: 0 to 95% non-condensing
• True RMS or average-sensing models
Temperature Coefficient: 0.01%/°C
• 0.25% of full scale accuracy Long Term Drift: less than 0.2% of rated output per year
• 0.01%/°C temperature coefficient Output Ripple (Peak): 0.5% maximum
Power Factor Range: any
• 0.2%/year long-term stability
Dielectric Test Input/Output/Power/Case: 2,000 Vrms
• 2.5 kV transient immunity for 1 minute
• 5 kV impulse test Response Time
To 90%: 200 ms maximum
• 2 kV dielectric testing
To 99%: 400 ms maximum
• Current and voltage outputs Surge Withstand: ANSI C37.90a (IEEE 472); BEAMA 219;
• ABS DIN rail mount or metal surface Special 5 kV (metal case only)
Calibration Range Full scale: ±10% minimum; ±2%
mount cases minimum (if applicable)
Operating Frequency: 60 Hz (unless otherwise specified)
Specifications
UL Approved Models: A100, A300, A104E, A304E,
Accuracy (20°C to 25°C): 0.25% of rated full scale output DA100, DA300, DA104E, DE304E
from 5% to 110% of rated input range

Overload Without Damage


Option Input Overrange with Acc. Cont. 10 s/h 1 s/h Burden
0 0-5 A 7.5 A 15 A 30 A 250 A Maximum input burden
1 0-1 A 1.5 A 3A 6A 100 A is 4 VA at full scale
2 0-2 A 3.0 A 6A 12 A 150 A regardless of option.
3 0-10 A 15 A 30 A 50 A 300 A Burden may be as low
4* 0-25 A 35 A 35 A 75 A 300 A as 0.1 VA. Consult factory if
critical.
*Metal case models only

4
Available Models – RA/DRA Series
AC Current Transducers True RMS Sensing, Zero-Based Input
Recommended where harmonics are present in the system.
A/DA Series Uses new low voltage integrated circuit technology that
computes the RMS value of the input waveform, regardless
Average Sensing, Zero-Based Input of shape, from the fundamental to the 50th harmonic. Self-
An economical and accurate means of current measurement powered or externally-powered. Readings down to virtually
on systems where the waveform is a pure sine wave. Can zero can be achieved with auxiliary-powered models. 4-20
also be used for non-critical applications with distorted mA output versions must have auxiliary power.
waveforms, where high accuracy is not required. Calibrated
To Order, Specify:
to the RMS (root mean square) value of the sine wave.
Available in single or triple versions, self-powered or A. ENCLOSURE
externally powered. 4-20 mA and 1-5 V output versions must Extruded Aluminum Metal, Surface Mount RA
have auxiliary power. ABS DIN, Rail Mount DRA
To Order, Specify: B. CONFIGURATION
Single 1
A. ENCLOSURE
Extruded Aluminum Metal, Surface Mount A C. INPUT
ABS DIN, Rail Mount DA 0-5 A 0
0-1 A 1
B. CONFIGURATION
Special X
Single 1
Triple 3 D. OUTPUT
0-1 mA (0-10,000 Ohms) 0
C. INPUT
4-20 mA (0-750 Ohms) Aux Power Only 4
0-5 A 0
Special X
0-1 A 1
0-2 A 2 E. SUFFIX (If Applicable)
0-10 A 3 25 to 125% Calibration A
0-25 A ① 4 50 Hz C
Special X 400 Hz D
① Metal case models only. 120 VAC Aux Power E
230 VAC Aux Power F
D. OUTPUT
Case Ground Terminal ① G
0-1 mA (0-10,000 Ohms) 0
DC Aux Power (Please Specify) K
0-3 mA (0-3,300 Ohms) 1
Special X
0-5 mA (0-2,000 Ohms) 2 ① Metal case models only.
0-10 mA (0-1,000 Ohms) 3
4-20 mA (0-750 Ohms) ② 4 EXAMPLE: RA-1-0-4-F is the ordering code for an RMS-
0-100 mV (2,000 Ohms min.) 5 Sensing Current Transducer in a metal surface mount
0-1 V (2,000 Ohms min.) 6 case, a single version, with a 0-5 A input, a 4-20 mA
0-5 V (2,000 Ohms min.) 7 output, and 230 VAC auxiliary power.
0-10 V (2,000 Ohms min.) 8
1-5 V (2,000 Ohms min.) ② 9
Special X
SA/DSA Series
E. SUFFIX (If Applicable) Three-Phase Summation Transducers
25 to 125% Calibration A Average sensing devices calibrated to the RMS value of the
50 Hz C sine wave. Available in three phase versions only, they
400 Hz D provide an output that is the arithmetic sum of the inputs.
120 VAC Aux Power E Self-powered or externally-powered. 4-20 mA and 1-5 V
230 VAC Aux Power F output versions must have auxiliary power.
Case Ground Terminal ① G To Order, Specify:
DC Aux Power (Please Specify) K
A. ENCLOSURE
Special X
① Metal case models only.
Extruded Aluminum Metal, Surface Mount SA
② Auxiliary power supply required.
ABS DIN, Rail Mount DSA
B. CONFIGURATION
EXAMPLE: DA-3-2-4-E is the ordering code for an
Triple 3
Average-Sensing Current Transducer in a DIN rail mount
case, a triple version, with a 0-2 A input, a 4-20 mA C. INPUT
output, and 120 VAC auxiliary power. 0-5 A 0
0-1 A 1
Special X

5
D. OUTPUT 0 ± 100 mV (2,000 Ohms min.) 5
0-1 mA (0-10,000 Ohms) 0 0 ± 1 V (2,000 Ohms min.) 6
0-3 mA (0-3,300 Ohms) 1 0 ± 5 V (1,000 Ohms min.) 7
0-5 mA (0-2,000 Ohms) 2 0 ± 10 V (2,000 Ohms min.) 8
0-10 mA (0-1,000 Ohms) 3 1-5 V (1,000 Ohms min.) 9
4-20 mA (0-750 Ohms) ② 4 F. SUFFIX (If Applicable)
0-100 mV (2,000 Ohms min.) 5 25 to 125% Calibration A
0-1 V (2,000 Ohms min.) 6 50 Hz C
0-5 V (2,000 Ohms min.) 7 400 Hz D
0-10 V (2,000 Ohms min.) 8 120 VAC Aux Power E
1-5 V (2,000 Ohms min.) ② 9 230 VAC Aux Power F
Special X Case Ground Terminal ① G
E. SUFFIX (If Applicable) DC Aux Power (Please Specify) K
25 to 125% Calibration A Special X
50 Hz C ① Metal case models only.
400 Hz D
EXAMPLE: BA-1-0-1-3-E is the ordering code for a
120 VAC Aux Power E
Single-Phase Average Sensing, Bi-Directional Current
230 VAC Aux Power F
Transducer in a metal surface mount case, a single
Case Ground Terminal ① G version, with a 0-5 A input, 120 VAC potential input, a 0
DC Aux Power (Please Specify) K ± 10 mA output, and 120 VAC auxiliary power.
Special X
① Metal case models only.
② Auxiliary power supply required. TA/DTA Series
EXAMPLE: DSA-3-1-2-A is the ordering code for a Three- Single-Phase, Average Sensing, Two-Wire Loop Powered
Phase Summation Current Transducer in a DIN rail mount Average sensing, zero-based input transducers that are
case, triple-phase, with a 0-1 A input, a 0-5 mA output, calibrated to the RMS value of the sine wave. Single-phase
and 25 to 125% calibration. versions only. Two-wire loop powered. 4-20 mA output only.
To Order, Specify:
BA/DBA Series A. ENCLOSURE
Single-Phase, Average Sensing, Bi-Directional Extruded Aluminum Metal, Surface Mount TA
Average sensing, zero-based input transducers that are bi- ABS DIN, Rail Mount DTA
directional and calibrated to the RMS value of the sine wave. B. CONFIGURATION
Single-phase versions only, they must be powered from a Single 1
potential source on the power line being measured. Output is
C. INPUT
proportional to the input magnitude, with polarity set by the
0-5 A 0
direction of current flow. 4-20 mA and 1-5 V versions use 12
0-1 A 1
mA and 3 V as the zero current reference.
Special X
To Order, Specify:
D. OUTPUT
A. ENCLOSURE 4-20 mA (Load limited by loop voltage, 4
Extruded Aluminum Metal, Surface Mount BA 18-30 VDC)
ABS DIN, Rail Mount DBA
E. SUFFIX (If Applicable)
B. CONFIGURATION 50 Hz C
Single 1 400 Hz D
C. INPUT Case Ground Terminal ① G
0-5 A 0 Special X
0-1 A 1 ① Metal case models only.
Special X EXAMPLE: TA-1-1-4-G is the ordering code for a Two-
D. POTENTIAL Wire Loop Powered Single-Phase, Average Sensing
120 VAC 0 Transducer in a metal surface mount case, single-phase
Special X with a 0-1 A input, a 4-20 mA output, and a case ground
E. OUTPUT terminal.
0 ± 1 mA (0-10,000 Ohms) 0 See page 29 for connections.
0 ± 3 mA (0-3,300 Ohms) 1
0 ± 5 mA (0-2,000 Ohms) 2
0 ± 10 mA (0-1,000 Ohms) 3
4-20 mA (0-750 Ohms) 4

6
AC Voltage Transducers

Voltage: The most basic AC measurement.


The magnitude of the waveform measured
across a source or load. RMS is the most
commonly used voltage value.

Standard Features Operating Temperature: -20°C to +70°C


• True RMS or average-sensing models Operating Humidity: 0 to 95% non-condensing
• 0.25% of full scale accuracy Temperature Coefficient: 0.01%/°C maximum
• 0.01%/°C temperature coefficient Long Term Drift: less than 0.2% of rated output per year
• 0.2%/year long-term stability Output Ripple (Peak): 0.5% maximum
• 2.5 kV or 5 kV transient immunity Power Factor Range: any
• 5 kV impulse test Dielectric Test Input/Output/Power/Case: 2000 Vrms
for 1 minute
• 2 kV dielectric testing
Response Time
• Current and voltage outputs
To 90%: 200 ms maximum
• ABS DIN rail mount or metal surface
To 99%: 400 ms maximum
mount cases
Surge Withstand: ANSI C37.90a (IEEE 472); BEAMA 219;
Special 5 kV (metal case only)
Specifications
Calibration Range Full scale: ±10%; ±2% (if applicable)
Accuracy (20°C to 25°C): 0.25% of rated full scale output
from 10% to 110% of rated input range (some models work Operating Frequency: 60 Hz (unless otherwise specified)
to zero) UL Approved Models: V100, V300, V104E, V304E,
DV100, DV300, DV104E, DV304E

Max. Input Max. Input


Option Input Nom. Input F.S. with Acc. Cont. 10 s Burden
0 120 V 150 V 180 V 200 V 250 V Maximum input burden
1 69 V 90 V 110 V 120 V 150 V is 4 VA at full scale
2 240 V 300 V 360 V 400 V 600 V regardless of option.
3 480 V 600 V 650 V 700 V 900 V Burden may be as low
4 to 9 Per Option 0 or 2 as applicable as 0.1 VA. Consult factory
if critical.

7
Available Models– RV/DRV Series
AC Voltage Transducers True RMS Sensing, Zero-Based Input
Recommended where harmonics are present in the system.
V/DV Series Uses new low voltage integrated circuit technology that
computes the RMS value of the input waveform, regardless
Average Sensing, Zero-Based Input of shape, from the fundamental to the 50th harmonic. Self-
An economical and accurate means of voltage measurement powered or externally-powered. Readings down to virtually
on systems where the waveform is a pure sine wave. Can zero can be achieved with auxiliary-powered models. 4-20
also be used for non-critical applications with distorted mA version must have auxiliary power.
waveforms, where high accuracy is not required. Calibrated
To Order, Specify:
to the RMS (root mean square) value of the sine wave.
Available in single or triple versions, self-powered or A. ENCLOSURE
externally powered. 4-20 mA and 1-5 V output versions must Extruded Aluminum Metal, Surface Mount RV
have auxiliary power. ABS DIN, Rail Mount DRV
To Order, Specify: B. CONFIGURATION
A. ENCLOSURE Single 1
Extruded Aluminum Metal, Surface Mount V C. INPUT
ABS DIN, Rail Mount DV 0-150 V 0
B. CONFIGURATION Special X
Single 1 D. OUTPUT
Triple 3 0-1 mA (0-10,000 Ohms) 0
4-20 mA (0-750 Ohms) Aux. Power Only 4
C. INPUT
Special X
0-150 V 0
0-90 V 1 E. SUFFIX (If Applicable)
0-300 V 2 25 to 125% Calibration A
0-600 V 3 50 Hz C
Special X 400 Hz D
120 VAC Aux Power E
D. OUTPUT
230 VAC Aux Power F
0-1 mA (0-10,000 Ohms) 0
Case Ground Terminal ① G
0-3 mA (0-3,000 Ohms) 1
DC Aux Power (Please Specify) K
0-5 mA (0-2,000 Ohms) 2
Special X
0-10 mA (0-1,000 Ohms) 3 ① Metal case models only.
4-20 mA (0-750 Ohms) ② 4
EXAMPLE: RV-1-0-4-F is the ordering code for an RMS-
0-100 mV (2,000 Ohms min.) 5
Sensing Voltage Transducer in a metal surface mount
0-1 V (2,000 Ohms min.) 6
case, single-phase, with a 0-150 V input, a 4-20 mA
0-5 V (2,000 Ohms min.) 7
output, and 230 VAC auxiliary power.
0-10 V (2,000 Ohms min.) 8
1-5 V (2,000 Ohms min.) ② 9
Special X VX/DVX Series
E. SUFFIX (If Applicable) Single-Phase, Average Sensing, Suppressed
25 to 125% Calibration A Zero-Based Input
50 Hz C Average sensing devices calibrated to the RMS value of the
400 Hz D sine wave. Available in single-phase versions only. Self-
120 VAC Aux Power E powered or externally-powered. 4-20 mA and 1-5 V output
230 VAC Aux Power F versions must have auxiliary power.
Case Ground Terminal ① G
DC Aux Power (Please Specify) K To Order, Specify:
Special X A. ENCLOSURE
① Metal case models only. Extruded Aluminum Metal, Surface Mount VX
② Auxiliary power supply required. ABS DIN, Rail Mount DVX
EXAMPLE: DV-3-2-4-E is the ordering code for an B. CONFIGURATION
Average-Sensing Voltage Transducer in a DIN rail mount Single 1
case, a triple version, with a 0-300 V input, a 4-20 mA C. INPUT
output, and 120 VAC auxiliary power. 90-150 V 4
100-140 V 5
110-130 V 6
180-300 V 7
200-280 V 8
220-260 V 9
Special X

8
D. OUTPUT E. SUFFIX (If Applicable)
0-1 mA (0-10,000 Ohms) 0 25 to 125% Calibration A
0-3 mA (0-3,300 Ohms) 1 50 Hz C
0-5 mA (0-2,000 Ohms) 2 400 Hz D
0-10 mA (0-1,000 Ohms) 3 120 VAC Aux Power E
4-20 mA (0-750 Ohms) ② 4 230 VAC Aux Power F
0-100 mV (2,000 Ohms min.) 5 Case Ground Terminal ① G
0-1 V (2,000 Ohms min.) 6 DC Aux Power (Please Specify) K
0-5 V (2,000 Ohms min.) 7 Special X
0-10 V (2,000 Ohms min.) 8 ① Metal case models only.
1-5 V (2,000 Ohms min.) ② 9 ② Auxiliary power supply required.

E. SUFFIX (If Applicable) EXAMPLE: RVX-1-9-0-C is the ordering code for a Single-
25 to 125% Calibration A Phase, True RMS Sensing, Suppressed Zero-Based Input,
50 Hz C Voltage Transducer in a metal surface mount case,
400 Hz D single-phase, with a 220-260 V input, a 0-1 mA output,
120 VAC Aux Power E and 50 Hz.
230 VAC Aux Power F
Case Ground Terminal ① G
DC Aux Power (Please Specify) K TV/DTV Series
Special X Single-Phase, Average Sensing, Two-Wire Loop Powered
① Metal case models only.
Average sensing, zero-based input transducers that are
② Auxiliary power supply required.
calibrated to the RMS value of the sine wave. Single-phase
EXAMPLE: DVX-1-4-2-A is the ordering code for a Single- versions only. Two-wire loop powered. 4-20 mA output only.
Phase, Average Sensing Voltage Transducer in a DIN rail To Order, Specify:
mount case, single-phase, with a 90-150 V input, a 0-5
A. ENCLOSURE
mA output, and 25 to 125% calibration.
Extruded Aluminum Metal, Surface Mount TV
ABS DIN, Rail Mount DTV
RVX/DRVX Series B. CONFIGURATION
Single-Phase, True RMS Sensing, Suppressed Single 1
Zero-Based Input C. INPUT
RMS sensing, suppressed zero-based input devices. 0-150 V 0
Available in single-phase versions only. Self-powered or Special X
externally-powered. 4-20 mA version must have auxiliary
D. OUTPUT
power.
4-20 mA (Load limited by loop voltage, 4
To Order, Specify: 18-30 VDC)
A. ENCLOSURE E. SUFFIX (If Applicable)
Extruded Aluminum Metal, Surface Mount RVX 50 Hz C
ABS DIN, Rail Mount DRVX 400 Hz D
B. CONFIGURATION Case Ground Terminal ① G
Single 1 Special X
① Metal case models only.
C. INPUT
90-150 V 4 EXAMPLE: TV-1-0-4-G is the ordering code for a Two-
100-140 V 5 Wire Loop Powered Single-Phase, Average Sensing
110-130 V 6 Transducer in a metal surface mount case, single-phase,
180-300 V 7 with a 0-150 V input, a 4-20 mA output, and a case
200-280 V 8 ground terminal.
220-260 V 9 See page 30 for connections.
Special X
D. OUTPUT
0-1 mA (0-10,000 Ohms) 0
4-20 mA (0-750 Ohms) ② 4
Special X

9
AC Power Transducers
Watts • VAR • Q • VA • WR • WQ
Watts: A measure of power or work being done. In an AC
circuit, current multiplied by voltage multiplied by the cosine
of the phase angle between current and voltage. Differing
loads cause current to lag or lead voltage by some angle in
degrees, which causes the power consumed (watts) to be
less than the product of the voltage times current.
VAR: Current and voltage that does no work. A Volt-Ampere
Reactance is essentially the opposite of a watt.
VAR is the product of voltage multiplied by
current in opposite quadrants. They increase as
the phase angle increases and can be either
leading (to the high side of the center zero based
output) or lagging (to the low side of zero).
Q: A measure of reactive power. Permits
calculation of VAR-hours to be recorded with one
counter in a positive direction between 0.866
leading and zero lagging, which is within the
typical power factor range of electrical equipment.
VA: Voltage times current. Also known as
“apparent power.”

Standard Features:
• 0.2% of reading accuracy
• <0.005%/°C temperature coefficient
Long Term Drift: <0.2%/year non-cumulative
• Low burden
Temperature Range
• Transient protected Operating: -20°C to +70°C
Storage: -40°C to +75°C
• Voltage, current, and process outputs
Temperature Coefficient: ≤0.005%/°C
• Electronic multipliers — over 200 real time Operating Humidity: 0-95% non-condensing
multiplications of Volts times Amps per Output Ripple Peak: ≤0.5% peak
Power Factor Range: Watt or VAR, any; Q, 0.866 lead to
cycle for accurate conversions of even the 0 lag
most distorted waveforms Operating Frequency: Nominal ±10% in accordance with
IEC 688
• Exceptional long-term stability Standard Calibration: Watt/Q is uni-directional, VAR/VA is
• 1, 1-1/2, 2, 2-1/2, and 3 element versions bi-directional, unless otherwise specified
Dielectric Test: 2,000 Vrms for 1 minute; 2,400 Vrms
• Self-powered or externally powered for 1 second
• ABS DIN rail or metal surface mount cases Transient/Surge Test: ANSI C37.90a (IEEE 472) BEAMA 219
• Isolated outputs on combined transducers Response Time: ≤200 msec to 90%, ≤400 msec to 99%
Calibration: Full scale, ±10% standard; Zero, ±2% standard
UL Approved Models: W10000, W10004, W15000,
Specifications W20000, W20004, W25000, W25004, W30000, W30004,
Accuracy (@ 25°C ±2°C) DW10000, DW10004, DW15000, DW15004, DW20000,
Watt: 0.19% of reading ±0.01% of full scale DW20004, DW25000, DW25004, DW30000, DW30004,
CosQ R10000, R10004, R15000, R15004, R20000, R20004,
VAR: 0.19% of reading ±0.01% of full scale R25000, R25004, R30000, R30004, DR10000, DR10004,
SinQ DR15000, DR15004, DR20000, DR20004, DR25000,
Q: 0.19% of reading ±0.01% of full scale DR24004, DR30000, DR30004
Cos(Q-60°)
VA: 0.19% of reading ±0.01% of full scale
10
Potential Table
POTENTIAL RANGE WITH POTENTIAL RANGE WITH MAXIMUM BURDEN POTENTIAL OVERLOAD
OPTION NOMINAL INPUT
ACCURACY (SELF-POWERED) ACCURACY (EXTERNAL-POWERED) AT NOMINAL INPUT CONTINUOUS
0 100 - 120 V 85 - 150 V 10 - 150 V 0.1 VA * 180 V
1 63 - 69 V 50 - 90 V 10 - 90 V 0.1 VA * 100 V
2 208 - 240 V 170 - 300 V 20 - 300 V 0.1 VA * 350 V
3 460 - 480 V 325 - 575 V 30 - 575 V 0.1 VA * 700 V
4 575 - 600 V 425 - 750 V 40 - 750 V 0.1 VA* 900 V
5 265 - 277 V 170 - 300 V 20 - 300 V 0.1 VA* 350 V
6 333 - 347 V 325 - 575 V 30 - 575 V 0.1 VA* 700 V

* Self-powered units have a burden of < 3 VA across either FA-N, or FA-FB.

Current Table
OVER-RANGE MAXIMUM OVERLOAD OVERLOAD OVERLOAD
OPTION INPUT
WITH ACCURACY BURDEN CONTINUOUS 10 SEC/HOUR 1 SEC/HOUR
0 0-5A 10 A 0.5 VA 15 A 30 A 200 A
1 0-1A 2A 0.5 VA 3A 6A 100 A
2 0-2A 4A 0.5 VA 6A 12 A 150 A
3 0 - 10 A 20 A 0.5 VA 30 A 50 A 300 A

Output Table
OPTION RANGE FULL SCALE OUTPUT LOADING COMPLIANCE OR MAXIMUM CURRENT
0 0 ± 1 mA 0 - 10,000 Ohms ± 11 V
1 0 ± 3 mA 0 - 3,300 Ohms ± 11 V
2 0 ± 5 mA 0 - 2,000 Ohms ± 11 V
3 0 ± 10 mA 0 - 1,000 Ohms ± 11 V
4 4 - 20 mA 0 - 750 Ohms 15 V
5 0 ± 100 mV ∞
20 Ohms - 5 mA
6 0±1V 200 Ohms - ∞ 5 mA
7 0±5V 1,000 Ohms - ∞ 5 mA
8 0 ± 10 V 2,000 Ohms - ∞ 5 mA
9 1-5V 1,000 Ohms - ∞ 5 mA

Standard Calibration of Watts, VAR, Q, or VA Per Element


V 100 - 120 V 60 - 69 V 208 - 240 V 460 - 480 V 575 - 600 V 265 - 277 V 333 - 347 V
A
0-5A 500 325 1,000 2,000 2,500 1,000 1,500
0-1A 100 65 200 400 500 200 300
0-2A 200 130 400 800 1,500 400 600
0 - 10 A 1,000 650 2,000 4,000 5,000 2,000 3,000

Application Table
APPLICATION NUMBER MODEL NUMBER SERIES RESTRICTIONS
AND OF
CONNECTION ELEMENTS WATT VAR Q VA VOLTAGE CURRENT
1 PHASE, 2 WIRE 1 DW10XXX DR10XXX DQ10XXX DVA10XXX NONE NONE
1 PHASE, 3 WIRE 1 DW10XXX DR10XXX DQ10XXX DVA10XXX NONE NONE
1 PHASE, 3 WIRE 11⁄2 DW15XXX DR15XXX DQ15XXX DVA15XXX NONE NONE
3 PHASE, 3 WIRE 1 ⁄2
1
DW15XXX DR15XXX DQ15XXX DVA15XXX BALANCED NONE
3 PHASE, 3 WIRE 2 DW20XXX DR20XXX DQ20XXX DVA20XXX NONE NONE
3 PHASE, 3 WIRE 21⁄2 DW25XXX DR25XXX DQ25XXX DVA25XXX NONE NONE
3 PHASE, 4 WIRE 21⁄2 DW25XXX DR25XXX DQ25XXX DVA25XXX BALANCED NONE
3 PHASE, 4 WIRE 3 DW30XXX DR30XXX DQ30XXX DVA30XXX NONE NONE

11
Available Models – G. SUFFIX (If Applicable)
25 - 125% Calibration Adjustment A
AC Power Transducers 50 Hz C
400 Hz D
To Order, Specify: External Power, 85 - 150 VAC E
A. ENCLOSURE External Power, 170 - 300 VAC F
Extruded Aluminum Metal, Surface Mount (no prefix) 4 - 20 mA Two-Wire Loop Output T
ABS DIN, Rail Mount D DC Aux Power (Please Specify) K
Case Ground Terminal ① G
B. MODEL
Special Calibration or Option X
Watt W
VAR R ① Metal case models only.
Q Q
VA VA SPECIAL CALIBRATION INSTRUCTIONS
Watt/VAR* WR Please specify: 1. CT Ratio; 2. PT Ratio; 3. Desired Full
Watt/Q WQ scale Calibration in kW, kVAR, kQ, or kVA.
C. CONFIGURATION EXAMPLE: DW-25-0-0-3-E-X is the ordering code for a
1 Element 10 Watt Transducer in a DIN rail mount case, 2-1/2 element,
1-1/2 Element 15 100-120 V input voltage, 0-5 A input current, 0 ± 10 mA
2 Element 20 output, 85-150 VAC external power, special calibration.
2-1/2 Element 25 See pages 31 - 33 for connections.
3 Element 30
D. INPUT NOMINAL VOLTAGE
(Reference Potential Table)
100 - 120 V 0
63 - 69 V 1
208 - 240 V 2
460 - 480 V 3
575 - 600 V 4
265 - 277 V 5
333 - 347 V 6
Special X
E. INPUT CURRENT (Reference Current Table)
0-5A 0
0-1A 1
0-2A 2
0 - 10 A 3
0 - 25 A 4
Special X
F. OUTPUT (Reference Output Table)
0 ± 1 mA (0 - 10,000 Ohms) 0
0 ± 3 mA (0 - 3,300 Ohms) 1
0 ± 5 mA (0 - 2,000 Ohms) 2
0 ± 10 mA (0 - 1,000 Ohms) 3
4 - 20 mA (0 - 750 Ohms) 4
0 ± 100 mV (2,000 Ohms min.) 5
0 ± 1 V (2,000 Ohms min.) 6
0 ± 5 V (1,000 Ohms min) 7
0 ± 10 V (2,000 Ohms min) 8
1 - 5 V (1,000 Ohms min) 9
Special X
Note: 4 - 20 mA units are uni-directional.
If a bi-directional unit is required, use
output designator X and state.

12
AC Energy Transducers

Watt/Watt-hour • VAR/VAR-hour
Q/Q-hour • Combined Watt/Watt-
hour and VAR/VAR-hour or
Watt/Watt-hour and Q/Q-hour
Uni-directional or Bi-directional

All these transducers are high accuracy


electronic multiplying devices for measuring
consumed energy. Mercury-wetted
contacts provide isolated bounce-free
output for driving electromechanical
counters; a solid-state output is included
for electronic counters and controllers.

Standard Features Specifications


• 0.2% of reading accuracy Accuracy (@ 25°C ±2°C)
Watt/Watt-hour: 0.19% of reading ±0.01% of full scale
• Voltage, current, and process outputs CosQ
• Low temperature coefficient VAR/VAR-hour: 0.19% of reading ±0.01% of full scale
SinQ
• No zero adjustment ever required Q/Q-hour: 0.19% of reading ±0.01% of full scale
• Low burdens Cos(Q-60°)
Temperature Range: -20°C to +70°C
• Exceptional long-term stability Temperature Coefficient: 0.005%/°C, 50 ppm typical
• Self-powered or externally powered Operating Humidity: 0-95% non-condensing
• Standardized wiring and mounting Output Ripple Peak: 0.5% of full scale
Power Factor Range: Watt or VAR, any; Q, 0.866 lead to 0 lag
• Metal surface mount cases Operating Frequency: Nominal ±10% in accordance with
IEC 688
Dielectric Test: 2,000 Vrms for 1 minute; 2,400 Vrms for
1 second (for solid state output); 1,200 Vrms for 1 minute;
1,600 Vrms for 1 second (for mercury wetted relay)
Surge Withstand: ANSI C37.90a (IEEE 472); BEAMA 219;
special 5 kV
Response Time: 200 msec to 90%, 400 msec to 99%
Calibration Adjustment: ±10% standard
Zero Adjustment: ±2% standard
Pulse Frequency: ±2% standard
Output, Contacts: SPDT (Form C) Mercury wetted; 100 W,
500 V maximum; contact resistance - 50 mOhms max;
expected life - 109 operations
Output, Solid-state: Dual open collector transistors; 1.5 W,
300 V maximum
Full scale Counts/Hour: Uni-directional, 10 to 20,000 CPH;
Bi-directional, 500 to 20,000 CPH

13
Potential Table
POTENTIAL RANGE WITH POTENTIAL RANGE WITH MAXIMUM POTENTIAL
OPTION NOMINAL INPUT
ACCURACY (SELF-POWERED) ACCURACY (EXTERNAL-POWERED) BURDEN OVERLOAD
0 120 V 85 - 150 V 0 - 150 V 0.02 VA 180 V

1 69 V 50 - 90 V 0 - 90 V 0.02 VA 100 V

2 230 V 170 - 300 V 0 - 300 V 0.02 VA 350 V

3 460 V 325 - 575 V 0 - 575 V 0.02 VA 680 V

4 600 V 425 - 750 V 0 - 750 V 0.02 VA 750 V

Note: Self-powered units have a potential burden of less than 4.5 VA on terminals 3 and 4.

Current Table
OVER-RANGE MAXIMUM OVERLOAD OVERLOAD OVERLOAD
OPTION INPUT
WITH ACCURACY BURDEN CONTINUOUS 10 SEC/HOUR 1 SEC/HOUR
0 0-5A 10 A 0.5 VA 15 A 30 A 250 A

1 0-1A 2A 0.5 VA 3A 6A 100 A

2 0-2A 4A 0.5 VA 6A 12 A 150 A

3 0 - 10 A 20 A 0.5 VA 30 A 50 A 300 A
4 0 - 25 A 35 A 0.5 VA 35 A 75 A 300 A

Output Table
OPTION RANGE FULL SCALE OUTPUT LOADING COMPLIANCE OR MAXIMUM CURRENT
0 0 ± 1 mA 0 - 10,000 Ohms ± 11 V
1 0 ± 3 mA 0 - 3,300 Ohms ± 11 V
2 0 ± 5 mA 0 - 2,000 Ohms ± 11 V
3 0 ± 10 mA 0 - 1,000 Ohms ± 11 V
4 4 - 20 mA 0 - 750 Ohms 15 V
5 0 ± 100 mV ∞
20 Ohms - 5 mA
6 0±1V 200 Ohms - ∞ 5 mA
7 0±5V 1,000 Ohms - ∞ 5 mA
8 0 ± 10 V 2,000 Ohms - ∞ 5 mA
9 1-5V 1,000 Ohms - ∞ 5 mA

Analog Full Scale Calibration (Watt/VAR/Q Per Element)


CURRENT
POTENTIAL 0-5A 0-1A 0-2A 0 - 10 A 0 - 25 A

120 V 500 100 200 1,000 2,500

69 V 325 65 130 650 1,625

230 V 1,000 200 400 2,000 5,000

460 V 2,000 400 800 4,000 10,000

600 V 2,500 500 1,000 5,000 12,500

Note: 11⁄2 Element Transducers are calibrated as 2 element. 21⁄2 Element Transducers are calibrated as 3 element.

Application Table
CONNECTION MODEL NUMBER RESTRICTIONS
WATT VAR Q WATT/VAR WATT/Q VOLTAGE LOAD

1 PHASE WH10 RH10 QH10 WRH10 WQH10 NONE NONE

3 PHASE 3 W WH15 RH15 QH15 WRH15 WQH15 BALANCED BALANCED

3 PHASE 3 W WH20 RH20 QH20 WRH20 WQH20 NONE NONE

3 PHASE 4 W WH25 RH25 QH25 WRH25 WQH25 BALANCED NONE

3 PHASE 4 W WH30 RH30 QH30 WRH30 WQH30 NONE NONE

14
Available Models – G. SUFFIX (If Applicable)
25 - 125% Calibration Adjustment A
AC Energy Transducers 50 Hz C
400 Hz D
To Order, Specify: External Power, 120 VAC E
A. MODEL External Power, 230 VAC F
Watt/Watt-hour WH Case ground terminal G
VAR/VAR-hour RH DC Aux Power (Please Specify) K
Q/Q-hour QH Special X
Watt/Watt-hour, VAR/VAR-hour WRH PULSE CALIBRATION INSTRUCTIONS
Watt/Watt-hour, Q-Q-hour WQH Full scale counts per hour must be stated.
B. CONFIGURATION CPH = CT Ratio x PT Ratio x FS Calibrating Power of Transducer
1 Element 10 Desired Primary Watt-hours Per Pulse
1-1/2 Element 15 EXAMPLE: WH-15-3-1-2-1-C is the ordering code for a
2 Element 20 Watt/Watt-hour Transducer in a metal surface mount
2-1/2 Element 25 case, 1-1/2 element, 460 V input voltage, 0-1 A input
3 Element 30 current, 0 ± 5 mA, Hg wetted output relay, uni-directional,
C. INPUT NOMINAL VOLTAGE 50 Hz power.
(Reference Potential Table) See pages 34 - 35 for connections.
120 V 0
69 V 1
230 V 2
460 V 3
600 V 4
Special X
D. INPUT NOMINAL CURRENT
(Reference Current Table)
0-5A 0
0-1A 1
0-2A 2
0 - 10 A 3
0 - 25 A 4
Special X
E. OUTPUT
(Reference Output Table)
0 ± 1 mA (0-10,000 Ohms) 0
0 ± 3 mA (0-3,300 Ohms) 1
0 ± 5 mA (0-2,000 Ohms) 2
0 ± 10 mA (0-1,000 Ohms) 3
4 - 20 mA (0-750 Ohms) ① 4
0 ± 100 mV (2,000 Ohms min.) 5
0 ± 1 V (2,000 Ohms min.) 6
0 ± 5 V (2,000 Ohms min.) 7
0 ± 10 V (2,000 Ohms min.) 8
1 - 5 V (2,000 Ohms min.) ① 9
Special X
NOTE: 4-20 mA units are uni-directional.
If a bi-directional unit is required, use output
designator X and state.
① Auxiliary power supply required.

F. PULSE OUTPUT
Solid-state, uni-directional 0
Hg wetted relay, uni-directional 1
Solid-state, bi-directional, WH, RH 2
Hg wetted relay, bi-directional, WH, RH 3
Solid-state, bi-directional, WRH 4
Hg wetted relay, bi-directional, WRH 5
Special X

15
Power Factor and
Phase Angle Transducers
mTech offers these devices for producing a DC output
linearly proportional to the phase angle difference
between two inputs. Outputs are bipolar, so leading and
lagging signals can be differentiated. The transducers are
single-phase; however, they can be used on three phase,
four-wire systems with balanced loads.
Phase Angle: These transducers compare two voltage
inputs.
Power Factor: For comparing one voltage and one
current input*.
*Conversion is required for linear phase
angle information.
A table is available on request.

Standard Features Specifications


• 0.25% of rated output accuracy Accuracy (@ 25°C ±2°C): 0.25% of full scale

• Voltage, current, and process outputs Temperature Range: -20°C to +70°C


Temperature Coefficient: 0.01%/°C, 100 ppm typical
• Low burdens Operating Humidity: 0-95% non-condensing
• Low temperature coefficient Output Ripple Peak: <0.5% of full scale
• Transient protected Power Factor Range: phase angle, any;
power factor, as selected by part number
• Standardized wiring and mounting Burden: Current, 0.5 VA (most options); Voltage, 3.5 VA
• Self-powered or externally powered nominal
Overload: Current, 3 x full scale, continuous, 250 A for 1
• ABS DIN rail mount or metal surface mount s/hr; Voltage, 1.2 x full scale continuous
cases Dielectric Test: 2,000 Vrms for 1 minute
Surge Withstand: ANSI C37.90a (IEEE 472); BEAMA 219;
special 5 kV
Response Time: 200 msec to 90%, 400 msec to 99%
Calibration Adjustment: ±10% standard
Zero Adjustment: ±2% standard
Operating Frequency: 60 Hz unless specified otherwise by
suffix to part number

16
Available Models – Power Factor/ G. SUFFIX (If Applicable)
25 - 125% Calibration Adjustment A
Phase Angle Transducers 50 Hz C
400 Hz D
To Order, Specify: External Power, 120 VAC E
A. ENCLOSURE External Power, 230 VAC F
Extruded Aluminum Metal, Surface Mount (no prefix) Case ground terminal ① G
ABS DIN, Rail Mount D DC Aux Power (Please Specify) K
L-L Calibration, Delta Systems L
B. MODEL
4 - 20 mA two-wire loop output T
Phase Angle PA
Special X
Power Factor PF ① Metal case models only.
C. NOMINAL INPUT VOLTAGE (± 25%)
EXAMPLE: DPA-1-2-0-2-3-D is the ordering code for a
120 V 0
Phase Angle Transducer in a DIN rail mount case, 69 VAC
69 V 1
input voltage, 240 V, ± 90°, 0 ± 50 mV 10 Ohms min.
240 V 2
output, 400 Hz power.
460 V 3
600 V 4 See page 36 for connections.
Special X
D. PA - NOMINAL INPUT VOLTAGE
120 V 0
69 V 1
240 V 2
460 V 3
600 V 4
Special X
PF - INPUT CURRENT
1-5A 0
0.2 - 1 A 1
0.4 - 2 A 2
2 - 10 A 3
5 - 25 A 4
Special X
E. Power Factor Phase Angle
±1 ± 90° 0
± .7 ± 60° 1
± .5 ± 45° 2
± .3 ± 30° 3
± .2 ± 15° 4
Special Special X
F. OUTPUT
0 - 1 mA (0 - 10,000 Ohms) 0
0 ± 1 mA (0 - 10,000 Ohms) 1
0 ± 0.5 mA (0 - 20,000 Ohms) 2
0 ± 50 mV (2,000 Ohms min.) 3
0 ± 100 mV (2,000 Ohms min.) 4
0±1V (2,000 Ohms min.) 5
0 ± 10 V (2,000 Ohms min.) 6
1-5V (2,000 Ohms min.) 7
4-20 mA (0-750 Ohms) 8
0 ±10 mA (0-1,000 Ohms) 9
Special X

17
Frequency Transducers

Frequency: The rate in cycles per second that an AC B. CENTER FREQUENCY


voltage alternates or the number of times in one second 400 Hz 4
that the wave repeats its pattern. Hertz (Hz) is the unit of 50 Hz 5
measure. mTech Frequency Transducers measure line 60 Hz 6
frequency, using ultra-stable crystal technology to Special X
develop a DC signal output proportional to the input. C. FREQUENCY SPAN
Different center frequencies and spans are available with 50/60 Hz 400 Hz
outputs being either center or downscale zero. ± 1 Hz ± 10 Hz 1
± 2 Hz ± 20 Hz 2
± 3 Hz ± 30 Hz 3
Standard Features ± 4 Hz ± 40 Hz 4
± 5 Hz ± 50 Hz 5
• 0.05% accuracy ± 6 Hz ± 60 Hz 6
• Low temperature coefficient ± 7 Hz ± 70 Hz 7
± 8 Hz ± 80 Hz 8
• Exceptional long-term stability ± 9 Hz ± 90 Hz 9
±10 Hz ±100 Hz 0
• Low burden Special Special X
• Transient protected D. NOMINAL INPUT VOLTAGE
• Voltage, current, and process outputs 120 V 0
69 V 1
• Standardized wiring and mounting 240 V 2
460 V 3
• ABS DIN rail mount or metal surface mount 600 V 4
cases Special X
E. OUTPUT
0 - 1 mA 0 - 10,000 Ohms 0
Specifications 0 ± 1 mA 0 - 10,000 Ohms 1
0 ± 0.5 mA 0 - 20,000 Ohms 2
Accuracy (@ 25°C ±2°C): 0.05% of center frequency 0 ± 50 mV 10 Ohms min. 3
Temperature Range: -20°C to +70°C 0 ± 100 mV 20 Ohms min. 4
Temperature Coefficient: 0.001%/°C, 10 ppm typical 0±1V 200 Ohms min. 5
0 ± 10 V 2,000 Ohms min. 6
Operating Humidity: 0-95% non-condensing 1-5V 1,000 Ohms min. 7
Power Factor Range: Any 4 - 20 mA 0 - 750 Ohms 8
Operating Voltage Range: -30% + 25% of nominal 0 ±10 mA 0 - 1,000 Ohms 9
Special X
Dielectric Test: 2,000 Vrms for 1 minute
Burden: 1.5 VA (most options) F. SUFFIX (If Applicable)
25 to 125% Calibration A
Surge Withstand: ANSI C37.90a (IEEE 472); BEAMA 219; External Power, 120 VAC E
special 5 kV External Power, 230 VAC F
Response Time: 200 msec to 90%, 400 msec to 99% Case Ground Terminal ① G
Calibration Adjustment: ±10% standard DC Aux Power (Please Specify) K
4 - 20 mA two-wire loop output T
Zero Adjustment: ±2% standard
Special X
① Metal case models only.

Available Models – EXAMPLE: H-6-4-3-7 is the ordering code for a Frequency


Transducer in a metal surface mount case, 60 Hz center
Frequency Transducers frequency, ± 4 Hz frequency span, 460 VAC input voltage,
1 - 5 V 1,000 Ohms min. output.
To Order, Specify:
See page 37 for connections.
A. ENCLOSURE
Extruded Aluminum Metal, Surface Mount H
ABS DIN, Rail Mount DH

18
RTD and Slidewire Transducers

For measuring temperature of transformer windings and other B. INPUT


applications that do not require the accuracy of a linearized Variable Resistance Standard 0
RTD reading, mTech makes a series of RTD and Slidewire Variable Resistance Inverse 1
Transducers. These ultra-linear devices convert a variable 10 Cu 1.427 RTD 2
input resistance to a voltage, current or process output. For 100 Pt 1.385 RTD (DIN) 3
level measurement applications, inverse outputs are available 100 Pt 1.392 RTD (REF) 4
with the output going from maximum to minimum while the 120 Ni 1.672 RTD 5
resistance changes from minimum to maximum. The devices 200 Pt 1.385 RTD (DIN) 6
will accommodate 2, 3, or 4-wire connections to allow 200 Pt 1.392 RTD (REF) 7
virtually every normally used input configuration. 500 Pt 1.385 RTD (DIN) 8
500 Pt 1.392 RTD (REF) 9
RTD: To measure temperature where the resistance of the
Special X
RTD changes in a fixed way with changes in temperature.
The transducer actually measures resistance and produces C. OUTPUT
an output proportional to the resistance. 0 ± 1 mA 0 - 10,000 Ohms 0
0 ± 3 mA 0 - 3,300 Ohms 1
Slidewire: For applications such as transformer tap position.
0 ± 5 mA 0 - 2,000 Ohms 2
0 ± 10 mA 0 - 1,000 Ohms 3
Standard Features 4 - 20 mA 0 - 750 Ohms. 4
• 0.2% of reading accuracy 0 ± 100 mV 20 Ohms min. 5
0±1V 200 Ohms min. 6
• Low temperature coefficient 0±5V 1,000 Ohms min. 7
• Exceptional long-term stability 0 ± 10 V 2,000 Ohms min. 8
• Narrow resistance spans 1-5V 1,000 Ohms min. 9
• Voltage, current, and process outputs Special X
• Standardized wiring and mounting D. AUXILIARY POWER
120 VAC 0
• ABS DIN rail mount or metal surface mount 230 VAC 1
cases DC Aux Power (Please Specify) K
Special X
E. MEASURED UNITS
Specifications Ohms O
Accuracy (@ 25°C ±2°C): 0.19% of reading ±0.01% of span Degrees Fahrenheit F
Temperature Range: -20°C to +70°C Degrees Celsius C
Degrees Kelvin K
Temperature Coefficient: 0.01%/°C, 100 ppm typical
F. Zero Output from Transducer
Operating Humidity: 0-95% non-condensing
State in Ohms or degrees Fahrenheit, Celsius, or Kelvin
Output Ripple (Peak): 0.5% of span (max.)
G. Low End of Output Span
Dielectric Test: 2,000 Vrms for 1 minute, 2,400 V for State in Ohms or degrees Fahrenheit, Celsius, or Kelvin
1 second
H. Top End of Output Span
Surge Withstand: ANSI C37.90a (IEEE 472); BEAMA 219; State in Ohms or degrees Fahrenheit, Celsius, or Kelvin
special 5 kV
I. SUFFIX (If Applicable)
Response Time: 200 msec to 90%, 400 msec to 99%
25 to 125% Calibration A
Calibration Adjustment: Span, ±10% standard; zero, ±2% Case Ground Terminal ① G
standard Special X
Power Requirement: 120 or 240 VAC, 3.5 watts ① Metal case models only.

EXAMPLE: DRES-5-4-0-F-0 °F-0 °F-100°F is the ordering


Available Models – code for an RTD Transducer in a DIN rail mount case, 120
Ni 1.672 RTD input, 4 - 20 mA 0 - 750 Ohms output, 120
RTD/Slidewire Transducers VAC auxiliary power, degrees Fahrenheit measured unit,
To Order, Specify: 0°F zero output, 0°F low end of output span, 100°F top
end of output span.
A. ENCLOSURE
Extruded Aluminum Metal, Surface Mount RES See page 37 for connections.
ABS DIN, Rail Mount DRES
19
DC Voltage Transducers/Ground Fault Detectors

Dual-purpose units that provide an analog output B. MODEL


proportional to the DC input and that check for grounding of DC Voltage DCV
either pole of a floating battery system. mTech offers these DC Current DCA
transducers for various battery voltages and ground leakage C. CONFIGURATION
sensitivities (as little as 5 mA at 125 VDC). Transient DC Current 0
protection is through multipole input and output filters. DC Voltage Only 1
Advanced operational amplifiers with ultra-high input DC Voltage + Ground Fault* 2
impedance ensures a high degree of input/output isolation Ground Fault Only* 3
and very low battery burden. The NO or NC* contact remains
*Not available in DIN mount.
energized only as long as the alarm condition exists. Two
top-mounted LEDs indicate whether the fault was positive or D. FULL SCALE VOLTAGE
negative and stay lit until the RESET button is pushed. 0 - 150 V 0
0 - 60 V 1
*Shipped NO unless NC is specified.
0 - 30 V 2
0 - 300 V 3
Standard Features 0 - 750 V 4
Current Specify
• Low battery drain Special X
• Sensitive ground leakage detection
E. NOMINAL BATTERY VOLTAGE
• High accuracy and linearity 125 V 0
• Transient protection 48 V 1
• Low temperature coefficient 24 V 2
250 V 3
• Standardized wiring and mounting 600 V 4
• ABS DIN rail mount or metal surface mount Special X
cases F. OUTPUT
0 - 1 mA 0 - 10,000 Ohms 0
0 - 3 mA 0 - 3,300 Ohms 1
Specifications 0 - 5 mA 0 - 2,000 Ohms 2
Accuracy (@ 25°C ±2°C): 0.2% of reading ±0.01% of rated 0 - 10 mA 0 - 1,000 Ohms 3
output 4 - 20 mA 0 - 750 Ohms 4
Temperature Range: -20°C to +70°C 0 - 100 mV 20 Ohms min. 5
0-1V 200 Ohms min. 6
Temperature Coefficient: 0.005%/°C, 50 ppm typical
0-5V 1,000 Ohms min. 7
Operating Humidity: 0-95% non-condensing 0 - 10 V 2,000 Ohms min. 8
Output Ripple (Peak): Less than 0.5% of full scale 1-5V 1,000 Ohms min. 9
Burden: Less than 0.10 watts at full scale Special X
Overload with Accuracy: 1.2 x full scale G. AUXILIARY POWER
Overload without Damage: 1.33 x full scale 120 VAC 0
240 VAC 1
Dielectric Test: 1,500 VAC for 1 minute
DC Aux Power (Please Specify) K
Surge Withstand: ANSI C37.90a (IEEE 472); BEAMA 219; Special X
special 5 kV
H. SUFFIX (If Applicable)
Response Time: 200 msec to 90%, 400 msec to 99% 25 to 125% Calibration A
Calibration Adjustment: ±10% standard Case Ground Terminal ① G
Zero Adjustment: ±2% standard 4 - 20 mA two-wire loop output T
Special X
① Metal case models only.
Available Models – DC Voltage
EXAMPLE: DDCV-2-0-1-9-0 is the ordering code for a DC
Transducers/Ground Fault Detectors Voltage Transducer/Ground Fault Detector in a DIN rail
mount case, 0 - 150 V full scale voltage, 48 V battery
To Order, Specify:
voltage, 1 - 5 V 1,000 Ohms min. output, and 120 VAC
A. ENCLOSURE auxiliary power.
Extruded Aluminum Metal, Surface Mount (no prefix)
See page 37 for connections.
ABS DIN, Rail Mount D

20
Line Post Sensor Transducers/Fault Alarms

mTech offers a series of transducers that interface with most


line post sensors on the market. These devices can also
serve as simple three-phase current or voltage transducers
with the added feature of providing alarms on faults. In
addition to monitoring excessive voltages or currents or an
excessive drop in the voltage on the network, they can be
used to detect any unbalance between the three phases, as
well as ground faults. With multiple transducers along a line,
fault locations can be pinpointed accurately and quickly.
Input Type: Line post sensor outputs are typically in the form
of low level AC voltage; however, some might be as high as
120 volts or in the form of a 5 amp current. In other
instances, the transducer may have to measure voltages or
currents in a three-phase system, either directly or through
current or potential transformers. mTech isolates inputs to its
transducers from each other, from the power supply, and
from the outputs. The user must specify the form of the
output from the sensor that will be the transducer’s input.
Configuration: One analog output and one alarm contact are
available for each of the three phases. For the neutral line
(separate section follows), there can be only one output,
either analog or relay contact. The user can specify any of
the given combinations of outputs for the desired application.
Unused terminals are left unconnected within the transducer.
Analog Output: Various outputs are available as standard. Auxiliary Power: External power is required to energize
Users can match the inputs to their RTUs, PLCs, meters, and mTech’s line post sensor transducers. Five standard AC and
other instrumentation. Outputs are isolated from the inputs DC options are available. If you have different requirements,
and the power supply, but not from each other; the negative please consult the factory.
output terminals are tied together internally.
Neutral: Calculated as the vector sum of the inputs to the Specifications
three phases, representing the current through the neutral line
or the unbalance between currents or voltages of the three Accuracy (@ 25°C ±2°C): 0.25% of full scale
phases. This feature is very useful for fault detection. A Temperature Range: -20°C to +70°C
neutral specified as 33% of phase indicates that any
Operating Humidity: 0-95% non-condensing
unbalance between the inputs from the three phases
amounting to 33% of the full scale input to one phase will Long-Term Drift: <0.1%/year, non-cumulative
result in a full scale output for the neutral line. Different Power Factor: Any
sensitivities can be selected, dependent upon the permissible Input Impedance: Input 0-20 V, 1 M Ohms typical; all others,
unbalance in the system. 0.1 VA input burden max.
Alarm % of Full scale: A number of standard set points are Output Ripple: 0.5% of full scale max.
available for the Alarm, as well as any other user-specified
value. The set point is given as a percentage of full scale. Dielectric Test: 2,000 Vrms for 1 minute

Alarm Function: An alarm can be triggered if the input either Surge Withstand: ANSI C37.90a (IEEE 472)
exceeds or goes below the set point. As a result, the Response Time: 200 msec to 90%; 400 msec to 99%; alarm
transducer can monitor either overvoltage or undervoltage. If - 10 msec minimum (actual trip time depends on magnitude
used for monitoring current through the line, the transducer of fault and operating level prior to fault)
should have its alarm set for overcurrent. The neutral alarm Calibration Adjustment: Span, ±10% standard; zero, ±2%
should be set to detect either any unbalance or excess of the standard; alarm, ±25% standard
neutral current limits.
Operating Frequency: 60 Hz ±10% with accuracy unless
Alarm Contact: Users can specify either Normally Open (NO) specified otherwise by suffix to part number
or Normally Closed (NC) contacts for the alarm outputs.
Power Requirements: 8 VA maximum
These outputs are isolated from each other, the inputs, the
power supply, and the analog outputs.

21
Available Models – Line Post Sensor H. AUXILIARY POWER
120 VAC 0
Transducers/Fault Alarms 240 VAC 1
To Order, Specify: 24 Vdc 2
48 Vdc 3
A. MODEL
125 Vdc 4
Line Post Sensor Transducer (Supplied in
Special X
Extruded Aluminum Metal, Surface Mount) LP
I. ALARM CONTACT
B. INPUT TYPE
Normally Open NO
AC Current A
Normally Closed NC
AC Voltage V
If not applicable Z
C. CONFIGURATION
J. ALARM FUNCTION
4 Analog Outputs & 3 Alarms 3
Overvoltage/Overcurrent O
3 Analog Outputs & 4 Alarms 4
Undervoltage U
3 Analog Outputs & 3 Alarms 5
If not applicable Z
4 Analog Outputs Only 6
3 Analog Outputs Only 7 K. SAFETY FEATURE
4 Alarms Only 8 On Power Supply Failure, Relays
3 Alarms Only 9 Switch to ALARM A
On Power Supply Failure, Relays
D. INPUT TO TRANSDUCER
Switch to NORMAL N
5A 0
If not applicable Z
10.00 V 1
2.00 V 2 L. SUFFIX
3.00 V 3 25% - 125% Adjustment (analog output only) A
4.00 V 4 50 Hz C
5.00 V 5 Case Ground Terminal G
120 V 6 Special X
Special X EXAMPLE: LP-A-4-0-2-3-5-0-NO-O-A-G is the ordering
E. NEUTRAL % OF PHASE code for a Line Post Sensor Transducer in a metal
33% 0 surface mount case, an AC current input, a 3 analog
10% 1 outputs/4 alarms configuration, a 5 A input to transducer,
20% 2 20% neutral % of phase, 0-10 mA 0-1,500 Ohms analog
25% 3 output, 33% alarm % of full scale, 120 VAC auxiliary
50% 4 power, a Normally Open alarm contact,
75% 5 overvoltage/overcurrent alarm function, power supply
100% 6 failure relays that switch to ALARM, and a case ground
Special X terminal.
If not applicable Z See page 38 for connections.
F. ANALOG OUTPUT
0 - 1 mA 0 - 15,000 Ohms 0
0 - 3 mA 0 - 5,000 Ohms 1
0 - 5 mA 0 - 3,000 Ohms 2
0 - 10 mA 0 - 1,500 Ohms 3
4 - 20 mA 0 - 750 Ohms. 4
0 - 100 mV 20 Ohms min. 5
0-1V 200 Ohms min. 6
0-5V 1,000 Ohms min. 7
0 - 10 V 2,000 Ohms min. 8
1-5V 1,000 Ohms min. 9
Special X
G. ALARM % OF FULL SCALE
133% 0
150% 1
100% 2
75% 3
50% 4
33% 5
25% 6
Special X

22
Line Post Sensor Transducer System

mTech offers a special system for converting three-phase AC


voltage and current signals from Lindsay series CMI and
CVMI sensors into DC current proportional to the input AC
current and AC voltage amplitude. The LPAV3 is a Line Post
Sensor Transducer System that also converts the phase
relationship between the current and voltage signals into a
DC current proportional to the phase angle difference
between the current and voltage waveforms that can be
readily converted to power factor.
The system provides an alarm for each current input phase,
as well as a neutral alarm. All are adjustable from 50% to
200% of rated input using a single calibrated dial. The neutral
alarm (phase unbalance) level is set to trigger at 1/3 the
phase level. The phase alarms are maskable and the neutral
alarm is preset at the factory. The other alarms are
electronically latched and are reset by contact closure at the
alarm reset terminals. If momentary alarms are desired
(present only while the fault exists), the alarm reset terminals
can be shorted.

Specifications Zero Adjustment: ±2%


Input: Current, 0-15 VAC; voltage, 0-15 VAC; phase angle, Response Time (to 99%): <400 msec
60° lead to 60° lag Dielectric Withstand Voltage (Input to Output to Case):
Overload Current: 20 VAC continuous 1,500 VAC for 1 min.
Overload Voltage: 20 VAC continuous Surge Withstand Capability: ANSI C37.90A; (IEEE 472)
Operating Frequency: 60 Hz Impulse Test, Uni-directional: 1.2 x 50 msec 6 kV crest
Operating Humidity: 0-95% non-condensing Test Voltage Across Output: 100 Volts RMS, 2 sec
Temperature Range: -30° to +60°C Output Open or Short Circuit: Protected
Maximum Temperature Effects on Accuracy: ±0.5% of Open Circuit Output at Rated Input: <15 Vdc
rated output Alarm Contacts: Normally open, SPST, form “A” contacts
Accuracy @25°C (% RO at 60 Hz): 0.5% of rated output that will close and retain closure until fault has been cleared
and alarm has been reset
Output: Current, 0-1.5 mA; voltage, 0-1.5 mA; power factor,
0 ±1.5 mA Phase Alarm Contacts: SPST form “A”, 120 VAC, 3 amp
resistive; trip levels adjustable from 50 to 200% of full scale
Output @ Rated Full scale: 1 mA
Neutral Alarm Contacts: SPST form “A”, 120 VAC, 3 amp
Output Ripple: 0.5% peak max. resistive; neutral contact trip level adjustable from 16% to
Output Load: 0-10,000 Ohms 70% of full scale
Compliance Voltage (min.): 11 VDC Alarm Contact Reset: Momentary alarms can be selected by
Calibration Adjustment: ±10% placing a jumper across reset terminals

23
Available Models – Line Post
Sensor Transducer System
To Order, Specify:
A. MODEL
Line Post Sensor Transducer System LPAV3
B. SENSOR INPUT CURRENT
600 A: 10 V 0
600 A: 6 V 1
Special X
C. SENSOR INPUT VOLTAGE
INPUTS RATIO
0-15 kV 0 1400: 1 V 0
0-25 kV 1 2200: 1 V 1
0-35 kV 2 3300: 1 V 2
Special X Special X
D. POWER FACTOR
±0.5 0
±0.3 1
±0.2 2
Special X
E. NEUTRAL % OF PHASE CURRENT
33% 0
10% 1
20% 2
25% 3
50% 4
75% 5
100% 6
Special X
F. OUTPUT
0-1 mA (0-10,000 Ohms) 0
0-100 mV (20 Ohms min.) 1
0-1 V (200 Ohms min.) 2
0-5 V (1,000 Ohms min.) 3
0-10 V (2,000 Ohms min.) 4
1-5 V (1,000 Ohms min.) 5
Special X
G. AUXILIARY POWER
120 VAC 0
240 VAC 1
12 Vdc 2
24 Vdc 3
48 Vdc 4
125 Vdc 5
Special X
H. SUFFIX
50 Hz C
400 Hz D
Case Ground Terminal G
Special X
EXAMPLE: LPAV3-1-22-0-4-5-3-D is the ordering code for
a Line Post Sensor Transducer System in a metal surface
mount case, 600 A: 6 V sensor input current, 0-35 kV
sensor input voltage with a 3300: 1 V ratio, ±0.5 power
factor, 50% neutral % of phase current, 1-5 V (1,000
Ohms min.) output, 24 Vdc auxiliary power, 400 Hz.
See page 38 for connections.

24
Portable Test Set for
Power Transducers

As a leading international manufacturer of power transducers, Built for ease of use and to last in the field: The TCS-914
mTech knows precisely what is required to maintain the is completely self-contained and mounted inside a rugged,
highest possible accuracies of these devices. Combined environmentally sealed, polycarbonate carrying case. The
instrumentation expertise has led to the development of a case comes with a hinged cover and storage compartment.
portable transducer test set the equivalent of seven different At only 47 cm (18.5") long by 37 cm (14.6") wide by 19 cm
instruments in one self-contained field unit. The Model (7.5") high and 12 kg (26.5 lbs), it is both compact and
TCS-914 provides field technicians with an easy and highly lightweight.
accurate, on-site means of testing all of the transducers The controls have been designed with the operator in mind.
throughout their plant or power system. All test procedures are easy to learn and perform. The front
Tests a wide range of models: The system is designed panel incorporates thumbwheel switches and percent of
for maximum versatility. It will test most mTech power setting controls for selecting current, voltage, and power
transducers (watt, VAR, voltage, current, expanded scale factor. In addition, there are facilities for full scale calibrating
voltage, and power factor models), as well as models of the of watts, VAR, volts, and amps, plus a frequency selector
same types made by other manufacturers. More specifically, switch for 50 Hz and 60 Hz.
it will measure, and indicate on a digital display, current, The solid-state TCS-914 is easily programmable, making it
voltage, watts, VAR, Q, VA, and it includes a second display extremely versatile. It generates voltage and current from a
to indicate null balance percent error and actual transducer stable internal distortion-free source and is independent of
output in engineering units. The TCS-914 also has special source frequency and distortion. All internal standards and
features such as expanded scale voltage testing and the parameters measured are true RMS and have an accuracy of
capability of monitoring a wide range of outputs. In fact, no 0.1% or higher for measuring: 0 ± 500 watts per element;
external adaptors are needed for transducers with outputs 0 ± 500 VAR per element; 0-300 volts; 0-10 amps; and field
such as 0-1 mA, 4-20 mA, 0-5 mA, 0-10 V, and others. adjustable zero and span for expanded scale volts. All digital
meters have an accuracy of 0.05% or higher for measuring:
0-300 volts; 0-19.99 amps; 0 ± 3,000 watts/VAR, true RMS;
and 0 ± 19.99 percent error.

25
Specifications OUTPUT DISPLAY:
Type: 3-1/2 digit LED
VOLTAGE OUTPUT: Metering Mode:
Range: 0-300 V Accuracy: ±(0.03% of reading + 0.02% full scale +
Accuracy: ±(0.05% of setting + 0.05% of range) 1 count)
Resolution: 1 V Null-Balance Mode:
Burden: 0-180 V: 100 mA Range: 0-±19.99%
180-300 V: 50 mA Accuracy: ± 0.1% ± 1 count
CURRENT OUTPUT: AMBIENT:
Range: 0-9.99 A Temperature: 25°C ± 15°C
Accuracy: ±(0.05% of setting + 0.05% of range) Humidity: 0-90%, non-condensing
Resolution: 0.01 A POWER-TO-OPERATE:
Compliance: 0-2.8 A: 4.0 V 100, 120 VAC +10% 60 Hz
2.8-9.99 A: 2.0 V 220, 240 VAC +10% 50 Hz
POWER FACTOR: DIMENSIONS:
Range: Full four quadrant in steps of 0.1 P.F. 47 cm (18.5") L x 37 cm (14.6") W x 19 cm (7.5") H
Accuracy: ±0.1 degrees
WEIGHT:
FREQUENCY OF OUTPUTS: 12 kg (26.5 lbs)
50 Hz: 50 Hz ±0.1%
60 Hz: 60 Hz ±0.1%
Sync: Line ±0.5%
External: External source ±0.5%

INTERNAL STANDARDS:
VOLTAGE:
Range: 0-300 V, true RMS
Accuracy: ±(0.05% of reading + 0.05% of range)
CURRENT:
Range: 0-10 A, true RMS
Accuracy: ±(0.05% of reading + 0.05% of range)
WATT:
Range: 0-3,000 W
Accuracy: ±(0.05% of reading + 0.05% of range)
CosQ
VAR:
Range: 0-3,000 VAR
Accuracy: ±(0.05% of reading + 0.05% of range)
SinQ
Q:
Range: 0-3,000 Q
Accuracy: ±(0.05% of reading + 0.05% of range)
Cos (Q-60°)
VA:
Range: 0-3,000 VA
Accuracy: ±(0.05% of reading + 0.05% of range)
STANDARDS OUTPUT:
Range: 0-4 V, automatically adjustable
Accuracy: ±0.1% full scale
OUTPUT PARAMETER DISPLAY:
Type: 4-1/2 digit LED
Accuracy: ±(0.03% of reading + 0.02% full scale
+ 2 counts)
TRANSDUCER INPUT:
Ranges: 0-1 mA, 0-10 mA, 4-20 mA, 4-12-20 mA
0-1 V, 0-10 V
Other ranges available upon request

26
Dimensions

DIN Rail Mount Cases

TYPICAL WITH TYPICAL WITH


70 67 DIN-1 70 67 DIN-2
PROTECTIVE PROTECTIVE
(2.76") (2.64") TOP VIEW (2.76") (2.64") TOP VIEW
COVER IN PLACE COVER IN PLACE

110 DIN-1 110 DIN-2


DIN-1 DIN-2
(4.34") SIDE VIEW (4.34") SIDE VIEW

55 105
(2.17") (4.13")

DIN-1 DIN-2
All single Current and Voltage and RTD/Slidewire models All multiple Current and Voltage and Power, Power Factor/Phase Angle,
Frequency, DC Voltage/Current models

Metal Surface Mount Cases


133 (5.25") 133 (5.25") 198.8 (7.83")
121 (4.75") 121 (4.75") 185.9 (7.32")
104 (4.10") 104 (4.10") 171.4 (6.75")

102 (4.00")
89 (3.50")
38 104 38 104 38 104
79 (3.10")
(1.50") (4.10") (1.50") (4.10") (1.50") (4.10")

38 53
(1.50") (2.10")

160
(6.30") 142
120.7 104 (5.60") 120.7
(4.75") (4.10") (4.75") 104
(4.10")
98 79
(3.85") (3.10")

Size 1 Size 2 Size 3 Size 4


Current: A1XX, RA1XX, Current: A3XX, SA3XX, A1X4, Current: BA1XX AC Energy
and TA1X4 except A1X9 AC Power: All
A1X4, A1X9 Voltage: V3XX, V1X4, V1X9
Voltage: V1XX, RV1XX, Power Factor/Phase Angle: All
VX1XX, and TX1X4 Frequency: All
except V1X4, V1X9 RTD/Slidewire: All
DC Voltage/Ground Fault: All

Dimensions are in millimeters (inches).

27
Dimensions

Metal Surface Mount Cases

123.2
123.9 127.0 104.1 (5.85")
(4.88") (5.00") (4.10")

198.8 (7.83") 198.8 (7.83")


185.9 (7.32") 185.9 (7.32")
171.4 (6.75") 171.4 (6.75")

104.1 38.1 104.1 38.1


(4.10") (1.50") (4.10") (1.50")

Size 5 Size 6
AC Energy Line Post Sensor Transducer/Fault Alarm: All

228.6 (9.00")
95.25 (3.75")
213.36 (8.40")

197.87 (7.79") 80.01 (3.15")

48.26
(1.90")

101.6 197.87
(4.00") (7.79")

Special Case:
Line Post Sensor Transducer System

Dimensions are in millimeters (inches).

28
Connections

Current Transducers
DIN Rail Mount Cases

DA1XX and DRA1XX DRA1X4T and DTA1X4 DA3XX DSA3XX DBA1XX


Series Series Series Series Series
ALL SINGLE ALL SINGLE ALL TRIPLE ALL SUMMED OUTPUT BIDIRECTIONAL
CURRENT CURRENT CURRENT TRANSDUCERS CURRENT TRANSDUCERS CURRENT TRANSDUCERS
TRANSDUCERS TRANSDUCERS
TWO WIRE

LOOP PWR.
24 V(dc) -OUTPUT+
-
-OUTPUT+ + -OUTPUT+ -OUTPUT+ -OUTPUT+ -OUTPUT+
0-750 ohms A B C
1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10
CD-1 CD-2 CD-3 CD-4 CD-5
6 7 8 9 10 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 11 12 13 14 15 16 17 18 19 20 11 12 13 14 15 16 17 18 19 20

AUX. PWR. AUX. PWR. AUX. PWR. •


AUX. PWR.
IF REQUIRED IF REQUIRED IF REQUIRED IF REQUIRED
• • •

• • • • • A (R) (R)(L1)
• • B (W)(S)(L2)
• C (B) (T) (L3)
N

Notes:
1. All 4-20 mA, 1-5 V and any other live zero output transducer must have an 2. Third phase of connection drawing (CD-3) is shown as direct connect. It is
external (auxiliary) source of power. typical for any transducer where the incoming signal will not exceed the
rated intput of the transducer.

Metal Surface Mount Cases


A1XX; RA1XX TA1X4 BA1XX A1X4 and A1X9 TA3XX; A3XX SA3XX
except ALL SINGLE BIDIRECTIONAL SINGLE ALL TRIPLE ALL SUMMED
A1X4 and A1X9 CURRENT CURRENT CURRENT CURRENT OUTPUT
ALL SINGLE TRANSDUCERS TRANSDUCERS TRANSDUCERS TRANSDUCERS CURRENT
CURRENT TWO WIRE 4-20 mA and TRANSDUCERS
TRANSDUCERS 1-5 V outputs
except 4-20 mA and -OUTPUT+
1-5 V outputs
LOOP PWR. -OUTPUT+ -OUTPUT+ -OUTPUT+ -OUTPUT+ -OUTPUT+
24 V(dc) A B C
- 1 2 3 4 5 6 6A 6B 1 2 3 4 5 6 1 2 3 4 5 6 1 2
-OUTPUT+ +
0-750 ohms CD-3 CD-5 CD-6
AUX. PWR. CD-4 AUX. PWR.
1 2 3 4 5 6 1 2 3 4 IF REQUIRED 7 8 9 10 11 12 12A 12B 3 4 5 6 7 8 12A 12B

CD-1 AUX. PWR. CD-2 AUX. PWR. AUX. PWR.


IF REQUIRED IF REQUIRED IF REQUIRED
• • •

• • • • A (R) (R)(L1)

• • • B (W)(S)(L2)
• • C (B) (T) (L3)
• N

Notes:
1. For supply connections use No. 14 AWG or larger wires rated for at least 75°C 4. CD-3 is shown directly connected to the measured source. This is typical for
(167°F). Use copper conductors only. any configuration where CTs and PTs are not used.
2. All 4-20 mA and 1-5 V transducer outputs require an external (auxiliary) source Attention:
of power. If the transducer is mounted on a non-metallic or ungrounded surface the installer
3. Bi-directional Current transducer (CD-3) must be supplied with a source of AC must provide the means for grounding and bonding as per NEC (National Electric
power that is in phase with the measured current at unity power factor. Code) requirements.

29
Connections

Voltage Transducers
DIN Rail Mount Cases

DV1XX DVX1XX DTV1X4 DV3XX DSV3XX TYPICAL


DRV1XX and DRV1XX Series Series Series DIRECT
Series ALL SINGLE ALL TRIPLE ALL SUMMED OUTPUT CONNECTION
ALL SINGLE VOLTAGE VOLTAGE VOLTAGE
VOLTAGE TRANSDUCERS TRANSDUCERS TRANSDUCERS
TRANSDUCERS TWO WIRE

LOOP PWR.
24 V(dc) -OUTPUT+
-
-OUTPUT+ + -OUTPUT+ -OUTPUT+ -OUTPUT+ -OUTPUT+
0-750 ohms A B C
1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5
CD-1 CD-2 CD-3 CD-4
6 7 8 9 10 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 11 12 13 14 15 16 17 18 19 20 6 7 8 9 10
- + - + - + - +
AUX. PWR. AUX. PWR. AUX. PWR. AUX. PWR.

IF REQUIRED IF REQUIRED IF REQUIRED IF REQUIRED
• • • • • • •
• • • • • • •
A (R) (R)(L1)
B (W)(S)(L2)
C (B) (T) (L3)
N

Notes:
1. For supply connections use No. 14 AWG or larger wires rated for at least 3. Third phase of connection drawing (CD-3) is shown as direct connect. It is
75°C (167°F). Use copper conductors only. typical for any transducer where the input will not exceed the rated input of
2. All 4-20 mA, 1-5 V and other live zero outputs, transducer must have an the transducer.
external (auxiliary) source of power.

Metal Surface Mount Cases

V1XX, RV1XX TV1X4 TV3X4, V3XX V1X4 and V1X9


VX1XX and RVX1XX VOLTAGE ALL TRIPLE SINGLE
except TRANSDUCERS VOLTAGE VOLTAGE
V1X4 and V1X9 TWO WIRE TRANSDUCERS TRANSDUCERS
ALL SINGLE 4-20 mA and
VOLTAGE 1-5 V outputs
TRANSDUCERS
except 4-20 mA and
1-5 V outputs -OUTPUT+
LOOP PWR.
24 V(dc) -OUTPUT+ -OUTPUT+ -OUTPUT+
- A B C
-OUTPUT+ +
0-750 ohms 1 2 3 4 5 6 1 2 3 4 5 6
1 2 3 4 5 6 1 2 3 4 CD-3 CD-4
AUX. PWR.
CD-1 CD-2 7 8 9 10 11 12 12A 12B
AUX. PWR.
IF REQUIRED
AUX. PWR.
• • •
IF REQUIRED
• • • • • •
• • • • •
A (R) (R)(L1)
B (W)(S)(L2)
C (B) (T) (L3)
N

Notes: Attention:
1. For supply connections use No. 14 AWG or larger wires rated for at least If the transducer is mounted on a non-metallic or ungrounded surface the installer
75°C (167°F). Use copper conductors only. must provide the means for grounding and bonding as per NEC (National Electric
2. All 4-20 mA and 1-5 V transducer outputs require an external (auxiliary) source Code) requirements.
of power.
3. CD-3 is shown with phase A directly connected to the power line; this is
typical for any transducer where the input voltage does not exceed the
input rating.

30
Connections

DIN Rail Mount Cases AC Power Transducers

1 ELEMENT 1 ELEMENT 11⁄2 ELEMENT


LINE LINE LINE
1F, 2 W 1F, 3 W 1F, 3 W
L1 N L1 N L2 L1 N L2




EXT. PWR. EXT. PWR. EXT. PWR.


IF REQUIRED +OUTPUT- IF REQUIRED +OUTPUT- IF REQUIRED +OUTPUT-
+ - + - + -
2 5 8 11 13 14 15 16 2 5 8 11 13 14 15 16 2 5 8 11 13 14 15 16
Va N Va N Va Vb
Ia• Ia Ia• Ia Ia• Ia Ic• Ic
1 3 4 6 7 9 1 3 4 6 7 9 1 3 4 6 7 9



LOAD

LOAD LINE LOAD


R S T
A B C
LINE
11⁄2 ELEMENT 2 ELEMENT
R S T 3F, 3 W 3F, 3 W



A B C







EXT. PWR. EXT. PWR.
IF REQUIRED +OUTPUT- IF REQUIRED +OUTPUT-


+ - + -
2 5 8 11 13 14 15 16 2 5 8 11 13 14 15 16
Va Vc Va Vb Vc Vb
Ia• Ia Ic• Ic Ia• Ia Ic• Ic
1 3 4 6 7 9 1 3 4 6 7 9


LOAD LOAD
LINE
R S T
LINE 2 ⁄ ELEMENT
12
LINE 2 ⁄ ELEMENT
12
A B C N 3 ELEMENT
3F, 3 W 3F, 4 W 3F, 4 W
R S T R S T
A B C A B C N












EXT. PWR. EXT. PWR. EXT. PWR.


IF REQUIRED +OUTPUT- IF REQUIRED +OUTPUT- IF REQUIRED +OUTPUT-

+ - + - + -
2 5 8 11 13 14 15 16 2 5 8 11 13 14 15 16 2 5 8 11 13 14 15 16
Va N Vc N Va N Vc N Va Vb Vc N
Ia• Ia Ic• Ia Ia• Ia Ib• Ib Ic• Ic Ia• Ia Ib• Ib Ic• Ic
1 3 4 6 7 9 1 3 4 6 7 9 1 3 4 6 7 9



LOAD

LOAD LOAD

LINE COMMON RETURN WIRING LINE TYPICAL ALL DIRECT CONNECT


APPLICABLE TO ALL MODELS APPLICABLE TO ALL MODELS
R S T R S T
A B C A B C







EXT. PWR. EXT. PWR.


IF REQUIRED +OUTPUT- IF REQUIRED +OUTPUT-

+ - + -
2 5 8 11 13 14 15 16 2 5 8 11 13 14 15 16
Va Vb Vc N Va Vb Vc N
Ia• Ia Ib• Ib Ic• Ic Ia• Ia Ib• Ib Ic• Ic
1 3 4 6 7 9 1 3 4 6 7 9


LOAD Typical drawing using 1 return wire from


CT. This can be used on any transducer
if it is the only or last turn in the CT loop.
LOAD 31
Connections

AC Power Transducers
(Single Output)
Metal Surface Mount Cases

1 ELEMENT 1 ELEMENT 11⁄2 ELEMENT 11⁄2 ELEMENT


1F, 2 W 1F, 3 W 1F, 3 W 3F, 3 W

LINE LINE LINE LINE


L1 N L2 L1 N L2 A B C







1 2 3 4 5 6 1 2 3 4 5 6

1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
Vc Va Vc Va
-OUTPUT+ EXT. PWR. -OUTPUT+ EXT. PWR.
V V• I I• V V• I I• IF REQUIRED IF REQUIRED
-OUTPUT+ EXT. PWR. -OUTPUT+ EXT. PWR. •
Ia Ic• Ia Ic Ia• Ic• Ia Ic
IF REQUIRED 7 8 9 10 11 12 7 8 9 10 11 12



LOAD LOAD LOAD LOAD
2 ELEMENT
3F, 3 W
21⁄2 ELEMENT 21⁄2 ELEMENT 3 ELEMENT
3F, 3 W 3F, 4 W LINE 3F, 4 W
A B C N



LINE LINE LINE
A B C A B C A B C N








1 2 3 4 5 6 1 2 3 4 5 6 6A 1 2 3 4 5 6 6A 1 2 3 4 5 6 6A
Va Vb Vc Vb N Va Vc N N Va Vc N N
Va Vb Vc
-OUTPUT+ EXT. PWR. -OUTPUT+ EXT. PWR. -OUTPUT+ EXT. PWR. -OUTPUT+ EXT. PWR.
IF REQUIRED IF REQUIRED IF REQUIRED IF REQUIRED
Ia• Ic• Ia Ic Ia• Ic• Ib• Ia Ic Ib Ia• Ic• Ib• Ia Ic Ib Ia• Ic• Ib• Ia Ic Ib
7 8 9 10 11 12 7 8 9 10 11 12 12A 7 8 9 10 11 12 12A 7 8 9 10 11 12 12A




LOAD LOAD

LOAD LOAD

TYPICAL CT/PT CONNECTION TYPICAL ALL DIRECT CONNECT


APPLICABLE TO ALL MODELS APPLICABLE TO ALL MODELS

LINE
A B C
LINE
A B C


1 2 3 4 5 6
Va Vb Vc Vb 1 2 3 4 5 6
-OUTPUT+ EXT. PWR.
IF REQUIRED Va Vb Vc Vb
Ia• Ic• Ia Ic -OUTPUT+ EXT. PWR.
7 8 9 10 11 12 IF REQUIRED
Ia• Ic• Ia Ic
7 8 9 10 11 12

Attention:
If the transducer is mounted on a non-metallic or ungrounded surface the installer

must provide the means for grounding and bonding as per NEC (National Electric
LOAD Code) requirements.
LOAD

32
Connections

AC Power Transducers
(Combined W/R/Q)
Metal Surface Mount Cases

1 ELEMENT 1 ELEMENT 11⁄2 ELEMENT 11⁄2 ELEMENT


1F, 2 W 1F, 3 W 1F, 3 W 3F, 3 W

LINE LINE LINE LINE


L1 N L2 L1 N L2 A B C







1 2 3 4 5 6 6A 1 2 3 4 5 6 6A
1 2 3 4 5 6 6A 1 2 3 4 5 6 6A Vb Va Vc Va
WATT VAR OR Q EXT. PWR. WATT VAR OR Q EXT. PWR.
V V• I I• V V• I I• -OUTPUT+ -OUTPUT+ IF REQUIRED -OUTPUT+ -OUTPUT+ IF REQUIRED
WATT
VAR OR Q EXT. PWR.
WATT
VAR OR Q EXT. PWR. Ia• Ic• Ia Ic Ia Ic
-OUTPUT+ -OUTPUT+
-OUTPUT+ IF REQUIRED -OUTPUT+ IF REQUIRED 7 8 9 10 11 12 12A 7 8 9 10 11 12 12A
7 8 9 10 11 12 12A 7 8 9 10 11 12 12A



LOAD LOAD LOAD LOAD

2 ELEMENT 21⁄2 ELEMENT 21⁄2 ELEMENT 3 ELEMENT


3F, 3 W 3F, 3 W 3F, 4 W LINE 3F, 4 W
A B C N



LINE LINE LINE
A B C A B C A B C N







1 2 3 4 5 6 6A 1 2 3 4 5 6 6A 6B 1 2 3 4 5 6 6A 6B 1 2 3 4 5 6 6A 6B
Vb Va Vc Vb N Va Vc N N Va Vc N N Va Vb Vc
WATT EXT. PWR. WATT VAR OR Q - EXT. PWR. WATT VAR OR Q - EXT. PWR. WATT VAR OR Q - EXT. PWR.
-OUTPUT+ VAR OR Q IF REQUIRED -OUTPUT+ OUTPUT + IF REQUIRED -OUTPUT+ OUTPUT + IF REQUIRED -OUTPUT+ OUTPUT + IF REQUIR
Ia• Ic• -OUTPUT+ Ia• Ic• Ib• Ia Ic Ib Ia• Ic• Ib• Ia Ic Ib Ia• Ic• Ib• Ia Ic Ib
7 8 9 10 11 12 12A 7 8 9 10 11 12 12A 12B 7 8 9 10 11 12 12A 12B 7 8 9 10 11 12 12A 12B



LOAD LOAD

LOAD LOAD

TYPICAL CT/PT CONNECTION TYPICAL ALL DIRECT CONNECT


APPLICABLE TO ALL MODELS APPLICABLE TO ALL MODELS

LINE LINE
A B C A B C


1 2 3 4 5 6 6A 1 2 3 4 5 6 6A
Vb Va Vc Vb Vb Va Vc Vb
WATT EXT. PWR. WATT EXT. PWR.
-OUTPUT+ VAR OR Q IF REQUIRED -OUTPUT+ VAR OR Q IF REQUIRED
Ia• Ic• -OUTPUT+ -OUTPUT+
Ia• Ic•
7 8 9 10 11 12 12A 7 8 9 10 11 12 12A

Attention:
If the transducer is mounted on a non-metallic or ungrounded surface the installer

must provide the means for grounding and bonding as per NEC (National Electric
LOAD LOAD Code) requirements.

33
Connections

AC Energy Transducers
(Single Output)
Metal Surface Mount Cases
LINE 1 ELEMENT LINE 11⁄2 ELEMENT LINE 2 ELEMENT
A B C A B C
1F, 2 W 3F, 3 W 3F, 3 W






UP UP
UP 1 2 3 4 5 6 6A 6B 1 2 3 4 5 6 6A 6B
6C 6C
1 2 3 4 5 6 6A 6B Vc Va Va Vb Vc Vb
-OUTPUT+ EXT. PWR. 6D -OUTPUT+ EXT. PWR. 6D
6C
V V• I I• IF REQUIRED 12B IF REQUIRED 12B
-OUTPUT+ 6D Ia• Ic• Ia Ic Ia• Ic• Ia Ic
EXT. PWR. 12C 12C
IF REQUIRED 12B 7 8 9 10 11 12 12A 7 8 9 10 11 12 12A
12D 12D
12C
7 8 9 10 11 12 12A 12D



LOAD LOAD LOAD

21⁄2 ELEMENT 21⁄2 ELEMENT LINE 3 ELEMENT


3F, 3 W 3F, 4 W A B C N 3F, 4 W



LINE LINE
A B C A B C N





UP UP UP

1 2 3 4 5 6 6A 6B 1 2 3 4 5 6 6A 6B 1 2 3 4 5 6 6A 6B
6C 6C 6C
N Va Vc N N Va Vc N
-OUTPUT+ 6D -OUTPUT+ 6D -OUTPUT+ 6D
EXT. PWR. EXT. PWR. EXT. PWR.
IF REQUIRED 12B IF REQUIRED 12B IF REQUIRED 12B
Ia• Ic• Ib• Ia Ic Ib 12C Ia• Ic• Ib• Ia Ic Ib 12C Ia• Ic• Ib• Ia Ic Ib 12C
7 8 9 10 11 12 12A 12D 7 8 9 10 11 12 12A 12D 7 8 9 10 11 12 12A 12D



LOAD

LOAD LOAD

TYPICAL ALL DIRECT CONNECT Notes:


TWO TYPES OF PULSE OUTPUTS
SOLID STATE LATCHING
APPLICABLE TO ALL MODELS
1 The arrow shows the direction of the mercury
wetted relay output.
RELAY OUTPUT RELAY LINE
+15V
2+ 5 6B
OUTPUT
2 The reverse direction is used only for bi-
directional pulse outputs.
3 8 6B
For supply connections use No. 14 AWG or larger
1 wires rated for at least 75°C (167°F). Use copper
6C 6C conductors only.

UP Attention:
1 2 3 4 5 6 6A 6B If the transducer is mounted on a non-metallic or
6D
+15V 3 8 6C
2+ 5 6D ungrounded surface the installer must provide the
-OUTPUT+ 6D
12B
means for grounding and bonding as per NEC
12C (National Electric Code) requirements.
7 8 9 10 11 12 12A 12D

LOAD

34
Connections

AC Energy Transducers
(Combined W/R/Q)
Metal Surface Mount Cases
1 ELEMENT 11⁄2 ELEMENT 2 ELEMENT
1F, 2 W 3F, 3 W 3F, 3 W

LINE LINE LINE


A B C A B C
UP UP



UP 6B 6B
6C 6C

6B
6D 6D


6C


12B 12B
6D

12C 12C

12B
12D 12D
12C
12D 1 2 3 4 5 6 6A 6B 1 2 3 4 5 6 6A 6B
1 2 3 4 5 6 6A 6B Vc V Vb Va Vc Vb
WATT VAR OR Q - EXT. PWR. WATT VAR OR Q - EXT. PWR.
V V• I I• -OUTPUT+ OUTPUT + IF REQUIRED -OUTPUT+ OUTPUT + IF REQUIRED
WATT VAR OR Q - EXT. PWR. Ia• Ic• Ia Ic Ia• Ic• Ia Ic
-OUTPUT+ OUTPUT + IF REQUIRED 7 8 9 10 11 12 12A 12B 7 8 9 10 11 12 12A 12B
6B 6B
7 8 9 10 11 12 12A 12B
6C 6C


6B
6D 6D
6C
12B 12B
6D
12C 12C


12B
12D 12D
12C
LOAD 12D LOAD LOAD

21⁄2 ELEMENT 21⁄2 ELEMENT 3 ELEMENT


3F, 3 W 3F, 4 W LINE 3F, 4 W
A B C N



LINE LINE
A B C A B C N
UP UP UP



6B 6B 6B
6C 6C 6C
6D 6D 6D



12B 12B 12B
12C 12C 12C
12D 12D 12D
1 2 3 4 5 6 6A 6B 1 2 3 4 5 6 6A 6B 1 2 3 4 5 6 6A 6B
N Va Vc N N Va Vc N N Va Vb Vc
WATT VAR OR Q - EXT. PWR. WATT VAR OR Q - EXT. PWR. WATT VAR OR Q - EXT. PWR.
-OUTPUT+ OUTPUT + IF REQUIRED -OUTPUT+ OUTPUT + IF REQUIRED -OUTPUT+ OUTPUT + IF REQUIRED
Ia• Ic• Ib• Ia Ic Ib Ia• Ic• Ib• Ia Ic Ib Ia• Ic• Ib• Ia Ic Ib
7 8 9 10 11 12 12A 12B 7 8 9 10 11 12 12A 12B 7 8 9 10 11 12 12A 12B
6B 6B 6B
6C 6C 6C

6D 6D 6D
12B 12B 12B
12C 12C 12C

12D 12D 12D


LOAD

LOAD LOAD

TWO TYPES OF PULSE OUTPUTS TYPICAL ALL DIRECT CONNECT


APPLICABLE TO ALL MODELS
SOLID STATE LATCHING
RELAY OUTPUT RELAY LINE Notes:

+15V
OUTPUT 1
1 The arrow shows the direction of the mercury
wetted relay output.
2+ 5 6B UP
3 8 6B 6B 2 The reverse direction is used only for bi-
directional pulse outputs.
6C
6D For supply connections use No. 14 AWG or larger
6C 6C 12B

wires rated for at least 75°C (167°F). Use copper


12C
12D
conductors only.
6D Attention:
+15V 3 8 1 2 3 4 5 6 6A 6B
2+ 5 6D
WATT
If the transducer is mounted on a non-metallic or
VAR OR Q - EXT. PWR.
-OUTPUT+ OUTPUT + IF REQUIRED ungrounded surface the installer must provide the
means for grounding and bonding as per NEC
7 8 9 10 11 12 12A 12B (National Electric Code) requirements.
6B
6C
6D
12B
LOAD
12C
12D

2
35
Connections

Power Factor/Phase Angle Transducers


DIN Rail Mount Cases
POWER FACTOR POWER FACTOR PHASE ANGLE
CT/PT CONNECTION CT/PT CONNECTION CT/PT CONNECTION
SINGLE PHASE THREE PHASE 3 WIRE SINGLE PHASE
OR LOAD OR LOAD
THREE PHASE 4 WIRE THREE PHASE 4 WIRE
C C
B B
LINE A • LOAD LINE A • LOAD
N


• •
• •



-16 +15 1 3 2 5 +13 -14 -16 +15 1 3 2 5 +13 -14 -16 +15 1 3 2 5 +13 -14
I• I V• V I• I V• V Va• Va Vb• Vb
-OUTPUT+ EXT. PWR. OUTPUT EXT. PWR. -OUTPUT+ EXT. PWR.
IF REQUIRED IF REQUIRED IF REQUIRED

N1 L1 N2 L2
LINE LINE
POWER FACTOR POWER FACTOR PHASE ANGLE
DIRECT CONNECTION DIRECT CONNECTION DIRECT CONNECTION
SINGLE PHASE THREE PHASE 3 WIRE SINGLE PHASE
OR LOAD OR LOAD
THREE PHASE 4 WIRE THREE PHASE 4 WIRE
C C
B B
LINE A LOAD LINE A LOAD
N

-16 +15 1 3 2 5 +13 -14 -16 +15 1 3 2 5 +13 -14 -16 +15 1 3 2 5 +13 -14
I• I V• V I• I V• V Va• Va Vb• Vb
-OUTPUT+ EXT. PWR. -OUTPUT+ EXT. PWR. -OUTPUT+ EXT. PWR.
IF REQUIRED IF REQUIRED IF REQUIRED

N1 L1 N2 L2
LINE LINE

Metal Surface Mount Cases


PHASE ANGLE PHASE ANGLE POWER FACTOR
CT/PT CONNECTION DIRECT CONNECTION CT/PT CONNECTION
SINGLE PHASE OR SINGLE PHASE OR THREE PHASE 3 WIRE
LOAD THREE PHASE 4 WIRE LOAD LOAD THREE PHASE 3 OR 4 WIRE LOAD
C
B
LINE A • LOAD
N




1 2 3 4 5 6 7 8
1 2 3 4 5 6 1 2 3 4 5 6 V• V I• I
Va• Va Vb• Vb Va• Va Vb• Vb -OUTPUT+ EXT. PWR.
-OUTPUT+ -OUTPUT+

N1 L1 N2 L2 N1 L1 N2 L2
LINE LINE LINE LINE

POWER FACTOR POWER FACTOR POWER FACTOR


CT/PT CONNECTION DIRECT CONNECTION DIRECT CONNECTION
SINGLE PHASE OR THREE PHASE 3 WIRE SINGLE PHASE OR
THREE PHASE 4 WIRE THREE PHASE 4 WIRE
C C C
B B B
LINE A • LOAD LINE A LOAD LINE A LOAD
N N N

1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
V• V I• I V• V I• I V• V I• I
-OUTPUT+ EXT. PWR. -OUTPUT+ EXT. PWR. -OUTPUT+ EXT. PWR.

Notes: 5. Phases can be rotated on three phase units.


1. For supply connections use No. 14 AWG or larger wires rated for at least 75°C 6. It is good practice to use ring lugs on current circuits.
(167°F). Use copper conductors only. 7. It is good practice to connect one side of the PT and CT to earth ground.
2. Power factor transducers do not understand physics and do not know that Attention:
power factor cannot exceed 90 degrees.
If the transducer is mounted on a non-metallic or ungrounded surface the installer
3. If reading appears to be out of range, reverse current or potential leads to suit. must provide the means for grounding and bonding as per NEC (National Electric
4. Direct connect transducers are available to 600 VAC and/or 25 A(ac). Code) requirements.

36
Connections

Frequency Transducers
DIN Rail Mount Cases Metal Surface Mount Cases

LOAD
LOAD

DC AUX. PWR.
+15 -16 2 5 +13 -14 OUTPUT IF REQUIRED

+OUTPUT- EXT. PWR. -1 +2 3 4 (-)5 (+)6


INPUT IF REQUIRED
INPUT

L N
L N LINE
LINE

RTD/Slidewire Transducers
DIN Rail Mount Cases Metal Surface Mount Cases

SLIDEWIRE TRANSDUCER RTD TRANSDUCER SLIDEWIRE TRANSDUCER RTD TRANSDUCER

- OUTPUT + EXT. PWR. - OUTPUT + EXT. PWR. - OUTPUT + - OUTPUT +


- + - +
EXT. PWR. EXT. PWR.
1 2 3 4 5 1 2 3 4 5 - + - +
1 2 3 4 1 2 3 4

6 7 8 9 10 6 7 8 9 10
5 6 7 8 5 6 7 8
- -
INPUT INPUT - -
VARIABLE RESISTOR RTD INPUT INPUT
VARIABLE RESISTOR RTD

DC Voltage Transducers/Ground Fault Detectors


DIN Rail Mount Cases Metal Surface Mount Cases
DC CURRENT/VOLTAGE TRANSDUCER DC VOLTAGE DC VOLTAGE TRANSDUCER
TRANSDUCER AND GROUND FAULT DETECTOR

- INPUT + - INPUT + - EXT. PWR. +


DC DC ALARM
- OUTPUT + - INPUT + - EXT. PWR. + - OUTPUT + - EXT. PWR. + - OUTPUT + OUTPUT

16 15 5 2 14 13 -1 +2 -3 +4 -5 +6 -1 +2 -3 +4 5 6 -7 +8
GRND. REF.

ALARM
- FAULT RESET + FAULT

Notes: Attention:
1. For supply connections use No. 14 AWG or larger wires rated for at least 75°C If the transducer is mounted on a non-metallic or ungrounded surface the installer
(167°F). Use copper conductors only. must provide the means for grounding and bonding as per NEC (National Electric
Code) requirements.

37
Connections

Line Post Sensor Transducers/Fault Alarms


Metal Surface Mount Cases

LINE ALARM
CBA ANALOG OUTPUTS ALARM OUTPUTS RESET (N.O)

N -A+ -B+ -C+ A B C N

1 2 3 4 5 6 7 8 9 10 11 12 13

OUTPUT OUTPUT OUTPUT ALARM ALARM ALARM


A B C A B C

INPUT INPUT INPUT ALARM NEUTRAL 48 V


A B C RESET OUTPUT (DC)

14 15 16 17 18 19 20 21 22 23 24 25 26


SENSOR OR PT - +
LOAD AUXILIARY POWER

Notes:
1. All transducers need an auxiliary power source. 5. The negative terminals of all analog outputs and the alarm reset are common
2. Not all connections are available on all models. Unused terminals are left internally.
unconnected internally. Attention:
3. The polarity indicated for the alarm reset terminals applies to solid-state If the transducer is mounted on a non-metallic or ungrounded surface the installer
switching device. must provide the means for grounding and bonding as per NEC (National Electric
4. The polarity indicated for the auxiliary power applies to DC sources. Code) requirements.

Line Post Sensor Transducer Systems


I V EXT. PWR.
INPUT INPUT L N
+ -

PHASE A PHASE B PHASE C

PHASE A PHASE B PHASE C

+ -
PHASE POWER NEUTRAL
CURRENT FACTOR ALARM
ALARM + CONNECTIONS FOR PHASE B AND C IDENTICAL TO PHASE A
- OUTPUT + -
CURRENT VOLTAGE ALARM
OUTPUT OUTPUT RESET

38
mTech: measurement technologies for
the power and process industries.

Instrumentation to precisely measure the critical process


signals of industry—from electricity, to temperature, to
pressure, to other critical parameters—is diverse, dependable,
and readily available from a single source. As a leading
manufacturer of power transducers and signal conditioners,
mTech can meet a host of your instrument needs:
• Power transducers in DIN rail mount and metal surface
mount configurations.
• DIN, metal, and transducer test sets.
• Smart power measurement transducers.
• Two-wire transmitters (XZ2 series).
• Universal four-wire transmitters (XZ7 series).
• DIN two-wire transmitters (XZ12 series).
• Alarm trip transmitters (XZ14 series).
• DIN four-wire transmitters (XZ15 series).
• DC V/I transmitters with two or four outputs
(DXZ15 series).
• Low cost transmitters, head mount, DIN rail; isolators
and power supplies (T and DAT series).
• Computer configurable DIN four-wire transmitters
(Max-Flex series).
• Computer configurable octal base plug-in transmitters
(Max-Pak series).
• I/P transducers.
• LED and LCD panel meters.

WARRANTY
Measurement Technologies, Ltd. (mTech) warrants this
product to be free from all latent defects in material and
workmanship under normal use and service. Should this
product be found within one (1) year from date of shipment
to be defective, mTech will repair such part and return to
buyer FOB mTech’s plant or will furnish FOB mTech’s plant a
similar product to replace it, provided written notice of such
defect is given to mTech within ten (10) days after discovery
of such defect and provided the original part is returned to
mTech’s plant with transportation charges prepaid.

THE FOREGOING WARRANTIES ARE IN LIEU OF ALL OTHER


WARRANTIES, EXPRESSED OR IMPLIED BUT NOT LIMITED
TO THE IMPLIED WARRANTIES OF MERCHANTABILITY AND
FITNESS FOR A PARTICULAR PURPOSE.
Measurement Technologies, Ltd.
P.O. Box 668
1900 Industrial Blvd., Suite 200
Colleyville, TX 76034 U.S.A.
Tel: 817-442-9930
Fax: 817-442-9990
www.measurement-technologies.com
email: sales@measurement-technologies.com

©Measurement Technologies, Ltd., 2001 10/01 Printed in U.S.A.