Professional Documents
Culture Documents
On-Line Measurement On Stability Margin of DC Distributed Power System
On-Line Measurement On Stability Margin of DC Distributed Power System
Abstract - In a DC distributed power system, the system level Nyquist stability criterion condition. Therefore, the
small-signal stability is determined by the minor loop gain, measurement of minor loop gain becomes a fimdamental
which is an impedance ratio ZJZ, between source and load technique in system stability of distributed power system.
power modules. This paper proposes a practical approach to
measure the stability margin of the minor loop gain ZJZ, online.
Currently, the measurement of minor loop gain adopts the
By injecting small-signal external perturbation current into iP most straightforward approach measure the impedance of
the DC bus and measuring the magnitude of the load side source and load modules Z, and Zi, and then calculate the
response current L ,the system stability margin can be figured stability margin of the minor loop gain ZdZi. Since this
out. Due to its simplicity in principle and implementation, this approach requires the measurement of both the magnitude
proposed measurement is useful for both stability analysis in and phase properties of Zo and Zi, and also complicated
system design and stability monitor in system operation.
process of the complex division of ZdZi, it is neither a
convenient nor an economical method.
I. INTRODUCTION
A simple measurement approach is proposed in this paper
A distributed power system is physically made up of a to examine the minor loop gain of distributed power system.
number of source and load modules, as illustrated in Fig. 1. By injecting small-signal external perturbation current i, into
Usually each module is designed based on its own stand- the DC bus and measuring the magnitude of the load side
alone operation. As a result, after system integration, the response current ;L, the system stability margin can be
interaction between modules may cause performance figured out. T h s proposed measurement approach has the
degradation, even system instability [ 1-41. following good features:
Simplicity in principle
In small-signal sense, the system stability is determined by Suitable for on-line measurement
the minor loop gain [4], which is the impedance ratio ZdZi Nonintrusive into any source/load modules
between source and load modules, as shown in Fig. 1. System
will be unstable if this minor loop gain does not satisfy the The whole paper is organized as follows. The concepts of
minor loop gain and system stability margin of distributed
_...- power system are reviewed briefly in section 11. Then the
DC bus Load subsystem principle of the proposed measurement is introduced in
section 111, followed by the discussion on its implementation.
Load 1 Finally, simulation and experiment results are provided to
- demonstrate the effective of this proposed method.
Load 2
11. SYSTEM STABILITY MARGIN
0 2000 IEEE
0-7803-5864-3/00/$10.00 1190
Authorized licensed use limited to: King Mongkut's University of Technology North Bangkok. Downloaded on July 13,2021 at 00:05:33 UTC from IEEE Xplore. Restrictions apply.
relative stability requires every points on loop gain curve are
separated from points (-1,O) by a certain distance, as a results,
the concept of forbidden region was proposed as a design
guideline to meet system relative stability requirement [131.
As shown in Fig. 4b, a forbidden region around point (-1,O)
can be defined, and the loop gain is required to neither cut
Zi into nor encircle this shadowed region.
Fig. 2 Impedance criterion
1191
Authorized licensed use limited to: King Mongkut's University of Technology North Bangkok. Downloaded on July 13,2021 at 00:05:33 UTC from IEEE Xplore. Restrictions apply.
operation. Especially in system operation, the designed
system stability margin is subject to change. As a small-
signal property, the minor loop gain changes at different
operating points. Parameter variation and fault conditions
may also reduce the designed stability margin. Therefore, an
online measurement on ZJZi can serve as a stability monitor.
Source
b)
I192
Authorized licensed use limited to: King Mongkut's University of Technology North Bangkok. Downloaded on July 13,2021 at 00:05:33 UTC from IEEE Xplore. Restrictions apply.
Basic plane geometry howledge shows that if minor loop
gain ZJZi is out of the shadowed forbidden region, there Obviously, the measurement can be carried out directly
is Dl(o)<l within all frequency range, and vice versa, i.e. with a commercial impedance analyzer. The reference of
perturbation pp(jo)can be introduced from the frequency-
swept output signal of the impedance analyzer, while
i L ( j o ) can be read through the test probe.
Based on i) and ii), it is easy to draw conclusion 1. According to the proposed measurement method, an
system stability margin monitor can be as simple as the one
An Dual Approach in Fig. 10. Two basic functions are implemented inside the
monitor.
For the stability margin measurement introduced in Fig. 6
and conclusion 1, an dual approach is also discovered. As One is a signal generator of ip, the small-signal sinusoidal
shown in Fig. 9, instead of an current perturbation, voltage
source Gp can be used to inject perturbation into the DC bus. perturbation current injected to the DC bus. Parameters for ip
Consequently, source side response voltage Gs is measured. can be input from an operator, such as the magnitude of ip,
Conclusion 2 serves the counterpart of conclusion 1 the frequency of 3, (starting frequency, ending frequency,
A
number of frequency points for sweep, number of cycles at
each frequency point.) These parameters usually vary from
system to system.
Application
1193
Authorized licensed use limited to: King Mongkut's University of Technology North Bangkok. Downloaded on July 13,2021 at 00:05:33 UTC from IEEE Xplore. Restrictions apply.
IV. SIMULATION The derturbation current ip
is injected into the DC bus
when system is in steady state. Fig. 13 shows the response
Simulations have been camed out on a test-bed of DC source c k e n t in both frequency domain and time domain.
distributed power system. As illustrated in Fig. 11. The test-
bed owns a 800V DC bus, a lOOkw 3-phase PFC rectifier [7] The response current ;L is much smaller than Tp in
as the source module, a 80kw 3-phase inverter [8] as load 1, magnitude, indicating sufficient system stability margin.
and a 20kw DCDC converter [9] as load 2. The magnitude of
ip is set as 1A (PP value is 2A), about 1% of the DC current
in the DC bus.
nn J l I
"." II I
rrter
Load
-30.0 J' I
I I I I I I
50.0 100.0 03k OJk I.0k Z.0k f W)
a) i L in frequency domain
I
Fig. 11 Test bed of distributed power system
.MU)
p.-
0.1 0.12 0.14 0.16 o.,l T(s4
b) i L in time domain
*. -
Fig. 13 Measured 1L shows sufficient stability margin
I
System in fault condition
*. 1.L. .Y *I. I.* 1l
f(WI
a) Impedance of test bed system A fault condition in the PFC rectifier is set up intentionally
to test the function of the. proposed stability monitor. The
bulk capacitor in the EM1 filter of the inverter is burn out,
causing a sudden drop of the magnitude in Zi, as shown in
Fig. 12a. As a result, the system minor loop expands in S-
plane and cuts into the round forbidden region as the solid
line in Fig. 12b.
Under the same perturbation, response current i L is over
i p in the frequency range around 3 H z , as shown in Fig. 14a
, alarming insufficient stability margin. In time domain, the
response current iL (t) is over 2A correspondingly, as shown
inFig. 14b.
-3.0 -2.0 -1.0 0.0 1.0 2.0
1194
Authorized licensed use limited to: King Mongkut's University of Technology North Bangkok. Downloaded on July 13,2021 at 00:05:33 UTC from IEEE Xplore. Restrictions apply.
10.0 The minor loop gain of this source-load system is
illustrated in Fig. 16. ZJZi is well separated from the
0.0 defined forbidden region, indicating the 48V DC bus
sufficient stability margin.
-10.0
-20.0
40.0 J' I
I I I I I I
50.0 100.0 03k 05k l.0k 2.Ok f(W
a) iL in frequency domain
126.0 - t
2.0A
Fig. 16 Stability margin of tested 48V DPS
Perturbation signal
from HP4194A @$-I I
Fig. 15 Tested 48V distributed power system
1195
Authorized licensed use limited to: King Mongkut's University of Technology North Bangkok. Downloaded on July 13,2021 at 00:05:33 UTC from IEEE Xplore. Restrictions apply.
CONCLUSION REFERENCES
To measure the stability margin of DC distributed power [I] C.M. Wildrick, F.C. Lee “A Method of Defining the Load Impedance
Specification for a Stable Distributed Power System,” IEEE
system, a practical on-line measurement approach is Transaction on Power Electronics, Vol. 10, No. 3, May. 1995, pp. 280-
proposed. By injecting small-signal extemal perturbation 5
current i, into the DC bus and measuring the magnitude of [2] A. Patil, C. Wildrick, F. C. Lee “Assessment of space station power
the load side response current ;L, the system stability margin system performance and stability,” quarterly progress review for NASA
Lewis Research Center, by Virginia Power Electronics Center,
can be figured out. The measurement can be implemented VPI&SU, Blacksburg, VA, Oct. 1992.
with a commercial impedance analyzer, or with a specially [3] Xiaogang Feng, Z. Ye, K. Xing, Fred C. Lee and Dusan Borojevic,
built circuit. Simulation and experimental results are provided “Impedance Specification and Impedance Improvement for DC
to demonstrate the effectiveness of the proposed method. Distributed Power System,” PESC’99 Charleston, US, June, 1999,
~~889-94
[4] R.D. Middlebrook, “Input filter consideration in design and application
of switching regulators”, hoc. IEEE Industrial Application Society
APPENDIX A Annual Meeting, 1976.
[5] Mohamed Belkhayat “Stability Criteria for AC Power Systems with
This appendix provides a proof of measurement approach Regulated Loads”, Dissertation, Purdue Univ. Dec. 1997.
of D , ( o ) i n (7) of the paper, based on basic circuit [6] Xiaogang Feng, Zhihong Ye, Kun Xing, Fred C. Lee and Dusan
Borojevic, “Individual Load Impedance Specification for a Stable DC
knowledge. Distributed Power System”, APEC’99, Dallas, US, Mar. 1999, pp923-9
As shown in Fig. A-1, is and iLare small-signal [7] Jia Wu, Heping Dai, Kung Xing, Fred C. Lee and Dushan Boroyevich
“Implementation of ZCT Soft-Switching Technique in a lOOkW PEBB
sinusoidal currents response to ip in source and load sides based Three-phase PFC Rectifier ”, PESC’99 Charleston, US, June,
respectively, while G b is the small-signal sinusoidal bus 1999, ~ ~ 6 4 7 - 5 2
voltage. [SI Richard Zhang “High Performance Power Converters for Nonlinear
and Unbalanced LoadlSource” Dissertation, VPI&SU, Blacksburg, VA,
Nov. 1998
According to definition, there are:
[9] Gujit Thandi “Modeling, control and stability of a PEBB based DC
distributed power system,” Thesis, VPI&SU, Blacksburg, VA, Jun.
1997
[IO] G.S. Popkiron, R.N. Schindler “Optimization of the perturbation
signal for electrochemical impedance spectroscopy in the time
domain”. Review of Scientific Instrument Vol 64,No 11, Nov, 1993
+b( jo) pp3 1 11-5.
Zi (jo)= v [I I ] Matthew B. Hams, Auther W.Kelley, Jason P. Rhode, and Mesut E.
iL(jw)
Baran, “Instrumentation for measurement of line impedance“,
proceedings of APEC’94, pp887-93.
[12] Auther W. Kelley, John M. Wilson, Jason P. Rhode, and Mesut Baran,
”On-line wideband measurement of induction motor impedance”,
proceedings of IAS’95, pp647-54.
[I31 George W. Hart, “Nonintrusive appliance load monitoring”,
proceedings of the IEEE, Vol. 80, No.12, Dec 1992, pp1872-91
Substitution (A-1) and (A-2) into (A-3) gives:
[I41 Steve B. Leeb and James L. Kirtley, Jr, “A multiscale transient event
detector for nonintrusive monitoring”, proceedings of IECON’93, Voll .
pp354-9.
(A-4)
1196
Authorized licensed use limited to: King Mongkut's University of Technology North Bangkok. Downloaded on July 13,2021 at 00:05:33 UTC from IEEE Xplore. Restrictions apply.