Professional Documents
Culture Documents
Analysis and Mitigation of Interactions Between PFC Converters and The AC Source
Analysis and Mitigation of Interactions Between PFC Converters and The AC Source
Analysis and Mitigation of Interactions Between PFC Converters and The AC Source
99
Authorized licensed use limited to: King Mongkut's University of Technology North Bangkok. Downloaded on February 25,2021 at 07:24:09 UTC from IEEE Xplore. Restrictions apply.
distortion at the input current of a PFC converter. The 111. IMPEDANCE MODELING
AND MEASUREMENT
input impedance model is then used to analyze the inter-
actions and to demonstrate correlation between model The converter-source interactions observed in Fig. 1
predictions and experimental measurements. An experi- can be analyzed based on impedance of both the
mental setup for measuring the input impedance is also converter input and the ac power source output. For
described. A practical mitigation method based on easy reference, Fig. 2 dsfines the major elements of the
. damping of the input filter is then presented and its
interconnected converter-source system, where C,,
effectiveness in eliminating undesired interactions represents the 1.5 pF filter capacitor at the input of the
demonstrated. The emphasis of the work is on airborne PFC converter module.
applications with 400 Hz o~ variable-frequency (in the
range of 360-800 Hz) ac input, where high performance
control is essential for meeting the stringent harmonic
current Limits. ,
100
Authorized licensed use limited to: King Mongkut's University of Technology North Bangkok. Downloaded on February 25,2021 at 07:24:09 UTC from IEEE Xplore. Restrictions apply.
The setup used here consists of a power amplifier be explained as follows: The frequency analyzer deter-
controlled by a frequency analyzer and connected in mines the input impedance by extracting, using Fourier
series with an ac power supply. Output frequency of analysis, the input current component at the injection
the ac power supply is fixed (e.g. at 400 Hz) while its frequency and comparing it with the injected voltage.
magnitude is adjusted at the rated supply voltage of Such extraction will be numerically difficult when the
the PFC module. The power amplifier is controlled injection frequency is close to the main supply
by the frequency analyzer to inject a variable- frequency, and impossible when the injection frequency
frequency voltage. The magnitude of the power is equal to the main supply frequency, which leads to
amplifier output is relatively small compared to that measurement error.
of the ac power supply so as to limit its active output
The input impedance as defined by (1) and (2) can
power. By sweeping the frequency of the control
also be measured by using a variable-frequency
signal over a prescribed range, the frequency
power supply without a power amplifier and a
analyzer can then determine the frequency response
frequency analyzer. The process would involve
of the input impedance in a single measurement.
manually changing the output frequency of the power
Depending on the voltage and current ratings of the 'supply and measuring the converter input current
power amplifier used, an injection transformer might
magnitude and phase relative to the input voltage to
also be need to provide the necessary voltage andlor
determine the input impedance at each frequency
current matching.
point. Bode plots such as those shown in Fig. 3 and 4
Measurement results of the PFC converter module can also be generated, provided that enough data
with 106 W output power are shown in Fig. 3 and Fig. 4 points are taken over the frequency range of interests.
for and zi,,($), respectively. The responses are This is however a very time-consuming process.
PfC
also compared to theoretical predictions by using the
impedance models (1) and (2). The measurement C. Source Impedance Measurement
results are found to correlate very well with model
Output impedance of the ac power supply, zscs) as
predictions in both cases. The ac power s ~ p p l youtput
defined in Fig. 2, can also be measured using a sunilar
frequency is 50 Hz when measuring (s) and 400
PfC setup as described in the previous subsection. Since the
Hz when measuring z~,,(~). The measurement results
ac power supply has linear output characteristics, it
show some noise around these frequencies, which can
101
Authorized licensed use limited to: King Mongkut's University of Technology North Bangkok. Downloaded on February 25,2021 at 07:24:09 UTC from IEEE Xplore. Restrictions apply.
doesn't need to be operated with rated output (voltage, experimental system, the output impedance of the Elgar
current, or frequency) and with any particular load ac power supply and the input impedance of the PFC
(such as the PFC converter). Instead, a resistive load converter (including the ac-side filter capacitor Cat) are
can be used and the output voltage can be kept compared in Fig. 6 . As can be seen, the magnitude of
relatively low. Furthermore, the output impedance shall the source output impedance exceeds that of the
be independent of the output frequency. converter input impedance at about 12 kHz and above,
while the phase difference at the intersection frequency
Fig. 5 shows the measured output impedance of
is about 165O, i.e., there is only 15' phase margin. The
the Elgar ac power supply. The measurement was
lack of sufficient phase margin clearly indicates a
taken under 400 Hz output, which also explains the
potential instability problem of the system in the 10-20
high measurement noise around 400 Hz. As can be
kHz range, which is confirmed by the measured
seen, the output impedance has a resonant frequency
current waveform in Fig. 1. The frequency of the
at about 40 kHz, below which the output is inductive.
dominant harmonic current seen in Fig. 1 is about 16
In the frequency range from 1 kHz to 40 kHz, the
kHz, which is close to what the impedance plots in
output can be approximately modeled by a 100 yH
Fig. 6 predicts.
inductor (which has 16 dB-Cl impedance at 10 kHz).
This is unusually high for a power supply, but The analysis and measurement results presented
actually serves well our purpose of demonstrating thus far served two purposes:
potential interactions between a PFC converter and 1 ) They demonstrated that converter-source interac-
the ac source. In an airborne ac power system, for tions can also occur in ac power systems involving
example, the distribution cable itself could have as single-phase PFC converters, and that such interac-
much as 100 yH inductance if the PFC.converter is tions can lead to excessive input current harmonic
located 50 meters or farther away from the generator. distortion of the PFC converter.
2) The results further demonstrated that the classical
Iv. INTERACTION ANALYSIS
AND MITIGATION stability criterion for interconnected converter-
source systems can also be applied to ac power
Stability of an interconnected converter-source
systems. In particular, the input impedance models
system requires that the ratio of the source output
(1) and (2) are shown to be accurate and useful for
impedance to the converter input impedance meet the predicting potential instability problems involving
Nyquist criterion [l]. To apply this criterion to our boost single-phase PFC converters.
50
B
m 30
40
E,
4 20
.-2
C
10
H -10
0
75 75
50 50
3
n
v
25
0
25
0
s
E
a
-25
-50
-25
-50
-75 -75
102
Authorized licensed use limited to: King Mongkut's University of Technology North Bangkok. Downloaded on February 25,2021 at 07:24:09 UTC from IEEE Xplore. Restrictions apply.
Having identified the source of the interactions, added filter capacitor reduces the input impedance
different methods can be applied to alleviate or such that it intersects with source output impedance
eliminate the problem. Reducing the source impedance at a lower frequency (10 kHz). On the other hand, the
by using an ac power supply with lower output damper provides a boost to the phase response of Zin
impedance, for example, may be an effective and easy in the high-frequency region, and the phase
solution in a laboratory environment, but may not be difference at the intersection frequency (10 kHz)
possible in practical systems where the source becomes 125' compared to 1 6 5 O before the damper is
impedance is dictated by system design. The 1.5 pF ac- added. Therefore, the damper in effect increased the
side filter capacitor, although appropriate for 50/60 Hz, system phase margin from 15' to 55', and is expected
is apparently too large for high-frequency lines. Using a to solve the interaction problem observed in Fig. 1.
smaller filter capacitor would increase the converter
Operation of the PFC converter with the added R&d
input impedance in the high-frequency region, thereby
damper was also measured. The results are shown in
reducing the potential for instability. For example, it
Fig. 8. Comparing with the waveform shown in Fig. 1,
was found that the converter input impedance would not
we can conclude that the damper has eliminated the
intersect with the source output impedance at any
stability problem and the associated harmonic current '
frequency if this capacitor is changed to 80 nF.
distortion. The remaining current distortion around
However, the effects of such a small filter capacitor on
the zero crossing of the input voltage is caused by the
the switching-frequency ripple generated by the PFC
limited control bandwidth of the current loop of the
converter also need to be evaluated, and additional
PFC converter when operated under high line
filtering elements may be needed to provide sufficient
frequencies. This problem can be further solved by
attenuation for high-frequency ripple [81.
applying the feedforward input current control
In the following, we will demonstrate that the method introduced in [lo]. To demonstrate that, Fig.
undesirable interactions can also be avoided by proper 9 shows the measured input current and voltage
damping of the input filter capacitor. For that purpose, waveform after feedforward control is added to the
we keep the 1.5 pF filter capacitor unchanged and add current loop of the PFC converter. The results clearly
an R&d damper in parallel with it. The damping demonstrated the effectiveness of feedforward control
capacitor, ,C, and resistor, Rd, are designed using the in reducing input current zero-crossing distortion, and
method presented in [9]. In this method, the damping further confirmed that the distortion observed in Fig. 8
capacitor is selected first. Defining a quantity ?I by is not due to interactions with the source.
'd
?I = 7 , (3)
Lac
40
the damping resistor is then designed based on the
30
following expression to achieve optimal damping:
m
10
0
L in the above expression is the inductance of the filter -10
inductor.
100 lo00 loo00 100000.
We don't have a filter inductor in our system.
However, the ac power source behaves like a 100 pH
Frequency (Hz) +
inductor in the frequency range where interactions are
likely to occur, as mentioned before in Section 111. 75
Therefore, we can design the damper based on L = 100 50
pH. Selection of Cd requires a trade-off between the 25
effectiveness of damping vs. the size of the damping a
W 0
capacitor. As a simple experiment, we use C, = ,C , =
1.5 pF, that is, ?I = 1. The optimal damping resistance is E
3 -25
then calculated from (4) to be 11.83 Q.
& -50
-75
The input impedance of the PFC converter with
,, and the designed parallel R g d damper is plotted
C 100 loo0 loo00 100000.
in Fig. 7 together with the measured output
impedance of the ac power source. For comparison,
Frequency (Hz) +
the input impedance before the damper is added is Fig. 7. Effects on parallel RC damper on PFC converter input
also plotted (by the dashed lines). As expected, the impedance. Dashed line&without damper; solid lines: with damper.
103
Authorized licensed use limited to: King Mongkut's University of Technology North Bangkok. Downloaded on February 25,2021 at 07:24:09 UTC from IEEE Xplore. Restrictions apply.
Fig. 8. Measured input current and voltage waveform after the addi- Fig. 9. Measured input current and voltage waveform after the addi-
tion of the parallel RC damper to the input filter capacitor. tion of the parallel RC damper and current feedforward control.
The large leading phase of the input current relative supported in part by Rockwell Collins, Inc., through the
to the input voltage in Fig. 8 and Fig. 9 is caused by the Center for Power Electronics Systems (CPES) - an
high line frequency (750 Hz) and the large filter Engineering Research Center of the NSF.
capacitor, Cue,as well as the added damping capacitor,
C & This phase shift can be reduced by using a smaller REFERENCES
filter capacitor and/or redesign of the input filter. The
R. D. Middlebrook, “Input filter considerations in design and
input impedance model introduced here provides a application of switching regulators,” Proceedings of IEEE
u s e l l tool for optimal design of input filters for single- Industry Applications Socieiy Annual Meeting, 1916, pp. 366-
phase PFC converters, which remains an interesting 382.
topic for future work. “Environmental conditions and test procedures for airborne
equipment” DO-I60D, Ch 16.
R. Red1 and A. S. Kislovski, “Source impedance and current-
V. CONCLUSIONS control loop interaction in high-frequency power-factor
correctors,” in Records ofIEEE PESC‘92, pp. 483-488.
Experimental results demonstrated that converter- C. D. Davidson and R. Szasz, “Compatibility of switchmode
source interactions can also exist in ac power systems rectifiers with engine generators,” in Proceedings of
involving single-phase PFC converters, and that such IhTELEC‘2000,pp. 626-63 1.
interactions can lead to excessive harmonic current G Spiazzi, L. Rossetto and J. A. Pomilio, “Analysis of EM1 filter
distortion. Recently developed input impedance models induced instabilities in boost power factor preregulators,” in
Recorb ofPESC ‘ 9 8 , 1 9 9 8 , ~ 1048-1053.
~.
for boost single-phase PFC converters were shown to be J. Sun, “Input impedance analysis of single-phase PFC
accurate and useful for predicting such interactions. converters,” in Proceedings of IEEE Applied Power Electronics
Mitigation of undesirable interactions by means of Conference, 2003, pp.361-367.
proper input filter design was also discussed. In addition Texas Instruments, “UCC3817 BiCMOS Power Factor Preregu-
to analytical methods, measurement techniques for -
lator Evaluation Board User’s Guide,” July 2001.
experimental evaluation of PFC converter interaction V. Vlatkovic, D. Borojevic, and F. C. Lee, “Input filter design for
power factor correctioii circuits,” IEEE Transactions on Power
with ac power sources were also presented. Electronics,vol. 11, no. 1, January 1996, pp. 199-205.
R. W. Erickson, “Optimal single resistor damping of input
ACKNOWLEDGEMENT filters,’’ in Proceedings of 1999 IEEEApplied Power Elecimnics
Conference, 1999, pp. 1073-1079.
The PFC demo board used in the experiments was [lo] M. Chen and J. Sun, “Feedforward current control of boost
provided by Texas Instruments. The work was single-phase PFC converters,” in Proceedings of 2004 IEEE
Applied Power Electronics Conference, pp. 1187-1193.
104
Authorized licensed use limited to: King Mongkut's University of Technology North Bangkok. Downloaded on February 25,2021 at 07:24:09 UTC from IEEE Xplore. Restrictions apply.