Download as pdf or txt
Download as pdf or txt
You are on page 1of 182

7SA522 V4_7 Var_Hyd#4_prn_15_47_39

General Device Settings


NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

1 General Device Settings

1.1 Group Device

Group Device
No. Settings Value Group

0610 Fault Display on LED / LCD Display Targets on every Pickup All
0625A Minimum hold time of latched LEDs 0 min All
0640 Start image Default Display image 1 All

Page 1 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39
Power System Data 1
NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

2 Power System Data 1

2.1 Group Power System Data 1; Group Transformers

Group Power System Data 1; Group Transformers


No. Settings Value Group

0201 CT Starpoint towards Line All


0203 Rated Primary Voltage 400.0 kV All
0204 Rated Secondary Voltage (Ph-Ph) 110 V All
0205 CT Rated Primary Current 1000 A All
0206 CT Rated Secondary Current 1A All
0210 U4 voltage transformer is not connected All
0211 Matching ratio Phase-VT To Open-Delta-VT 1.73 All
0215 Matching ratio Usy1 / Usy2 1.00 All
0220 I4 current transformer is Neutral Current of the parallel line All
0221 Matching ratio I4/Iph for CT's 1.000 All

2.2 Group Power System Data 1; Group Power System

Group Power System Data 1; Group Power System


No. Settings Value Group

0207 System Starpoint is Solid Earthed All


0230 Rated Frequency 50 Hz All
0235 Phase Sequence L1 L2 L3 All
0236 Distance measurement unit km All
0237 Setting format for zero seq.comp. format Zero seq. comp. factors RE/RL and XE/XL All
0238A Earth Fault O/C: setting for 1pole AR all stages together All

Page 2 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

2.3 Group Power System Data 1; Group Breaker

Group Power System Data 1; Group Breaker


No. Settings Value Group

0240A Minimum TRIP Command Duration 0.10 sec All


0241A Maximum Close Command Duration 0.10 sec All
0242 Dead Time for CB test-autoreclosure 1.00 sec All

Page 3 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39
Oscillographic Fault Records
NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

3 Oscillographic Fault Records

3.1 Group Oscillographic Fault Records

Group Oscillographic Fault Records


No. Settings Value Group

0402A Waveform Capture Save with Pickup All


0403A Scope of Waveform Data Power System fault All
0410 Max. length of a Waveform Capture Record 3.00 sec All
0411 Captured Waveform Prior to Trigger 0.50 sec All
0412 Captured Waveform after Event 0.50 sec All
0415 Capture Time via Binary Input 1.00 sec All

Page 4 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39
Settings groups
NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

4 Settings groups

4.1 Group Power System Data 2; Group Power System

Group Power System Data 2; Group Power System


No. Settings Value Group

1103 Measurement: Full Scale Voltage (100%) 400.0 kV A


1104 Measurement: Full Scale Current (100%) 1000 A A
1105 Line Angle 85 ° A
1211 Angle of inclination, distance charact. 85 ° A
1107 P,Q operational measured values sign not reversed A
1110 x' - Line Reactance per length unit 0.0844 Ohm / km A
1111 Line Length 193.0 km A
1116 Zero seq. comp. factor RE/RL for Z1 2.00 A
1117 Zero seq. comp. factor XE/XL for Z1 0.83 A
1118 Zero seq. comp.factor RE/RL(> Z1) 2.00 A
1119 Zero seq. comp.factor XE/XL(> Z1) 0.83 A
1126 Mutual Parallel Line comp. ratio RM/RL 7.79 A
1127 Mutual Parallel Line comp. ratio XM/XL 0.28 A
1128 Neutral current RATIO Parallel Line Comp 85 % A

4.2 Group Power System Data 2; Group Line Status

Group Power System Data 2; Group Line Status


No. Settings Value Group

1130A Pole Open Current Threshold 0.05 A A


1131A Pole Open Voltage Threshold 20 V A

Page 5 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Group Power System Data 2; Group Line Status(2)


No. Settings Value Group

1132A Seal-in Time after ALL closures 0.20 sec A


1133A minimal time for line open before SOTF 0.05 sec A
1134 Recognition of Line Closures with Current OR Voltage or Manual close BI A
1135 RESET of Trip Command with Pole Open Current Threshold only A
1136 open pole detector with measurement (U/I,trip,pickup,CBaux) A
1140A CT Saturation Threshold 20.0 A A
1150A Seal-in Time after MANUAL closures 0.20 sec A
1151 Manual CLOSE COMMAND generation NO A
1152 MANUAL Closure Impulse after CONTROL <none> All

4.3 Group Power System Data 2; Group Trip 1-/3-pole

Group Power System Data 2; Group Trip 1-/3-pole


No. Settings Value Group

1155 3 pole coupling with Trip A


1156A Trip type with 2phase faults 3pole A

4.4 Group Distance protection, general settings; Group General

Group Distance protection, general settings; Group General


No. Settings Value Group

1201 Distance protection ON A


1202 Phase Current threshold for dist. meas. 0.10 A A
1211 Angle of inclination, distance charact. 85 ° A

Page 6 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Group Distance protection, general settings; Group General(2)


No. Settings Value Group

1208 Series compensated line NO A


1215 Mutual coupling parall.line compensation YES A
1232 Instantaneous trip after SwitchOnToFault with Zone Z1B A
1241 R load, minimum Load Impedance (ph-e) 23.652 Ohm A
1242 PHI load, maximum Load Angle (ph-e) 26 ° A
1243 R load, minimum Load Impedance (ph-ph) 23.652 Ohm A
1244 PHI load, maximum Load Angle (ph-ph) 26 ° A
1317A Single pole trip for faults in Z2 NO A
1357 Z1B enabled before 1st AR (int. or ext.) NO A

4.5 Group Distance protection, general settings; Group Earth faults

Group Distance protection, general settings; Group Earth faults


No. Settings Value Group

1203 3I0 threshold for neutral current pickup 0.10 A A


1204 3U0 threshold zero seq. voltage pickup 5V A
1207A 3I0>-pickup-stabilisation (3I0> /Iphmax) 0.15 A
1209A criterion of earth fault recognition 3I0> OR 3U0> A
1221A Loop selection with 2Ph-E faults all loops A

Page 7 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39
Group Distance protection, general settings; Group Time Delays
NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

4.6 Group Distance protection, general settings; Group Time Delays

Group Distance protection, general settings; Group Time Delays


No. Settings Value Group

1210 Condition for zone timer start with distance pickup A


1305 T1-1phase, delay for single phase faults 0.00 sec A
1306 T1multi-ph, delay for multi phase faults 0.00 sec A
1315 T2-1phase, delay for single phase faults 0.40 sec A
1316 T2multi-ph, delay for multi phase faults 0.40 sec A
1325 T3 delay 1.00 sec A
1335 T4 delay 0.50 sec A
1345 T5 delay oo sec A
1365 T6 delay oo sec A
1355 T1B-1phase, delay for single ph. faults 0.00 sec A
1356 T1B-multi-ph, delay for multi ph. faults 0.00 sec A

4.7 Group Distance zones (quadrilateral); Group Zone Z1

Group Distance zones (quadrilateral); Group Zone Z1


No. Settings Value Group

1301 Operating mode Z1 Forward A


1302 R(Z1), Resistance for ph-ph-faults 4.130 Ohm A
1303 X(Z1), Reactance 13.040 Ohm A
1304 RE(Z1), Resistance for ph-e faults 15.130 Ohm A
1305 T1-1phase, delay for single phase faults 0.00 sec A
1306 T1multi-ph, delay for multi phase faults 0.00 sec A
1307 Zone Reduction Angle (load compensation) 5° A

Page 8 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

4.8 Group Distance zones (quadrilateral); Group Zone Z1B-exten.

Group Distance zones (quadrilateral); Group Zone Z1B-exten.


No. Settings Value Group

1351 Operating mode Z1B (overrreach zone) Forward A


1352 R(Z1B), Resistance for ph-ph-faults 8.250 Ohm A
1353 X(Z1B), Reactance 19.550 Ohm A
1354 RE(Z1B), Resistance for ph-e faults 19.250 Ohm A
1355 T1B-1phase, delay for single ph. faults 0.00 sec A
1356 T1B-multi-ph, delay for multi ph. faults 0.00 sec A
1357 Z1B enabled before 1st AR (int. or ext.) NO A

4.9 Group Distance zones (quadrilateral); Group Zone Z2

Group Distance zones (quadrilateral); Group Zone Z2


No. Settings Value Group

1311 Operating mode Z2 Forward A


1312 R(Z2), Resistance for ph-ph-faults 8.250 Ohm A
1313 X(Z2), Reactance 19.550 Ohm A
1314 RE(Z2), Resistance for ph-e faults 19.250 Ohm A
1315 T2-1phase, delay for single phase faults 0.40 sec A
1316 T2multi-ph, delay for multi phase faults 0.40 sec A
1317A Single pole trip for faults in Z2 NO A

Page 9 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39
Group Distance zones (quadrilateral); Group Zone Z3
NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

4.10 Group Distance zones (quadrilateral); Group Zone Z3

Group Distance zones (quadrilateral); Group Zone Z3


No. Settings Value Group

1321 Operating mode Z3 Forward A


1322 R(Z3), Resistance for ph-ph-faults 13.750 Ohm A
1323 X(Z3), Reactance 24.440 Ohm A
1324 RE(Z3), Resistance for ph-e faults 23.370 Ohm A
1325 T3 delay 1.00 sec A

4.11 Group Distance zones (quadrilateral); Group Zone Z4

Group Distance zones (quadrilateral); Group Zone Z4


No. Settings Value Group

1331 Operating mode Z4 Reverse A


1332 R(Z4), Resistance for ph-ph-faults 13.750 Ohm A
1333 X(Z4), Reactance 3.260 Ohm A
1334 RE(Z4), Resistance for ph-e faults 23.370 Ohm A
1335 T4 delay 0.50 sec A

4.12 Group Distance zones (quadrilateral); Group Zone Z5

Group Distance zones (quadrilateral); Group Zone Z5


No. Settings Value Group

1341 Operating mode Z5 Non-Directional A


1342 R(Z5), Resistance for ph-ph-faults 16.500 Ohm A

Page 10 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Group Distance zones (quadrilateral); Group Zone Z5(2)


No. Settings Value Group

1343 X(Z5)+, Reactance for Forward direction 29.330 Ohm A


1344 RE(Z5), Resistance for ph-e faults 28.040 Ohm A
1345 T5 delay oo sec A
1346 X(Z5)-, Reactance for Reverse direction 29.330 Ohm A

4.13 Group Distance zones (quadrilateral); Group Zone Z6

Group Distance zones (quadrilateral); Group Zone Z6


No. Settings Value Group

1361 Operating mode Z6 Inactive A


1362 R(Z6), Resistance for ph-ph-faults 15.000 Ohm A
1363 X(Z6)+, Reactance for Forward direction 15.000 Ohm A
1364 RE(Z6), Resistance for ph-e faults 15.000 Ohm A
1365 T6 delay oo sec A
1366 X(Z6)-, Reactance for Reverse direction 4.000 Ohm A

4.14 Group Power Swing

Group Power Swing


No. Settings Value Group

2002 Power Swing Operating mode Z2 and higher blocked A


2006 Power swing trip NO A

Page 11 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

4.15 Group Teleprotection for Distance prot.

Group Teleprotection for Distance prot.


No. Settings Value Group

2101 Teleprotection for Distance protection ON A


2102 Type of Line Two Terminals A
2103A Time for send signal prolongation 0.07 sec A
2112A DIS transient block by EF NO A
2113 Memorize receive signal NO A

4.16 Group Instantaneous HighSpeed SOTF Overcurrent

Group Instantaneous HighSpeed SOTF Overcurrent


No. Settings Value Group

2401 Inst. High Speed SOTF-O/C is ON A


2404 I>>> Pickup 2.50 A A

4.17 Group Backup overcurrent; Group General

Group Backup overcurrent; Group General


No. Settings Value Group

2601 Operating mode ON:only active with Loss of VT sec. cir. A


2680 Trip time delay after SOTF 0.00 sec A

Page 12 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

4.18 Group Backup overcurrent; Group I>>

Group Backup overcurrent; Group I>>


No. Settings Value Group

2610 Iph>> Pickup oo A A


2611 T Iph>> Time delay 0.30 sec A
2612 3I0>> Pickup oo A A
2613 T 3I0>> Time delay 2.00 sec A
2614 Instantaneous trip via BI NO A
2615 Instantaneous trip after SwitchOnToFault NO A

4.19 Group Backup overcurrent; Group I>

Group Backup overcurrent; Group I>


No. Settings Value Group

2620 Iph> Pickup oo A A


2621 T Iph> Time delay 0.50 sec A
2622 3I0> Pickup oo A A
2623 T 3I0> Time delay 2.00 sec A
2624 Instantaneous trip via Teleprot./BI NO A
2625 Instantaneous trip after SwitchOnToFault NO A

Page 13 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39
Group Backup overcurrent; Group Inverse
NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

4.20 Group Backup overcurrent; Group Inverse

Group Backup overcurrent; Group Inverse


No. Settings Value Group

2640 Ip> Pickup 1.50 A A


2642 T Ip Time Dial 0.50 sec A
2646 T Ip Additional Time Delay 0.00 sec A
2650 3I0p Pickup 1.50 A A
2652 T 3I0p Time Dial 0.50 sec A
2656 T 3I0p Additional Time Delay 0.00 sec A
2660 IEC Curve Normal Inverse A
2670 Instantaneous trip via Teleprot./BI NO A
2671 Instantaneous trip after SwitchOnToFault NO A

4.21 Group Backup overcurrent; Group I - STUB

Group Backup overcurrent; Group I - STUB


No. Settings Value Group

2630 Iph> STUB Pickup 1.50 A A


2631 T Iph STUB Time delay 0.05 sec A
2632 3I0> STUB Pickup oo A A
2633 T 3I0 STUB Time delay 2.00 sec A
2634 Instantaneous trip via Teleprot./BI NO A
2635 Instantaneous trip after SwitchOnToFault NO A

Page 14 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39
Group Measurement Supervision; Group Balance / Summ.
NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

4.22 Group Measurement Supervision; Group Balance / Summ.

Group Measurement Supervision; Group Balance / Summ.


No. Settings Value Group

2901 Measurement Supervision ON A


2902A Voltage Threshold for Balance Monitoring 50 V A
2903A Balance Factor for Voltage Monitor 0.75 A
2904A Current Balance Monitor 0.50 A A
2905A Balance Factor for Current Monitor 0.50 A
2906A Summated Current Monitoring Threshold 0.10 A A
2907A Summated Current Monitoring Factor 0.10 A
2908A T Balance Factor for Voltage Monitor 5 sec A
2909A T Current Balance Monitor 30 sec A

4.23 Group Measurement Supervision; Group Fuse Fail. Mon.

Group Measurement Supervision; Group Fuse Fail. Mon.


No. Settings Value Group

2910 Fuse Failure Monitor ON A


2911A Minimum Voltage Threshold U> 50 V A
2912A Maximum Current Threshold I< 0.20 A A
2913A Maximum Voltage Threshold U< (3phase) 10 V A
2914A Delta Current Threshold (3phase) 0.20 A A
2915 Voltage Failure Supervision with current supervision A
2916A Delay Voltage Failure Supervision 5.00 sec A

Page 15 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39
Group Measurement Supervision; Group VT mcb
NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

4.24 Group Measurement Supervision; Group VT mcb

Group Measurement Supervision; Group VT mcb


No. Settings Value Group

2921 VT mcb operating time 0 ms A

4.25 Group Measurement Supervision; Group Load Angle

Group Measurement Supervision; Group Load Angle


No. Settings Value Group

2941 Limit setting PhiA 200 ° A


2942 Limit setting PhiB 340 ° A
2943 Minimum value I1> 0.05 A A
2944 Minimum value U1> 20 V A

4.26 Group Earth fault overcurrent; Group General

Group Earth fault overcurrent; Group General


No. Settings Value Group

3101 Earth Fault overcurrent function ON A


3102 Block E/F for Distance protection with every Pickup A
3174 Block E/F for Distance Protection Pickup in each zone A
3103 Block E/F for 1pole Dead time YES A
3104A Stabilisation Slope with Iphase 10 % A
3109 Single pole trip with earth flt.prot. NO A
3170 2nd harmonic ratio for inrush restraint 10 % A

Page 16 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Group Earth fault overcurrent; Group General(2)


No. Settings Value Group

3171 Max.Current, overriding inrush restraint 7.50 A A


3172 Instantaneous mode after SwitchOnToFault with Pickup and direction A
3173 Trip time delay after SOTF 0.00 sec A

4.27 Group Earth fault overcurrent; Group 3I0>>>

Group Earth fault overcurrent; Group 3I0>>>


No. Settings Value Group

3110 Operating mode Inactive A


3111 3I0>>> Pickup 4.00 A A
3112 T 3I0>>> Time delay 0.30 sec A
3113 Instantaneous trip via Teleprot./BI NO A
3114 Instantaneous trip after SwitchOnToFault NO A
3115 Inrush Blocking NO A

4.28 Group Earth fault overcurrent; Group 3I0>>

Group Earth fault overcurrent; Group 3I0>>


No. Settings Value Group

3120 Operating mode Inactive A


3121 3I0>> Pickup 2.00 A A
3122 T 3I0>> Time Delay 0.60 sec A
3123 Instantaneous trip via Teleprot./BI NO A
3124 Instantaneous trip after SwitchOnToFault NO A

Page 17 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Group Earth fault overcurrent; Group 3I0>>(2)


No. Settings Value Group

3125 Inrush Blocking NO A

4.29 Group Earth fault overcurrent; Group 3I0>

Group Earth fault overcurrent; Group 3I0>


No. Settings Value Group

3130 Operating mode Inactive A


3131 3I0> Pickup 1.00 A A
3132 T 3I0> Time Delay 0.90 sec A
3133 Instantaneous trip via Teleprot./BI NO A
3134 Instantaneous trip after SwitchOnToFault NO A
3135 Inrush Blocking NO A

4.30 Group Earth fault overcurrent; Group 3I0 InverseTime

Group Earth fault overcurrent; Group 3I0 InverseTime


No. Settings Value Group

3140 Operating mode Forward A


3141 3I0p Pickup 0.30 A A
3143 3I0p Time Dial 0.35 sec A
3147 Additional Time Delay 0.00 sec A
3148 Instantaneous trip via Teleprot./BI NO A
3149 Instantaneous trip after SwitchOnToFault NO A
3150 Inrush Blocking NO A

Page 18 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Group Earth fault overcurrent; Group 3I0 InverseTime(2)


No. Settings Value Group

3151 IEC Curve Normal Inverse A

4.31 Group Earth fault overcurrent; Group Direction

Group Earth fault overcurrent; Group Direction


No. Settings Value Group

3160 Polarization with U2 and I2 (negative sequence) A


3162A ALPHA, lower angle for forward direction 338 ° A
3163A BETA, upper angle for forward direction 122 ° A
3164 Min. zero seq.voltage 3U0 for polarizing 2.0 V A
3166 Min. neg. seq. polarizing voltage 3U2 5.0 V A
3167 Min. neg. seq. polarizing current 3I2 0.10 A A
3168 Compensation angle PHI comp. for Sr 255 ° A
3169 Forward direction power threshold 0.3 VA A
3186A 3U0 min for forward direction 0.0 V A
3187A Reactance X of series capacitor 0.000 Ohm A

4.32 Group Voltage Protection; Group U> Phase-Earth

Group Voltage Protection; Group U> Phase-Earth


No. Settings Value Group

3701 Operating mode Uph-e overvoltage prot. ON A


3702 Uph-e> Pickup 69.3 V A
3703 T Uph-e> Time Delay 5.00 sec A

Page 19 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Group Voltage Protection; Group U> Phase-Earth(2)


No. Settings Value Group

3704 Uph-e>> Pickup 89.0 V A


3705 T Uph-e>> Time Delay 0.10 sec A
3709A Uph-e>(>) Reset ratio 0.99 A

4.33 Group Voltage Protection; Group U> Phase-Phase

Group Voltage Protection; Group U> Phase-Phase


No. Settings Value Group

3711 Operating mode Uph-ph overvoltage prot. OFF A


3712 Uph-ph> Pickup 150.0 V A
3713 T Uph-ph> Time Delay 2.00 sec A
3714 Uph-ph>> Pickup 175.0 V A
3715 T Uph-ph>> Time Delay 1.00 sec A
3719A Uph-ph>(>) Reset ratio 0.98 A

4.34 Group Voltage Protection; Group 3U0> or Ux>

Group Voltage Protection; Group 3U0> or Ux>


No. Settings Value Group

3721 Operating mode 3U0 (or Ux) overvoltage OFF A


3722 3U0> Pickup (or Ux>) 30.0 V A
3723 T 3U0> Time Delay (or T Ux>) 2.00 sec A
3724 3U0>> Pickup (or Ux>>) 50.0 V A
3725 T 3U0>> Time Delay (or T Ux>>) 1.00 sec A

Page 20 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Group Voltage Protection; Group 3U0> or Ux>(2)


No. Settings Value Group

3728A 3U0>(>): Stabilization 3U0-Measurement ON A


3729A 3U0>(>) Reset ratio (or Ux) 0.95 A

4.35 Group Voltage Protection; Group U> Postive Seq.

Group Voltage Protection; Group U> Postive Seq.


No. Settings Value Group

3731 Operating mode U1 overvoltage prot. OFF A


3732 U1> Pickup 150.0 V A
3733 T U1> Time Delay 2.00 sec A
3734 U1>> Pickup 175.0 V A
3735 T U1>> Time Delay 1.00 sec A
3739A U1>(>) Reset ratio 0.98 A

4.36 Group Voltage Protection; Group U> Negative Seq

Group Voltage Protection; Group U> Negative Seq


No. Settings Value Group

3741 Operating mode U2 overvoltage prot. OFF A


3742 U2> Pickup 30.0 V A
3743 T U2> Time Delay 2.00 sec A
3744 U2>> Pickup 50.0 V A
3745 T U2>> Time Delay 1.00 sec A
3749A U2>(>) Reset ratio 0.98 A

Page 21 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

4.37 Group Voltage Protection; Group U< Phase-Earth

Group Voltage Protection; Group U< Phase-Earth


No. Settings Value Group

3751 Operating mode Uph-e undervoltage prot. OFF A


3752 Uph-e< Pickup 30.0 V A
3753 T Uph-e< Time Delay 2.00 sec A
3754 Uph-e<< Pickup 10.0 V A
3755 T Uph-e<< Time Delay 1.00 sec A
3758 Current supervision (Uph-e) ON A
3759A Uph-e<(<) Reset ratio 1.05 A

4.38 Group Voltage Protection; Group U< Phase-Phase

Group Voltage Protection; Group U< Phase-Phase


No. Settings Value Group

3761 Operating mode Uph-ph undervoltage prot. OFF A


3762 Uph-ph< Pickup 50.0 V A
3763 T Uph-ph< Time Delay 2.00 sec A
3764 Uph-ph<< Pickup 17.0 V A
3765 T Uph-ph<< Time Delay 1.00 sec A
3768 Current supervision (Uph-ph) ON A
3769A Uph-ph<(<) Reset ratio 1.05 A

Page 22 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39
Group Voltage Protection; Group U< Postive Seq.
NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

4.39 Group Voltage Protection; Group U< Postive Seq.

Group Voltage Protection; Group U< Postive Seq.


No. Settings Value Group

3771 Operating mode U1 undervoltage prot. OFF A


3772 U1< Pickup 30.0 V A
3773 T U1< Time Delay 2.00 sec A
3774 U1<< Pickup 10.0 V A
3775 T U1<< Time Delay 1.00 sec A
3778 Current supervision (U1) ON A
3779A U1<(<) Reset ratio 1.05 A

4.40 Group Fault Locator; Group Fault Locator

Group Fault Locator; Group Fault Locator


No. Settings Value Group

3802 Start fault locator with TRIP A


3805 Mutual coupling parall.line compensation YES A
3806 Load Compensation YES A

Page 23 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39
Time Synchronization
NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

5 Time Synchronization

Source of time synchronization: Ethernet NTP


Fault indication after: 10 Min.
Time format for display German
Offset to time signal: 00:00
No daylight saving time switchover
Daylight saving time offset to GMT: +02:00
Start of daylight saving time: Last Sunday in March at 02:00 o'clock
End of daylight saving time: Last Sunday in October at 03:00 o'clock
Time zone offset to GMT: +05:30

Page 24 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39
Annunciation
NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

6 Annunciation

6.1 Event Log - 17-12-2016 11:33:17.679 (SIGNALS\BM000001.SFP)

Event Log - 17-12-2016 11:33:17.679 (SIGNALS\BM000001.SFP)


Number Indication Value Date and time Cause State

00060 Reset LED ON 17.12.2016 10:44:17.856 Spontaneous


Com.Issued=AutoLocal
Reset LED ON 17.12.2016 10:44:17.855 Spontaneous
Command Issued=Local
00060 Reset LED ON 17.12.2016 09:54:22.034 Spontaneous
Com.Issued=AutoLocal
Reset LED ON 17.12.2016 09:54:22.034 Spontaneous
Command Issued=Local
00060 Reset LED ON 17.12.2016 09:54:14.835 Spontaneous
Com.Issued=AutoLocal
Reset LED ON 17.12.2016 09:54:14.835 Spontaneous
Command Issued=Local
00381 >Single-phase trip permitted from ext.AR ON 16.12.2016 23:14:24.336 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P ON 16.12.2016 23:14:24.327 Spontaneous
00381 >Single-phase trip permitted from ext.AR OFF 16.12.2016 22:59:02.146 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P OFF 16.12.2016 22:59:02.141 Spontaneous
OVST1/2 OFF 16.12.2016 22:59:02.135 Spontaneous
M1_TRIP OFF 16.12.2016 22:59:02.115 Spontaneous
M1_TRIP ON 16.12.2016 22:59:02.108 Spontaneous
00301 Power System fault 249 - OFF 16.12.2016 22:59:02.105 Spontaneous
Com.Issued=AutoLocal
00301 Power System fault 249 - ON 16.12.2016 22:59:02.085 Spontaneous
Com.Issued=AutoLocal
M CB_BO ON 16.12.2016 22:59:02.069 Spontaneous
M CB_YO ON 16.12.2016 22:59:02.069 Spontaneous
M CB_RO ON 16.12.2016 22:59:02.069 Spontaneous

Page 25 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 17-12-2016 11:33:17.679 (SIGNALS\BM000001.SFP)(2)


Number Indication Value Date and time Cause State

00004 >Trigger Waveform Capture ON 16.12.2016 22:59:02.046 Spontaneous


Com.Issued=AutoLocal
OVST1/2 ON 16.12.2016 22:59:02.042 Spontaneous
00381 >Single-phase trip permitted from ext.AR ON 14.12.2016 20:10:04.696 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P ON 14.12.2016 20:10:04.688 Spontaneous
00590 Line closure detected OFF 14.12.2016 20:09:37.526 Spontaneous
Com.Issued=AutoLocal
01332 Earth fault protection is BLOCKED OFF 14.12.2016 20:09:37.366 Spontaneous
Com.Issued=AutoLocal
14083 E/F 3I0p is blocked OFF 14.12.2016 20:09:37.366 Spontaneous
Com.Issued=AutoLocal
M CB_YO OFF 14.12.2016 20:09:37.335 Spontaneous
00592 Single pole open detected in L2 OFF 14.12.2016 20:09:37.325 Spontaneous
Com.Issued=AutoLocal
00590 Line closure detected ON 14.12.2016 20:09:37.325 Spontaneous
Com.Issued=AutoLocal
DTRC1/2 OFF 14.12.2016 20:09:37.297 Spontaneous
00381 >Single-phase trip permitted from ext.AR OFF 14.12.2016 20:09:37.246 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P OFF 14.12.2016 20:09:37.244 Spontaneous
00004 >Trigger Waveform Capture ON 14.12.2016 20:09:37.206 Spontaneous
Com.Issued=AutoLocal
DTRC1/2 ON 14.12.2016 20:09:37.203 Spontaneous
M2_TRIP OFF 14.12.2016 20:09:36.339 Spontaneous
Com.Issued=AutoLocal
M1_TRIP OFF 14.12.2016 20:09:36.320 Spontaneous
01335 Earth fault protection Trip is blocked OFF 14.12.2016 20:09:36.308 Spontaneous
Com.Issued=AutoLocal
00301 Power System fault 247 - OFF 14.12.2016 20:09:36.302 Spontaneous
Com.Issued=AutoLocal
04010 >Dis.Tele. Carrier RECEPTION Channel 2 OFF 14.12.2016 20:09:36.298 Spontaneous
Com.Issued=AutoLocal

Page 26 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 17-12-2016 11:33:17.679 (SIGNALS\BM000001.SFP)(3)


Number Indication Value Date and time Cause State

04009 >Dis.Tele.Carrier RECEPTION Channel 1,L3 OFF 14.12.2016 20:09:36.298 Spontaneous


Com.Issued=AutoLocal
04008 >Dis.Tele.Carrier RECEPTION Channel 1,L2 OFF 14.12.2016 20:09:36.298 Spontaneous
Com.Issued=AutoLocal
04007 >Dis.Tele.Carrier RECEPTION Channel 1,L1 OFF 14.12.2016 20:09:36.298 Spontaneous
Com.Issued=AutoLocal
04006 >Dis.Tele. Carrier RECEPTION Channel 1 OFF 14.12.2016 20:09:36.298 Spontaneous
Com.Issued=AutoLocal
M/TCBAR OFF 14.12.2016 20:09:36.292 Spontaneous
01332 Earth fault protection is BLOCKED ON 14.12.2016 20:09:36.258 Spontaneous
Com.Issued=AutoLocal
14083 E/F 3I0p is blocked ON 14.12.2016 20:09:36.258 Spontaneous
Com.Issued=AutoLocal
00592 Single pole open detected in L2 ON 14.12.2016 20:09:36.252 Spontaneous
Com.Issued=AutoLocal
M CB_YO ON 14.12.2016 20:09:36.229 Spontaneous
M2_TRIP ON 14.12.2016 20:09:36.235 Spontaneous
Com.Issued=AutoLocal
04010 >Dis.Tele. Carrier RECEPTION Channel 2 ON 14.12.2016 20:09:36.235 Spontaneous
Com.Issued=AutoLocal
04009 >Dis.Tele.Carrier RECEPTION Channel 1,L3 ON 14.12.2016 20:09:36.235 Spontaneous
Com.Issued=AutoLocal
04008 >Dis.Tele.Carrier RECEPTION Channel 1,L2 ON 14.12.2016 20:09:36.235 Spontaneous
Com.Issued=AutoLocal
04007 >Dis.Tele.Carrier RECEPTION Channel 1,L1 ON 14.12.2016 20:09:36.235 Spontaneous
Com.Issued=AutoLocal
04006 >Dis.Tele. Carrier RECEPTION Channel 1 ON 14.12.2016 20:09:36.235 Spontaneous
Com.Issued=AutoLocal
00004 >Trigger Waveform Capture ON 14.12.2016 20:09:36.216 Spontaneous
Com.Issued=AutoLocal
M/TCBAR ON 14.12.2016 20:09:36.214 Spontaneous
M1_TRIP ON 14.12.2016 20:09:36.210 Spontaneous

Page 27 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 17-12-2016 11:33:17.679 (SIGNALS\BM000001.SFP)(4)


Number Indication Value Date and time Cause State

01335 Earth fault protection Trip is blocked ON 14.12.2016 20:09:36.208 Spontaneous


Com.Issued=AutoLocal
00301 Power System fault 247 - ON 14.12.2016 20:09:36.200 Spontaneous
Com.Issued=AutoLocal
00381 >Single-phase trip permitted from ext.AR ON 23.11.2016 16:34:17.666 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P ON 23.11.2016 16:34:17.662 Spontaneous
M CB_BO OFF 23.11.2016 16:14:15.369 Spontaneous
M CB_YO OFF 23.11.2016 16:14:15.369 Spontaneous
M CB_RO OFF 23.11.2016 16:14:15.369 Spontaneous
00004 >Trigger Waveform Capture ON 23.11.2016 14:18:16.506 Spontaneous
Com.Issued=AutoLocal
M CB_BO ON 23.11.2016 14:18:16.506 Spontaneous
M CB_RO ON 23.11.2016 14:18:16.506 Spontaneous
M CB_YO ON 23.11.2016 14:18:16.504 Spontaneous
00381 >Single-phase trip permitted from ext.AR OFF 23.11.2016 14:14:24.936 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P OFF 23.11.2016 14:14:24.927 Spontaneous
00070 Setting calculation is running OFF 15.10.2016 15:58:28.050 Spontaneous
Com.Issued=AutoLocal
00072 Level-2 change ON 15.10.2016 15:58:28.048 Spontaneous
Com.Issued=AutoLocal
00070 Setting calculation is running ON 15.10.2016 15:56:43.512 Spontaneous
Com.Issued=AutoLocal
00590 Line closure detected OFF 26.09.2016 03:36:53.380 Spontaneous
Com.Issued=AutoLocal
M CB_BO OFF 26.09.2016 03:36:53.180 Spontaneous
M CB_YO OFF 26.09.2016 03:36:53.180 Spontaneous
M CB_RO OFF 26.09.2016 03:36:53.180 Spontaneous
00590 Line closure detected ON 26.09.2016 03:36:53.180 Spontaneous
Com.Issued=AutoLocal
OVST1/2 OFF 26.09.2016 03:22:30.814 Spontaneous

Page 28 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 17-12-2016 11:33:17.679 (SIGNALS\BM000001.SFP)(5)


Number Indication Value Date and time Cause State

M1_TRIP OFF 26.09.2016 03:22:30.801 Spontaneous


M1_TRIP ON 26.09.2016 03:22:30.791 Spontaneous
00301 Power System fault 245 - OFF 26.09.2016 03:22:30.790 Spontaneous
Com.Issued=AutoLocal
00301 Power System fault 245 - ON 26.09.2016 03:22:30.770 Spontaneous
Com.Issued=AutoLocal
M CB_BO ON 26.09.2016 03:22:30.756 Spontaneous
M CB_YO ON 26.09.2016 03:22:30.756 Spontaneous
M CB_RO ON 26.09.2016 03:22:30.756 Spontaneous
00004 >Trigger Waveform Capture ON 26.09.2016 03:22:30.736 Spontaneous
Com.Issued=AutoLocal
OVST1/2 ON 26.09.2016 03:22:30.731 Spontaneous
00590 Line closure detected OFF 26.09.2016 02:31:40.793 Spontaneous
Com.Issued=AutoLocal
00004 >Trigger Waveform Capture ON 26.09.2016 02:31:40.626 Spontaneous
Com.Issued=AutoLocal
M1_TRIP OFF 26.09.2016 02:31:40.624 Spontaneous
M1_TRIP ON 26.09.2016 02:31:40.617 Spontaneous
00301 Power System fault 243 - OFF 26.09.2016 02:31:40.614 Spontaneous
Com.Issued=AutoLocal
M CB_BO OFF 26.09.2016 02:31:40.592 Spontaneous
M CB_YO OFF 26.09.2016 02:31:40.592 Spontaneous
M CB_RO OFF 26.09.2016 02:31:40.592 Spontaneous
00301 Power System fault 243 - ON 26.09.2016 02:31:40.594 Spontaneous
Com.Issued=AutoLocal
00590 Line closure detected ON 26.09.2016 02:31:40.592 Spontaneous
Com.Issued=AutoLocal
00381 >Single-phase trip permitted from ext.AR ON 26.09.2016 02:11:39.136 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P ON 26.09.2016 02:11:39.132 Spontaneous
00381 >Single-phase trip permitted from ext.AR OFF 26.09.2016 02:10:08.066 Spontaneous
Com.Issued=AutoLocal

Page 29 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 17-12-2016 11:33:17.679 (SIGNALS\BM000001.SFP)(6)


Number Indication Value Date and time Cause State

PREPARE 3P OFF 26.09.2016 02:10:08.062 Spontaneous


OVST1/2 OFF 26.09.2016 02:10:07.893 Spontaneous
M CB_BO ON 26.09.2016 02:10:07.832 Spontaneous
M CB_YO ON 26.09.2016 02:10:07.832 Spontaneous
M CB_RO ON 26.09.2016 02:10:07.832 Spontaneous
00004 >Trigger Waveform Capture ON 26.09.2016 02:10:07.816 Spontaneous
Com.Issued=AutoLocal
OVST1/2 ON 26.09.2016 02:10:07.807 Spontaneous
00590 Line closure detected OFF 26.09.2016 02:09:11.221 Spontaneous
Com.Issued=AutoLocal
M CB_BO OFF 26.09.2016 02:09:11.036 Spontaneous
M CB_YO OFF 26.09.2016 02:09:11.036 Spontaneous
M CB_RO OFF 26.09.2016 02:09:11.036 Spontaneous
00590 Line closure detected ON 26.09.2016 02:09:11.019 Spontaneous
Com.Issued=AutoLocal
00381 >Single-phase trip permitted from ext.AR ON 26.09.2016 02:00:53.506 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P ON 26.09.2016 02:00:53.499 Spontaneous
00381 >Single-phase trip permitted from ext.AR OFF 26.09.2016 01:58:10.956 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P OFF 26.09.2016 01:58:10.950 Spontaneous
OVST1/2 OFF 26.09.2016 01:58:10.854 Spontaneous
M1_TRIP OFF 26.09.2016 01:58:10.842 Spontaneous
M1_TRIP ON 26.09.2016 01:58:10.833 Spontaneous
00301 Power System fault 241 - OFF 26.09.2016 01:58:10.832 Spontaneous
Com.Issued=AutoLocal
00301 Power System fault 241 - ON 26.09.2016 01:58:10.811 Spontaneous
Com.Issued=AutoLocal
M CB_BO ON 26.09.2016 01:58:10.796 Spontaneous
M CB_YO ON 26.09.2016 01:58:10.796 Spontaneous
M CB_RO ON 26.09.2016 01:58:10.796 Spontaneous

Page 30 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 17-12-2016 11:33:17.679 (SIGNALS\BM000001.SFP)(7)


Number Indication Value Date and time Cause State

00004 >Trigger Waveform Capture ON 26.09.2016 01:58:10.777 Spontaneous


Com.Issued=AutoLocal
OVST1/2 ON 26.09.2016 01:58:10.770 Spontaneous
00590 Line closure detected OFF 25.09.2016 06:27:56.118 Spontaneous
Com.Issued=AutoLocal
M CB_BO OFF 25.09.2016 06:27:55.931 Spontaneous
M CB_YO OFF 25.09.2016 06:27:55.931 Spontaneous
M CB_RO OFF 25.09.2016 06:27:55.931 Spontaneous
00590 Line closure detected ON 25.09.2016 06:27:55.916 Spontaneous
Com.Issued=AutoLocal
OVST1/2 OFF 25.09.2016 01:35:01.074 Spontaneous
M1_TRIP OFF 25.09.2016 01:35:01.060 Spontaneous
M1_TRIP ON 25.09.2016 01:35:01.052 Spontaneous
00301 Power System fault 239 - OFF 25.09.2016 01:35:01.048 Spontaneous
Com.Issued=AutoLocal
00301 Power System fault 239 - ON 25.09.2016 01:35:01.028 Spontaneous
Com.Issued=AutoLocal
M CB_BO ON 25.09.2016 01:35:01.014 Spontaneous
M CB_YO ON 25.09.2016 01:35:01.014 Spontaneous
M CB_RO ON 25.09.2016 01:35:01.014 Spontaneous
00004 >Trigger Waveform Capture ON 25.09.2016 01:35:00.996 Spontaneous
Com.Issued=AutoLocal
OVST1/2 ON 25.09.2016 01:35:00.989 Spontaneous
00590 Line closure detected OFF 25.09.2016 01:21:00.528 Spontaneous
Com.Issued=AutoLocal
M CB_BO OFF 25.09.2016 01:21:00.342 Spontaneous
M CB_YO OFF 25.09.2016 01:21:00.342 Spontaneous
M CB_RO OFF 25.09.2016 01:21:00.342 Spontaneous
00590 Line closure detected ON 25.09.2016 01:21:00.326 Spontaneous
Com.Issued=AutoLocal
00381 >Single-phase trip permitted from ext.AR ON 25.09.2016 01:03:01.616 Spontaneous
Com.Issued=AutoLocal

Page 31 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 17-12-2016 11:33:17.679 (SIGNALS\BM000001.SFP)(8)


Number Indication Value Date and time Cause State

PREPARE 3P ON 25.09.2016 01:03:01.607 Spontaneous


00381 >Single-phase trip permitted from ext.AR OFF 25.09.2016 01:01:11.426 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P OFF 25.09.2016 01:01:11.418 Spontaneous
OVST1/2 OFF 25.09.2016 01:01:11.265 Spontaneous
M1_TRIP OFF 25.09.2016 01:01:11.254 Spontaneous
M1_TRIP ON 25.09.2016 01:01:11.246 Spontaneous
00301 Power System fault 237 - OFF 25.09.2016 01:01:11.244 Spontaneous
Com.Issued=AutoLocal
00301 Power System fault 237 - ON 25.09.2016 01:01:11.223 Spontaneous
Com.Issued=AutoLocal
M CB_BO ON 25.09.2016 01:01:11.206 Spontaneous
M CB_YO ON 25.09.2016 01:01:11.206 Spontaneous
M CB_RO ON 25.09.2016 01:01:11.206 Spontaneous
00004 >Trigger Waveform Capture ON 25.09.2016 01:01:11.186 Spontaneous
Com.Issued=AutoLocal
OVST1/2 ON 25.09.2016 01:01:11.180 Spontaneous
00060 Reset LED ON 25.07.2016 10:04:02.946 Spontaneous
Com.Issued=AutoLocal
Reset LED ON 25.07.2016 10:04:02.946 Spontaneous
Command Issued=Local
M CB_BO OFF 13.07.2016 12:48:21.377 Spontaneous
M CB_YO OFF 13.07.2016 12:48:21.377 Spontaneous
M CB_RO OFF 13.07.2016 12:48:21.377 Spontaneous
00004 >Trigger Waveform Capture ON 13.07.2016 12:48:21.367 Spontaneous
Com.Issued=AutoLocal
M CB_BO ON 13.07.2016 12:48:21.365 Spontaneous
M CB_RO ON 13.07.2016 12:48:21.365 Spontaneous
M CB_YO ON 13.07.2016 12:48:21.363 Spontaneous
M CB_BO OFF 13.07.2016 12:48:09.340 Spontaneous
M CB_YO OFF 13.07.2016 12:48:09.340 Spontaneous
M CB_RO OFF 13.07.2016 12:48:09.340 Spontaneous

Page 32 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 17-12-2016 11:33:17.679 (SIGNALS\BM000001.SFP)(9)


Number Indication Value Date and time Cause State

00004 >Trigger Waveform Capture ON 13.07.2016 12:48:09.238 Spontaneous


Com.Issued=AutoLocal
M CB_BO ON 13.07.2016 12:48:09.235 Spontaneous
M CB_YO ON 13.07.2016 12:48:09.235 Spontaneous
M CB_RO ON 13.07.2016 12:48:09.235 Spontaneous
M CB_BO OFF 13.07.2016 12:48:09.229 Spontaneous
M CB_YO OFF 13.07.2016 12:48:09.229 Spontaneous
M CB_RO OFF 13.07.2016 12:48:09.229 Spontaneous
00004 >Trigger Waveform Capture ON 13.07.2016 12:48:09.207 Spontaneous
Com.Issued=AutoLocal
M CB_BO ON 13.07.2016 12:48:09.201 Spontaneous
M CB_YO ON 13.07.2016 12:48:09.201 Spontaneous
M CB_RO ON 13.07.2016 12:48:09.201 Spontaneous
M CB_BO OFF 13.07.2016 12:48:08.073 Spontaneous
M CB_YO OFF 13.07.2016 12:48:08.073 Spontaneous
M CB_RO OFF 13.07.2016 12:48:08.073 Spontaneous
00004 >Trigger Waveform Capture ON 13.07.2016 12:48:08.007 Spontaneous
Com.Issued=AutoLocal
M CB_BO ON 13.07.2016 12:48:08.004 Spontaneous
M CB_RO ON 13.07.2016 12:48:08.004 Spontaneous
M CB_YO ON 13.07.2016 12:48:08.003 Spontaneous
00004 >Trigger Waveform Capture ON 11.07.2016 13:57:51.326 Spontaneous
Com.Issued=AutoLocal
T CB_BO OFF 11.07.2016 13:57:51.322 Spontaneous
T CB_BO ON 11.07.2016 13:57:51.318 Spontaneous
00004 >Trigger Waveform Capture ON 11.07.2016 13:57:44.726 Spontaneous
Com.Issued=AutoLocal
T CB_BO OFF 11.07.2016 13:57:44.723 Spontaneous
T CB_BO ON 11.07.2016 13:57:44.719 Spontaneous
T CB_BO OFF 11.07.2016 13:57:44.523 Spontaneous
00004 >Trigger Waveform Capture ON 11.07.2016 13:57:44.506 Spontaneous
Com.Issued=AutoLocal

Page 33 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 17-12-2016 11:33:17.679 (SIGNALS\BM000001.SFP)(10)


Number Indication Value Date and time Cause State

T CB_BO ON 11.07.2016 13:57:44.504 Spontaneous


00004 >Trigger Waveform Capture ON 11.07.2016 13:57:44.316 Spontaneous
Com.Issued=AutoLocal

6.2 Event Log - 21-12-2016 11:00:28.604 (SIGNALS\BM000002.SFP)

Event Log - 21-12-2016 11:00:28.604 (SIGNALS\BM000002.SFP)


Number Indication Value Date and time Cause State

00381 >Single-phase trip permitted from ext.AR ON 21.12.2016 01:12:19.336 Spontaneous


Com.Issued=AutoLocal
PREPARE 3P ON 21.12.2016 01:12:19.331 Spontaneous
00381 >Single-phase trip permitted from ext.AR OFF 21.12.2016 01:09:46.486 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P OFF 21.12.2016 01:09:46.483 Spontaneous
OVST1/2 OFF 21.12.2016 01:09:46.378 Spontaneous
M1_TRIP OFF 21.12.2016 01:09:46.366 Spontaneous
M1_TRIP ON 21.12.2016 01:09:46.358 Spontaneous
00301 Power System fault 258 - OFF 21.12.2016 01:09:46.355 Spontaneous
Com.Issued=AutoLocal
00301 Power System fault 258 - ON 21.12.2016 01:09:46.334 Spontaneous
Com.Issued=AutoLocal
M CB_BO ON 21.12.2016 01:09:46.319 Spontaneous
M CB_YO ON 21.12.2016 01:09:46.319 Spontaneous
M CB_RO ON 21.12.2016 01:09:46.319 Spontaneous
00004 >Trigger Waveform Capture ON 21.12.2016 01:09:46.296 Spontaneous
Com.Issued=AutoLocal
OVST1/2 ON 21.12.2016 01:09:46.294 Spontaneous
M CB_BO OFF 20.12.2016 11:07:44.933 Spontaneous
M CB_YO OFF 20.12.2016 11:07:44.933 Spontaneous
M CB_RO OFF 20.12.2016 11:07:44.933 Spontaneous

Page 34 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 21-12-2016 11:00:28.604 (SIGNALS\BM000002.SFP)(2)


Number Indication Value Date and time Cause State

00381 >Single-phase trip permitted from ext.AR ON 20.12.2016 02:14:59.306 Spontaneous


Com.Issued=AutoLocal
PREPARE 3P ON 20.12.2016 02:14:59.297 Spontaneous
OVST1/2 OFF 20.12.2016 02:06:16.566 Spontaneous
M1_TRIP OFF 20.12.2016 02:06:16.516 Spontaneous
00301 Power System fault 256 - OFF 20.12.2016 02:06:16.503 Spontaneous
Com.Issued=AutoLocal
M2_TRIP OFF 20.12.2016 02:06:16.503 Spontaneous
Com.Issued=AutoLocal
M/TCBAR OFF 20.12.2016 02:06:16.494 Spontaneous
OVST1/2 ON 20.12.2016 02:06:16.480 Spontaneous
00381 >Single-phase trip permitted from ext.AR OFF 20.12.2016 02:06:15.506 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P OFF 20.12.2016 02:06:15.502 Spontaneous
M/TCBAR ON 20.12.2016 02:06:15.444 Spontaneous
M2_TRIP ON 20.12.2016 02:06:15.439 Spontaneous
Com.Issued=AutoLocal
00004 >Trigger Waveform Capture ON 20.12.2016 02:06:11.467 Spontaneous
Com.Issued=AutoLocal
M1_TRIP ON 20.12.2016 02:06:11.464 Spontaneous
00301 Power System fault 256 - ON 20.12.2016 02:06:11.441 Spontaneous
Com.Issued=AutoLocal
00381 >Single-phase trip permitted from ext.AR ON 20.12.2016 02:03:26.677 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P ON 20.12.2016 02:03:26.668 Spontaneous
OVST1/2 OFF 20.12.2016 02:01:30.738 Spontaneous
M1_TRIP OFF 20.12.2016 02:01:30.686 Spontaneous
M/TCBAR OFF 20.12.2016 02:01:30.669 Spontaneous
00301 Power System fault 255 - OFF 20.12.2016 02:01:30.675 Spontaneous
Com.Issued=AutoLocal
M2_TRIP OFF 20.12.2016 02:01:30.675 Spontaneous
Com.Issued=AutoLocal

Page 35 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 21-12-2016 11:00:28.604 (SIGNALS\BM000002.SFP)(3)


Number Indication Value Date and time Cause State

OVST1/2 ON 20.12.2016 02:01:30.655 Spontaneous


00381 >Single-phase trip permitted from ext.AR OFF 20.12.2016 02:01:29.676 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P OFF 20.12.2016 02:01:29.676 Spontaneous
M/TCBAR ON 20.12.2016 02:01:29.621 Spontaneous
M2_TRIP ON 20.12.2016 02:01:29.615 Spontaneous
Com.Issued=AutoLocal
00004 >Trigger Waveform Capture ON 20.12.2016 02:01:25.646 Spontaneous
Com.Issued=AutoLocal
M1_TRIP ON 20.12.2016 02:01:25.638 Spontaneous
00301 Power System fault 255 - ON 20.12.2016 02:01:25.615 Spontaneous
Com.Issued=AutoLocal
00381 >Single-phase trip permitted from ext.AR ON 19.12.2016 23:16:21.066 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P ON 19.12.2016 23:16:21.058 Spontaneous
00381 >Single-phase trip permitted from ext.AR OFF 19.12.2016 22:58:43.246 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P OFF 19.12.2016 22:58:43.238 Spontaneous
OVST1/2 OFF 19.12.2016 22:58:43.233 Spontaneous
M CB_BO ON 19.12.2016 22:58:43.168 Spontaneous
M CB_YO ON 19.12.2016 22:58:43.168 Spontaneous
M CB_RO ON 19.12.2016 22:58:43.168 Spontaneous
00004 >Trigger Waveform Capture ON 19.12.2016 22:58:43.146 Spontaneous
Com.Issued=AutoLocal
OVST1/2 ON 19.12.2016 22:58:43.143 Spontaneous
M CB_BO OFF 19.12.2016 09:12:00.475 Spontaneous
M CB_YO OFF 19.12.2016 09:12:00.475 Spontaneous
M CB_RO OFF 19.12.2016 09:12:00.475 Spontaneous
00381 >Single-phase trip permitted from ext.AR ON 18.12.2016 22:02:05.986 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P ON 18.12.2016 22:02:05.982 Spontaneous
OVST1/2 OFF 18.12.2016 21:58:32.247 Spontaneous

Page 36 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 21-12-2016 11:00:28.604 (SIGNALS\BM000002.SFP)(4)


Number Indication Value Date and time Cause State

00381 >Single-phase trip permitted from ext.AR OFF 18.12.2016 21:58:32.246 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P OFF 18.12.2016 21:58:32.243 Spontaneous
M1_TRIP OFF 18.12.2016 21:58:32.229 Spontaneous
M1_TRIP ON 18.12.2016 21:58:32.220 Spontaneous
00301 Power System fault 253 - OFF 18.12.2016 21:58:32.219 Spontaneous
Com.Issued=AutoLocal
00301 Power System fault 253 - ON 18.12.2016 21:58:32.199 Spontaneous
Com.Issued=AutoLocal
M CB_BO ON 18.12.2016 21:58:32.183 Spontaneous
M CB_YO ON 18.12.2016 21:58:32.183 Spontaneous
M CB_RO ON 18.12.2016 21:58:32.183 Spontaneous
00004 >Trigger Waveform Capture ON 18.12.2016 21:58:32.166 Spontaneous
Com.Issued=AutoLocal
OVST1/2 ON 18.12.2016 21:58:32.157 Spontaneous
00590 Line closure detected OFF 18.12.2016 08:29:12.292 Spontaneous
Com.Issued=AutoLocal
M CB_BO OFF 18.12.2016 08:29:12.094 Spontaneous
M CB_YO OFF 18.12.2016 08:29:12.094 Spontaneous
M CB_RO OFF 18.12.2016 08:29:12.094 Spontaneous
00590 Line closure detected ON 18.12.2016 08:29:12.092 Spontaneous
Com.Issued=AutoLocal
00381 >Single-phase trip permitted from ext.AR ON 17.12.2016 22:08:07.276 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P ON 17.12.2016 22:08:07.268 Spontaneous
00381 >Single-phase trip permitted from ext.AR OFF 17.12.2016 22:01:31.996 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P OFF 17.12.2016 22:01:31.994 Spontaneous
OVST1/2 OFF 17.12.2016 22:01:31.991 Spontaneous
M1_TRIP OFF 17.12.2016 22:01:31.976 Spontaneous
M1_TRIP ON 17.12.2016 22:01:31.968 Spontaneous

Page 37 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 21-12-2016 11:00:28.604 (SIGNALS\BM000002.SFP)(5)


Number Indication Value Date and time Cause State

00301 Power System fault 251 - OFF 17.12.2016 22:01:31.965 Spontaneous


Com.Issued=AutoLocal
00301 Power System fault 251 - ON 17.12.2016 22:01:31.944 Spontaneous
Com.Issued=AutoLocal
M CB_BO ON 17.12.2016 22:01:31.928 Spontaneous
M CB_YO ON 17.12.2016 22:01:31.928 Spontaneous
M CB_RO ON 17.12.2016 22:01:31.928 Spontaneous
00004 >Trigger Waveform Capture ON 17.12.2016 22:01:31.906 Spontaneous
Com.Issued=AutoLocal
OVST1/2 ON 17.12.2016 22:01:31.902 Spontaneous
M CB_BO OFF 17.12.2016 12:56:02.961 Spontaneous
M CB_YO OFF 17.12.2016 12:56:02.961 Spontaneous
M CB_RO OFF 17.12.2016 12:56:02.961 Spontaneous
00060 Reset LED ON 17.12.2016 11:19:06.282 Spontaneous
Com.Issued=AutoLocal
Reset LED ON 17.12.2016 11:19:06.281 Spontaneous
Command Issued=Local
00060 Reset LED ON 17.12.2016 10:44:17.856 Spontaneous
Com.Issued=AutoLocal
Reset LED ON 17.12.2016 10:44:17.855 Spontaneous
Command Issued=Local
00060 Reset LED ON 17.12.2016 09:54:22.034 Spontaneous
Com.Issued=AutoLocal
Reset LED ON 17.12.2016 09:54:22.034 Spontaneous
Command Issued=Local
00060 Reset LED ON 17.12.2016 09:54:14.835 Spontaneous
Com.Issued=AutoLocal
Reset LED ON 17.12.2016 09:54:14.835 Spontaneous
Command Issued=Local
00381 >Single-phase trip permitted from ext.AR ON 16.12.2016 23:14:24.336 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P ON 16.12.2016 23:14:24.327 Spontaneous

Page 38 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 21-12-2016 11:00:28.604 (SIGNALS\BM000002.SFP)(6)


Number Indication Value Date and time Cause State

00381 >Single-phase trip permitted from ext.AR OFF 16.12.2016 22:59:02.146 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P OFF 16.12.2016 22:59:02.141 Spontaneous
OVST1/2 OFF 16.12.2016 22:59:02.135 Spontaneous
M1_TRIP OFF 16.12.2016 22:59:02.115 Spontaneous
M1_TRIP ON 16.12.2016 22:59:02.108 Spontaneous
00301 Power System fault 249 - OFF 16.12.2016 22:59:02.105 Spontaneous
Com.Issued=AutoLocal
00301 Power System fault 249 - ON 16.12.2016 22:59:02.085 Spontaneous
Com.Issued=AutoLocal
M CB_BO ON 16.12.2016 22:59:02.069 Spontaneous
M CB_YO ON 16.12.2016 22:59:02.069 Spontaneous
M CB_RO ON 16.12.2016 22:59:02.069 Spontaneous
00004 >Trigger Waveform Capture ON 16.12.2016 22:59:02.046 Spontaneous
Com.Issued=AutoLocal
OVST1/2 ON 16.12.2016 22:59:02.042 Spontaneous
00381 >Single-phase trip permitted from ext.AR ON 14.12.2016 20:10:04.696 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P ON 14.12.2016 20:10:04.688 Spontaneous
00590 Line closure detected OFF 14.12.2016 20:09:37.526 Spontaneous
Com.Issued=AutoLocal
01332 Earth fault protection is BLOCKED OFF 14.12.2016 20:09:37.366 Spontaneous
Com.Issued=AutoLocal
14083 E/F 3I0p is blocked OFF 14.12.2016 20:09:37.366 Spontaneous
Com.Issued=AutoLocal
M CB_YO OFF 14.12.2016 20:09:37.335 Spontaneous
00592 Single pole open detected in L2 OFF 14.12.2016 20:09:37.325 Spontaneous
Com.Issued=AutoLocal
00590 Line closure detected ON 14.12.2016 20:09:37.325 Spontaneous
Com.Issued=AutoLocal
DTRC1/2 OFF 14.12.2016 20:09:37.297 Spontaneous
00381 >Single-phase trip permitted from ext.AR OFF 14.12.2016 20:09:37.246 Spontaneous
Com.Issued=AutoLocal

Page 39 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 21-12-2016 11:00:28.604 (SIGNALS\BM000002.SFP)(7)


Number Indication Value Date and time Cause State

PREPARE 3P OFF 14.12.2016 20:09:37.244 Spontaneous


00004 >Trigger Waveform Capture ON 14.12.2016 20:09:37.206 Spontaneous
Com.Issued=AutoLocal
DTRC1/2 ON 14.12.2016 20:09:37.203 Spontaneous
M2_TRIP OFF 14.12.2016 20:09:36.339 Spontaneous
Com.Issued=AutoLocal
M1_TRIP OFF 14.12.2016 20:09:36.320 Spontaneous
01335 Earth fault protection Trip is blocked OFF 14.12.2016 20:09:36.308 Spontaneous
Com.Issued=AutoLocal
00301 Power System fault 247 - OFF 14.12.2016 20:09:36.302 Spontaneous
Com.Issued=AutoLocal
04010 >Dis.Tele. Carrier RECEPTION Channel 2 OFF 14.12.2016 20:09:36.298 Spontaneous
Com.Issued=AutoLocal
04009 >Dis.Tele.Carrier RECEPTION Channel 1,L3 OFF 14.12.2016 20:09:36.298 Spontaneous
Com.Issued=AutoLocal
04008 >Dis.Tele.Carrier RECEPTION Channel 1,L2 OFF 14.12.2016 20:09:36.298 Spontaneous
Com.Issued=AutoLocal
04007 >Dis.Tele.Carrier RECEPTION Channel 1,L1 OFF 14.12.2016 20:09:36.298 Spontaneous
Com.Issued=AutoLocal
04006 >Dis.Tele. Carrier RECEPTION Channel 1 OFF 14.12.2016 20:09:36.298 Spontaneous
Com.Issued=AutoLocal
M/TCBAR OFF 14.12.2016 20:09:36.292 Spontaneous
01332 Earth fault protection is BLOCKED ON 14.12.2016 20:09:36.258 Spontaneous
Com.Issued=AutoLocal
14083 E/F 3I0p is blocked ON 14.12.2016 20:09:36.258 Spontaneous
Com.Issued=AutoLocal
00592 Single pole open detected in L2 ON 14.12.2016 20:09:36.252 Spontaneous
Com.Issued=AutoLocal
M CB_YO ON 14.12.2016 20:09:36.229 Spontaneous
M2_TRIP ON 14.12.2016 20:09:36.235 Spontaneous
Com.Issued=AutoLocal
04010 >Dis.Tele. Carrier RECEPTION Channel 2 ON 14.12.2016 20:09:36.235 Spontaneous
Com.Issued=AutoLocal

Page 40 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 21-12-2016 11:00:28.604 (SIGNALS\BM000002.SFP)(8)


Number Indication Value Date and time Cause State

04009 >Dis.Tele.Carrier RECEPTION Channel 1,L3 ON 14.12.2016 20:09:36.235 Spontaneous


Com.Issued=AutoLocal
04008 >Dis.Tele.Carrier RECEPTION Channel 1,L2 ON 14.12.2016 20:09:36.235 Spontaneous
Com.Issued=AutoLocal
04007 >Dis.Tele.Carrier RECEPTION Channel 1,L1 ON 14.12.2016 20:09:36.235 Spontaneous
Com.Issued=AutoLocal
04006 >Dis.Tele. Carrier RECEPTION Channel 1 ON 14.12.2016 20:09:36.235 Spontaneous
Com.Issued=AutoLocal
00004 >Trigger Waveform Capture ON 14.12.2016 20:09:36.216 Spontaneous
Com.Issued=AutoLocal
M/TCBAR ON 14.12.2016 20:09:36.214 Spontaneous
M1_TRIP ON 14.12.2016 20:09:36.210 Spontaneous
01335 Earth fault protection Trip is blocked ON 14.12.2016 20:09:36.208 Spontaneous
Com.Issued=AutoLocal
00301 Power System fault 247 - ON 14.12.2016 20:09:36.200 Spontaneous
Com.Issued=AutoLocal
00381 >Single-phase trip permitted from ext.AR ON 23.11.2016 16:34:17.666 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P ON 23.11.2016 16:34:17.662 Spontaneous
M CB_BO OFF 23.11.2016 16:14:15.369 Spontaneous
M CB_YO OFF 23.11.2016 16:14:15.369 Spontaneous
M CB_RO OFF 23.11.2016 16:14:15.369 Spontaneous
00004 >Trigger Waveform Capture ON 23.11.2016 14:18:16.506 Spontaneous
Com.Issued=AutoLocal
M CB_BO ON 23.11.2016 14:18:16.506 Spontaneous
M CB_RO ON 23.11.2016 14:18:16.506 Spontaneous
M CB_YO ON 23.11.2016 14:18:16.504 Spontaneous
00381 >Single-phase trip permitted from ext.AR OFF 23.11.2016 14:14:24.936 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P OFF 23.11.2016 14:14:24.927 Spontaneous
00070 Setting calculation is running OFF 15.10.2016 15:58:28.050 Spontaneous
Com.Issued=AutoLocal

Page 41 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 21-12-2016 11:00:28.604 (SIGNALS\BM000002.SFP)(9)


Number Indication Value Date and time Cause State

00072 Level-2 change ON 15.10.2016 15:58:28.048 Spontaneous


Com.Issued=AutoLocal
00070 Setting calculation is running ON 15.10.2016 15:56:43.512 Spontaneous
Com.Issued=AutoLocal
00590 Line closure detected OFF 26.09.2016 03:36:53.380 Spontaneous
Com.Issued=AutoLocal
M CB_BO OFF 26.09.2016 03:36:53.180 Spontaneous
M CB_YO OFF 26.09.2016 03:36:53.180 Spontaneous
M CB_RO OFF 26.09.2016 03:36:53.180 Spontaneous
00590 Line closure detected ON 26.09.2016 03:36:53.180 Spontaneous
Com.Issued=AutoLocal
OVST1/2 OFF 26.09.2016 03:22:30.814 Spontaneous
M1_TRIP OFF 26.09.2016 03:22:30.801 Spontaneous
M1_TRIP ON 26.09.2016 03:22:30.791 Spontaneous
00301 Power System fault 245 - OFF 26.09.2016 03:22:30.790 Spontaneous
Com.Issued=AutoLocal
00301 Power System fault 245 - ON 26.09.2016 03:22:30.770 Spontaneous
Com.Issued=AutoLocal
M CB_BO ON 26.09.2016 03:22:30.756 Spontaneous
M CB_YO ON 26.09.2016 03:22:30.756 Spontaneous
M CB_RO ON 26.09.2016 03:22:30.756 Spontaneous
00004 >Trigger Waveform Capture ON 26.09.2016 03:22:30.736 Spontaneous
Com.Issued=AutoLocal
OVST1/2 ON 26.09.2016 03:22:30.731 Spontaneous
00590 Line closure detected OFF 26.09.2016 02:31:40.793 Spontaneous
Com.Issued=AutoLocal
00004 >Trigger Waveform Capture ON 26.09.2016 02:31:40.626 Spontaneous
Com.Issued=AutoLocal
M1_TRIP OFF 26.09.2016 02:31:40.624 Spontaneous
M1_TRIP ON 26.09.2016 02:31:40.617 Spontaneous
00301 Power System fault 243 - OFF 26.09.2016 02:31:40.614 Spontaneous
Com.Issued=AutoLocal

Page 42 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 21-12-2016 11:00:28.604 (SIGNALS\BM000002.SFP)(10)


Number Indication Value Date and time Cause State

M CB_BO OFF 26.09.2016 02:31:40.592 Spontaneous


M CB_YO OFF 26.09.2016 02:31:40.592 Spontaneous
M CB_RO OFF 26.09.2016 02:31:40.592 Spontaneous
00301 Power System fault 243 - ON 26.09.2016 02:31:40.594 Spontaneous
Com.Issued=AutoLocal
00590 Line closure detected ON 26.09.2016 02:31:40.592 Spontaneous
Com.Issued=AutoLocal
00381 >Single-phase trip permitted from ext.AR ON 26.09.2016 02:11:39.136 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P ON 26.09.2016 02:11:39.132 Spontaneous
00381 >Single-phase trip permitted from ext.AR OFF 26.09.2016 02:10:08.066 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P OFF 26.09.2016 02:10:08.062 Spontaneous
OVST1/2 OFF 26.09.2016 02:10:07.893 Spontaneous

6.3 Event Log - 03-10-2017 16:09:19.332 (SIGNALS\BM000003.SFP)

Event Log - 03-10-2017 16:09:19.332 (SIGNALS\BM000003.SFP)


Number Indication Value Date and time Cause State

00060 Reset LED ON 03.10.2017 12:48:56.714 Spontaneous


Com.Issued=AutoLocal
Reset LED ON 03.10.2017 12:48:56.714 Spontaneous
Command Issued=Local
M1_TRIP OFF 01.10.2017 20:52:38.826 Spontaneous
M CB_BO OFF 01.10.2017 20:52:38.809 Spontaneous
M CB_YO OFF 01.10.2017 20:52:38.809 Spontaneous
M CB_RO OFF 01.10.2017 20:52:38.809 Spontaneous
00301 Power System fault 303 - OFF 01.10.2017 20:52:38.815 Spontaneous
Com.Issued=AutoLocal
00004 >Trigger Waveform Capture ON 01.10.2017 20:52:35.787 Spontaneous
Com.Issued=AutoLocal

Page 43 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 03-10-2017 16:09:19.332 (SIGNALS\BM000003.SFP)(2)


Number Indication Value Date and time Cause State

M1_TRIP ON 01.10.2017 20:52:35.782 Spontaneous


00301 Power System fault 303 - ON 01.10.2017 20:52:35.760 Spontaneous
Com.Issued=AutoLocal
00381 >Single-phase trip permitted from ext.AR ON 01.10.2017 20:26:25.867 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P ON 01.10.2017 20:26:25.858 Spontaneous
DTRC1/2 OFF 01.10.2017 20:24:07.987 Spontaneous
M1_TRIP OFF 01.10.2017 20:24:07.934 Spontaneous
00301 Power System fault 302 - OFF 01.10.2017 20:24:07.921 Spontaneous
Com.Issued=AutoLocal
M2_TRIP OFF 01.10.2017 20:24:07.921 Spontaneous
Com.Issued=AutoLocal
DTRC1/2 ON 01.10.2017 20:24:07.903 Spontaneous
M1_TRIP ON 01.10.2017 20:24:07.030 Spontaneous
00301 Power System fault 302 - ON 01.10.2017 20:24:07.007 Spontaneous
Com.Issued=AutoLocal
M1_TRIP OFF 01.10.2017 20:24:06.978 Spontaneous
M CB_RO ON 01.10.2017 20:24:06.977 Spontaneous
M CB_YO ON 01.10.2017 20:24:06.975 Spontaneous
00301 Power System fault 301 - OFF 01.10.2017 20:24:06.969 Spontaneous
Com.Issued=AutoLocal
M CB_BO ON 01.10.2017 20:24:06.969 Spontaneous
M CB_BO OFF 01.10.2017 20:24:06.961 Spontaneous
M CB_YO OFF 01.10.2017 20:24:06.961 Spontaneous
M CB_RO OFF 01.10.2017 20:24:06.961 Spontaneous
M/TCBAR OFF 01.10.2017 20:24:06.953 Spontaneous
00381 >Single-phase trip permitted from ext.AR OFF 01.10.2017 20:24:06.937 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P OFF 01.10.2017 20:24:06.928 Spontaneous
M/TCBAR ON 01.10.2017 20:24:06.869 Spontaneous
M2_TRIP ON 01.10.2017 20:24:06.865 Spontaneous
Com.Issued=AutoLocal

Page 44 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 03-10-2017 16:09:19.332 (SIGNALS\BM000003.SFP)(3)


Number Indication Value Date and time Cause State

00004 >Trigger Waveform Capture ON 01.10.2017 20:24:01.897 Spontaneous


Com.Issued=AutoLocal
M1_TRIP ON 01.10.2017 20:24:01.891 Spontaneous
00301 Power System fault 301 - ON 01.10.2017 20:24:01.867 Spontaneous
Com.Issued=AutoLocal
00381 >Single-phase trip permitted from ext.AR ON 01.10.2017 19:35:57.168 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P ON 01.10.2017 19:35:57.167 Spontaneous
00381 >Single-phase trip permitted from ext.AR OFF 01.10.2017 19:34:25.177 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P OFF 01.10.2017 19:34:25.176 Spontaneous
DTRC1/2 OFF 01.10.2017 19:34:25.010 Spontaneous
M1_TRIP OFF 01.10.2017 19:34:24.999 Spontaneous
M1_TRIP ON 01.10.2017 19:34:24.990 Spontaneous
00301 Power System fault 300 - OFF 01.10.2017 19:34:24.988 Spontaneous
Com.Issued=AutoLocal
00301 Power System fault 300 - ON 01.10.2017 19:34:24.968 Spontaneous
Com.Issued=AutoLocal
M CB_BO ON 01.10.2017 19:34:24.952 Spontaneous
M CB_YO ON 01.10.2017 19:34:24.952 Spontaneous
M CB_RO ON 01.10.2017 19:34:24.952 Spontaneous
00004 >Trigger Waveform Capture ON 01.10.2017 19:34:24.927 Spontaneous
Com.Issued=AutoLocal
DTRC1/2 ON 01.10.2017 19:34:24.926 Spontaneous
M1_TRIP OFF 23.09.2017 22:35:33.194 Spontaneous
00301 Power System fault 297 - OFF 23.09.2017 22:35:33.183 Spontaneous
Com.Issued=AutoLocal
00004 >Trigger Waveform Capture ON 23.09.2017 22:35:33.178 Spontaneous
Com.Issued=AutoLocal
M1_TRIP ON 23.09.2017 22:35:33.178 Spontaneous
00301 Power System fault 297 - ON 23.09.2017 22:35:33.153 Spontaneous
Com.Issued=AutoLocal

Page 45 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 03-10-2017 16:09:19.332 (SIGNALS\BM000003.SFP)(4)


Number Indication Value Date and time Cause State

M CB_BO OFF 18.09.2017 14:57:34.592 Spontaneous


M CB_YO OFF 18.09.2017 14:57:34.592 Spontaneous
M CB_RO OFF 18.09.2017 14:57:34.592 Spontaneous
00381 >Single-phase trip permitted from ext.AR ON 18.09.2017 14:44:31.367 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P ON 18.09.2017 14:44:31.359 Spontaneous
DTRC1/2 OFF 17.09.2017 02:06:02.093 Spontaneous
M1_TRIP OFF 17.09.2017 02:06:02.083 Spontaneous
M1_TRIP ON 17.09.2017 02:06:02.074 Spontaneous
00301 Power System fault 296 - OFF 17.09.2017 02:06:02.073 Spontaneous
Com.Issued=AutoLocal
00381 >Single-phase trip permitted from ext.AR OFF 17.09.2017 02:06:02.068 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P OFF 17.09.2017 02:06:02.065 Spontaneous
00301 Power System fault 296 - ON 17.09.2017 02:06:02.052 Spontaneous
Com.Issued=AutoLocal
M CB_BO ON 17.09.2017 02:06:02.034 Spontaneous
M CB_YO ON 17.09.2017 02:06:02.034 Spontaneous
M CB_RO ON 17.09.2017 02:06:02.034 Spontaneous
00004 >Trigger Waveform Capture ON 17.09.2017 02:06:02.018 Spontaneous
Com.Issued=AutoLocal
DTRC1/2 ON 17.09.2017 02:06:02.008 Spontaneous
00590 Line closure detected OFF 16.09.2017 07:54:36.437 Spontaneous
Com.Issued=AutoLocal
00590 Line closure detected ON 16.09.2017 07:54:36.237 Spontaneous
Com.Issued=AutoLocal
M CB_BO OFF 16.09.2017 07:54:36.235 Spontaneous
M CB_YO OFF 16.09.2017 07:54:36.235 Spontaneous
M CB_RO OFF 16.09.2017 07:54:36.235 Spontaneous
00381 >Single-phase trip permitted from ext.AR ON 15.09.2017 22:59:34.788 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P ON 15.09.2017 22:59:34.788 Spontaneous

Page 46 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 03-10-2017 16:09:19.332 (SIGNALS\BM000003.SFP)(5)


Number Indication Value Date and time Cause State

00381 >Single-phase trip permitted from ext.AR OFF 15.09.2017 22:58:25.177 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P OFF 15.09.2017 22:58:25.174 Spontaneous
DTRC1/2 OFF 15.09.2017 22:58:24.928 Spontaneous
M1_TRIP OFF 15.09.2017 22:58:24.913 Spontaneous
M1_TRIP ON 15.09.2017 22:58:24.904 Spontaneous
00301 Power System fault 294 - OFF 15.09.2017 22:58:24.903 Spontaneous
Com.Issued=AutoLocal
00301 Power System fault 294 - ON 15.09.2017 22:58:24.883 Spontaneous
Com.Issued=AutoLocal
M CB_BO ON 15.09.2017 22:58:24.867 Spontaneous
M CB_YO ON 15.09.2017 22:58:24.867 Spontaneous
M CB_RO ON 15.09.2017 22:58:24.867 Spontaneous
00004 >Trigger Waveform Capture ON 15.09.2017 22:58:24.848 Spontaneous
Com.Issued=AutoLocal
DTRC1/2 ON 15.09.2017 22:58:24.841 Spontaneous
00060 Reset LED ON 28.08.2017 12:25:05.961 Spontaneous
Com.Issued=AutoLocal
Reset LED ON 28.08.2017 12:25:05.961 Spontaneous
Command Issued=Local
00590 Line closure detected OFF 28.08.2017 08:11:34.463 Spontaneous
Com.Issued=AutoLocal
M CB_BO OFF 28.08.2017 08:11:34.275 Spontaneous
M CB_YO OFF 28.08.2017 08:11:34.275 Spontaneous
M CB_RO OFF 28.08.2017 08:11:34.275 Spontaneous
00590 Line closure detected ON 28.08.2017 08:11:34.261 Spontaneous
Com.Issued=AutoLocal
00381 >Single-phase trip permitted from ext.AR ON 26.08.2017 00:45:12.957 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P ON 26.08.2017 00:45:12.950 Spontaneous
00381 >Single-phase trip permitted from ext.AR OFF 26.08.2017 00:44:01.417 Spontaneous
Com.Issued=AutoLocal

Page 47 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 03-10-2017 16:09:19.332 (SIGNALS\BM000003.SFP)(6)


Number Indication Value Date and time Cause State

PREPARE 3P OFF 26.08.2017 00:44:01.417 Spontaneous


DTRC1/2 OFF 26.08.2017 00:44:01.180 Spontaneous
M1_TRIP OFF 26.08.2017 00:44:01.168 Spontaneous
M1_TRIP ON 26.08.2017 00:44:01.160 Spontaneous
00301 Power System fault 292 - OFF 26.08.2017 00:44:01.158 Spontaneous
Com.Issued=AutoLocal
00301 Power System fault 292 - ON 26.08.2017 00:44:01.138 Spontaneous
Com.Issued=AutoLocal
M CB_BO ON 26.08.2017 00:44:01.121 Spontaneous
M CB_YO ON 26.08.2017 00:44:01.121 Spontaneous
M CB_RO ON 26.08.2017 00:44:01.121 Spontaneous
00004 >Trigger Waveform Capture ON 26.08.2017 00:44:01.097 Spontaneous
Com.Issued=AutoLocal
DTRC1/2 ON 26.08.2017 00:44:01.095 Spontaneous
M CB_BO OFF 21.08.2017 15:00:54.426 Spontaneous
M CB_YO OFF 21.08.2017 15:00:54.426 Spontaneous
M CB_RO OFF 21.08.2017 15:00:54.426 Spontaneous
M1_TRIP OFF 21.08.2017 15:00:47.312 Spontaneous
00301 Power System fault 290 - OFF 21.08.2017 15:00:47.301 Spontaneous
Com.Issued=AutoLocal
00004 >Trigger Waveform Capture ON 21.08.2017 15:00:47.227 Spontaneous
Com.Issued=AutoLocal
M1_TRIP ON 21.08.2017 15:00:47.224 Spontaneous
00301 Power System fault 290 - ON 21.08.2017 15:00:47.201 Spontaneous
Com.Issued=AutoLocal
M1_TRIP OFF 21.08.2017 15:00:47.192 Spontaneous
00004 >Trigger Waveform Capture ON 21.08.2017 15:00:47.187 Spontaneous
Com.Issued=AutoLocal
M1_TRIP ON 21.08.2017 15:00:47.185 Spontaneous
00301 Power System fault 288 - OFF 21.08.2017 15:00:47.181 Spontaneous
Com.Issued=AutoLocal

Page 48 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 03-10-2017 16:09:19.332 (SIGNALS\BM000003.SFP)(7)


Number Indication Value Date and time Cause State

00301 Power System fault 288 - ON 21.08.2017 15:00:47.161 Spontaneous


Com.Issued=AutoLocal
00060 Reset LED ON 20.08.2017 03:22:07.900 Spontaneous
Com.Issued=AutoLocal
Reset LED ON 20.08.2017 03:22:07.900 Spontaneous
Command Issued=Local
00060 Reset LED ON 20.08.2017 03:22:06.898 Spontaneous
Com.Issued=AutoLocal
Reset LED ON 20.08.2017 03:22:06.898 Spontaneous
Command Issued=Local
00381 >Single-phase trip permitted from ext.AR ON 20.08.2017 03:18:45.548 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P ON 20.08.2017 03:18:45.547 Spontaneous
00381 >Single-phase trip permitted from ext.AR OFF 20.08.2017 03:17:13.697 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P OFF 20.08.2017 03:17:13.690 Spontaneous
DTRC1/2 OFF 20.08.2017 03:17:13.523 Spontaneous
M1_TRIP OFF 20.08.2017 03:17:13.510 Spontaneous
M1_TRIP ON 20.08.2017 03:17:13.501 Spontaneous
00301 Power System fault 287 - OFF 20.08.2017 03:17:13.499 Spontaneous
Com.Issued=AutoLocal
00301 Power System fault 287 - ON 20.08.2017 03:17:13.479 Spontaneous
Com.Issued=AutoLocal
M CB_BO ON 20.08.2017 03:17:13.463 Spontaneous
M CB_YO ON 20.08.2017 03:17:13.463 Spontaneous
M CB_RO ON 20.08.2017 03:17:13.463 Spontaneous
00004 >Trigger Waveform Capture ON 20.08.2017 03:17:13.447 Spontaneous
Com.Issued=AutoLocal
DTRC1/2 ON 20.08.2017 03:17:13.438 Spontaneous
00590 Line closure detected OFF 20.08.2017 03:16:27.734 Spontaneous
Com.Issued=AutoLocal
M CB_YO OFF 20.08.2017 03:16:27.548 Spontaneous
M CB_BO OFF 20.08.2017 03:16:27.547 Spontaneous

Page 49 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 03-10-2017 16:09:19.332 (SIGNALS\BM000003.SFP)(8)


Number Indication Value Date and time Cause State

M CB_RO OFF 20.08.2017 03:16:27.547 Spontaneous


00590 Line closure detected ON 20.08.2017 03:16:27.534 Spontaneous
Com.Issued=AutoLocal
00381 >Single-phase trip permitted from ext.AR ON 20.08.2017 02:49:14.487 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P ON 20.08.2017 02:49:14.481 Spontaneous
00381 >Single-phase trip permitted from ext.AR OFF 20.08.2017 02:48:25.498 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P OFF 20.08.2017 02:48:25.493 Spontaneous
00004 >Trigger Waveform Capture ON 20.08.2017 02:48:25.127 Spontaneous
Com.Issued=AutoLocal
M CB_RO ON 20.08.2017 02:48:25.127 Spontaneous
M CB_BO ON 20.08.2017 02:48:25.126 Spontaneous
M CB_YO ON 20.08.2017 02:48:25.122 Spontaneous
00060 Reset LED ON 13.06.2017 11:48:20.683 Spontaneous
Com.Issued=AutoLocal
Reset LED ON 13.06.2017 11:48:20.683 Spontaneous
Command Issued=Local
M1_TRIP OFF 05.06.2017 19:15:12.138 Spontaneous
00301 Power System fault 284 - OFF 05.06.2017 19:15:12.124 Spontaneous
Com.Issued=AutoLocal
00004 >Trigger Waveform Capture ON 05.06.2017 19:15:11.627 Spontaneous
Com.Issued=AutoLocal
M1_TRIP ON 05.06.2017 19:15:11.627 Spontaneous
00301 Power System fault 284 - ON 05.06.2017 19:15:11.604 Spontaneous
Com.Issued=AutoLocal
M1_TRIP OFF 28.05.2017 20:03:05.467 Spontaneous
M CB_BO OFF 28.05.2017 20:03:05.450 Spontaneous
M CB_YO OFF 28.05.2017 20:03:05.450 Spontaneous
M CB_RO OFF 28.05.2017 20:03:05.450 Spontaneous
00301 Power System fault 283 - OFF 28.05.2017 20:03:05.456 Spontaneous
Com.Issued=AutoLocal

Page 50 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 03-10-2017 16:09:19.332 (SIGNALS\BM000003.SFP)(9)


Number Indication Value Date and time Cause State

00004 >Trigger Waveform Capture ON 28.05.2017 20:03:02.247 Spontaneous


Com.Issued=AutoLocal
M1_TRIP ON 28.05.2017 20:03:02.238 Spontaneous
00301 Power System fault 283 - ON 28.05.2017 20:03:02.215 Spontaneous
Com.Issued=AutoLocal
M1_TRIP OFF 28.05.2017 08:27:42.746 Spontaneous
M1_TRIP ON 28.05.2017 08:27:42.739 Spontaneous
00301 Power System fault 282 - OFF 28.05.2017 08:27:42.736 Spontaneous
Com.Issued=AutoLocal
00301 Power System fault 282 - ON 28.05.2017 08:27:42.716 Spontaneous
Com.Issued=AutoLocal
M CB_BO ON 28.05.2017 08:27:42.680 Spontaneous
M CB_RO ON 28.05.2017 08:27:42.680 Spontaneous
00004 >Trigger Waveform Capture ON 28.05.2017 08:27:42.677 Spontaneous
Com.Issued=AutoLocal
M CB_YO ON 28.05.2017 08:27:42.676 Spontaneous
M CB_BO OFF 23.05.2017 18:47:17.096 Spontaneous
M CB_YO OFF 23.05.2017 18:47:17.096 Spontaneous
M CB_RO OFF 23.05.2017 18:47:17.096 Spontaneous
M CB_RO ON 23.05.2017 15:40:07.891 Spontaneous
M CB_BO ON 23.05.2017 15:40:07.890 Spontaneous
00004 >Trigger Waveform Capture ON 23.05.2017 15:40:07.888 Spontaneous
Com.Issued=AutoLocal
M CB_YO ON 23.05.2017 15:40:07.887 Spontaneous
M1_TRIP OFF 10.05.2017 02:39:36.125 Spontaneous
00004 >Trigger Waveform Capture ON 10.05.2017 02:39:36.079 Spontaneous
Com.Issued=AutoLocal
M1_TRIP ON 10.05.2017 02:39:36.077 Spontaneous
00070 Setting calculation is running OFF 02.05.2017 15:54:38.725 Spontaneous
Com.Issued=AutoLocal
00070 Setting calculation is running ON 02.05.2017 15:54:12.909 Spontaneous
Com.Issued=AutoLocal

Page 51 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 03-10-2017 16:09:19.332 (SIGNALS\BM000003.SFP)(10)


Number Indication Value Date and time Cause State

00068 Clock Synchronization Error ON 04.03.2017 17:15:24.600 Spontaneous


Com.Issued=AutoLocal
00301 Power System fault 278 - OFF 08.01.2017 06:54:01.126 Spontaneous
Com.Issued=AutoLocal
00301 Power System fault 278 - ON 08.01.2017 06:54:01.086 Spontaneous
Com.Issued=AutoLocal
M CB_YO OFF 24.12.2016 18:49:02.181 Spontaneous
M CB_BO OFF 24.12.2016 18:49:02.180 Spontaneous
M CB_RO OFF 24.12.2016 18:49:02.180 Spontaneous
M1_TRIP OFF 24.12.2016 18:48:38.547 Spontaneous
00301 Power System fault 277 - OFF 24.12.2016 18:48:38.535 Spontaneous
Com.Issued=AutoLocal
00004 >Trigger Waveform Capture ON 24.12.2016 18:48:38.506 Spontaneous
Com.Issued=AutoLocal
M1_TRIP ON 24.12.2016 18:48:38.497 Spontaneous

6.4 Event Log - 08-04-2018 10:58:31.269 (SIGNALS\BM000004.SFP)

Event Log - 08-04-2018 10:58:31.269 (SIGNALS\BM000004.SFP)


Number Indication Value Date and time Cause State

00381 >Single-phase trip permitted from ext.AR ON 08.04.2018 06:41:50.974 Spontaneous


Com.Issued=AutoLocal
PREPARE 3P ON 08.04.2018 06:41:50.974 Spontaneous
M1_TRIP OFF 08.04.2018 06:40:22.747 Spontaneous
00301 Power System fault 1115 - OFF 08.04.2018 06:40:22.737 Spontaneous
Com.Issued=AutoLocal
M2_TRIP OFF 08.04.2018 06:40:22.737 Spontaneous
Com.Issued=AutoLocal
M/TCBAR OFF 08.04.2018 06:40:22.732 Spontaneous
00381 >Single-phase trip permitted from ext.AR OFF 08.04.2018 06:37:47.110 Spontaneous
Com.Issued=AutoLocal

Page 52 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 08-04-2018 10:58:31.269 (SIGNALS\BM000004.SFP)(2)


Number Indication Value Date and time Cause State

PREPARE 3P OFF 08.04.2018 06:37:47.110 Spontaneous


M/TCBAR ON 08.04.2018 06:37:47.053 Spontaneous
M2_TRIP ON 08.04.2018 06:37:47.047 Spontaneous
Com.Issued=AutoLocal
00004 >Trigger Waveform Capture ON 08.04.2018 06:37:42.072 Spontaneous
Com.Issued=AutoLocal
M1_TRIP ON 08.04.2018 06:37:42.072 Spontaneous
00301 Power System fault 1115 - ON 08.04.2018 06:37:42.049 Spontaneous
Com.Issued=AutoLocal
00381 >Single-phase trip permitted from ext.AR ON 08.04.2018 06:28:59.555 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P ON 08.04.2018 06:28:59.555 Spontaneous
00060 Reset LED ON 08.04.2018 06:28:47.796 Spontaneous
Com.Issued=AutoLocal
Reset LED ON 08.04.2018 06:28:47.796 Spontaneous
Command Issued=Local
M1_TRIP OFF 08.04.2018 06:26:25.537 Spontaneous
00301 Power System fault 1114 - OFF 08.04.2018 06:26:25.526 Spontaneous
Com.Issued=AutoLocal
M2_TRIP OFF 08.04.2018 06:26:25.526 Spontaneous
Com.Issued=AutoLocal
M/TCBAR OFF 08.04.2018 06:26:25.523 Spontaneous
00060 Reset LED ON 08.04.2018 05:58:38.684 Spontaneous
Com.Issued=AutoLocal
Reset LED ON 08.04.2018 05:58:38.684 Spontaneous
Command Issued=Local
M/TCBAR ON 08.04.2018 05:41:43.973 Spontaneous
M2_TRIP ON 08.04.2018 05:41:43.947 Spontaneous
Com.Issued=AutoLocal
00004 >Trigger Waveform Capture ON 08.04.2018 05:41:38.971 Spontaneous
Com.Issued=AutoLocal
M1_TRIP ON 08.04.2018 05:41:38.971 Spontaneous

Page 53 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 08-04-2018 10:58:31.269 (SIGNALS\BM000004.SFP)(3)


Number Indication Value Date and time Cause State

00301 Power System fault 1114 - ON 08.04.2018 05:41:38.949 Spontaneous


Com.Issued=AutoLocal
M1_TRIP OFF 08.04.2018 05:41:38.619 Spontaneous
M/TCBAR OFF 08.04.2018 05:41:38.612 Spontaneous
00301 Power System fault 1113 - OFF 08.04.2018 05:41:38.611 Spontaneous
Com.Issued=AutoLocal
M2_TRIP OFF 08.04.2018 05:41:38.609 Spontaneous
Com.Issued=AutoLocal
00060 Reset LED ON 08.04.2018 05:39:07.978 Spontaneous
Com.Issued=AutoLocal
Reset LED ON 08.04.2018 05:39:07.976 Spontaneous
Command Issued=Local
00060 Reset LED ON 08.04.2018 05:39:06.975 Spontaneous
Com.Issued=AutoLocal
Reset LED ON 08.04.2018 05:39:06.975 Spontaneous
Command Issued=Local
M/TCBAR ON 08.04.2018 05:26:53.543 Spontaneous
M2_TRIP ON 08.04.2018 05:26:53.527 Spontaneous
Com.Issued=AutoLocal
00004 >Trigger Waveform Capture ON 08.04.2018 05:26:48.554 Spontaneous
Com.Issued=AutoLocal
M1_TRIP ON 08.04.2018 05:26:48.554 Spontaneous
00301 Power System fault 1113 - ON 08.04.2018 05:26:48.531 Spontaneous
Com.Issued=AutoLocal
M1_TRIP OFF 08.04.2018 05:26:48.402 Spontaneous
00301 Power System fault 1112 - OFF 08.04.2018 05:26:48.391 Spontaneous
Com.Issued=AutoLocal
M2_TRIP OFF 08.04.2018 05:26:48.391 Spontaneous
Com.Issued=AutoLocal
M/TCBAR OFF 08.04.2018 05:26:48.378 Spontaneous
M2_TRIP ON 08.04.2018 05:16:42.528 Spontaneous
Com.Issued=AutoLocal

Page 54 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 08-04-2018 10:58:31.269 (SIGNALS\BM000004.SFP)(4)


Number Indication Value Date and time Cause State

00004 >Trigger Waveform Capture ON 08.04.2018 05:16:42.526 Spontaneous


Com.Issued=AutoLocal
M/TCBAR ON 08.04.2018 05:16:42.526 Spontaneous
01332 Earth fault protection is BLOCKED OFF 08.04.2018 05:16:38.273 Spontaneous
Com.Issued=AutoLocal
14083 E/F 3I0p is blocked OFF 08.04.2018 05:16:38.273 Spontaneous
Com.Issued=AutoLocal
00592 Single pole open detected in L2 OFF 08.04.2018 05:16:38.243 Spontaneous
Com.Issued=AutoLocal
01332 Earth fault protection is BLOCKED ON 08.04.2018 05:16:37.566 Spontaneous
Com.Issued=AutoLocal
14083 E/F 3I0p is blocked ON 08.04.2018 05:16:37.566 Spontaneous
Com.Issued=AutoLocal
00592 Single pole open detected in L2 ON 08.04.2018 05:16:37.566 Spontaneous
Com.Issued=AutoLocal
M2_TRIP OFF 08.04.2018 05:16:37.561 Spontaneous
Com.Issued=AutoLocal
01335 Earth fault protection Trip is blocked OFF 08.04.2018 05:16:37.556 Spontaneous
Com.Issued=AutoLocal
M1_TRIP ON 08.04.2018 05:16:37.553 Spontaneous
M1_TRIP OFF 08.04.2018 05:16:37.550 Spontaneous
M/TCBAR OFF 08.04.2018 05:16:37.536 Spontaneous
M CB_BO ON 08.04.2018 05:16:37.483 Spontaneous
M CB_RO ON 08.04.2018 05:16:37.483 Spontaneous
M CB_YO ON 08.04.2018 05:16:37.474 Spontaneous
M2_TRIP ON 08.04.2018 05:16:37.460 Spontaneous
Com.Issued=AutoLocal
M/TCBAR ON 08.04.2018 05:16:37.457 Spontaneous
00004 >Trigger Waveform Capture ON 08.04.2018 05:16:37.066 Spontaneous
Com.Issued=AutoLocal
M1_TRIP ON 08.04.2018 05:16:37.065 Spontaneous
01335 Earth fault protection Trip is blocked ON 08.04.2018 05:16:37.064 Spontaneous
Com.Issued=AutoLocal

Page 55 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 08-04-2018 10:58:31.269 (SIGNALS\BM000004.SFP)(5)


Number Indication Value Date and time Cause State

00301 Power System fault 1112 - ON 08.04.2018 05:16:37.059 Spontaneous


Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 31.03.2018 10:58:53.232 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 31.03.2018 10:58:49.533 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 31.03.2018 10:58:48.633 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 31.03.2018 10:58:41.933 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 31.03.2018 10:58:40.433 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 31.03.2018 10:58:36.133 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 31.03.2018 10:58:16.132 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 31.03.2018 10:58:06.032 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 31.03.2018 10:58:04.832 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 31.03.2018 10:57:55.132 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 31.03.2018 10:57:51.332 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 31.03.2018 10:57:45.932 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 31.03.2018 10:57:31.932 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 31.03.2018 10:57:25.032 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 31.03.2018 10:57:24.332 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 31.03.2018 10:57:17.432 Spontaneous
Com.Issued=AutoLocal

Page 56 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 08-04-2018 10:58:31.269 (SIGNALS\BM000004.SFP)(6)


Number Indication Value Date and time Cause State

009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 31.03.2018 10:57:15.932 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 31.03.2018 10:57:11.632 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 31.03.2018 10:56:51.632 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 31.03.2018 10:56:43.732 Spontaneous
Com.Issued=AutoLocal
00060 Reset LED ON 31.03.2018 09:33:35.382 Spontaneous
Com.Issued=AutoLocal
Reset LED ON 31.03.2018 09:33:35.382 Spontaneous
Command Issued=Local
M CB_BO OFF 05.03.2018 18:03:22.928 Spontaneous
M CB_YO OFF 05.03.2018 18:03:22.928 Spontaneous
M CB_RO OFF 05.03.2018 18:03:22.928 Spontaneous
00068 Clock Synchronization Error ON 22.02.2018 11:28:41.932 Spontaneous
Com.Issued=AutoLocal
009.0100.01 Failure EN100 Modul OFF 22.02.2018 11:19:06.307 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 22.02.2018 11:18:36.132 Spontaneous
Com.Issued=AutoLocal
009.0102.01 Failure EN100 Link Channel 2 (Ch2) ON 22.02.2018 11:18:36.032 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 22.02.2018 11:18:36.032 Spontaneous
Com.Issued=AutoLocal
00051 Device is Operational and Protecting ON 22.02.2018 11:18:35.905 Spontaneous
Com.Issued=AutoLocal
10229 U1<(<) Undervolt. is switched OFF ON 22.02.2018 11:18:35.845 Spontaneous
Com.Issued=AutoLocal
10227 Uph-ph<(<) Undervolt. is switched OFF ON 22.02.2018 11:18:35.845 Spontaneous
Com.Issued=AutoLocal
10225 Uph-e<(<) Undervolt. is switched OFF ON 22.02.2018 11:18:35.844 Spontaneous
Com.Issued=AutoLocal

Page 57 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 08-04-2018 10:58:31.269 (SIGNALS\BM000004.SFP)(7)


Number Indication Value Date and time Cause State

10223 U2>(>) Overvolt. is switched OFF ON 22.02.2018 11:18:35.844 Spontaneous


Com.Issued=AutoLocal
10221 U1>(>) Overvolt. is switched OFF ON 22.02.2018 11:18:35.844 Spontaneous
Com.Issued=AutoLocal
10219 3U0>(>) Overvolt. is switched OFF ON 22.02.2018 11:18:35.844 Spontaneous
Com.Issued=AutoLocal
10217 Uph-ph>(>) Overvolt. is switched OFF ON 22.02.2018 11:18:35.844 Spontaneous
Com.Issued=AutoLocal
10231 Over-/Under-Voltage protection is ACTIVE ON 22.02.2018 11:18:35.844 Spontaneous
Com.Issued=AutoLocal
07152 Backup O/C is BLOCKED ON 22.02.2018 11:18:35.844 Spontaneous
Com.Issued=AutoLocal
M CB_BO ON 22.02.2018 11:18:35.843 Spontaneous
M CB_YO ON 22.02.2018 11:18:35.843 Spontaneous
M CB_RO ON 22.02.2018 11:18:35.843 Spontaneous
PREPARE 3P OFF 22.02.2018 11:18:35.843 Spontaneous
00067 Resume ON 22.02.2018 11:18:35.818 Spontaneous
Com.Issued=AutoLocal
00052 At Least 1 Protection Funct. is Active ON 22.02.2018 11:18:35.842 Spontaneous
Com.Issued=AutoLocal
009.0100.01 Failure EN100 Modul ON 22.02.2018 11:18:35.841 Spontaneous
Com.Issued=AutoLocal
00381 >Single-phase trip permitted from ext.AR ON 22.02.2018 11:14:18.095 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P ON 22.02.2018 11:14:18.095 Spontaneous
00068 Clock Synchronization Error ON 21.02.2018 15:57:20.932 Spontaneous
Com.Issued=AutoLocal
009.0100.01 Failure EN100 Modul OFF 21.02.2018 15:47:45.299 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 21.02.2018 15:47:15.132 Spontaneous
Com.Issued=AutoLocal
009.0102.01 Failure EN100 Link Channel 2 (Ch2) ON 21.02.2018 15:47:15.032 Spontaneous
Com.Issued=AutoLocal

Page 58 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 08-04-2018 10:58:31.269 (SIGNALS\BM000004.SFP)(8)


Number Indication Value Date and time Cause State

009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 21.02.2018 15:47:15.032 Spontaneous


Com.Issued=AutoLocal
00051 Device is Operational and Protecting ON 21.02.2018 15:47:14.905 Spontaneous
Com.Issued=AutoLocal
10229 U1<(<) Undervolt. is switched OFF ON 21.02.2018 15:47:14.845 Spontaneous
Com.Issued=AutoLocal
10227 Uph-ph<(<) Undervolt. is switched OFF ON 21.02.2018 15:47:14.845 Spontaneous
Com.Issued=AutoLocal
10225 Uph-e<(<) Undervolt. is switched OFF ON 21.02.2018 15:47:14.845 Spontaneous
Com.Issued=AutoLocal
10223 U2>(>) Overvolt. is switched OFF ON 21.02.2018 15:47:14.844 Spontaneous
Com.Issued=AutoLocal
10221 U1>(>) Overvolt. is switched OFF ON 21.02.2018 15:47:14.844 Spontaneous
Com.Issued=AutoLocal
10219 3U0>(>) Overvolt. is switched OFF ON 21.02.2018 15:47:14.844 Spontaneous
Com.Issued=AutoLocal
10217 Uph-ph>(>) Overvolt. is switched OFF ON 21.02.2018 15:47:14.844 Spontaneous
Com.Issued=AutoLocal
10231 Over-/Under-Voltage protection is ACTIVE ON 21.02.2018 15:47:14.844 Spontaneous
Com.Issued=AutoLocal
07152 Backup O/C is BLOCKED ON 21.02.2018 15:47:14.844 Spontaneous
Com.Issued=AutoLocal
M CB_BO ON 21.02.2018 15:47:14.843 Spontaneous
M CB_YO ON 21.02.2018 15:47:14.843 Spontaneous
M CB_RO ON 21.02.2018 15:47:14.843 Spontaneous
PREPARE 3P OFF 21.02.2018 15:47:14.843 Spontaneous
00067 Resume ON 21.02.2018 15:47:14.818 Spontaneous
Com.Issued=AutoLocal
00052 At Least 1 Protection Funct. is Active ON 21.02.2018 15:47:14.842 Spontaneous
Com.Issued=AutoLocal
009.0100.01 Failure EN100 Modul ON 21.02.2018 15:47:14.841 Spontaneous
Com.Issued=AutoLocal

Page 59 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 08-04-2018 10:58:31.269 (SIGNALS\BM000004.SFP)(9)


Number Indication Value Date and time Cause State

00381 >Single-phase trip permitted from ext.AR ON 21.02.2018 15:42:34.367 Spontaneous


Com.Issued=AutoLocal
PREPARE 3P ON 21.02.2018 15:42:34.360 Spontaneous
00004 >Trigger Waveform Capture ON 21.02.2018 09:52:20.927 Spontaneous
Com.Issued=AutoLocal
M CB_RO ON 21.02.2018 09:52:20.925 Spontaneous
M CB_BO ON 21.02.2018 09:52:20.924 Spontaneous
M CB_YO ON 21.02.2018 09:52:20.921 Spontaneous
00060 Reset LED ON 30.01.2018 10:10:31.334 Spontaneous
Com.Issued=AutoLocal
Reset LED ON 30.01.2018 10:10:31.334 Spontaneous
Command Issued=Local
00070 Setting calculation is running OFF 30.01.2018 10:10:24.808 Spontaneous
Com.Issued=AutoLocal
00070 Setting calculation is running ON 30.01.2018 10:09:56.631 Spontaneous
Com.Issued=AutoLocal
00070 Setting calculation is running OFF 30.01.2018 10:02:39.540 Spontaneous
Com.Issued=AutoLocal
00072 Level-2 change ON 30.01.2018 10:02:39.539 Spontaneous
Com.Issued=AutoLocal
00070 Setting calculation is running ON 30.01.2018 10:02:14.628 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 23.01.2018 01:17:13.332 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 23.01.2018 01:17:09.632 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 23.01.2018 01:17:08.732 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 23.01.2018 01:17:02.031 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 23.01.2018 01:17:00.631 Spontaneous
Com.Issued=AutoLocal

Page 60 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 08-04-2018 10:58:31.269 (SIGNALS\BM000004.SFP)(10)


Number Indication Value Date and time Cause State

009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 23.01.2018 01:16:56.231 Spontaneous


Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 23.01.2018 01:16:36.331 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 23.01.2018 00:47:21.732 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 20.12.2017 22:33:59.031 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 20.12.2017 22:33:55.331 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 20.12.2017 22:33:54.531 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 20.12.2017 22:33:47.731 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 20.12.2017 22:33:46.231 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 20.12.2017 22:33:41.931 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 20.12.2017 22:33:22.131 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 20.12.2017 22:33:18.331 Spontaneous
Com.Issued=AutoLocal
00590 Line closure detected OFF 31.10.2017 19:12:30.449 Spontaneous
Com.Issued=AutoLocal
M1_TRIP OFF 31.10.2017 19:12:30.396 Spontaneous
00301 Power System fault 1109 - OFF 31.10.2017 19:12:30.385 Spontaneous
Com.Issued=AutoLocal
00004 >Trigger Waveform Capture ON 31.10.2017 19:12:30.377 Spontaneous
Com.Issued=AutoLocal
M1_TRIP ON 31.10.2017 19:12:30.368 Spontaneous
00301 Power System fault 1109 - ON 31.10.2017 19:12:30.344 Spontaneous
Com.Issued=AutoLocal
M CB_BO OFF 31.10.2017 19:12:30.261 Spontaneous

Page 61 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 08-04-2018 10:58:31.269 (SIGNALS\BM000004.SFP)(11)


Number Indication Value Date and time Cause State

M CB_YO OFF 31.10.2017 19:12:30.261 Spontaneous


M CB_RO OFF 31.10.2017 19:12:30.261 Spontaneous
00590 Line closure detected ON 31.10.2017 19:12:30.246 Spontaneous
Com.Issued=AutoLocal
00060 Reset LED ON 31.10.2017 19:11:11.700 Spontaneous
Com.Issued=AutoLocal
Reset LED ON 31.10.2017 19:11:11.700 Spontaneous
Command Issued=Local
M1_TRIP OFF 31.10.2017 19:11:08.733 Spontaneous
00301 Power System fault 1108 - OFF 31.10.2017 19:11:08.723 Spontaneous
Com.Issued=AutoLocal
M2_TRIP OFF 31.10.2017 19:11:08.723 Spontaneous
Com.Issued=AutoLocal
00060 Reset LED ON 31.10.2017 19:09:00.910 Spontaneous
Com.Issued=AutoLocal
Reset LED ON 31.10.2017 19:09:00.910 Spontaneous
Command Issued=Local
00060 Reset LED ON 31.10.2017 19:09:00.000 Spontaneous
Com.Issued=AutoLocal
Reset LED ON 31.10.2017 19:09:00.000 Spontaneous
Command Issued=Local
00060 Reset LED ON 31.10.2017 19:08:55.410 Spontaneous
Com.Issued=AutoLocal
Reset LED ON 31.10.2017 19:08:55.410 Spontaneous
Command Issued=Local
00060 Reset LED ON 31.10.2017 19:08:10.411 Spontaneous
Com.Issued=AutoLocal
Reset LED ON 31.10.2017 19:08:10.410 Spontaneous
Command Issued=Local
00060 Reset LED ON 31.10.2017 19:07:59.201 Spontaneous
Com.Issued=AutoLocal
Reset LED ON 31.10.2017 19:07:59.201 Spontaneous
Command Issued=Local

Page 62 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 08-04-2018 10:58:31.269 (SIGNALS\BM000004.SFP)(12)


Number Indication Value Date and time Cause State

00060 Reset LED ON 31.10.2017 19:07:57.501 Spontaneous


Com.Issued=AutoLocal
Reset LED ON 31.10.2017 19:07:57.501 Spontaneous
Command Issued=Local
M2_TRIP ON 31.10.2017 19:06:16.981 Spontaneous
Com.Issued=AutoLocal
00004 >Trigger Waveform Capture ON 31.10.2017 19:06:12.008 Spontaneous
Com.Issued=AutoLocal
M1_TRIP ON 31.10.2017 19:06:12.005 Spontaneous
00301 Power System fault 1108 - ON 31.10.2017 19:06:11.983 Spontaneous
Com.Issued=AutoLocal
04010 >Dis.Tele. Carrier RECEPTION Channel 2 OFF 31.10.2017 18:24:11.962 Spontaneous
Com.Issued=AutoLocal

6.5 Event Log - 08-04-2018 11:04:16.606 (SIGNALS\BM000005.SFP)

Event Log - 08-04-2018 11:04:16.606 (SIGNALS\BM000005.SFP)


Number Indication Value Date and time Cause State

00381 >Single-phase trip permitted from ext.AR ON 08.04.2018 06:41:50.974 Spontaneous


Com.Issued=AutoLocal
PREPARE 3P ON 08.04.2018 06:41:50.974 Spontaneous
M1_TRIP OFF 08.04.2018 06:40:22.747 Spontaneous
00301 Power System fault 1115 - OFF 08.04.2018 06:40:22.737 Spontaneous
Com.Issued=AutoLocal
M2_TRIP OFF 08.04.2018 06:40:22.737 Spontaneous
Com.Issued=AutoLocal
M/TCBAR OFF 08.04.2018 06:40:22.732 Spontaneous
00381 >Single-phase trip permitted from ext.AR OFF 08.04.2018 06:37:47.110 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P OFF 08.04.2018 06:37:47.110 Spontaneous
M/TCBAR ON 08.04.2018 06:37:47.053 Spontaneous

Page 63 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 08-04-2018 11:04:16.606 (SIGNALS\BM000005.SFP)(2)


Number Indication Value Date and time Cause State

M2_TRIP ON 08.04.2018 06:37:47.047 Spontaneous


Com.Issued=AutoLocal
00004 >Trigger Waveform Capture ON 08.04.2018 06:37:42.072 Spontaneous
Com.Issued=AutoLocal
M1_TRIP ON 08.04.2018 06:37:42.072 Spontaneous
00301 Power System fault 1115 - ON 08.04.2018 06:37:42.049 Spontaneous
Com.Issued=AutoLocal
00381 >Single-phase trip permitted from ext.AR ON 08.04.2018 06:28:59.555 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P ON 08.04.2018 06:28:59.555 Spontaneous
00060 Reset LED ON 08.04.2018 06:28:47.796 Spontaneous
Com.Issued=AutoLocal
Reset LED ON 08.04.2018 06:28:47.796 Spontaneous
Command Issued=Local
M1_TRIP OFF 08.04.2018 06:26:25.537 Spontaneous
00301 Power System fault 1114 - OFF 08.04.2018 06:26:25.526 Spontaneous
Com.Issued=AutoLocal
M2_TRIP OFF 08.04.2018 06:26:25.526 Spontaneous
Com.Issued=AutoLocal
M/TCBAR OFF 08.04.2018 06:26:25.523 Spontaneous
00060 Reset LED ON 08.04.2018 05:58:38.684 Spontaneous
Com.Issued=AutoLocal
Reset LED ON 08.04.2018 05:58:38.684 Spontaneous
Command Issued=Local
M/TCBAR ON 08.04.2018 05:41:43.973 Spontaneous
M2_TRIP ON 08.04.2018 05:41:43.947 Spontaneous
Com.Issued=AutoLocal
00004 >Trigger Waveform Capture ON 08.04.2018 05:41:38.971 Spontaneous
Com.Issued=AutoLocal
M1_TRIP ON 08.04.2018 05:41:38.971 Spontaneous
00301 Power System fault 1114 - ON 08.04.2018 05:41:38.949 Spontaneous
Com.Issued=AutoLocal
M1_TRIP OFF 08.04.2018 05:41:38.619 Spontaneous

Page 64 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 08-04-2018 11:04:16.606 (SIGNALS\BM000005.SFP)(3)


Number Indication Value Date and time Cause State

M/TCBAR OFF 08.04.2018 05:41:38.612 Spontaneous


00301 Power System fault 1113 - OFF 08.04.2018 05:41:38.611 Spontaneous
Com.Issued=AutoLocal
M2_TRIP OFF 08.04.2018 05:41:38.609 Spontaneous
Com.Issued=AutoLocal
00060 Reset LED ON 08.04.2018 05:39:07.978 Spontaneous
Com.Issued=AutoLocal
Reset LED ON 08.04.2018 05:39:07.976 Spontaneous
Command Issued=Local
00060 Reset LED ON 08.04.2018 05:39:06.975 Spontaneous
Com.Issued=AutoLocal
Reset LED ON 08.04.2018 05:39:06.975 Spontaneous
Command Issued=Local
M/TCBAR ON 08.04.2018 05:26:53.543 Spontaneous
M2_TRIP ON 08.04.2018 05:26:53.527 Spontaneous
Com.Issued=AutoLocal
00004 >Trigger Waveform Capture ON 08.04.2018 05:26:48.554 Spontaneous
Com.Issued=AutoLocal
M1_TRIP ON 08.04.2018 05:26:48.554 Spontaneous
00301 Power System fault 1113 - ON 08.04.2018 05:26:48.531 Spontaneous
Com.Issued=AutoLocal
M1_TRIP OFF 08.04.2018 05:26:48.402 Spontaneous
00301 Power System fault 1112 - OFF 08.04.2018 05:26:48.391 Spontaneous
Com.Issued=AutoLocal
M2_TRIP OFF 08.04.2018 05:26:48.391 Spontaneous
Com.Issued=AutoLocal
M/TCBAR OFF 08.04.2018 05:26:48.378 Spontaneous
M2_TRIP ON 08.04.2018 05:16:42.528 Spontaneous
Com.Issued=AutoLocal
00004 >Trigger Waveform Capture ON 08.04.2018 05:16:42.526 Spontaneous
Com.Issued=AutoLocal
M/TCBAR ON 08.04.2018 05:16:42.526 Spontaneous

Page 65 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 08-04-2018 11:04:16.606 (SIGNALS\BM000005.SFP)(4)


Number Indication Value Date and time Cause State

01332 Earth fault protection is BLOCKED OFF 08.04.2018 05:16:38.273 Spontaneous


Com.Issued=AutoLocal
14083 E/F 3I0p is blocked OFF 08.04.2018 05:16:38.273 Spontaneous
Com.Issued=AutoLocal
00592 Single pole open detected in L2 OFF 08.04.2018 05:16:38.243 Spontaneous
Com.Issued=AutoLocal
01332 Earth fault protection is BLOCKED ON 08.04.2018 05:16:37.566 Spontaneous
Com.Issued=AutoLocal
14083 E/F 3I0p is blocked ON 08.04.2018 05:16:37.566 Spontaneous
Com.Issued=AutoLocal
00592 Single pole open detected in L2 ON 08.04.2018 05:16:37.566 Spontaneous
Com.Issued=AutoLocal
M2_TRIP OFF 08.04.2018 05:16:37.561 Spontaneous
Com.Issued=AutoLocal
01335 Earth fault protection Trip is blocked OFF 08.04.2018 05:16:37.556 Spontaneous
Com.Issued=AutoLocal
M1_TRIP ON 08.04.2018 05:16:37.553 Spontaneous
M1_TRIP OFF 08.04.2018 05:16:37.550 Spontaneous
M/TCBAR OFF 08.04.2018 05:16:37.536 Spontaneous
M CB_BO ON 08.04.2018 05:16:37.483 Spontaneous
M CB_RO ON 08.04.2018 05:16:37.483 Spontaneous
M CB_YO ON 08.04.2018 05:16:37.474 Spontaneous
M2_TRIP ON 08.04.2018 05:16:37.460 Spontaneous
Com.Issued=AutoLocal
M/TCBAR ON 08.04.2018 05:16:37.457 Spontaneous
00004 >Trigger Waveform Capture ON 08.04.2018 05:16:37.066 Spontaneous
Com.Issued=AutoLocal
M1_TRIP ON 08.04.2018 05:16:37.065 Spontaneous
01335 Earth fault protection Trip is blocked ON 08.04.2018 05:16:37.064 Spontaneous
Com.Issued=AutoLocal
00301 Power System fault 1112 - ON 08.04.2018 05:16:37.059 Spontaneous
Com.Issued=AutoLocal

Page 66 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 08-04-2018 11:04:16.606 (SIGNALS\BM000005.SFP)(5)


Number Indication Value Date and time Cause State

009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 31.03.2018 10:58:53.232 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 31.03.2018 10:58:49.533 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 31.03.2018 10:58:48.633 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 31.03.2018 10:58:41.933 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 31.03.2018 10:58:40.433 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 31.03.2018 10:58:36.133 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 31.03.2018 10:58:16.132 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 31.03.2018 10:58:06.032 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 31.03.2018 10:58:04.832 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 31.03.2018 10:57:55.132 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 31.03.2018 10:57:51.332 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 31.03.2018 10:57:45.932 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 31.03.2018 10:57:31.932 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 31.03.2018 10:57:25.032 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 31.03.2018 10:57:24.332 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 31.03.2018 10:57:17.432 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 31.03.2018 10:57:15.932 Spontaneous
Com.Issued=AutoLocal

Page 67 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 08-04-2018 11:04:16.606 (SIGNALS\BM000005.SFP)(6)


Number Indication Value Date and time Cause State

009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 31.03.2018 10:57:11.632 Spontaneous


Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 31.03.2018 10:56:51.632 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 31.03.2018 10:56:43.732 Spontaneous
Com.Issued=AutoLocal
00060 Reset LED ON 31.03.2018 09:33:35.382 Spontaneous
Com.Issued=AutoLocal
Reset LED ON 31.03.2018 09:33:35.382 Spontaneous
Command Issued=Local
M CB_BO OFF 05.03.2018 18:03:22.928 Spontaneous
M CB_YO OFF 05.03.2018 18:03:22.928 Spontaneous
M CB_RO OFF 05.03.2018 18:03:22.928 Spontaneous
00068 Clock Synchronization Error ON 22.02.2018 11:28:41.932 Spontaneous
Com.Issued=AutoLocal
009.0100.01 Failure EN100 Modul OFF 22.02.2018 11:19:06.307 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 22.02.2018 11:18:36.132 Spontaneous
Com.Issued=AutoLocal
009.0102.01 Failure EN100 Link Channel 2 (Ch2) ON 22.02.2018 11:18:36.032 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 22.02.2018 11:18:36.032 Spontaneous
Com.Issued=AutoLocal
00051 Device is Operational and Protecting ON 22.02.2018 11:18:35.905 Spontaneous
Com.Issued=AutoLocal
10229 U1<(<) Undervolt. is switched OFF ON 22.02.2018 11:18:35.845 Spontaneous
Com.Issued=AutoLocal
10227 Uph-ph<(<) Undervolt. is switched OFF ON 22.02.2018 11:18:35.845 Spontaneous
Com.Issued=AutoLocal
10225 Uph-e<(<) Undervolt. is switched OFF ON 22.02.2018 11:18:35.844 Spontaneous
Com.Issued=AutoLocal
10223 U2>(>) Overvolt. is switched OFF ON 22.02.2018 11:18:35.844 Spontaneous
Com.Issued=AutoLocal

Page 68 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 08-04-2018 11:04:16.606 (SIGNALS\BM000005.SFP)(7)


Number Indication Value Date and time Cause State

10221 U1>(>) Overvolt. is switched OFF ON 22.02.2018 11:18:35.844 Spontaneous


Com.Issued=AutoLocal
10219 3U0>(>) Overvolt. is switched OFF ON 22.02.2018 11:18:35.844 Spontaneous
Com.Issued=AutoLocal
10217 Uph-ph>(>) Overvolt. is switched OFF ON 22.02.2018 11:18:35.844 Spontaneous
Com.Issued=AutoLocal
10231 Over-/Under-Voltage protection is ACTIVE ON 22.02.2018 11:18:35.844 Spontaneous
Com.Issued=AutoLocal
07152 Backup O/C is BLOCKED ON 22.02.2018 11:18:35.844 Spontaneous
Com.Issued=AutoLocal
M CB_BO ON 22.02.2018 11:18:35.843 Spontaneous
M CB_YO ON 22.02.2018 11:18:35.843 Spontaneous
M CB_RO ON 22.02.2018 11:18:35.843 Spontaneous
PREPARE 3P OFF 22.02.2018 11:18:35.843 Spontaneous
00067 Resume ON 22.02.2018 11:18:35.818 Spontaneous
Com.Issued=AutoLocal
00052 At Least 1 Protection Funct. is Active ON 22.02.2018 11:18:35.842 Spontaneous
Com.Issued=AutoLocal
009.0100.01 Failure EN100 Modul ON 22.02.2018 11:18:35.841 Spontaneous
Com.Issued=AutoLocal
00381 >Single-phase trip permitted from ext.AR ON 22.02.2018 11:14:18.095 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P ON 22.02.2018 11:14:18.095 Spontaneous
00068 Clock Synchronization Error ON 21.02.2018 15:57:20.932 Spontaneous
Com.Issued=AutoLocal
009.0100.01 Failure EN100 Modul OFF 21.02.2018 15:47:45.299 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 21.02.2018 15:47:15.132 Spontaneous
Com.Issued=AutoLocal
009.0102.01 Failure EN100 Link Channel 2 (Ch2) ON 21.02.2018 15:47:15.032 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 21.02.2018 15:47:15.032 Spontaneous
Com.Issued=AutoLocal

Page 69 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 08-04-2018 11:04:16.606 (SIGNALS\BM000005.SFP)(8)


Number Indication Value Date and time Cause State

00051 Device is Operational and Protecting ON 21.02.2018 15:47:14.905 Spontaneous


Com.Issued=AutoLocal
10229 U1<(<) Undervolt. is switched OFF ON 21.02.2018 15:47:14.845 Spontaneous
Com.Issued=AutoLocal
10227 Uph-ph<(<) Undervolt. is switched OFF ON 21.02.2018 15:47:14.845 Spontaneous
Com.Issued=AutoLocal
10225 Uph-e<(<) Undervolt. is switched OFF ON 21.02.2018 15:47:14.845 Spontaneous
Com.Issued=AutoLocal
10223 U2>(>) Overvolt. is switched OFF ON 21.02.2018 15:47:14.844 Spontaneous
Com.Issued=AutoLocal
10221 U1>(>) Overvolt. is switched OFF ON 21.02.2018 15:47:14.844 Spontaneous
Com.Issued=AutoLocal
10219 3U0>(>) Overvolt. is switched OFF ON 21.02.2018 15:47:14.844 Spontaneous
Com.Issued=AutoLocal
10217 Uph-ph>(>) Overvolt. is switched OFF ON 21.02.2018 15:47:14.844 Spontaneous
Com.Issued=AutoLocal
10231 Over-/Under-Voltage protection is ACTIVE ON 21.02.2018 15:47:14.844 Spontaneous
Com.Issued=AutoLocal
07152 Backup O/C is BLOCKED ON 21.02.2018 15:47:14.844 Spontaneous
Com.Issued=AutoLocal
M CB_BO ON 21.02.2018 15:47:14.843 Spontaneous
M CB_YO ON 21.02.2018 15:47:14.843 Spontaneous
M CB_RO ON 21.02.2018 15:47:14.843 Spontaneous
PREPARE 3P OFF 21.02.2018 15:47:14.843 Spontaneous
00067 Resume ON 21.02.2018 15:47:14.818 Spontaneous
Com.Issued=AutoLocal
00052 At Least 1 Protection Funct. is Active ON 21.02.2018 15:47:14.842 Spontaneous
Com.Issued=AutoLocal
009.0100.01 Failure EN100 Modul ON 21.02.2018 15:47:14.841 Spontaneous
Com.Issued=AutoLocal
00381 >Single-phase trip permitted from ext.AR ON 21.02.2018 15:42:34.367 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P ON 21.02.2018 15:42:34.360 Spontaneous

Page 70 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 08-04-2018 11:04:16.606 (SIGNALS\BM000005.SFP)(9)


Number Indication Value Date and time Cause State

00004 >Trigger Waveform Capture ON 21.02.2018 09:52:20.927 Spontaneous


Com.Issued=AutoLocal
M CB_RO ON 21.02.2018 09:52:20.925 Spontaneous
M CB_BO ON 21.02.2018 09:52:20.924 Spontaneous
M CB_YO ON 21.02.2018 09:52:20.921 Spontaneous
00060 Reset LED ON 30.01.2018 10:10:31.334 Spontaneous
Com.Issued=AutoLocal
Reset LED ON 30.01.2018 10:10:31.334 Spontaneous
Command Issued=Local
00070 Setting calculation is running OFF 30.01.2018 10:10:24.808 Spontaneous
Com.Issued=AutoLocal
00070 Setting calculation is running ON 30.01.2018 10:09:56.631 Spontaneous
Com.Issued=AutoLocal
00070 Setting calculation is running OFF 30.01.2018 10:02:39.540 Spontaneous
Com.Issued=AutoLocal
00072 Level-2 change ON 30.01.2018 10:02:39.539 Spontaneous
Com.Issued=AutoLocal
00070 Setting calculation is running ON 30.01.2018 10:02:14.628 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 23.01.2018 01:17:13.332 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 23.01.2018 01:17:09.632 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 23.01.2018 01:17:08.732 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 23.01.2018 01:17:02.031 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 23.01.2018 01:17:00.631 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 23.01.2018 01:16:56.231 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 23.01.2018 01:16:36.331 Spontaneous
Com.Issued=AutoLocal

Page 71 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 08-04-2018 11:04:16.606 (SIGNALS\BM000005.SFP)(10)


Number Indication Value Date and time Cause State

009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 23.01.2018 00:47:21.732 Spontaneous


Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 20.12.2017 22:33:59.031 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 20.12.2017 22:33:55.331 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 20.12.2017 22:33:54.531 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 20.12.2017 22:33:47.731 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 20.12.2017 22:33:46.231 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 20.12.2017 22:33:41.931 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 20.12.2017 22:33:22.131 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 20.12.2017 22:33:18.331 Spontaneous
Com.Issued=AutoLocal
00590 Line closure detected OFF 31.10.2017 19:12:30.449 Spontaneous
Com.Issued=AutoLocal
M1_TRIP OFF 31.10.2017 19:12:30.396 Spontaneous
00301 Power System fault 1109 - OFF 31.10.2017 19:12:30.385 Spontaneous
Com.Issued=AutoLocal
00004 >Trigger Waveform Capture ON 31.10.2017 19:12:30.377 Spontaneous
Com.Issued=AutoLocal
M1_TRIP ON 31.10.2017 19:12:30.368 Spontaneous
00301 Power System fault 1109 - ON 31.10.2017 19:12:30.344 Spontaneous
Com.Issued=AutoLocal
M CB_BO OFF 31.10.2017 19:12:30.261 Spontaneous
M CB_YO OFF 31.10.2017 19:12:30.261 Spontaneous
M CB_RO OFF 31.10.2017 19:12:30.261 Spontaneous
00590 Line closure detected ON 31.10.2017 19:12:30.246 Spontaneous
Com.Issued=AutoLocal

Page 72 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 08-04-2018 11:04:16.606 (SIGNALS\BM000005.SFP)(11)


Number Indication Value Date and time Cause State

00060 Reset LED ON 31.10.2017 19:11:11.700 Spontaneous


Com.Issued=AutoLocal
Reset LED ON 31.10.2017 19:11:11.700 Spontaneous
Command Issued=Local
M1_TRIP OFF 31.10.2017 19:11:08.733 Spontaneous
00301 Power System fault 1108 - OFF 31.10.2017 19:11:08.723 Spontaneous
Com.Issued=AutoLocal
M2_TRIP OFF 31.10.2017 19:11:08.723 Spontaneous
Com.Issued=AutoLocal
00060 Reset LED ON 31.10.2017 19:09:00.910 Spontaneous
Com.Issued=AutoLocal
Reset LED ON 31.10.2017 19:09:00.910 Spontaneous
Command Issued=Local
00060 Reset LED ON 31.10.2017 19:09:00.000 Spontaneous
Com.Issued=AutoLocal
Reset LED ON 31.10.2017 19:09:00.000 Spontaneous
Command Issued=Local
00060 Reset LED ON 31.10.2017 19:08:55.410 Spontaneous
Com.Issued=AutoLocal
Reset LED ON 31.10.2017 19:08:55.410 Spontaneous
Command Issued=Local
00060 Reset LED ON 31.10.2017 19:08:10.411 Spontaneous
Com.Issued=AutoLocal
Reset LED ON 31.10.2017 19:08:10.410 Spontaneous
Command Issued=Local
00060 Reset LED ON 31.10.2017 19:07:59.201 Spontaneous
Com.Issued=AutoLocal
Reset LED ON 31.10.2017 19:07:59.201 Spontaneous
Command Issued=Local
00060 Reset LED ON 31.10.2017 19:07:57.501 Spontaneous
Com.Issued=AutoLocal
Reset LED ON 31.10.2017 19:07:57.501 Spontaneous
Command Issued=Local

Page 73 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 08-04-2018 11:04:16.606 (SIGNALS\BM000005.SFP)(12)


Number Indication Value Date and time Cause State

M2_TRIP ON 31.10.2017 19:06:16.981 Spontaneous


Com.Issued=AutoLocal
00004 >Trigger Waveform Capture ON 31.10.2017 19:06:12.008 Spontaneous
Com.Issued=AutoLocal
M1_TRIP ON 31.10.2017 19:06:12.005 Spontaneous
00301 Power System fault 1108 - ON 31.10.2017 19:06:11.983 Spontaneous
Com.Issued=AutoLocal
04010 >Dis.Tele. Carrier RECEPTION Channel 2 OFF 31.10.2017 18:24:11.962 Spontaneous
Com.Issued=AutoLocal

6.6 Event Log - 11-04-2018 16:23:49.352 (SIGNALS\BM000006.SFP)

Event Log - 11-04-2018 16:23:49.352 (SIGNALS\BM000006.SFP)


Number Indication Value Date and time Cause State

00381 >Single-phase trip permitted from ext.AR ON 08.04.2018 06:41:50.974 Spontaneous


Com.Issued=AutoLocal
PREPARE 3P ON 08.04.2018 06:41:50.974 Spontaneous
M1_TRIP OFF 08.04.2018 06:40:22.747 Spontaneous
00301 Power System fault 1115 - OFF 08.04.2018 06:40:22.737 Spontaneous
Com.Issued=AutoLocal
M2_TRIP OFF 08.04.2018 06:40:22.737 Spontaneous
Com.Issued=AutoLocal
M/TCBAR OFF 08.04.2018 06:40:22.732 Spontaneous
00381 >Single-phase trip permitted from ext.AR OFF 08.04.2018 06:37:47.110 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P OFF 08.04.2018 06:37:47.110 Spontaneous
M/TCBAR ON 08.04.2018 06:37:47.053 Spontaneous
M2_TRIP ON 08.04.2018 06:37:47.047 Spontaneous
Com.Issued=AutoLocal
00004 >Trigger Waveform Capture ON 08.04.2018 06:37:42.072 Spontaneous
Com.Issued=AutoLocal

Page 74 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 11-04-2018 16:23:49.352 (SIGNALS\BM000006.SFP)(2)


Number Indication Value Date and time Cause State

M1_TRIP ON 08.04.2018 06:37:42.072 Spontaneous


00301 Power System fault 1115 - ON 08.04.2018 06:37:42.049 Spontaneous
Com.Issued=AutoLocal
00381 >Single-phase trip permitted from ext.AR ON 08.04.2018 06:28:59.555 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P ON 08.04.2018 06:28:59.555 Spontaneous
00060 Reset LED ON 08.04.2018 06:28:47.796 Spontaneous
Com.Issued=AutoLocal
Reset LED ON 08.04.2018 06:28:47.796 Spontaneous
Command Issued=Local
M1_TRIP OFF 08.04.2018 06:26:25.537 Spontaneous
00301 Power System fault 1114 - OFF 08.04.2018 06:26:25.526 Spontaneous
Com.Issued=AutoLocal
M2_TRIP OFF 08.04.2018 06:26:25.526 Spontaneous
Com.Issued=AutoLocal
M/TCBAR OFF 08.04.2018 06:26:25.523 Spontaneous
00060 Reset LED ON 08.04.2018 05:58:38.684 Spontaneous
Com.Issued=AutoLocal
Reset LED ON 08.04.2018 05:58:38.684 Spontaneous
Command Issued=Local
M/TCBAR ON 08.04.2018 05:41:43.973 Spontaneous
M2_TRIP ON 08.04.2018 05:41:43.947 Spontaneous
Com.Issued=AutoLocal
00004 >Trigger Waveform Capture ON 08.04.2018 05:41:38.971 Spontaneous
Com.Issued=AutoLocal
M1_TRIP ON 08.04.2018 05:41:38.971 Spontaneous
00301 Power System fault 1114 - ON 08.04.2018 05:41:38.949 Spontaneous
Com.Issued=AutoLocal
M1_TRIP OFF 08.04.2018 05:41:38.619 Spontaneous
M/TCBAR OFF 08.04.2018 05:41:38.612 Spontaneous
00301 Power System fault 1113 - OFF 08.04.2018 05:41:38.611 Spontaneous
Com.Issued=AutoLocal

Page 75 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 11-04-2018 16:23:49.352 (SIGNALS\BM000006.SFP)(3)


Number Indication Value Date and time Cause State

M2_TRIP OFF 08.04.2018 05:41:38.609 Spontaneous


Com.Issued=AutoLocal
00060 Reset LED ON 08.04.2018 05:39:07.978 Spontaneous
Com.Issued=AutoLocal
Reset LED ON 08.04.2018 05:39:07.976 Spontaneous
Command Issued=Local
00060 Reset LED ON 08.04.2018 05:39:06.975 Spontaneous
Com.Issued=AutoLocal
Reset LED ON 08.04.2018 05:39:06.975 Spontaneous
Command Issued=Local
M/TCBAR ON 08.04.2018 05:26:53.543 Spontaneous
M2_TRIP ON 08.04.2018 05:26:53.527 Spontaneous
Com.Issued=AutoLocal
00004 >Trigger Waveform Capture ON 08.04.2018 05:26:48.554 Spontaneous
Com.Issued=AutoLocal
M1_TRIP ON 08.04.2018 05:26:48.554 Spontaneous
00301 Power System fault 1113 - ON 08.04.2018 05:26:48.531 Spontaneous
Com.Issued=AutoLocal
M1_TRIP OFF 08.04.2018 05:26:48.402 Spontaneous
00301 Power System fault 1112 - OFF 08.04.2018 05:26:48.391 Spontaneous
Com.Issued=AutoLocal
M2_TRIP OFF 08.04.2018 05:26:48.391 Spontaneous
Com.Issued=AutoLocal
M/TCBAR OFF 08.04.2018 05:26:48.378 Spontaneous
M2_TRIP ON 08.04.2018 05:16:42.528 Spontaneous
Com.Issued=AutoLocal
00004 >Trigger Waveform Capture ON 08.04.2018 05:16:42.526 Spontaneous
Com.Issued=AutoLocal
M/TCBAR ON 08.04.2018 05:16:42.526 Spontaneous
01332 Earth fault protection is BLOCKED OFF 08.04.2018 05:16:38.273 Spontaneous
Com.Issued=AutoLocal
14083 E/F 3I0p is blocked OFF 08.04.2018 05:16:38.273 Spontaneous
Com.Issued=AutoLocal

Page 76 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 11-04-2018 16:23:49.352 (SIGNALS\BM000006.SFP)(4)


Number Indication Value Date and time Cause State

00592 Single pole open detected in L2 OFF 08.04.2018 05:16:38.243 Spontaneous


Com.Issued=AutoLocal
01332 Earth fault protection is BLOCKED ON 08.04.2018 05:16:37.566 Spontaneous
Com.Issued=AutoLocal
14083 E/F 3I0p is blocked ON 08.04.2018 05:16:37.566 Spontaneous
Com.Issued=AutoLocal
00592 Single pole open detected in L2 ON 08.04.2018 05:16:37.566 Spontaneous
Com.Issued=AutoLocal
M2_TRIP OFF 08.04.2018 05:16:37.561 Spontaneous
Com.Issued=AutoLocal
01335 Earth fault protection Trip is blocked OFF 08.04.2018 05:16:37.556 Spontaneous
Com.Issued=AutoLocal
M1_TRIP ON 08.04.2018 05:16:37.553 Spontaneous
M1_TRIP OFF 08.04.2018 05:16:37.550 Spontaneous
M/TCBAR OFF 08.04.2018 05:16:37.536 Spontaneous
M CB_BO ON 08.04.2018 05:16:37.483 Spontaneous
M CB_RO ON 08.04.2018 05:16:37.483 Spontaneous
M CB_YO ON 08.04.2018 05:16:37.474 Spontaneous
M2_TRIP ON 08.04.2018 05:16:37.460 Spontaneous
Com.Issued=AutoLocal
M/TCBAR ON 08.04.2018 05:16:37.457 Spontaneous
00004 >Trigger Waveform Capture ON 08.04.2018 05:16:37.066 Spontaneous
Com.Issued=AutoLocal
M1_TRIP ON 08.04.2018 05:16:37.065 Spontaneous
01335 Earth fault protection Trip is blocked ON 08.04.2018 05:16:37.064 Spontaneous
Com.Issued=AutoLocal
00301 Power System fault 1112 - ON 08.04.2018 05:16:37.059 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 31.03.2018 10:58:53.232 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 31.03.2018 10:58:49.533 Spontaneous
Com.Issued=AutoLocal

Page 77 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 11-04-2018 16:23:49.352 (SIGNALS\BM000006.SFP)(5)


Number Indication Value Date and time Cause State

009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 31.03.2018 10:58:48.633 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 31.03.2018 10:58:41.933 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 31.03.2018 10:58:40.433 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 31.03.2018 10:58:36.133 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 31.03.2018 10:58:16.132 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 31.03.2018 10:58:06.032 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 31.03.2018 10:58:04.832 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 31.03.2018 10:57:55.132 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 31.03.2018 10:57:51.332 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 31.03.2018 10:57:45.932 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 31.03.2018 10:57:31.932 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 31.03.2018 10:57:25.032 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 31.03.2018 10:57:24.332 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 31.03.2018 10:57:17.432 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 31.03.2018 10:57:15.932 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 31.03.2018 10:57:11.632 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 31.03.2018 10:56:51.632 Spontaneous
Com.Issued=AutoLocal

Page 78 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 11-04-2018 16:23:49.352 (SIGNALS\BM000006.SFP)(6)


Number Indication Value Date and time Cause State

009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 31.03.2018 10:56:43.732 Spontaneous


Com.Issued=AutoLocal
00060 Reset LED ON 31.03.2018 09:33:35.382 Spontaneous
Com.Issued=AutoLocal
Reset LED ON 31.03.2018 09:33:35.382 Spontaneous
Command Issued=Local
M CB_BO OFF 05.03.2018 18:03:22.928 Spontaneous
M CB_YO OFF 05.03.2018 18:03:22.928 Spontaneous
M CB_RO OFF 05.03.2018 18:03:22.928 Spontaneous
00068 Clock Synchronization Error ON 22.02.2018 11:28:41.932 Spontaneous
Com.Issued=AutoLocal
009.0100.01 Failure EN100 Modul OFF 22.02.2018 11:19:06.307 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 22.02.2018 11:18:36.132 Spontaneous
Com.Issued=AutoLocal
009.0102.01 Failure EN100 Link Channel 2 (Ch2) ON 22.02.2018 11:18:36.032 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 22.02.2018 11:18:36.032 Spontaneous
Com.Issued=AutoLocal
00051 Device is Operational and Protecting ON 22.02.2018 11:18:35.905 Spontaneous
Com.Issued=AutoLocal
10229 U1<(<) Undervolt. is switched OFF ON 22.02.2018 11:18:35.845 Spontaneous
Com.Issued=AutoLocal
10227 Uph-ph<(<) Undervolt. is switched OFF ON 22.02.2018 11:18:35.845 Spontaneous
Com.Issued=AutoLocal
10225 Uph-e<(<) Undervolt. is switched OFF ON 22.02.2018 11:18:35.844 Spontaneous
Com.Issued=AutoLocal
10223 U2>(>) Overvolt. is switched OFF ON 22.02.2018 11:18:35.844 Spontaneous
Com.Issued=AutoLocal
10221 U1>(>) Overvolt. is switched OFF ON 22.02.2018 11:18:35.844 Spontaneous
Com.Issued=AutoLocal
10219 3U0>(>) Overvolt. is switched OFF ON 22.02.2018 11:18:35.844 Spontaneous
Com.Issued=AutoLocal

Page 79 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 11-04-2018 16:23:49.352 (SIGNALS\BM000006.SFP)(7)


Number Indication Value Date and time Cause State

10217 Uph-ph>(>) Overvolt. is switched OFF ON 22.02.2018 11:18:35.844 Spontaneous


Com.Issued=AutoLocal
10231 Over-/Under-Voltage protection is ACTIVE ON 22.02.2018 11:18:35.844 Spontaneous
Com.Issued=AutoLocal
07152 Backup O/C is BLOCKED ON 22.02.2018 11:18:35.844 Spontaneous
Com.Issued=AutoLocal
M CB_BO ON 22.02.2018 11:18:35.843 Spontaneous
M CB_YO ON 22.02.2018 11:18:35.843 Spontaneous
M CB_RO ON 22.02.2018 11:18:35.843 Spontaneous
PREPARE 3P OFF 22.02.2018 11:18:35.843 Spontaneous
00067 Resume ON 22.02.2018 11:18:35.818 Spontaneous
Com.Issued=AutoLocal
00052 At Least 1 Protection Funct. is Active ON 22.02.2018 11:18:35.842 Spontaneous
Com.Issued=AutoLocal
009.0100.01 Failure EN100 Modul ON 22.02.2018 11:18:35.841 Spontaneous
Com.Issued=AutoLocal
00381 >Single-phase trip permitted from ext.AR ON 22.02.2018 11:14:18.095 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P ON 22.02.2018 11:14:18.095 Spontaneous
00068 Clock Synchronization Error ON 21.02.2018 15:57:20.932 Spontaneous
Com.Issued=AutoLocal
009.0100.01 Failure EN100 Modul OFF 21.02.2018 15:47:45.299 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 21.02.2018 15:47:15.132 Spontaneous
Com.Issued=AutoLocal
009.0102.01 Failure EN100 Link Channel 2 (Ch2) ON 21.02.2018 15:47:15.032 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 21.02.2018 15:47:15.032 Spontaneous
Com.Issued=AutoLocal
00051 Device is Operational and Protecting ON 21.02.2018 15:47:14.905 Spontaneous
Com.Issued=AutoLocal
10229 U1<(<) Undervolt. is switched OFF ON 21.02.2018 15:47:14.845 Spontaneous
Com.Issued=AutoLocal

Page 80 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 11-04-2018 16:23:49.352 (SIGNALS\BM000006.SFP)(8)


Number Indication Value Date and time Cause State

10227 Uph-ph<(<) Undervolt. is switched OFF ON 21.02.2018 15:47:14.845 Spontaneous


Com.Issued=AutoLocal
10225 Uph-e<(<) Undervolt. is switched OFF ON 21.02.2018 15:47:14.845 Spontaneous
Com.Issued=AutoLocal
10223 U2>(>) Overvolt. is switched OFF ON 21.02.2018 15:47:14.844 Spontaneous
Com.Issued=AutoLocal
10221 U1>(>) Overvolt. is switched OFF ON 21.02.2018 15:47:14.844 Spontaneous
Com.Issued=AutoLocal
10219 3U0>(>) Overvolt. is switched OFF ON 21.02.2018 15:47:14.844 Spontaneous
Com.Issued=AutoLocal
10217 Uph-ph>(>) Overvolt. is switched OFF ON 21.02.2018 15:47:14.844 Spontaneous
Com.Issued=AutoLocal
10231 Over-/Under-Voltage protection is ACTIVE ON 21.02.2018 15:47:14.844 Spontaneous
Com.Issued=AutoLocal
07152 Backup O/C is BLOCKED ON 21.02.2018 15:47:14.844 Spontaneous
Com.Issued=AutoLocal
M CB_BO ON 21.02.2018 15:47:14.843 Spontaneous
M CB_YO ON 21.02.2018 15:47:14.843 Spontaneous
M CB_RO ON 21.02.2018 15:47:14.843 Spontaneous
PREPARE 3P OFF 21.02.2018 15:47:14.843 Spontaneous
00067 Resume ON 21.02.2018 15:47:14.818 Spontaneous
Com.Issued=AutoLocal
00052 At Least 1 Protection Funct. is Active ON 21.02.2018 15:47:14.842 Spontaneous
Com.Issued=AutoLocal
009.0100.01 Failure EN100 Modul ON 21.02.2018 15:47:14.841 Spontaneous
Com.Issued=AutoLocal
00381 >Single-phase trip permitted from ext.AR ON 21.02.2018 15:42:34.367 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P ON 21.02.2018 15:42:34.360 Spontaneous
00004 >Trigger Waveform Capture ON 21.02.2018 09:52:20.927 Spontaneous
Com.Issued=AutoLocal
M CB_RO ON 21.02.2018 09:52:20.925 Spontaneous
M CB_BO ON 21.02.2018 09:52:20.924 Spontaneous

Page 81 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 11-04-2018 16:23:49.352 (SIGNALS\BM000006.SFP)(9)


Number Indication Value Date and time Cause State

M CB_YO ON 21.02.2018 09:52:20.921 Spontaneous


00060 Reset LED ON 30.01.2018 10:10:31.334 Spontaneous
Com.Issued=AutoLocal
Reset LED ON 30.01.2018 10:10:31.334 Spontaneous
Command Issued=Local
00070 Setting calculation is running OFF 30.01.2018 10:10:24.808 Spontaneous
Com.Issued=AutoLocal
00070 Setting calculation is running ON 30.01.2018 10:09:56.631 Spontaneous
Com.Issued=AutoLocal
00070 Setting calculation is running OFF 30.01.2018 10:02:39.540 Spontaneous
Com.Issued=AutoLocal
00072 Level-2 change ON 30.01.2018 10:02:39.539 Spontaneous
Com.Issued=AutoLocal
00070 Setting calculation is running ON 30.01.2018 10:02:14.628 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 23.01.2018 01:17:13.332 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 23.01.2018 01:17:09.632 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 23.01.2018 01:17:08.732 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 23.01.2018 01:17:02.031 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 23.01.2018 01:17:00.631 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 23.01.2018 01:16:56.231 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 23.01.2018 01:16:36.331 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 23.01.2018 00:47:21.732 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 20.12.2017 22:33:59.031 Spontaneous
Com.Issued=AutoLocal

Page 82 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 11-04-2018 16:23:49.352 (SIGNALS\BM000006.SFP)(10)


Number Indication Value Date and time Cause State

009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 20.12.2017 22:33:55.331 Spontaneous


Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 20.12.2017 22:33:54.531 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 20.12.2017 22:33:47.731 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 20.12.2017 22:33:46.231 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 20.12.2017 22:33:41.931 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 20.12.2017 22:33:22.131 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 20.12.2017 22:33:18.331 Spontaneous
Com.Issued=AutoLocal
00590 Line closure detected OFF 31.10.2017 19:12:30.449 Spontaneous
Com.Issued=AutoLocal
M1_TRIP OFF 31.10.2017 19:12:30.396 Spontaneous
00301 Power System fault 1109 - OFF 31.10.2017 19:12:30.385 Spontaneous
Com.Issued=AutoLocal
00004 >Trigger Waveform Capture ON 31.10.2017 19:12:30.377 Spontaneous
Com.Issued=AutoLocal
M1_TRIP ON 31.10.2017 19:12:30.368 Spontaneous
00301 Power System fault 1109 - ON 31.10.2017 19:12:30.344 Spontaneous
Com.Issued=AutoLocal
M CB_BO OFF 31.10.2017 19:12:30.261 Spontaneous
M CB_YO OFF 31.10.2017 19:12:30.261 Spontaneous
M CB_RO OFF 31.10.2017 19:12:30.261 Spontaneous
00590 Line closure detected ON 31.10.2017 19:12:30.246 Spontaneous
Com.Issued=AutoLocal
00060 Reset LED ON 31.10.2017 19:11:11.700 Spontaneous
Com.Issued=AutoLocal
Reset LED ON 31.10.2017 19:11:11.700 Spontaneous
Command Issued=Local

Page 83 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 11-04-2018 16:23:49.352 (SIGNALS\BM000006.SFP)(11)


Number Indication Value Date and time Cause State

M1_TRIP OFF 31.10.2017 19:11:08.733 Spontaneous


00301 Power System fault 1108 - OFF 31.10.2017 19:11:08.723 Spontaneous
Com.Issued=AutoLocal
M2_TRIP OFF 31.10.2017 19:11:08.723 Spontaneous
Com.Issued=AutoLocal
00060 Reset LED ON 31.10.2017 19:09:00.910 Spontaneous
Com.Issued=AutoLocal
Reset LED ON 31.10.2017 19:09:00.910 Spontaneous
Command Issued=Local
00060 Reset LED ON 31.10.2017 19:09:00.000 Spontaneous
Com.Issued=AutoLocal
Reset LED ON 31.10.2017 19:09:00.000 Spontaneous
Command Issued=Local
00060 Reset LED ON 31.10.2017 19:08:55.410 Spontaneous
Com.Issued=AutoLocal
Reset LED ON 31.10.2017 19:08:55.410 Spontaneous
Command Issued=Local
00060 Reset LED ON 31.10.2017 19:08:10.411 Spontaneous
Com.Issued=AutoLocal
Reset LED ON 31.10.2017 19:08:10.410 Spontaneous
Command Issued=Local
00060 Reset LED ON 31.10.2017 19:07:59.201 Spontaneous
Com.Issued=AutoLocal
Reset LED ON 31.10.2017 19:07:59.201 Spontaneous
Command Issued=Local
00060 Reset LED ON 31.10.2017 19:07:57.501 Spontaneous
Com.Issued=AutoLocal
Reset LED ON 31.10.2017 19:07:57.501 Spontaneous
Command Issued=Local
M2_TRIP ON 31.10.2017 19:06:16.981 Spontaneous
Com.Issued=AutoLocal
00004 >Trigger Waveform Capture ON 31.10.2017 19:06:12.008 Spontaneous
Com.Issued=AutoLocal
M1_TRIP ON 31.10.2017 19:06:12.005 Spontaneous

Page 84 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 11-04-2018 16:23:49.352 (SIGNALS\BM000006.SFP)(12)


Number Indication Value Date and time Cause State

00301 Power System fault 1108 - ON 31.10.2017 19:06:11.983 Spontaneous


Com.Issued=AutoLocal
04010 >Dis.Tele. Carrier RECEPTION Channel 2 OFF 31.10.2017 18:24:11.962 Spontaneous
Com.Issued=AutoLocal

6.7 Event Log - 11-04-2018 16:28:02.605 (SIGNALS\BM000007.SFP)

Event Log - 11-04-2018 16:28:02.605 (SIGNALS\BM000007.SFP)


Number Indication Value Date and time Cause State

00381 >Single-phase trip permitted from ext.AR ON 08.04.2018 06:41:50.974 Spontaneous


Com.Issued=AutoLocal
PREPARE 3P ON 08.04.2018 06:41:50.974 Spontaneous
M1_TRIP OFF 08.04.2018 06:40:22.747 Spontaneous
00301 Power System fault 1115 - OFF 08.04.2018 06:40:22.737 Spontaneous
Com.Issued=AutoLocal
M2_TRIP OFF 08.04.2018 06:40:22.737 Spontaneous
Com.Issued=AutoLocal
M/TCBAR OFF 08.04.2018 06:40:22.732 Spontaneous
00381 >Single-phase trip permitted from ext.AR OFF 08.04.2018 06:37:47.110 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P OFF 08.04.2018 06:37:47.110 Spontaneous
M/TCBAR ON 08.04.2018 06:37:47.053 Spontaneous
M2_TRIP ON 08.04.2018 06:37:47.047 Spontaneous
Com.Issued=AutoLocal
00004 >Trigger Waveform Capture ON 08.04.2018 06:37:42.072 Spontaneous
Com.Issued=AutoLocal
M1_TRIP ON 08.04.2018 06:37:42.072 Spontaneous
00301 Power System fault 1115 - ON 08.04.2018 06:37:42.049 Spontaneous
Com.Issued=AutoLocal
00381 >Single-phase trip permitted from ext.AR ON 08.04.2018 06:28:59.555 Spontaneous
Com.Issued=AutoLocal

Page 85 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 11-04-2018 16:28:02.605 (SIGNALS\BM000007.SFP)(2)


Number Indication Value Date and time Cause State

PREPARE 3P ON 08.04.2018 06:28:59.555 Spontaneous


00060 Reset LED ON 08.04.2018 06:28:47.796 Spontaneous
Com.Issued=AutoLocal
Reset LED ON 08.04.2018 06:28:47.796 Spontaneous
Command Issued=Local
M1_TRIP OFF 08.04.2018 06:26:25.537 Spontaneous
00301 Power System fault 1114 - OFF 08.04.2018 06:26:25.526 Spontaneous
Com.Issued=AutoLocal
M2_TRIP OFF 08.04.2018 06:26:25.526 Spontaneous
Com.Issued=AutoLocal
M/TCBAR OFF 08.04.2018 06:26:25.523 Spontaneous
00060 Reset LED ON 08.04.2018 05:58:38.684 Spontaneous
Com.Issued=AutoLocal
Reset LED ON 08.04.2018 05:58:38.684 Spontaneous
Command Issued=Local
M/TCBAR ON 08.04.2018 05:41:43.973 Spontaneous
M2_TRIP ON 08.04.2018 05:41:43.947 Spontaneous
Com.Issued=AutoLocal
00004 >Trigger Waveform Capture ON 08.04.2018 05:41:38.971 Spontaneous
Com.Issued=AutoLocal
M1_TRIP ON 08.04.2018 05:41:38.971 Spontaneous
00301 Power System fault 1114 - ON 08.04.2018 05:41:38.949 Spontaneous
Com.Issued=AutoLocal
M1_TRIP OFF 08.04.2018 05:41:38.619 Spontaneous
M/TCBAR OFF 08.04.2018 05:41:38.612 Spontaneous
00301 Power System fault 1113 - OFF 08.04.2018 05:41:38.611 Spontaneous
Com.Issued=AutoLocal
M2_TRIP OFF 08.04.2018 05:41:38.609 Spontaneous
Com.Issued=AutoLocal
00060 Reset LED ON 08.04.2018 05:39:07.978 Spontaneous
Com.Issued=AutoLocal
Reset LED ON 08.04.2018 05:39:07.976 Spontaneous
Command Issued=Local

Page 86 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 11-04-2018 16:28:02.605 (SIGNALS\BM000007.SFP)(3)


Number Indication Value Date and time Cause State

00060 Reset LED ON 08.04.2018 05:39:06.975 Spontaneous


Com.Issued=AutoLocal
Reset LED ON 08.04.2018 05:39:06.975 Spontaneous
Command Issued=Local
M/TCBAR ON 08.04.2018 05:26:53.543 Spontaneous
M2_TRIP ON 08.04.2018 05:26:53.527 Spontaneous
Com.Issued=AutoLocal
00004 >Trigger Waveform Capture ON 08.04.2018 05:26:48.554 Spontaneous
Com.Issued=AutoLocal
M1_TRIP ON 08.04.2018 05:26:48.554 Spontaneous
00301 Power System fault 1113 - ON 08.04.2018 05:26:48.531 Spontaneous
Com.Issued=AutoLocal
M1_TRIP OFF 08.04.2018 05:26:48.402 Spontaneous
00301 Power System fault 1112 - OFF 08.04.2018 05:26:48.391 Spontaneous
Com.Issued=AutoLocal
M2_TRIP OFF 08.04.2018 05:26:48.391 Spontaneous
Com.Issued=AutoLocal
M/TCBAR OFF 08.04.2018 05:26:48.378 Spontaneous
M2_TRIP ON 08.04.2018 05:16:42.528 Spontaneous
Com.Issued=AutoLocal
00004 >Trigger Waveform Capture ON 08.04.2018 05:16:42.526 Spontaneous
Com.Issued=AutoLocal
M/TCBAR ON 08.04.2018 05:16:42.526 Spontaneous
01332 Earth fault protection is BLOCKED OFF 08.04.2018 05:16:38.273 Spontaneous
Com.Issued=AutoLocal
14083 E/F 3I0p is blocked OFF 08.04.2018 05:16:38.273 Spontaneous
Com.Issued=AutoLocal
00592 Single pole open detected in L2 OFF 08.04.2018 05:16:38.243 Spontaneous
Com.Issued=AutoLocal
01332 Earth fault protection is BLOCKED ON 08.04.2018 05:16:37.566 Spontaneous
Com.Issued=AutoLocal
14083 E/F 3I0p is blocked ON 08.04.2018 05:16:37.566 Spontaneous
Com.Issued=AutoLocal

Page 87 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 11-04-2018 16:28:02.605 (SIGNALS\BM000007.SFP)(4)


Number Indication Value Date and time Cause State

00592 Single pole open detected in L2 ON 08.04.2018 05:16:37.566 Spontaneous


Com.Issued=AutoLocal
M2_TRIP OFF 08.04.2018 05:16:37.561 Spontaneous
Com.Issued=AutoLocal
01335 Earth fault protection Trip is blocked OFF 08.04.2018 05:16:37.556 Spontaneous
Com.Issued=AutoLocal
M1_TRIP ON 08.04.2018 05:16:37.553 Spontaneous
M1_TRIP OFF 08.04.2018 05:16:37.550 Spontaneous
M/TCBAR OFF 08.04.2018 05:16:37.536 Spontaneous
M CB_BO ON 08.04.2018 05:16:37.483 Spontaneous
M CB_RO ON 08.04.2018 05:16:37.483 Spontaneous
M CB_YO ON 08.04.2018 05:16:37.474 Spontaneous
M2_TRIP ON 08.04.2018 05:16:37.460 Spontaneous
Com.Issued=AutoLocal
M/TCBAR ON 08.04.2018 05:16:37.457 Spontaneous
00004 >Trigger Waveform Capture ON 08.04.2018 05:16:37.066 Spontaneous
Com.Issued=AutoLocal
M1_TRIP ON 08.04.2018 05:16:37.065 Spontaneous
01335 Earth fault protection Trip is blocked ON 08.04.2018 05:16:37.064 Spontaneous
Com.Issued=AutoLocal
00301 Power System fault 1112 - ON 08.04.2018 05:16:37.059 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 31.03.2018 10:58:53.232 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 31.03.2018 10:58:49.533 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 31.03.2018 10:58:48.633 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 31.03.2018 10:58:41.933 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 31.03.2018 10:58:40.433 Spontaneous
Com.Issued=AutoLocal

Page 88 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 11-04-2018 16:28:02.605 (SIGNALS\BM000007.SFP)(5)


Number Indication Value Date and time Cause State

009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 31.03.2018 10:58:36.133 Spontaneous


Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 31.03.2018 10:58:16.132 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 31.03.2018 10:58:06.032 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 31.03.2018 10:58:04.832 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 31.03.2018 10:57:55.132 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 31.03.2018 10:57:51.332 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 31.03.2018 10:57:45.932 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 31.03.2018 10:57:31.932 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 31.03.2018 10:57:25.032 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 31.03.2018 10:57:24.332 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 31.03.2018 10:57:17.432 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 31.03.2018 10:57:15.932 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 31.03.2018 10:57:11.632 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 31.03.2018 10:56:51.632 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 31.03.2018 10:56:43.732 Spontaneous
Com.Issued=AutoLocal
00060 Reset LED ON 31.03.2018 09:33:35.382 Spontaneous
Com.Issued=AutoLocal
Reset LED ON 31.03.2018 09:33:35.382 Spontaneous
Command Issued=Local

Page 89 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 11-04-2018 16:28:02.605 (SIGNALS\BM000007.SFP)(6)


Number Indication Value Date and time Cause State

M CB_BO OFF 05.03.2018 18:03:22.928 Spontaneous


M CB_YO OFF 05.03.2018 18:03:22.928 Spontaneous
M CB_RO OFF 05.03.2018 18:03:22.928 Spontaneous
00068 Clock Synchronization Error ON 22.02.2018 11:28:41.932 Spontaneous
Com.Issued=AutoLocal
009.0100.01 Failure EN100 Modul OFF 22.02.2018 11:19:06.307 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 22.02.2018 11:18:36.132 Spontaneous
Com.Issued=AutoLocal
009.0102.01 Failure EN100 Link Channel 2 (Ch2) ON 22.02.2018 11:18:36.032 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 22.02.2018 11:18:36.032 Spontaneous
Com.Issued=AutoLocal
00051 Device is Operational and Protecting ON 22.02.2018 11:18:35.905 Spontaneous
Com.Issued=AutoLocal
10229 U1<(<) Undervolt. is switched OFF ON 22.02.2018 11:18:35.845 Spontaneous
Com.Issued=AutoLocal
10227 Uph-ph<(<) Undervolt. is switched OFF ON 22.02.2018 11:18:35.845 Spontaneous
Com.Issued=AutoLocal
10225 Uph-e<(<) Undervolt. is switched OFF ON 22.02.2018 11:18:35.844 Spontaneous
Com.Issued=AutoLocal
10223 U2>(>) Overvolt. is switched OFF ON 22.02.2018 11:18:35.844 Spontaneous
Com.Issued=AutoLocal
10221 U1>(>) Overvolt. is switched OFF ON 22.02.2018 11:18:35.844 Spontaneous
Com.Issued=AutoLocal
10219 3U0>(>) Overvolt. is switched OFF ON 22.02.2018 11:18:35.844 Spontaneous
Com.Issued=AutoLocal
10217 Uph-ph>(>) Overvolt. is switched OFF ON 22.02.2018 11:18:35.844 Spontaneous
Com.Issued=AutoLocal
10231 Over-/Under-Voltage protection is ACTIVE ON 22.02.2018 11:18:35.844 Spontaneous
Com.Issued=AutoLocal
07152 Backup O/C is BLOCKED ON 22.02.2018 11:18:35.844 Spontaneous
Com.Issued=AutoLocal

Page 90 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 11-04-2018 16:28:02.605 (SIGNALS\BM000007.SFP)(7)


Number Indication Value Date and time Cause State

M CB_BO ON 22.02.2018 11:18:35.843 Spontaneous


M CB_YO ON 22.02.2018 11:18:35.843 Spontaneous
M CB_RO ON 22.02.2018 11:18:35.843 Spontaneous
PREPARE 3P OFF 22.02.2018 11:18:35.843 Spontaneous
00067 Resume ON 22.02.2018 11:18:35.818 Spontaneous
Com.Issued=AutoLocal
00052 At Least 1 Protection Funct. is Active ON 22.02.2018 11:18:35.842 Spontaneous
Com.Issued=AutoLocal
009.0100.01 Failure EN100 Modul ON 22.02.2018 11:18:35.841 Spontaneous
Com.Issued=AutoLocal
00381 >Single-phase trip permitted from ext.AR ON 22.02.2018 11:14:18.095 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P ON 22.02.2018 11:14:18.095 Spontaneous
00068 Clock Synchronization Error ON 21.02.2018 15:57:20.932 Spontaneous
Com.Issued=AutoLocal
009.0100.01 Failure EN100 Modul OFF 21.02.2018 15:47:45.299 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 21.02.2018 15:47:15.132 Spontaneous
Com.Issued=AutoLocal
009.0102.01 Failure EN100 Link Channel 2 (Ch2) ON 21.02.2018 15:47:15.032 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 21.02.2018 15:47:15.032 Spontaneous
Com.Issued=AutoLocal
00051 Device is Operational and Protecting ON 21.02.2018 15:47:14.905 Spontaneous
Com.Issued=AutoLocal
10229 U1<(<) Undervolt. is switched OFF ON 21.02.2018 15:47:14.845 Spontaneous
Com.Issued=AutoLocal
10227 Uph-ph<(<) Undervolt. is switched OFF ON 21.02.2018 15:47:14.845 Spontaneous
Com.Issued=AutoLocal
10225 Uph-e<(<) Undervolt. is switched OFF ON 21.02.2018 15:47:14.845 Spontaneous
Com.Issued=AutoLocal
10223 U2>(>) Overvolt. is switched OFF ON 21.02.2018 15:47:14.844 Spontaneous
Com.Issued=AutoLocal

Page 91 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 11-04-2018 16:28:02.605 (SIGNALS\BM000007.SFP)(8)


Number Indication Value Date and time Cause State

10221 U1>(>) Overvolt. is switched OFF ON 21.02.2018 15:47:14.844 Spontaneous


Com.Issued=AutoLocal
10219 3U0>(>) Overvolt. is switched OFF ON 21.02.2018 15:47:14.844 Spontaneous
Com.Issued=AutoLocal
10217 Uph-ph>(>) Overvolt. is switched OFF ON 21.02.2018 15:47:14.844 Spontaneous
Com.Issued=AutoLocal
10231 Over-/Under-Voltage protection is ACTIVE ON 21.02.2018 15:47:14.844 Spontaneous
Com.Issued=AutoLocal
07152 Backup O/C is BLOCKED ON 21.02.2018 15:47:14.844 Spontaneous
Com.Issued=AutoLocal
M CB_BO ON 21.02.2018 15:47:14.843 Spontaneous
M CB_YO ON 21.02.2018 15:47:14.843 Spontaneous
M CB_RO ON 21.02.2018 15:47:14.843 Spontaneous
PREPARE 3P OFF 21.02.2018 15:47:14.843 Spontaneous
00067 Resume ON 21.02.2018 15:47:14.818 Spontaneous
Com.Issued=AutoLocal
00052 At Least 1 Protection Funct. is Active ON 21.02.2018 15:47:14.842 Spontaneous
Com.Issued=AutoLocal
009.0100.01 Failure EN100 Modul ON 21.02.2018 15:47:14.841 Spontaneous
Com.Issued=AutoLocal
00381 >Single-phase trip permitted from ext.AR ON 21.02.2018 15:42:34.367 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P ON 21.02.2018 15:42:34.360 Spontaneous
00004 >Trigger Waveform Capture ON 21.02.2018 09:52:20.927 Spontaneous
Com.Issued=AutoLocal
M CB_RO ON 21.02.2018 09:52:20.925 Spontaneous
M CB_BO ON 21.02.2018 09:52:20.924 Spontaneous
M CB_YO ON 21.02.2018 09:52:20.921 Spontaneous
00060 Reset LED ON 30.01.2018 10:10:31.334 Spontaneous
Com.Issued=AutoLocal
Reset LED ON 30.01.2018 10:10:31.334 Spontaneous
Command Issued=Local

Page 92 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 11-04-2018 16:28:02.605 (SIGNALS\BM000007.SFP)(9)


Number Indication Value Date and time Cause State

00070 Setting calculation is running OFF 30.01.2018 10:10:24.808 Spontaneous


Com.Issued=AutoLocal
00070 Setting calculation is running ON 30.01.2018 10:09:56.631 Spontaneous
Com.Issued=AutoLocal
00070 Setting calculation is running OFF 30.01.2018 10:02:39.540 Spontaneous
Com.Issued=AutoLocal
00072 Level-2 change ON 30.01.2018 10:02:39.539 Spontaneous
Com.Issued=AutoLocal
00070 Setting calculation is running ON 30.01.2018 10:02:14.628 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 23.01.2018 01:17:13.332 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 23.01.2018 01:17:09.632 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 23.01.2018 01:17:08.732 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 23.01.2018 01:17:02.031 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 23.01.2018 01:17:00.631 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 23.01.2018 01:16:56.231 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 23.01.2018 01:16:36.331 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 23.01.2018 00:47:21.732 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 20.12.2017 22:33:59.031 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 20.12.2017 22:33:55.331 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 20.12.2017 22:33:54.531 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 20.12.2017 22:33:47.731 Spontaneous
Com.Issued=AutoLocal

Page 93 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 11-04-2018 16:28:02.605 (SIGNALS\BM000007.SFP)(10)


Number Indication Value Date and time Cause State

009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 20.12.2017 22:33:46.231 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 20.12.2017 22:33:41.931 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 20.12.2017 22:33:22.131 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 20.12.2017 22:33:18.331 Spontaneous
Com.Issued=AutoLocal
00590 Line closure detected OFF 31.10.2017 19:12:30.449 Spontaneous
Com.Issued=AutoLocal
M1_TRIP OFF 31.10.2017 19:12:30.396 Spontaneous
00301 Power System fault 1109 - OFF 31.10.2017 19:12:30.385 Spontaneous
Com.Issued=AutoLocal
00004 >Trigger Waveform Capture ON 31.10.2017 19:12:30.377 Spontaneous
Com.Issued=AutoLocal
M1_TRIP ON 31.10.2017 19:12:30.368 Spontaneous
00301 Power System fault 1109 - ON 31.10.2017 19:12:30.344 Spontaneous
Com.Issued=AutoLocal
M CB_BO OFF 31.10.2017 19:12:30.261 Spontaneous
M CB_YO OFF 31.10.2017 19:12:30.261 Spontaneous
M CB_RO OFF 31.10.2017 19:12:30.261 Spontaneous
00590 Line closure detected ON 31.10.2017 19:12:30.246 Spontaneous
Com.Issued=AutoLocal
00060 Reset LED ON 31.10.2017 19:11:11.700 Spontaneous
Com.Issued=AutoLocal
Reset LED ON 31.10.2017 19:11:11.700 Spontaneous
Command Issued=Local
M1_TRIP OFF 31.10.2017 19:11:08.733 Spontaneous
00301 Power System fault 1108 - OFF 31.10.2017 19:11:08.723 Spontaneous
Com.Issued=AutoLocal
M2_TRIP OFF 31.10.2017 19:11:08.723 Spontaneous
Com.Issued=AutoLocal

Page 94 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 11-04-2018 16:28:02.605 (SIGNALS\BM000007.SFP)(11)


Number Indication Value Date and time Cause State

00060 Reset LED ON 31.10.2017 19:09:00.910 Spontaneous


Com.Issued=AutoLocal
Reset LED ON 31.10.2017 19:09:00.910 Spontaneous
Command Issued=Local
00060 Reset LED ON 31.10.2017 19:09:00.000 Spontaneous
Com.Issued=AutoLocal
Reset LED ON 31.10.2017 19:09:00.000 Spontaneous
Command Issued=Local
00060 Reset LED ON 31.10.2017 19:08:55.410 Spontaneous
Com.Issued=AutoLocal
Reset LED ON 31.10.2017 19:08:55.410 Spontaneous
Command Issued=Local
00060 Reset LED ON 31.10.2017 19:08:10.411 Spontaneous
Com.Issued=AutoLocal
Reset LED ON 31.10.2017 19:08:10.410 Spontaneous
Command Issued=Local
00060 Reset LED ON 31.10.2017 19:07:59.201 Spontaneous
Com.Issued=AutoLocal
Reset LED ON 31.10.2017 19:07:59.201 Spontaneous
Command Issued=Local
00060 Reset LED ON 31.10.2017 19:07:57.501 Spontaneous
Com.Issued=AutoLocal
Reset LED ON 31.10.2017 19:07:57.501 Spontaneous
Command Issued=Local
M2_TRIP ON 31.10.2017 19:06:16.981 Spontaneous
Com.Issued=AutoLocal
00004 >Trigger Waveform Capture ON 31.10.2017 19:06:12.008 Spontaneous
Com.Issued=AutoLocal
M1_TRIP ON 31.10.2017 19:06:12.005 Spontaneous
00301 Power System fault 1108 - ON 31.10.2017 19:06:11.983 Spontaneous
Com.Issued=AutoLocal
04010 >Dis.Tele. Carrier RECEPTION Channel 2 OFF 31.10.2017 18:24:11.962 Spontaneous
Com.Issued=AutoLocal

Page 95 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39
Event Log - 13-06-2018 17:09:51.190 (SIGNALS\BM000008.SFP)
NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

6.8 Event Log - 13-06-2018 17:09:51.190 (SIGNALS\BM000008.SFP)

Event Log - 13-06-2018 17:09:51.190 (SIGNALS\BM000008.SFP)


Number Indication Value Date and time Cause State

M CB_BO OFF 13.06.2018 16:28:05.142 Spontaneous


M CB_YO OFF 13.06.2018 16:28:05.142 Spontaneous
M CB_RO OFF 13.06.2018 16:28:05.142 Spontaneous
M CB_BO ON 13.06.2018 12:23:40.950 Spontaneous
M CB_RO ON 13.06.2018 12:23:40.950 Spontaneous
00004 >Trigger Waveform Capture ON 13.06.2018 12:23:40.941 Spontaneous
Com.Issued=AutoLocal
M CB_YO ON 13.06.2018 12:23:40.941 Spontaneous
00060 Reset LED ON 13.06.2018 11:12:26.412 Spontaneous
Com.Issued=AutoLocal
Reset LED ON 13.06.2018 11:12:26.412 Spontaneous
Command Issued=Local
00195 Failure: Broken Conductor OFF 13.06.2018 08:46:28.817 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance OFF 13.06.2018 08:46:28.817 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 13.06.2018 05:42:01.042 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance ON 13.06.2018 05:42:01.042 Spontaneous
Com.Issued=AutoLocal
00301 Power System fault 1122 - OFF 01.06.2018 18:36:42.988 Spontaneous
Com.Issued=AutoLocal
00301 Power System fault 1122 - ON 01.06.2018 18:36:42.938 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 01.06.2018 08:48:57.540 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance OFF 01.06.2018 08:48:57.540 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 01.06.2018 02:10:56.944 Spontaneous
Com.Issued=AutoLocal

Page 96 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 13-06-2018 17:09:51.190 (SIGNALS\BM000008.SFP)(2)


Number Indication Value Date and time Cause State

00163 Failure: Current Balance ON 01.06.2018 02:10:56.944 Spontaneous


Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 01.06.2018 01:06:51.850 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance OFF 01.06.2018 01:06:51.850 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 31.05.2018 22:05:24.081 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance ON 31.05.2018 22:05:24.081 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 31.05.2018 12:15:33.204 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance OFF 31.05.2018 12:15:33.204 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 31.05.2018 12:09:10.693 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 31.05.2018 12:06:33.197 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 31.05.2018 11:35:35.643 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 31.05.2018 11:33:28.146 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 31.05.2018 10:24:25.540 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 31.05.2018 09:40:32.975 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 31.05.2018 09:07:35.424 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance ON 31.05.2018 09:07:35.424 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 31.05.2018 08:53:47.905 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance OFF 31.05.2018 08:53:47.905 Spontaneous
Com.Issued=AutoLocal

Page 97 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 13-06-2018 17:09:51.190 (SIGNALS\BM000008.SFP)(3)


Number Indication Value Date and time Cause State

00195 Failure: Broken Conductor ON 31.05.2018 08:17:35.349 Spontaneous


Com.Issued=AutoLocal
00163 Failure: Current Balance ON 31.05.2018 08:17:35.349 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 31.05.2018 07:51:30.318 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance OFF 31.05.2018 07:51:30.318 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 31.05.2018 06:31:22.697 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance ON 31.05.2018 06:31:22.697 Spontaneous
Com.Issued=AutoLocal
00301 Power System fault 1121 - OFF 31.05.2018 02:14:36.686 Spontaneous
Com.Issued=AutoLocal
00301 Power System fault 1121 - ON 31.05.2018 02:14:36.626 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 30.05.2018 12:44:39.607 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance OFF 30.05.2018 12:44:39.607 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 30.05.2018 12:28:59.581 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance ON 30.05.2018 12:28:59.581 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance OFF 30.05.2018 12:14:14.563 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance ON 30.05.2018 11:43:07.009 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance OFF 30.05.2018 11:11:34.466 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 30.05.2018 10:56:51.938 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 30.05.2018 10:17:24.387 Spontaneous
Com.Issued=AutoLocal

Page 98 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 13-06-2018 17:09:51.190 (SIGNALS\BM000008.SFP)(4)


Number Indication Value Date and time Cause State

00163 Failure: Current Balance ON 30.05.2018 10:07:29.372 Spontaneous


Com.Issued=AutoLocal
00163 Failure: Current Balance OFF 30.05.2018 08:18:39.204 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 30.05.2018 08:02:39.178 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 30.05.2018 07:58:44.174 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 30.05.2018 07:58:06.675 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 30.05.2018 07:49:34.168 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance ON 30.05.2018 07:49:34.168 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 30.05.2018 05:09:56.426 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance OFF 30.05.2018 05:09:56.426 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 30.05.2018 04:52:16.402 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance ON 30.05.2018 04:52:16.402 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 30.05.2018 02:59:41.230 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance OFF 30.05.2018 02:59:41.230 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 30.05.2018 01:30:41.093 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance ON 30.05.2018 01:30:41.093 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 30.05.2018 00:55:06.046 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance OFF 30.05.2018 00:55:06.046 Spontaneous
Com.Issued=AutoLocal

Page 99 of 182
7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 13-06-2018 17:09:51.190 (SIGNALS\BM000008.SFP)(5)


Number Indication Value Date and time Cause State

00195 Failure: Broken Conductor ON 29.05.2018 21:56:50.782 Spontaneous


Com.Issued=AutoLocal
00163 Failure: Current Balance ON 29.05.2018 21:56:50.782 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 29.05.2018 20:11:43.119 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance OFF 29.05.2018 20:11:43.119 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 29.05.2018 19:15:28.033 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance ON 29.05.2018 19:15:28.033 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 29.05.2018 17:46:42.906 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance OFF 29.05.2018 17:46:42.905 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 29.05.2018 14:56:05.150 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance ON 29.05.2018 14:56:05.150 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 29.05.2018 10:42:04.769 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance OFF 29.05.2018 10:42:04.769 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 29.05.2018 10:41:52.270 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance ON 29.05.2018 10:01:47.210 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance OFF 29.05.2018 09:29:57.167 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance ON 29.05.2018 06:24:04.384 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 29.05.2018 00:59:01.399 Spontaneous
Com.Issued=AutoLocal

Page 100 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 13-06-2018 17:09:51.190 (SIGNALS\BM000008.SFP)(6)


Number Indication Value Date and time Cause State

00163 Failure: Current Balance OFF 29.05.2018 00:59:01.399 Spontaneous


Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 28.05.2018 16:27:45.642 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 28.05.2018 16:25:00.636 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 28.05.2018 16:23:10.629 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 28.05.2018 16:17:03.118 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 28.05.2018 16:12:03.116 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 28.05.2018 16:05:43.105 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 28.05.2018 16:00:45.603 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 28.05.2018 15:39:08.065 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 28.05.2018 15:38:18.066 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 28.05.2018 15:34:55.561 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 28.05.2018 15:28:58.050 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 28.05.2018 15:26:30.544 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 28.05.2018 15:25:33.045 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 28.05.2018 15:22:13.040 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 28.05.2018 14:52:00.495 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 28.05.2018 06:51:59.782 Spontaneous
Com.Issued=AutoLocal

Page 101 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 13-06-2018 17:09:51.190 (SIGNALS\BM000008.SFP)(7)


Number Indication Value Date and time Cause State

00195 Failure: Broken Conductor ON 28.05.2018 06:31:44.752 Spontaneous


Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 28.05.2018 06:08:04.717 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 28.05.2018 06:07:29.708 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 28.05.2018 05:53:22.189 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 28.05.2018 05:51:44.692 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 28.05.2018 05:38:54.671 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 28.05.2018 05:35:24.666 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 28.05.2018 05:31:17.162 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 28.05.2018 05:03:24.614 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 28.05.2018 05:00:19.608 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 28.05.2018 04:36:54.573 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 28.05.2018 04:20:19.555 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 28.05.2018 04:19:14.555 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 28.05.2018 03:39:31.989 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 28.05.2018 00:34:26.715 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 28.05.2018 00:28:54.203 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 28.05.2018 00:25:04.199 Spontaneous
Com.Issued=AutoLocal

Page 102 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 13-06-2018 17:09:51.190 (SIGNALS\BM000008.SFP)(8)


Number Indication Value Date and time Cause State

00195 Failure: Broken Conductor OFF 27.05.2018 23:16:56.601 Spontaneous


Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 27.05.2018 22:52:01.568 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 27.05.2018 22:50:34.060 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 27.05.2018 22:25:24.028 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 27.05.2018 22:23:14.021 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 27.05.2018 22:18:29.013 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 27.05.2018 22:09:16.502 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 27.05.2018 21:13:18.915 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 27.05.2018 21:08:08.909 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 27.05.2018 21:07:08.910 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 27.05.2018 21:03:41.406 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 27.05.2018 19:12:21.236 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 26.05.2018 20:09:31.669 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 26.05.2018 19:12:21.590 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 25.05.2018 06:13:20.781 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 25.05.2018 06:11:38.274 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance ON 25.05.2018 04:44:53.143 Spontaneous
Com.Issued=AutoLocal

Page 103 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 13-06-2018 17:09:51.190 (SIGNALS\BM000008.SFP)(9)


Number Indication Value Date and time Cause State

00163 Failure: Current Balance OFF 25.05.2018 04:10:03.095 Spontaneous


Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 24.05.2018 11:21:56.590 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 24.05.2018 05:46:13.591 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance ON 24.05.2018 05:46:13.591 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 24.05.2018 03:15:48.365 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance OFF 24.05.2018 03:15:48.365 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 24.05.2018 03:05:00.851 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance ON 24.05.2018 03:05:00.851 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 24.05.2018 00:53:03.148 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance OFF 24.05.2018 00:53:03.148 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 23.05.2018 18:22:37.571 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance ON 23.05.2018 18:22:37.571 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 23.05.2018 18:06:45.045 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance OFF 23.05.2018 18:06:45.045 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 22.05.2018 11:09:57.276 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 22.05.2018 07:23:11.934 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 21.05.2018 18:59:13.324 Spontaneous
Com.Issued=AutoLocal

Page 104 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 13-06-2018 17:09:51.190 (SIGNALS\BM000008.SFP)(10)


Number Indication Value Date and time Cause State

00163 Failure: Current Balance ON 21.05.2018 18:59:13.324 Spontaneous


Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 21.05.2018 17:55:35.729 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance OFF 21.05.2018 17:55:35.729 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 21.05.2018 11:07:30.125 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance ON 21.05.2018 11:07:30.125 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 19.05.2018 21:28:11.757 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance OFF 19.05.2018 21:28:11.757 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 18.05.2018 06:57:55.810 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance ON 18.05.2018 06:57:55.810 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 18.05.2018 03:01:15.463 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance OFF 18.05.2018 03:01:15.463 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 17.05.2018 18:55:52.237 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance ON 17.05.2018 18:55:52.237 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 17.05.2018 18:11:02.164 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance OFF 17.05.2018 18:11:02.164 Spontaneous
Com.Issued=AutoLocal
00301 Power System fault 1120 - OFF 17.05.2018 17:01:26.073 Spontaneous
Com.Issued=AutoLocal
00301 Power System fault 1120 - ON 17.05.2018 17:01:26.023 Spontaneous
Com.Issued=AutoLocal

Page 105 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 13-06-2018 17:09:51.190 (SIGNALS\BM000008.SFP)(11)


Number Indication Value Date and time Cause State

00195 Failure: Broken Conductor ON 17.05.2018 04:59:46.988 Spontaneous


Com.Issued=AutoLocal
00163 Failure: Current Balance ON 17.05.2018 04:59:46.988 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 17.05.2018 04:53:39.482 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance OFF 17.05.2018 04:53:39.482 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 16.05.2018 12:46:55.546 Spontaneous
Com.Issued=AutoLocal
00301 Power System fault 1119 - OFF 14.05.2018 20:26:38.612 Spontaneous
Com.Issued=AutoLocal
00301 Power System fault 1119 - ON 14.05.2018 20:26:38.562 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance ON 14.05.2018 08:20:10.869 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance OFF 14.05.2018 07:54:00.834 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance ON 14.05.2018 06:20:53.197 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance OFF 14.05.2018 02:54:27.885 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance ON 14.05.2018 02:40:27.866 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance OFF 14.05.2018 01:20:57.745 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance ON 14.05.2018 00:46:10.196 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance OFF 13.05.2018 23:48:42.612 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance ON 13.05.2018 22:28:27.492 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance OFF 13.05.2018 17:10:44.527 Spontaneous
Com.Issued=AutoLocal

Page 106 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 13-06-2018 17:09:51.190 (SIGNALS\BM000008.SFP)(12)


Number Indication Value Date and time Cause State

00163 Failure: Current Balance ON 13.05.2018 10:02:48.884 Spontaneous


Com.Issued=AutoLocal
00163 Failure: Current Balance OFF 13.05.2018 09:40:03.858 Spontaneous
Com.Issued=AutoLocal
00301 Power System fault 1118 - OFF 13.05.2018 05:35:05.155 Spontaneous
Com.Issued=AutoLocal
00301 Power System fault 1118 - ON 13.05.2018 05:35:05.085 Spontaneous
Com.Issued=AutoLocal
00301 Power System fault 1117 - OFF 13.05.2018 05:24:12.631 Spontaneous
Com.Issued=AutoLocal
00301 Power System fault 1117 - ON 13.05.2018 05:24:12.581 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance ON 12.05.2018 17:11:34.386 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance OFF 12.05.2018 09:19:43.680 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance ON 12.05.2018 08:18:16.089 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance OFF 12.05.2018 07:39:01.037 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance ON 12.05.2018 06:19:55.915 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance OFF 12.05.2018 05:37:05.849 Spontaneous
Com.Issued=AutoLocal

6.9 Event Log - 13-06-2018 17:10:04.757 (SIGNALS\BM000009.SFP)

Event Log - 13-06-2018 17:10:04.757 (SIGNALS\BM000009.SFP)


Number Indication Value Date and time Cause State

M CB_BO OFF 13.06.2018 16:28:05.142 Spontaneous


M CB_YO OFF 13.06.2018 16:28:05.142 Spontaneous
M CB_RO OFF 13.06.2018 16:28:05.142 Spontaneous

Page 107 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 13-06-2018 17:10:04.757 (SIGNALS\BM000009.SFP)(2)


Number Indication Value Date and time Cause State

M CB_BO ON 13.06.2018 12:23:40.950 Spontaneous


M CB_RO ON 13.06.2018 12:23:40.950 Spontaneous
00004 >Trigger Waveform Capture ON 13.06.2018 12:23:40.941 Spontaneous
Com.Issued=AutoLocal
M CB_YO ON 13.06.2018 12:23:40.941 Spontaneous
00060 Reset LED ON 13.06.2018 11:12:26.412 Spontaneous
Com.Issued=AutoLocal
Reset LED ON 13.06.2018 11:12:26.412 Spontaneous
Command Issued=Local
00195 Failure: Broken Conductor OFF 13.06.2018 08:46:28.817 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance OFF 13.06.2018 08:46:28.817 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 13.06.2018 05:42:01.042 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance ON 13.06.2018 05:42:01.042 Spontaneous
Com.Issued=AutoLocal
00301 Power System fault 1122 - OFF 01.06.2018 18:36:42.988 Spontaneous
Com.Issued=AutoLocal
00301 Power System fault 1122 - ON 01.06.2018 18:36:42.938 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 01.06.2018 08:48:57.540 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance OFF 01.06.2018 08:48:57.540 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 01.06.2018 02:10:56.944 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance ON 01.06.2018 02:10:56.944 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 01.06.2018 01:06:51.850 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance OFF 01.06.2018 01:06:51.850 Spontaneous
Com.Issued=AutoLocal

Page 108 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 13-06-2018 17:10:04.757 (SIGNALS\BM000009.SFP)(3)


Number Indication Value Date and time Cause State

00195 Failure: Broken Conductor ON 31.05.2018 22:05:24.081 Spontaneous


Com.Issued=AutoLocal
00163 Failure: Current Balance ON 31.05.2018 22:05:24.081 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 31.05.2018 12:15:33.204 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance OFF 31.05.2018 12:15:33.204 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 31.05.2018 12:09:10.693 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 31.05.2018 12:06:33.197 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 31.05.2018 11:35:35.643 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 31.05.2018 11:33:28.146 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 31.05.2018 10:24:25.540 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 31.05.2018 09:40:32.975 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 31.05.2018 09:07:35.424 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance ON 31.05.2018 09:07:35.424 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 31.05.2018 08:53:47.905 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance OFF 31.05.2018 08:53:47.905 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 31.05.2018 08:17:35.349 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance ON 31.05.2018 08:17:35.349 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 31.05.2018 07:51:30.318 Spontaneous
Com.Issued=AutoLocal

Page 109 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 13-06-2018 17:10:04.757 (SIGNALS\BM000009.SFP)(4)


Number Indication Value Date and time Cause State

00163 Failure: Current Balance OFF 31.05.2018 07:51:30.318 Spontaneous


Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 31.05.2018 06:31:22.697 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance ON 31.05.2018 06:31:22.697 Spontaneous
Com.Issued=AutoLocal
00301 Power System fault 1121 - OFF 31.05.2018 02:14:36.686 Spontaneous
Com.Issued=AutoLocal
00301 Power System fault 1121 - ON 31.05.2018 02:14:36.626 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 30.05.2018 12:44:39.607 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance OFF 30.05.2018 12:44:39.607 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 30.05.2018 12:28:59.581 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance ON 30.05.2018 12:28:59.581 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance OFF 30.05.2018 12:14:14.563 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance ON 30.05.2018 11:43:07.009 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance OFF 30.05.2018 11:11:34.466 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 30.05.2018 10:56:51.938 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 30.05.2018 10:17:24.387 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance ON 30.05.2018 10:07:29.372 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance OFF 30.05.2018 08:18:39.204 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 30.05.2018 08:02:39.178 Spontaneous
Com.Issued=AutoLocal

Page 110 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 13-06-2018 17:10:04.757 (SIGNALS\BM000009.SFP)(5)


Number Indication Value Date and time Cause State

00195 Failure: Broken Conductor ON 30.05.2018 07:58:44.174 Spontaneous


Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 30.05.2018 07:58:06.675 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 30.05.2018 07:49:34.168 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance ON 30.05.2018 07:49:34.168 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 30.05.2018 05:09:56.426 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance OFF 30.05.2018 05:09:56.426 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 30.05.2018 04:52:16.402 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance ON 30.05.2018 04:52:16.402 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 30.05.2018 02:59:41.230 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance OFF 30.05.2018 02:59:41.230 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 30.05.2018 01:30:41.093 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance ON 30.05.2018 01:30:41.093 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 30.05.2018 00:55:06.046 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance OFF 30.05.2018 00:55:06.046 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 29.05.2018 21:56:50.782 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance ON 29.05.2018 21:56:50.782 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 29.05.2018 20:11:43.119 Spontaneous
Com.Issued=AutoLocal

Page 111 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 13-06-2018 17:10:04.757 (SIGNALS\BM000009.SFP)(6)


Number Indication Value Date and time Cause State

00163 Failure: Current Balance OFF 29.05.2018 20:11:43.119 Spontaneous


Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 29.05.2018 19:15:28.033 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance ON 29.05.2018 19:15:28.033 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 29.05.2018 17:46:42.906 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance OFF 29.05.2018 17:46:42.905 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 29.05.2018 14:56:05.150 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance ON 29.05.2018 14:56:05.150 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 29.05.2018 10:42:04.769 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance OFF 29.05.2018 10:42:04.769 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 29.05.2018 10:41:52.270 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance ON 29.05.2018 10:01:47.210 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance OFF 29.05.2018 09:29:57.167 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance ON 29.05.2018 06:24:04.384 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 29.05.2018 00:59:01.399 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance OFF 29.05.2018 00:59:01.399 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 28.05.2018 16:27:45.642 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 28.05.2018 16:25:00.636 Spontaneous
Com.Issued=AutoLocal

Page 112 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 13-06-2018 17:10:04.757 (SIGNALS\BM000009.SFP)(7)


Number Indication Value Date and time Cause State

00195 Failure: Broken Conductor ON 28.05.2018 16:23:10.629 Spontaneous


Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 28.05.2018 16:17:03.118 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 28.05.2018 16:12:03.116 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 28.05.2018 16:05:43.105 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 28.05.2018 16:00:45.603 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 28.05.2018 15:39:08.065 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 28.05.2018 15:38:18.066 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 28.05.2018 15:34:55.561 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 28.05.2018 15:28:58.050 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 28.05.2018 15:26:30.544 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 28.05.2018 15:25:33.045 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 28.05.2018 15:22:13.040 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 28.05.2018 14:52:00.495 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 28.05.2018 06:51:59.782 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 28.05.2018 06:31:44.752 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 28.05.2018 06:08:04.717 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 28.05.2018 06:07:29.708 Spontaneous
Com.Issued=AutoLocal

Page 113 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 13-06-2018 17:10:04.757 (SIGNALS\BM000009.SFP)(8)


Number Indication Value Date and time Cause State

00195 Failure: Broken Conductor OFF 28.05.2018 05:53:22.189 Spontaneous


Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 28.05.2018 05:51:44.692 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 28.05.2018 05:38:54.671 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 28.05.2018 05:35:24.666 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 28.05.2018 05:31:17.162 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 28.05.2018 05:03:24.614 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 28.05.2018 05:00:19.608 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 28.05.2018 04:36:54.573 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 28.05.2018 04:20:19.555 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 28.05.2018 04:19:14.555 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 28.05.2018 03:39:31.989 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 28.05.2018 00:34:26.715 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 28.05.2018 00:28:54.203 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 28.05.2018 00:25:04.199 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 27.05.2018 23:16:56.601 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 27.05.2018 22:52:01.568 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 27.05.2018 22:50:34.060 Spontaneous
Com.Issued=AutoLocal

Page 114 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 13-06-2018 17:10:04.757 (SIGNALS\BM000009.SFP)(9)


Number Indication Value Date and time Cause State

00195 Failure: Broken Conductor ON 27.05.2018 22:25:24.028 Spontaneous


Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 27.05.2018 22:23:14.021 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 27.05.2018 22:18:29.013 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 27.05.2018 22:09:16.502 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 27.05.2018 21:13:18.915 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 27.05.2018 21:08:08.909 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 27.05.2018 21:07:08.910 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 27.05.2018 21:03:41.406 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 27.05.2018 19:12:21.236 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 26.05.2018 20:09:31.669 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 26.05.2018 19:12:21.590 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 25.05.2018 06:13:20.781 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 25.05.2018 06:11:38.274 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance ON 25.05.2018 04:44:53.143 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance OFF 25.05.2018 04:10:03.095 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 24.05.2018 11:21:56.590 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 24.05.2018 05:46:13.591 Spontaneous
Com.Issued=AutoLocal

Page 115 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 13-06-2018 17:10:04.757 (SIGNALS\BM000009.SFP)(10)


Number Indication Value Date and time Cause State

00163 Failure: Current Balance ON 24.05.2018 05:46:13.591 Spontaneous


Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 24.05.2018 03:15:48.365 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance OFF 24.05.2018 03:15:48.365 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 24.05.2018 03:05:00.851 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance ON 24.05.2018 03:05:00.851 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 24.05.2018 00:53:03.148 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance OFF 24.05.2018 00:53:03.148 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 23.05.2018 18:22:37.571 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance ON 23.05.2018 18:22:37.571 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 23.05.2018 18:06:45.045 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance OFF 23.05.2018 18:06:45.045 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 22.05.2018 11:09:57.276 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 22.05.2018 07:23:11.934 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 21.05.2018 18:59:13.324 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance ON 21.05.2018 18:59:13.324 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 21.05.2018 17:55:35.729 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance OFF 21.05.2018 17:55:35.729 Spontaneous
Com.Issued=AutoLocal

Page 116 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 13-06-2018 17:10:04.757 (SIGNALS\BM000009.SFP)(11)


Number Indication Value Date and time Cause State

00195 Failure: Broken Conductor ON 21.05.2018 11:07:30.125 Spontaneous


Com.Issued=AutoLocal
00163 Failure: Current Balance ON 21.05.2018 11:07:30.125 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 19.05.2018 21:28:11.757 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance OFF 19.05.2018 21:28:11.757 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 18.05.2018 06:57:55.810 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance ON 18.05.2018 06:57:55.810 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 18.05.2018 03:01:15.463 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance OFF 18.05.2018 03:01:15.463 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 17.05.2018 18:55:52.237 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance ON 17.05.2018 18:55:52.237 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 17.05.2018 18:11:02.164 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance OFF 17.05.2018 18:11:02.164 Spontaneous
Com.Issued=AutoLocal
00301 Power System fault 1120 - OFF 17.05.2018 17:01:26.073 Spontaneous
Com.Issued=AutoLocal
00301 Power System fault 1120 - ON 17.05.2018 17:01:26.023 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 17.05.2018 04:59:46.988 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance ON 17.05.2018 04:59:46.988 Spontaneous
Com.Issued=AutoLocal
00195 Failure: Broken Conductor OFF 17.05.2018 04:53:39.482 Spontaneous
Com.Issued=AutoLocal

Page 117 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 13-06-2018 17:10:04.757 (SIGNALS\BM000009.SFP)(12)


Number Indication Value Date and time Cause State

00163 Failure: Current Balance OFF 17.05.2018 04:53:39.482 Spontaneous


Com.Issued=AutoLocal
00195 Failure: Broken Conductor ON 16.05.2018 12:46:55.546 Spontaneous
Com.Issued=AutoLocal
00301 Power System fault 1119 - OFF 14.05.2018 20:26:38.612 Spontaneous
Com.Issued=AutoLocal
00301 Power System fault 1119 - ON 14.05.2018 20:26:38.562 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance ON 14.05.2018 08:20:10.869 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance OFF 14.05.2018 07:54:00.834 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance ON 14.05.2018 06:20:53.197 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance OFF 14.05.2018 02:54:27.885 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance ON 14.05.2018 02:40:27.866 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance OFF 14.05.2018 01:20:57.745 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance ON 14.05.2018 00:46:10.196 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance OFF 13.05.2018 23:48:42.612 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance ON 13.05.2018 22:28:27.492 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance OFF 13.05.2018 17:10:44.527 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance ON 13.05.2018 10:02:48.884 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance OFF 13.05.2018 09:40:03.858 Spontaneous
Com.Issued=AutoLocal
00301 Power System fault 1118 - OFF 13.05.2018 05:35:05.155 Spontaneous
Com.Issued=AutoLocal

Page 118 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 13-06-2018 17:10:04.757 (SIGNALS\BM000009.SFP)(13)


Number Indication Value Date and time Cause State

00301 Power System fault 1118 - ON 13.05.2018 05:35:05.085 Spontaneous


Com.Issued=AutoLocal
00301 Power System fault 1117 - OFF 13.05.2018 05:24:12.631 Spontaneous
Com.Issued=AutoLocal
00301 Power System fault 1117 - ON 13.05.2018 05:24:12.581 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance ON 12.05.2018 17:11:34.386 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance OFF 12.05.2018 09:19:43.680 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance ON 12.05.2018 08:18:16.089 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance OFF 12.05.2018 07:39:01.037 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance ON 12.05.2018 06:19:55.915 Spontaneous
Com.Issued=AutoLocal
00163 Failure: Current Balance OFF 12.05.2018 05:37:05.849 Spontaneous
Com.Issued=AutoLocal

6.10 Event Log - 18-04-2019 12:45:19.834 (SIGNALS\BM000010.SFP)

Event Log - 18-04-2019 12:45:19.834 (SIGNALS\BM000010.SFP)


Number Indication Value Date and time Cause State

00060 Reset LED ON 18.04.2019 12:27:59.427 Spontaneous


Com.Issued=AutoLocal
Reset LED ON 18.04.2019 12:27:59.427 Spontaneous
Command Issued=Local
M CB_BO OFF 17.04.2019 17:27:43.192 Spontaneous
M CB_YO OFF 17.04.2019 17:27:43.192 Spontaneous
M CB_RO OFF 17.04.2019 17:27:43.192 Spontaneous
00060 Reset LED ON 17.04.2019 17:26:30.491 Spontaneous
Com.Issued=AutoLocal

Page 119 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 18-04-2019 12:45:19.834 (SIGNALS\BM000010.SFP)(2)


Number Indication Value Date and time Cause State

Reset LED ON 17.04.2019 17:26:30.491 Spontaneous


Command Issued=Local
00060 Reset LED ON 17.04.2019 17:26:29.691 Spontaneous
Com.Issued=AutoLocal
Reset LED ON 17.04.2019 17:26:29.691 Spontaneous
Command Issued=Local
00060 Reset LED ON 17.04.2019 17:26:28.890 Spontaneous
Com.Issued=AutoLocal
Reset LED ON 17.04.2019 17:26:28.890 Spontaneous
Command Issued=Local
00381 >Single-phase trip permitted from ext.AR ON 17.04.2019 16:32:50.423 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P ON 17.04.2019 16:32:50.423 Spontaneous
04010 >Dis.Tele. Carrier RECEPTION Channel 2 OFF 17.04.2019 16:12:36.095 Spontaneous
Com.Issued=AutoLocal
04009 >Dis.Tele.Carrier RECEPTION Channel 1,L3 OFF 17.04.2019 16:12:36.095 Spontaneous
Com.Issued=AutoLocal
04008 >Dis.Tele.Carrier RECEPTION Channel 1,L2 OFF 17.04.2019 16:12:36.095 Spontaneous
Com.Issued=AutoLocal
04007 >Dis.Tele.Carrier RECEPTION Channel 1,L1 OFF 17.04.2019 16:12:36.095 Spontaneous
Com.Issued=AutoLocal
04006 >Dis.Tele. Carrier RECEPTION Channel 1 OFF 17.04.2019 16:12:36.095 Spontaneous
Com.Issued=AutoLocal
ON/OFF (SP) ON 17.04.2019 16:12:36.059 Spontaneous
ON/OFF (SP) OFF 17.04.2019 16:12:36.058 Spontaneous
M1_TRIP OFF 17.04.2019 16:12:36.055 Spontaneous
07130 >BLOCK I-STUB ON 17.04.2019 16:12:36.059 Spontaneous
Com.Issued=AutoLocal
07152 Backup O/C is BLOCKED ON 17.04.2019 16:12:36.058 Spontaneous
Com.Issued=AutoLocal
07131 >Enable I-STUB-Bus function OFF 17.04.2019 16:12:36.058 Spontaneous
Com.Issued=AutoLocal

Page 120 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 18-04-2019 12:45:19.834 (SIGNALS\BM000010.SFP)(3)


Number Indication Value Date and time Cause State

M2_TRIP OFF 17.04.2019 16:12:36.052 Spontaneous


Com.Issued=AutoLocal
M/TCBAR OFF 17.04.2019 16:12:36.037 Spontaneous
01335 Earth fault protection Trip is blocked OFF 17.04.2019 16:12:36.041 Spontaneous
Com.Issued=AutoLocal
04010 >Dis.Tele. Carrier RECEPTION Channel 2 ON 17.04.2019 16:12:36.039 Spontaneous
Com.Issued=AutoLocal
04009 >Dis.Tele.Carrier RECEPTION Channel 1,L3 ON 17.04.2019 16:12:36.039 Spontaneous
Com.Issued=AutoLocal
04008 >Dis.Tele.Carrier RECEPTION Channel 1,L2 ON 17.04.2019 16:12:36.039 Spontaneous
Com.Issued=AutoLocal
04007 >Dis.Tele.Carrier RECEPTION Channel 1,L1 ON 17.04.2019 16:12:36.039 Spontaneous
Com.Issued=AutoLocal
04006 >Dis.Tele. Carrier RECEPTION Channel 1 ON 17.04.2019 16:12:36.039 Spontaneous
Com.Issued=AutoLocal
00301 Power System fault 155 - OFF 17.04.2019 16:12:36.038 Spontaneous
Com.Issued=AutoLocal
00381 >Single-phase trip permitted from ext.AR OFF 17.04.2019 16:12:36.023 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P OFF 17.04.2019 16:12:36.015 Spontaneous
M CB_RO ON 17.04.2019 16:12:35.976 Spontaneous
M CB_BO ON 17.04.2019 16:12:35.973 Spontaneous
ON/OFF (SP) ON 17.04.2019 16:12:35.970 Spontaneous
M CB_YO ON 17.04.2019 16:12:35.970 Spontaneous
07152 Backup O/C is BLOCKED OFF 17.04.2019 16:12:35.970 Spontaneous
Com.Issued=AutoLocal
07131 >Enable I-STUB-Bus function ON 17.04.2019 16:12:35.970 Spontaneous
Com.Issued=AutoLocal
M/TCBAR ON 17.04.2019 16:12:35.954 Spontaneous
M1_TRIP ON 17.04.2019 16:12:35.952 Spontaneous
ON/OFF (SP) OFF 17.04.2019 16:12:35.948 Spontaneous
00004 >Trigger Waveform Capture ON 17.04.2019 16:12:35.954 Spontaneous
Com.Issued=AutoLocal

Page 121 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 18-04-2019 12:45:19.834 (SIGNALS\BM000010.SFP)(4)


Number Indication Value Date and time Cause State

01335 Earth fault protection Trip is blocked ON 17.04.2019 16:12:35.951 Spontaneous


Com.Issued=AutoLocal
M2_TRIP ON 17.04.2019 16:12:35.948 Spontaneous
Com.Issued=AutoLocal
07130 >BLOCK I-STUB OFF 17.04.2019 16:12:35.948 Spontaneous
Com.Issued=AutoLocal
04056 Dis. Telep. Carrier SEND signal ON 17.04.2019 16:12:35.947 Spontaneous
Com.Issued=AutoLocal
00301 Power System fault 155 - ON 17.04.2019 16:12:35.947 Spontaneous
Com.Issued=AutoLocal
00060 Reset LED ON 15.04.2019 12:50:52.968 Spontaneous
Com.Issued=AutoLocal
Reset LED ON 15.04.2019 12:50:52.968 Spontaneous
Command Issued=Local
01335 Earth fault protection Trip is blocked OFF 05.04.2019 19:55:31.113 Spontaneous
Com.Issued=AutoLocal
M1_TRIP OFF 05.04.2019 19:55:31.079 Spontaneous
00301 Power System fault 154 - OFF 05.04.2019 19:55:31.069 Spontaneous
Com.Issued=AutoLocal
ON/OFF (SP) OFF 05.04.2019 19:55:31.053 Spontaneous
ON/OFF (SP) ON 05.04.2019 19:55:31.053 Spontaneous
07152 Backup O/C is BLOCKED ON 05.04.2019 19:55:31.053 Spontaneous
Com.Issued=AutoLocal
07131 >Enable I-STUB-Bus function OFF 05.04.2019 19:55:31.053 Spontaneous
Com.Issued=AutoLocal
07130 >BLOCK I-STUB ON 05.04.2019 19:55:31.053 Spontaneous
Com.Issued=AutoLocal
ON/OFF (SP) ON 05.04.2019 19:55:31.025 Spontaneous
07152 Backup O/C is BLOCKED OFF 05.04.2019 19:55:31.025 Spontaneous
Com.Issued=AutoLocal
07131 >Enable I-STUB-Bus function ON 05.04.2019 19:55:31.025 Spontaneous
Com.Issued=AutoLocal

Page 122 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 18-04-2019 12:45:19.834 (SIGNALS\BM000010.SFP)(5)


Number Indication Value Date and time Cause State

00004 >Trigger Waveform Capture ON 05.04.2019 19:55:31.015 Spontaneous


Com.Issued=AutoLocal
M1_TRIP ON 05.04.2019 19:55:31.005 Spontaneous
01335 Earth fault protection Trip is blocked ON 05.04.2019 19:55:31.013 Spontaneous
Com.Issued=AutoLocal
00301 Power System fault 154 - ON 05.04.2019 19:55:31.009 Spontaneous
Com.Issued=AutoLocal
ON/OFF (SP) OFF 05.04.2019 19:55:31.002 Spontaneous
07130 >BLOCK I-STUB OFF 05.04.2019 19:55:31.002 Spontaneous
Com.Issued=AutoLocal
M CB_BO OFF 05.04.2019 18:16:26.249 Spontaneous
M CB_YO OFF 05.04.2019 18:16:26.249 Spontaneous
M CB_RO OFF 05.04.2019 18:16:26.249 Spontaneous
M1_TRIP OFF 05.04.2019 18:16:22.854 Spontaneous
00301 Power System fault 153 - OFF 05.04.2019 18:16:22.844 Spontaneous
Com.Issued=AutoLocal
00004 >Trigger Waveform Capture ON 05.04.2019 18:16:22.794 Spontaneous
Com.Issued=AutoLocal
M1_TRIP ON 05.04.2019 18:16:22.786 Spontaneous
00301 Power System fault 153 - ON 05.04.2019 18:16:22.764 Spontaneous
Com.Issued=AutoLocal
ON/OFF (SP) ON 05.04.2019 17:46:56.390 Spontaneous
07130 >BLOCK I-STUB ON 05.04.2019 17:46:56.390 Spontaneous
Com.Issued=AutoLocal
ON/OFF (SP) OFF 05.04.2019 17:46:55.132 Spontaneous
07152 Backup O/C is BLOCKED ON 05.04.2019 17:46:55.132 Spontaneous
Com.Issued=AutoLocal
07131 >Enable I-STUB-Bus function OFF 05.04.2019 17:46:55.132 Spontaneous
Com.Issued=AutoLocal
ON/OFF (SP) ON 05.04.2019 17:46:43.879 Spontaneous
07152 Backup O/C is BLOCKED OFF 05.04.2019 17:46:43.879 Spontaneous
Com.Issued=AutoLocal

Page 123 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 18-04-2019 12:45:19.834 (SIGNALS\BM000010.SFP)(6)


Number Indication Value Date and time Cause State

07131 >Enable I-STUB-Bus function ON 05.04.2019 17:46:43.879 Spontaneous


Com.Issued=AutoLocal
ON/OFF (SP) OFF 05.04.2019 17:46:43.222 Spontaneous
07130 >BLOCK I-STUB OFF 05.04.2019 17:46:43.222 Spontaneous
Com.Issued=AutoLocal
ON/OFF (SP) ON 05.04.2019 17:46:27.540 Spontaneous
07130 >BLOCK I-STUB ON 05.04.2019 17:46:27.540 Spontaneous
Com.Issued=AutoLocal
ON/OFF (SP) OFF 05.04.2019 17:46:26.779 Spontaneous
07152 Backup O/C is BLOCKED ON 05.04.2019 17:46:26.779 Spontaneous
Com.Issued=AutoLocal
07131 >Enable I-STUB-Bus function OFF 05.04.2019 17:46:26.779 Spontaneous
Com.Issued=AutoLocal
M/TCBAR OFF 05.04.2019 16:23:53.140 Spontaneous
00004 >Trigger Waveform Capture ON 05.04.2019 16:23:53.063 Spontaneous
Com.Issued=AutoLocal
M/TCBAR ON 05.04.2019 16:23:53.061 Spontaneous
M/TCBAR OFF 05.04.2019 16:22:15.558 Spontaneous
M1_TRIP OFF 05.04.2019 16:22:15.530 Spontaneous
ON/OFF (SP) ON 05.04.2019 16:22:15.528 Spontaneous
ON/OFF (SP) OFF 05.04.2019 16:22:15.528 Spontaneous
07152 Backup O/C is BLOCKED OFF 05.04.2019 16:22:15.528 Spontaneous
Com.Issued=AutoLocal
07131 >Enable I-STUB-Bus function ON 05.04.2019 16:22:15.528 Spontaneous
Com.Issued=AutoLocal
07130 >BLOCK I-STUB OFF 05.04.2019 16:22:15.528 Spontaneous
Com.Issued=AutoLocal
ON/OFF (SP) ON 05.04.2019 16:22:15.501 Spontaneous
07130 >BLOCK I-STUB ON 05.04.2019 16:22:15.501 Spontaneous
Com.Issued=AutoLocal
00004 >Trigger Waveform Capture ON 05.04.2019 16:22:15.484 Spontaneous
Com.Issued=AutoLocal
M1_TRIP ON 05.04.2019 16:22:15.481 Spontaneous

Page 124 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 18-04-2019 12:45:19.834 (SIGNALS\BM000010.SFP)(7)


Number Indication Value Date and time Cause State

M/TCBAR ON 05.04.2019 16:22:15.480 Spontaneous


ON/OFF (SP) OFF 05.04.2019 16:22:15.477 Spontaneous
07152 Backup O/C is BLOCKED ON 05.04.2019 16:22:15.477 Spontaneous
Com.Issued=AutoLocal
07131 >Enable I-STUB-Bus function OFF 05.04.2019 16:22:15.477 Spontaneous
Com.Issued=AutoLocal
M/TCBAR OFF 05.04.2019 16:18:41.524 Spontaneous
00004 >Trigger Waveform Capture ON 05.04.2019 16:18:41.453 Spontaneous
Com.Issued=AutoLocal
M/TCBAR ON 05.04.2019 16:18:41.446 Spontaneous
M/TCBAR OFF 05.04.2019 16:17:08.637 Spontaneous
00004 >Trigger Waveform Capture ON 05.04.2019 16:16:03.953 Spontaneous
Com.Issued=AutoLocal
M/TCBAR ON 05.04.2019 16:16:03.953 Spontaneous
M/TCBAR OFF 05.04.2019 16:12:55.258 Spontaneous
00004 >Trigger Waveform Capture ON 05.04.2019 16:12:48.823 Spontaneous
Com.Issued=AutoLocal
M/TCBAR ON 05.04.2019 16:12:48.823 Spontaneous
M/TCBAR OFF 05.04.2019 16:12:22.042 Spontaneous
00004 >Trigger Waveform Capture ON 05.04.2019 16:12:07.004 Spontaneous
Com.Issued=AutoLocal
M/TCBAR ON 05.04.2019 16:12:06.997 Spontaneous
M/TCBAR OFF 05.04.2019 16:11:28.316 Spontaneous
00004 >Trigger Waveform Capture ON 05.04.2019 16:11:26.923 Spontaneous
Com.Issued=AutoLocal
M/TCBAR ON 05.04.2019 16:11:26.915 Spontaneous
ON/OFF (SP) ON 05.04.2019 16:11:23.214 Spontaneous
07152 Backup O/C is BLOCKED OFF 05.04.2019 16:11:23.214 Spontaneous
Com.Issued=AutoLocal
07131 >Enable I-STUB-Bus function ON 05.04.2019 16:11:23.214 Spontaneous
Com.Issued=AutoLocal
M1_TRIP OFF 05.04.2019 16:11:23.211 Spontaneous

Page 125 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 18-04-2019 12:45:19.834 (SIGNALS\BM000010.SFP)(8)


Number Indication Value Date and time Cause State

ON/OFF (SP) OFF 05.04.2019 16:11:23.210 Spontaneous


M/TCBAR OFF 05.04.2019 16:11:23.209 Spontaneous
07130 >BLOCK I-STUB OFF 05.04.2019 16:11:23.210 Spontaneous
Com.Issued=AutoLocal
ON/OFF (SP) ON 05.04.2019 16:11:14.316 Spontaneous
07130 >BLOCK I-STUB ON 05.04.2019 16:11:14.316 Spontaneous
Com.Issued=AutoLocal
M1_TRIP ON 05.04.2019 16:11:14.298 Spontaneous
ON/OFF (SP) OFF 05.04.2019 16:11:14.294 Spontaneous
07152 Backup O/C is BLOCKED ON 05.04.2019 16:11:14.294 Spontaneous
Com.Issued=AutoLocal
07131 >Enable I-STUB-Bus function OFF 05.04.2019 16:11:14.294 Spontaneous
Com.Issued=AutoLocal
00004 >Trigger Waveform Capture ON 05.04.2019 16:11:13.883 Spontaneous
Com.Issued=AutoLocal
M/TCBAR ON 05.04.2019 16:11:13.881 Spontaneous
M1_TRIP OFF 05.04.2019 16:11:13.366 Spontaneous
ON/OFF (SP) ON 05.04.2019 16:11:13.365 Spontaneous
ON/OFF (SP) OFF 05.04.2019 16:11:13.365 Spontaneous
07152 Backup O/C is BLOCKED OFF 05.04.2019 16:11:13.365 Spontaneous
Com.Issued=AutoLocal
07131 >Enable I-STUB-Bus function ON 05.04.2019 16:11:13.365 Spontaneous
Com.Issued=AutoLocal
07130 >BLOCK I-STUB OFF 05.04.2019 16:11:13.365 Spontaneous
Com.Issued=AutoLocal
ON/OFF (SP) ON 05.04.2019 16:11:13.340 Spontaneous
07130 >BLOCK I-STUB ON 05.04.2019 16:11:13.340 Spontaneous
Com.Issued=AutoLocal
00004 >Trigger Waveform Capture ON 05.04.2019 16:11:13.323 Spontaneous
Com.Issued=AutoLocal
M1_TRIP ON 05.04.2019 16:11:13.320 Spontaneous
ON/OFF (SP) OFF 05.04.2019 16:11:13.316 Spontaneous

Page 126 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 18-04-2019 12:45:19.834 (SIGNALS\BM000010.SFP)(9)


Number Indication Value Date and time Cause State

07152 Backup O/C is BLOCKED ON 05.04.2019 16:11:13.316 Spontaneous


Com.Issued=AutoLocal
07131 >Enable I-STUB-Bus function OFF 05.04.2019 16:11:13.316 Spontaneous
Com.Issued=AutoLocal
M1_TRIP OFF 05.04.2019 16:11:11.176 Spontaneous
ON/OFF (SP) ON 05.04.2019 16:11:11.175 Spontaneous
ON/OFF (SP) OFF 05.04.2019 16:11:11.175 Spontaneous
07152 Backup O/C is BLOCKED OFF 05.04.2019 16:11:11.175 Spontaneous
Com.Issued=AutoLocal
07131 >Enable I-STUB-Bus function ON 05.04.2019 16:11:11.175 Spontaneous
Com.Issued=AutoLocal
07130 >BLOCK I-STUB OFF 05.04.2019 16:11:11.175 Spontaneous
Com.Issued=AutoLocal
00004 >Trigger Waveform Capture ON 05.04.2019 16:11:11.133 Spontaneous
Com.Issued=AutoLocal
ON/OFF (SP) ON 05.04.2019 16:11:11.132 Spontaneous
M1_TRIP ON 05.04.2019 16:11:11.128 Spontaneous
ON/OFF (SP) OFF 05.04.2019 16:11:11.124 Spontaneous
07130 >BLOCK I-STUB ON 05.04.2019 16:11:11.132 Spontaneous
Com.Issued=AutoLocal
07152 Backup O/C is BLOCKED ON 05.04.2019 16:11:11.124 Spontaneous
Com.Issued=AutoLocal
07131 >Enable I-STUB-Bus function OFF 05.04.2019 16:11:11.124 Spontaneous
Com.Issued=AutoLocal
M1_TRIP OFF 05.04.2019 16:11:10.946 Spontaneous
ON/OFF (SP) ON 05.04.2019 16:11:10.945 Spontaneous
ON/OFF (SP) OFF 05.04.2019 16:11:10.945 Spontaneous
07152 Backup O/C is BLOCKED OFF 05.04.2019 16:11:10.945 Spontaneous
Com.Issued=AutoLocal
07131 >Enable I-STUB-Bus function ON 05.04.2019 16:11:10.945 Spontaneous
Com.Issued=AutoLocal
07130 >BLOCK I-STUB OFF 05.04.2019 16:11:10.945 Spontaneous
Com.Issued=AutoLocal

Page 127 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 18-04-2019 12:45:19.834 (SIGNALS\BM000010.SFP)(10)


Number Indication Value Date and time Cause State

00004 >Trigger Waveform Capture ON 05.04.2019 16:11:10.903 Spontaneous


Com.Issued=AutoLocal
M1_TRIP ON 05.04.2019 16:11:10.899 Spontaneous
ON/OFF (SP) OFF 05.04.2019 16:11:10.896 Spontaneous
ON/OFF (SP) ON 05.04.2019 16:11:10.895 Spontaneous
07131 >Enable I-STUB-Bus function OFF 05.04.2019 16:11:10.896 Spontaneous
Com.Issued=AutoLocal
07152 Backup O/C is BLOCKED ON 05.04.2019 16:11:10.895 Spontaneous
Com.Issued=AutoLocal
07130 >BLOCK I-STUB ON 05.04.2019 16:11:10.895 Spontaneous
Com.Issued=AutoLocal
M1_TRIP OFF 05.04.2019 16:11:10.881 Spontaneous
ON/OFF (SP) ON 05.04.2019 16:11:10.880 Spontaneous
ON/OFF (SP) OFF 05.04.2019 16:11:10.880 Spontaneous
07152 Backup O/C is BLOCKED OFF 05.04.2019 16:11:10.880 Spontaneous
Com.Issued=AutoLocal
07131 >Enable I-STUB-Bus function ON 05.04.2019 16:11:10.880 Spontaneous
Com.Issued=AutoLocal
07130 >BLOCK I-STUB OFF 05.04.2019 16:11:10.880 Spontaneous
Com.Issued=AutoLocal
00004 >Trigger Waveform Capture ON 05.04.2019 16:11:10.833 Spontaneous
Com.Issued=AutoLocal
M1_TRIP ON 05.04.2019 16:11:10.833 Spontaneous
ON/OFF (SP) ON 05.04.2019 16:11:10.832 Spontaneous
ON/OFF (SP) OFF 05.04.2019 16:11:10.829 Spontaneous
07130 >BLOCK I-STUB ON 05.04.2019 16:11:10.832 Spontaneous
Com.Issued=AutoLocal
07152 Backup O/C is BLOCKED ON 05.04.2019 16:11:10.829 Spontaneous
Com.Issued=AutoLocal
07131 >Enable I-STUB-Bus function OFF 05.04.2019 16:11:10.829 Spontaneous
Com.Issued=AutoLocal
M1_TRIP OFF 05.04.2019 16:11:10.731 Spontaneous
ON/OFF (SP) ON 05.04.2019 16:11:10.730 Spontaneous

Page 128 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 18-04-2019 12:45:19.834 (SIGNALS\BM000010.SFP)(11)


Number Indication Value Date and time Cause State

ON/OFF (SP) OFF 05.04.2019 16:11:10.730 Spontaneous


07152 Backup O/C is BLOCKED OFF 05.04.2019 16:11:10.730 Spontaneous
Com.Issued=AutoLocal
07131 >Enable I-STUB-Bus function ON 05.04.2019 16:11:10.730 Spontaneous
Com.Issued=AutoLocal
07130 >BLOCK I-STUB OFF 05.04.2019 16:11:10.730 Spontaneous
Com.Issued=AutoLocal
00004 >Trigger Waveform Capture ON 05.04.2019 16:11:10.693 Spontaneous
Com.Issued=AutoLocal
M1_TRIP ON 05.04.2019 16:11:10.684 Spontaneous

6.11 Event Log - 26-04-2022 16:27:30.092 (SIGNALS\BM000011.SFP)

Event Log - 26-04-2022 16:27:30.092 (SIGNALS\BM000011.SFP)


Number Indication Value Date and time Cause State

M CB_BO OFF 22.04.2022 13:46:32.941 Spontaneous


M CB_YO OFF 22.04.2022 13:46:32.941 Spontaneous
M CB_RO OFF 22.04.2022 13:46:32.941 Spontaneous
00060 Reset LED ON 22.04.2022 13:32:31.230 Spontaneous
Com.Issued=AutoLocal
Reset LED ON 22.04.2022 13:32:31.230 Spontaneous
Command Issued=Local
00381 >Single-phase trip permitted from ext.AR ON 22.04.2022 13:32:15.223 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P ON 22.04.2022 13:32:15.222 Spontaneous
01332 Earth fault protection is BLOCKED OFF 22.04.2022 12:47:39.006 Spontaneous
Com.Issued=AutoLocal
14083 E/F 3I0p is blocked OFF 22.04.2022 12:47:39.006 Spontaneous
Com.Issued=AutoLocal
04010 >Dis.Tele. Carrier RECEPTION Channel 2 OFF 22.04.2022 12:47:38.996 Spontaneous
Com.Issued=AutoLocal

Page 129 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 26-04-2022 16:27:30.092 (SIGNALS\BM000011.SFP)(2)


Number Indication Value Date and time Cause State

04009 >Dis.Tele.Carrier RECEPTION Channel 1,L3 OFF 22.04.2022 12:47:38.996 Spontaneous


Com.Issued=AutoLocal
04008 >Dis.Tele.Carrier RECEPTION Channel 1,L2 OFF 22.04.2022 12:47:38.996 Spontaneous
Com.Issued=AutoLocal
04007 >Dis.Tele.Carrier RECEPTION Channel 1,L1 OFF 22.04.2022 12:47:38.996 Spontaneous
Com.Issued=AutoLocal
04006 >Dis.Tele. Carrier RECEPTION Channel 1 OFF 22.04.2022 12:47:38.996 Spontaneous
Com.Issued=AutoLocal
M1_TRIP OFF 22.04.2022 12:47:38.974 Spontaneous
00593 Single pole open detected in L3 OFF 22.04.2022 12:47:38.966 Spontaneous
Com.Issued=AutoLocal
00301 Power System fault 253 - OFF 22.04.2022 12:47:38.962 Spontaneous
Com.Issued=AutoLocal
04010 >Dis.Tele. Carrier RECEPTION Channel 2 ON 22.04.2022 12:47:38.953 Spontaneous
Com.Issued=AutoLocal
04009 >Dis.Tele.Carrier RECEPTION Channel 1,L3 ON 22.04.2022 12:47:38.953 Spontaneous
Com.Issued=AutoLocal
04008 >Dis.Tele.Carrier RECEPTION Channel 1,L2 ON 22.04.2022 12:47:38.953 Spontaneous
Com.Issued=AutoLocal
04007 >Dis.Tele.Carrier RECEPTION Channel 1,L1 ON 22.04.2022 12:47:38.953 Spontaneous
Com.Issued=AutoLocal
04006 >Dis.Tele. Carrier RECEPTION Channel 1 ON 22.04.2022 12:47:38.953 Spontaneous
Com.Issued=AutoLocal
00004 >Trigger Waveform Capture ON 22.04.2022 12:47:38.933 Spontaneous
Com.Issued=AutoLocal
M1_TRIP ON 22.04.2022 12:47:38.924 Spontaneous
00301 Power System fault 253 - ON 22.04.2022 12:47:38.901 Spontaneous
Com.Issued=AutoLocal
M/TCBAR OFF 22.04.2022 12:47:38.867 Spontaneous
ON/OFF (SP) OFF 22.04.2022 12:47:38.862 Spontaneous
ON/OFF (SP) ON 22.04.2022 12:47:38.862 Spontaneous
07152 Backup O/C is BLOCKED ON 22.04.2022 12:47:38.862 Spontaneous
Com.Issued=AutoLocal

Page 130 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 26-04-2022 16:27:30.092 (SIGNALS\BM000011.SFP)(3)


Number Indication Value Date and time Cause State

07131 >Enable I-STUB-Bus function OFF 22.04.2022 12:47:38.862 Spontaneous


Com.Issued=AutoLocal
07130 >BLOCK I-STUB ON 22.04.2022 12:47:38.862 Spontaneous
Com.Issued=AutoLocal
01332 Earth fault protection is BLOCKED ON 22.04.2022 12:47:38.856 Spontaneous
Com.Issued=AutoLocal
14083 E/F 3I0p is blocked ON 22.04.2022 12:47:38.856 Spontaneous
Com.Issued=AutoLocal
00593 Single pole open detected in L3 ON 22.04.2022 12:47:38.856 Spontaneous
Com.Issued=AutoLocal
M2_TRIP OFF 22.04.2022 12:47:38.855 Spontaneous
Com.Issued=AutoLocal
M1_TRIP OFF 22.04.2022 12:47:38.847 Spontaneous
01335 Earth fault protection Trip is blocked OFF 22.04.2022 12:47:38.846 Spontaneous
Com.Issued=AutoLocal
00301 Power System fault 252 - OFF 22.04.2022 12:47:38.837 Spontaneous
Com.Issued=AutoLocal
00590 Line closure detected OFF 22.04.2022 12:47:38.801 Spontaneous
Com.Issued=AutoLocal
ON/OFF (SP) ON 22.04.2022 12:47:38.790 Spontaneous
M/TCBAR ON 22.04.2022 12:47:38.788 Spontaneous
07152 Backup O/C is BLOCKED OFF 22.04.2022 12:47:38.790 Spontaneous
Com.Issued=AutoLocal
07131 >Enable I-STUB-Bus function ON 22.04.2022 12:47:38.790 Spontaneous
Com.Issued=AutoLocal
01332 Earth fault protection is BLOCKED OFF 22.04.2022 12:47:38.786 Spontaneous
Com.Issued=AutoLocal
14083 E/F 3I0p is blocked OFF 22.04.2022 12:47:38.786 Spontaneous
Com.Issued=AutoLocal
M CB_BO ON 22.04.2022 12:47:38.780 Spontaneous
M CB_YO ON 22.04.2022 12:47:38.780 Spontaneous
M CB_RO ON 22.04.2022 12:47:38.780 Spontaneous
M1_TRIP ON 22.04.2022 12:47:38.779 Spontaneous

Page 131 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 26-04-2022 16:27:30.092 (SIGNALS\BM000011.SFP)(4)


Number Indication Value Date and time Cause State

ON/OFF (SP) OFF 22.04.2022 12:47:38.768 Spontaneous


07130 >BLOCK I-STUB OFF 22.04.2022 12:47:38.768 Spontaneous
Com.Issued=AutoLocal
01335 Earth fault protection Trip is blocked ON 22.04.2022 12:47:38.766 Spontaneous
Com.Issued=AutoLocal
M CB_BO OFF 22.04.2022 12:47:38.757 Spontaneous
00004 >Trigger Waveform Capture ON 22.04.2022 12:47:38.763 Spontaneous
Com.Issued=AutoLocal
M2_TRIP ON 22.04.2022 12:47:38.758 Spontaneous
Com.Issued=AutoLocal
00301 Power System fault 252 - ON 22.04.2022 12:47:38.756 Spontaneous
Com.Issued=AutoLocal
00593 Single pole open detected in L3 OFF 22.04.2022 12:47:38.746 Spontaneous
Com.Issued=AutoLocal
00590 Line closure detected ON 22.04.2022 12:47:38.746 Spontaneous
Com.Issued=AutoLocal
OVST1/2 OFF 22.04.2022 12:47:38.733 Spontaneous
00381 >Single-phase trip permitted from ext.AR OFF 22.04.2022 12:47:38.683 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P OFF 22.04.2022 12:47:38.677 Spontaneous
00004 >Trigger Waveform Capture ON 22.04.2022 12:47:38.643 Spontaneous
Com.Issued=AutoLocal
OVST1/2 ON 22.04.2022 12:47:38.635 Spontaneous
M1_TRIP OFF 22.04.2022 12:47:37.744 Spontaneous
ON/OFF (SP) OFF 22.04.2022 12:47:37.743 Spontaneous
ON/OFF (SP) ON 22.04.2022 12:47:37.743 Spontaneous
07152 Backup O/C is BLOCKED ON 22.04.2022 12:47:37.743 Spontaneous
Com.Issued=AutoLocal
07131 >Enable I-STUB-Bus function OFF 22.04.2022 12:47:37.743 Spontaneous
Com.Issued=AutoLocal
07130 >BLOCK I-STUB ON 22.04.2022 12:47:37.743 Spontaneous
Com.Issued=AutoLocal

Page 132 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 26-04-2022 16:27:30.092 (SIGNALS\BM000011.SFP)(5)


Number Indication Value Date and time Cause State

01335 Earth fault protection Trip is blocked OFF 22.04.2022 12:47:37.736 Spontaneous
Com.Issued=AutoLocal
M2_TRIP OFF 22.04.2022 12:47:37.732 Spontaneous
Com.Issued=AutoLocal
00301 Power System fault 250 - OFF 22.04.2022 12:47:37.728 Spontaneous
Com.Issued=AutoLocal
M/TCBAR OFF 22.04.2022 12:47:37.713 Spontaneous
04010 >Dis.Tele. Carrier RECEPTION Channel 2 OFF 22.04.2022 12:47:37.697 Spontaneous
Com.Issued=AutoLocal
04009 >Dis.Tele.Carrier RECEPTION Channel 1,L3 OFF 22.04.2022 12:47:37.697 Spontaneous
Com.Issued=AutoLocal
04008 >Dis.Tele.Carrier RECEPTION Channel 1,L2 OFF 22.04.2022 12:47:37.697 Spontaneous
Com.Issued=AutoLocal
04007 >Dis.Tele.Carrier RECEPTION Channel 1,L1 OFF 22.04.2022 12:47:37.697 Spontaneous
Com.Issued=AutoLocal
04006 >Dis.Tele. Carrier RECEPTION Channel 1 OFF 22.04.2022 12:47:37.697 Spontaneous
Com.Issued=AutoLocal
01332 Earth fault protection is BLOCKED ON 22.04.2022 12:47:37.676 Spontaneous
Com.Issued=AutoLocal
14083 E/F 3I0p is blocked ON 22.04.2022 12:47:37.676 Spontaneous
Com.Issued=AutoLocal
00593 Single pole open detected in L3 ON 22.04.2022 12:47:37.676 Spontaneous
Com.Issued=AutoLocal
ON/OFF (SP) ON 22.04.2022 12:47:37.649 Spontaneous
M CB_BO ON 22.04.2022 12:47:37.649 Spontaneous
07152 Backup O/C is BLOCKED OFF 22.04.2022 12:47:37.649 Spontaneous
Com.Issued=AutoLocal
04010 >Dis.Tele. Carrier RECEPTION Channel 2 ON 22.04.2022 12:47:37.649 Spontaneous
Com.Issued=AutoLocal
04009 >Dis.Tele.Carrier RECEPTION Channel 1,L3 ON 22.04.2022 12:47:37.649 Spontaneous
Com.Issued=AutoLocal
04008 >Dis.Tele.Carrier RECEPTION Channel 1,L2 ON 22.04.2022 12:47:37.649 Spontaneous
Com.Issued=AutoLocal

Page 133 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 26-04-2022 16:27:30.092 (SIGNALS\BM000011.SFP)(6)


Number Indication Value Date and time Cause State

04007 >Dis.Tele.Carrier RECEPTION Channel 1,L1 ON 22.04.2022 12:47:37.649 Spontaneous


Com.Issued=AutoLocal
04006 >Dis.Tele. Carrier RECEPTION Channel 1 ON 22.04.2022 12:47:37.649 Spontaneous
Com.Issued=AutoLocal
07131 >Enable I-STUB-Bus function ON 22.04.2022 12:47:37.649 Spontaneous
Com.Issued=AutoLocal
M/TCBAR ON 22.04.2022 12:47:37.634 Spontaneous
M1_TRIP ON 22.04.2022 12:47:37.630 Spontaneous
ON/OFF (SP) OFF 22.04.2022 12:47:37.627 Spontaneous
00004 >Trigger Waveform Capture ON 22.04.2022 12:47:37.638 Spontaneous
Com.Issued=AutoLocal
01335 Earth fault protection Trip is blocked ON 22.04.2022 12:47:37.636 Spontaneous
Com.Issued=AutoLocal
M2_TRIP ON 22.04.2022 12:47:37.633 Spontaneous
Com.Issued=AutoLocal
04056 Dis. Telep. Carrier SEND signal ON 22.04.2022 12:47:37.632 Spontaneous
Com.Issued=AutoLocal
00301 Power System fault 250 - ON 22.04.2022 12:47:37.632 Spontaneous
Com.Issued=AutoLocal
07130 >BLOCK I-STUB OFF 22.04.2022 12:47:37.627 Spontaneous
Com.Issued=AutoLocal
00060 Reset LED ON 01.02.2022 12:12:15.104 Spontaneous
Com.Issued=AutoLocal
Reset LED ON 01.02.2022 12:12:15.104 Spontaneous
Command Issued=Local
M CB_BO OFF 13.12.2021 10:03:36.125 Spontaneous
M CB_YO OFF 13.12.2021 10:03:36.125 Spontaneous
M CB_RO OFF 13.12.2021 10:03:36.125 Spontaneous
01332 Earth fault protection is BLOCKED OFF 13.12.2021 10:03:31.080 Spontaneous
Com.Issued=AutoLocal
14083 E/F 3I0p is blocked OFF 13.12.2021 10:03:31.080 Spontaneous
Com.Issued=AutoLocal

Page 134 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 26-04-2022 16:27:30.092 (SIGNALS\BM000011.SFP)(7)


Number Indication Value Date and time Cause State

00592 Single pole open detected in L2 OFF 13.12.2021 10:03:31.034 Spontaneous


Com.Issued=AutoLocal
01332 Earth fault protection is BLOCKED ON 13.12.2021 10:03:31.030 Spontaneous
Com.Issued=AutoLocal
14083 E/F 3I0p is blocked ON 13.12.2021 10:03:31.030 Spontaneous
Com.Issued=AutoLocal
00592 Single pole open detected in L2 ON 13.12.2021 10:03:31.029 Spontaneous
Com.Issued=AutoLocal
00381 >Single-phase trip permitted from ext.AR ON 09.12.2021 21:23:51.383 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P ON 09.12.2021 21:23:51.374 Spontaneous
00381 >Single-phase trip permitted from ext.AR OFF 09.12.2021 21:21:56.674 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P OFF 09.12.2021 21:21:56.674 Spontaneous
00004 >Trigger Waveform Capture ON 09.12.2021 21:21:56.474 Spontaneous
Com.Issued=AutoLocal
M CB_BO ON 09.12.2021 21:21:56.472 Spontaneous
M CB_RO ON 09.12.2021 21:21:56.472 Spontaneous
M CB_YO ON 09.12.2021 21:21:56.470 Spontaneous
ON/OFF (SP) OFF 24.11.2021 03:36:47.223 Spontaneous
ON/OFF (SP) ON 24.11.2021 03:36:47.219 Spontaneous
07131 >Enable I-STUB-Bus function OFF 24.11.2021 03:36:47.223 Spontaneous
Com.Issued=AutoLocal
07131 >Enable I-STUB-Bus function ON 24.11.2021 03:36:47.219 Spontaneous
Com.Issued=AutoLocal
00004 >Trigger Waveform Capture ON 24.11.2021 03:36:47.204 Spontaneous
Com.Issued=AutoLocal
ON/OFF (SP) OFF 24.11.2021 03:36:47.203 Spontaneous
T CB_RO OFF 24.11.2021 03:36:47.202 Spontaneous
T CB_RO ON 24.11.2021 03:36:47.200 Spontaneous
ON/OFF (SP) ON 24.11.2021 03:36:47.199 Spontaneous
ON/OFF (SP) OFF 24.11.2021 03:36:47.194 Spontaneous

Page 135 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 26-04-2022 16:27:30.092 (SIGNALS\BM000011.SFP)(8)


Number Indication Value Date and time Cause State

07131 >Enable I-STUB-Bus function OFF 24.11.2021 03:36:47.203 Spontaneous


Com.Issued=AutoLocal
07131 >Enable I-STUB-Bus function ON 24.11.2021 03:36:47.199 Spontaneous
Com.Issued=AutoLocal
07131 >Enable I-STUB-Bus function OFF 24.11.2021 03:36:47.194 Spontaneous
Com.Issued=AutoLocal
ON/OFF (SP) ON 24.11.2021 03:36:47.189 Spontaneous
07131 >Enable I-STUB-Bus function ON 24.11.2021 03:36:47.189 Spontaneous
Com.Issued=AutoLocal
00004 >Trigger Waveform Capture ON 24.11.2021 03:36:47.184 Spontaneous
Com.Issued=AutoLocal
ON/OFF (SP) OFF 24.11.2021 03:36:47.184 Spontaneous
T CB_BO OFF 24.11.2021 03:36:47.183 Spontaneous
T CB_RO OFF 24.11.2021 03:36:47.183 Spontaneous
T CB_BO ON 24.11.2021 03:36:47.181 Spontaneous
T CB_RO ON 24.11.2021 03:36:47.181 Spontaneous
ON/OFF (SP) ON 24.11.2021 03:36:47.179 Spontaneous
07131 >Enable I-STUB-Bus function OFF 24.11.2021 03:36:47.184 Spontaneous
Com.Issued=AutoLocal
07131 >Enable I-STUB-Bus function ON 24.11.2021 03:36:47.179 Spontaneous
Com.Issued=AutoLocal
00004 >Trigger Waveform Capture ON 24.11.2021 03:36:47.174 Spontaneous
Com.Issued=AutoLocal
07131 >Enable I-STUB-Bus function OFF 24.11.2021 03:36:47.174 Spontaneous
Com.Issued=AutoLocal
ON/OFF (SP) OFF 24.11.2021 03:36:47.174 Spontaneous
T CB_RO OFF 24.11.2021 03:36:47.174 Spontaneous
T CB_BO OFF 24.11.2021 03:36:47.173 Spontaneous
T CB_BO ON 24.11.2021 03:36:47.171 Spontaneous
T CB_RO ON 24.11.2021 03:36:47.171 Spontaneous
ON/OFF (SP) ON 24.11.2021 03:36:47.169 Spontaneous

Page 136 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 26-04-2022 16:27:30.092 (SIGNALS\BM000011.SFP)(9)


Number Indication Value Date and time Cause State

07131 >Enable I-STUB-Bus function ON 24.11.2021 03:36:47.169 Spontaneous


Com.Issued=AutoLocal
00004 >Trigger Waveform Capture ON 24.11.2021 03:36:47.164 Spontaneous
Com.Issued=AutoLocal
07131 >Enable I-STUB-Bus function OFF 24.11.2021 03:36:47.164 Spontaneous
Com.Issued=AutoLocal
ON/OFF (SP) OFF 24.11.2021 03:36:47.164 Spontaneous
T CB_RO OFF 24.11.2021 03:36:47.163 Spontaneous
T CB_RO ON 24.11.2021 03:36:47.161 Spontaneous
ON/OFF (SP) ON 24.11.2021 03:36:47.159 Spontaneous
07131 >Enable I-STUB-Bus function ON 24.11.2021 03:36:47.159 Spontaneous
Com.Issued=AutoLocal
07131 >Enable I-STUB-Bus function OFF 24.11.2021 03:36:47.154 Spontaneous
Com.Issued=AutoLocal
ON/OFF (SP) OFF 24.11.2021 03:36:47.154 Spontaneous
ON/OFF (SP) ON 24.11.2021 03:36:47.149 Spontaneous
07131 >Enable I-STUB-Bus function ON 24.11.2021 03:36:47.149 Spontaneous
Com.Issued=AutoLocal
00004 >Trigger Waveform Capture ON 24.11.2021 03:36:47.144 Spontaneous
Com.Issued=AutoLocal
07131 >Enable I-STUB-Bus function OFF 24.11.2021 03:36:47.144 Spontaneous
Com.Issued=AutoLocal
ON/OFF (SP) OFF 24.11.2021 03:36:47.144 Spontaneous
T CB_RO OFF 24.11.2021 03:36:47.143 Spontaneous
T CB_RO ON 24.11.2021 03:36:47.140 Spontaneous
ON/OFF (SP) ON 24.11.2021 03:36:47.139 Spontaneous
ON/OFF (SP) OFF 24.11.2021 03:36:47.134 Spontaneous
07131 >Enable I-STUB-Bus function ON 24.11.2021 03:36:47.139 Spontaneous
Com.Issued=AutoLocal
07131 >Enable I-STUB-Bus function OFF 24.11.2021 03:36:47.134 Spontaneous
Com.Issued=AutoLocal
ON/OFF (SP) ON 24.11.2021 03:36:47.130 Spontaneous

Page 137 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 26-04-2022 16:27:30.092 (SIGNALS\BM000011.SFP)(10)


Number Indication Value Date and time Cause State

07131 >Enable I-STUB-Bus function ON 24.11.2021 03:36:47.130 Spontaneous


Com.Issued=AutoLocal
00004 >Trigger Waveform Capture ON 24.11.2021 03:36:47.124 Spontaneous
Com.Issued=AutoLocal
ON/OFF (SP) OFF 24.11.2021 03:36:47.124 Spontaneous
T CB_RO OFF 24.11.2021 03:36:47.123 Spontaneous
T CB_BO OFF 24.11.2021 03:36:47.122 Spontaneous
T CB_BO ON 24.11.2021 03:36:47.120 Spontaneous
T CB_RO ON 24.11.2021 03:36:47.120 Spontaneous
ON/OFF (SP) ON 24.11.2021 03:36:47.119 Spontaneous
07131 >Enable I-STUB-Bus function OFF 24.11.2021 03:36:47.124 Spontaneous
Com.Issued=AutoLocal
07131 >Enable I-STUB-Bus function ON 24.11.2021 03:36:47.119 Spontaneous
Com.Issued=AutoLocal
00004 >Trigger Waveform Capture ON 24.11.2021 03:36:47.114 Spontaneous
Com.Issued=AutoLocal
07131 >Enable I-STUB-Bus function OFF 24.11.2021 03:36:47.114 Spontaneous
Com.Issued=AutoLocal
ON/OFF (SP) OFF 24.11.2021 03:36:47.114 Spontaneous
T CB_RO OFF 24.11.2021 03:36:47.113 Spontaneous
ON/OFF (SP) ON 24.11.2021 03:36:47.110 Spontaneous
T CB_RO ON 24.11.2021 03:36:47.110 Spontaneous
07131 >Enable I-STUB-Bus function ON 24.11.2021 03:36:47.110 Spontaneous
Com.Issued=AutoLocal
00004 >Trigger Waveform Capture ON 24.11.2021 03:36:47.104 Spontaneous
Com.Issued=AutoLocal
ON/OFF (SP) OFF 24.11.2021 03:36:47.104 Spontaneous
T CB_RO OFF 24.11.2021 03:36:47.103 Spontaneous
T CB_RO ON 24.11.2021 03:36:47.100 Spontaneous
ON/OFF (SP) ON 24.11.2021 03:36:47.099 Spontaneous
07131 >Enable I-STUB-Bus function OFF 24.11.2021 03:36:47.104 Spontaneous
Com.Issued=AutoLocal

Page 138 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 26-04-2022 16:27:30.092 (SIGNALS\BM000011.SFP)(11)


Number Indication Value Date and time Cause State

07131 >Enable I-STUB-Bus function ON 24.11.2021 03:36:47.099 Spontaneous


Com.Issued=AutoLocal
00004 >Trigger Waveform Capture ON 24.11.2021 03:36:47.094 Spontaneous
Com.Issued=AutoLocal
07131 >Enable I-STUB-Bus function OFF 24.11.2021 03:36:47.094 Spontaneous
Com.Issued=AutoLocal
ON/OFF (SP) OFF 24.11.2021 03:36:47.094 Spontaneous
T CB_RO OFF 24.11.2021 03:36:47.093 Spontaneous

6.12 Event Log - 11-08-2023 12:31:23.369 (SIGNALS\BM000012.SFP)

Event Log - 11-08-2023 12:31:23.369 (SIGNALS\BM000012.SFP)


Number Indication Value Date and time Cause State

00060 Reset LED ON 07.08.2023 14:36:50.362 Spontaneous


Com.Issued=AutoLocal
Reset LED ON 07.08.2023 14:36:50.362 Spontaneous
Command Issued=Local
00381 >Single-phase trip permitted from ext.AR ON 05.08.2023 23:55:39.512 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P ON 05.08.2023 23:55:39.509 Spontaneous
M1_TRIP OFF 05.08.2023 23:22:40.753 Spontaneous
M CB_BO OFF 05.08.2023 23:22:40.734 Spontaneous
M CB_YO OFF 05.08.2023 23:22:40.734 Spontaneous
M CB_RO OFF 05.08.2023 23:22:40.734 Spontaneous
00301 Power System fault 453 - OFF 05.08.2023 23:22:40.739 Spontaneous
Com.Issued=AutoLocal
M1_TRIP ON 05.08.2023 23:22:37.140 Spontaneous
00301 Power System fault 453 - ON 05.08.2023 23:22:37.117 Spontaneous
Com.Issued=AutoLocal
M CB_RO ON 05.08.2023 09:12:58.741 Spontaneous
M CB_BO ON 05.08.2023 09:12:58.737 Spontaneous

Page 139 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 11-08-2023 12:31:23.369 (SIGNALS\BM000012.SFP)(2)


Number Indication Value Date and time Cause State

00004 >Trigger Waveform Capture ON 05.08.2023 09:12:58.732 Spontaneous


Com.Issued=AutoLocal
M CB_YO ON 05.08.2023 09:12:58.728 Spontaneous
00381 >Single-phase trip permitted from ext.AR OFF 05.08.2023 08:09:41.832 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P OFF 05.08.2023 08:09:41.831 Spontaneous
M1_TRIP OFF 14.07.2023 18:15:05.143 Spontaneous
00301 Power System fault 450 - OFF 14.07.2023 18:15:05.133 Spontaneous
Com.Issued=AutoLocal
00004 >Trigger Waveform Capture ON 14.07.2023 18:15:05.122 Spontaneous
Com.Issued=AutoLocal
M1_TRIP ON 14.07.2023 18:15:05.117 Spontaneous
00301 Power System fault 450 - ON 14.07.2023 18:15:05.092 Spontaneous
Com.Issued=AutoLocal
00060 Reset LED ON 26.06.2023 13:38:23.217 Spontaneous
Com.Issued=AutoLocal
Reset LED ON 26.06.2023 13:38:23.217 Spontaneous
Command Issued=Local
00381 >Single-phase trip permitted from ext.AR ON 23.06.2023 20:43:21.242 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P ON 23.06.2023 20:43:21.239 Spontaneous
00590 Line closure detected OFF 23.06.2023 20:42:54.024 Spontaneous
Com.Issued=AutoLocal
01332 Earth fault protection is BLOCKED OFF 23.06.2023 20:42:53.869 Spontaneous
Com.Issued=AutoLocal
14083 E/F 3I0p is blocked OFF 23.06.2023 20:42:53.869 Spontaneous
Com.Issued=AutoLocal
M CB_YO OFF 23.06.2023 20:42:53.834 Spontaneous
00592 Single pole open detected in L2 OFF 23.06.2023 20:42:53.827 Spontaneous
Com.Issued=AutoLocal
00590 Line closure detected ON 23.06.2023 20:42:53.827 Spontaneous
Com.Issued=AutoLocal
OVST1/2 OFF 23.06.2023 20:42:53.804 Spontaneous

Page 140 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 11-08-2023 12:31:23.369 (SIGNALS\BM000012.SFP)(3)


Number Indication Value Date and time Cause State

00381 >Single-phase trip permitted from ext.AR OFF 23.06.2023 20:42:53.752 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P OFF 23.06.2023 20:42:53.749 Spontaneous
00004 >Trigger Waveform Capture ON 23.06.2023 20:42:53.712 Spontaneous
Com.Issued=AutoLocal
OVST1/2 ON 23.06.2023 20:42:53.708 Spontaneous
M1_TRIP OFF 23.06.2023 20:42:52.817 Spontaneous
ON/OFF (SP) OFF 23.06.2023 20:42:52.816 Spontaneous
ON/OFF (SP) ON 23.06.2023 20:42:52.816 Spontaneous
07152 Backup O/C is BLOCKED ON 23.06.2023 20:42:52.816 Spontaneous
Com.Issued=AutoLocal
07131 >Enable I-STUB-Bus function OFF 23.06.2023 20:42:52.816 Spontaneous
Com.Issued=AutoLocal
07130 >BLOCK I-STUB ON 23.06.2023 20:42:52.816 Spontaneous
Com.Issued=AutoLocal
M2_TRIP OFF 23.06.2023 20:42:52.808 Spontaneous
Com.Issued=AutoLocal
M/TCBAR OFF 23.06.2023 20:42:52.794 Spontaneous
01335 Earth fault protection Trip is blocked OFF 23.06.2023 20:42:52.802 Spontaneous
Com.Issued=AutoLocal
00301 Power System fault 449 - OFF 23.06.2023 20:42:52.796 Spontaneous
Com.Issued=AutoLocal
04010 >Dis.Tele. Carrier RECEPTION Channel 2 OFF 23.06.2023 20:42:52.756 Spontaneous
Com.Issued=AutoLocal
04009 >Dis.Tele.Carrier RECEPTION Channel 1,L3 OFF 23.06.2023 20:42:52.756 Spontaneous
Com.Issued=AutoLocal
04008 >Dis.Tele.Carrier RECEPTION Channel 1,L2 OFF 23.06.2023 20:42:52.756 Spontaneous
Com.Issued=AutoLocal
04007 >Dis.Tele.Carrier RECEPTION Channel 1,L1 OFF 23.06.2023 20:42:52.756 Spontaneous
Com.Issued=AutoLocal
04006 >Dis.Tele. Carrier RECEPTION Channel 1 OFF 23.06.2023 20:42:52.756 Spontaneous
Com.Issued=AutoLocal

Page 141 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 11-08-2023 12:31:23.369 (SIGNALS\BM000012.SFP)(4)


Number Indication Value Date and time Cause State

01332 Earth fault protection is BLOCKED ON 23.06.2023 20:42:52.752 Spontaneous


Com.Issued=AutoLocal
14083 E/F 3I0p is blocked ON 23.06.2023 20:42:52.752 Spontaneous
Com.Issued=AutoLocal
00592 Single pole open detected in L2 ON 23.06.2023 20:42:52.752 Spontaneous
Com.Issued=AutoLocal
M CB_YO ON 23.06.2023 20:42:52.732 Spontaneous
M/TCBAR ON 23.06.2023 20:42:52.716 Spontaneous
ON/OFF (SP) ON 23.06.2023 20:42:52.714 Spontaneous
07152 Backup O/C is BLOCKED OFF 23.06.2023 20:42:52.714 Spontaneous
Com.Issued=AutoLocal
07131 >Enable I-STUB-Bus function ON 23.06.2023 20:42:52.714 Spontaneous
Com.Issued=AutoLocal
M2_TRIP ON 23.06.2023 20:42:52.706 Spontaneous
Com.Issued=AutoLocal
04010 >Dis.Tele. Carrier RECEPTION Channel 2 ON 23.06.2023 20:42:52.706 Spontaneous
Com.Issued=AutoLocal
04009 >Dis.Tele.Carrier RECEPTION Channel 1,L3 ON 23.06.2023 20:42:52.706 Spontaneous
Com.Issued=AutoLocal
04008 >Dis.Tele.Carrier RECEPTION Channel 1,L2 ON 23.06.2023 20:42:52.706 Spontaneous
Com.Issued=AutoLocal
04007 >Dis.Tele.Carrier RECEPTION Channel 1,L1 ON 23.06.2023 20:42:52.706 Spontaneous
Com.Issued=AutoLocal
04006 >Dis.Tele. Carrier RECEPTION Channel 1 ON 23.06.2023 20:42:52.706 Spontaneous
Com.Issued=AutoLocal
00004 >Trigger Waveform Capture ON 23.06.2023 20:42:52.704 Spontaneous
Com.Issued=AutoLocal
M1_TRIP ON 23.06.2023 20:42:52.695 Spontaneous
ON/OFF (SP) OFF 23.06.2023 20:42:52.691 Spontaneous
01335 Earth fault protection Trip is blocked ON 23.06.2023 20:42:52.693 Spontaneous
Com.Issued=AutoLocal
07130 >BLOCK I-STUB OFF 23.06.2023 20:42:52.691 Spontaneous
Com.Issued=AutoLocal

Page 142 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 11-08-2023 12:31:23.369 (SIGNALS\BM000012.SFP)(5)


Number Indication Value Date and time Cause State

00301 Power System fault 449 - ON 23.06.2023 20:42:52.688 Spontaneous


Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 01.06.2023 06:45:49.064 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 01.06.2023 06:45:45.364 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 01.06.2023 06:45:44.464 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 01.06.2023 06:45:37.864 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) OFF 01.06.2023 06:45:36.464 Spontaneous
Com.Issued=AutoLocal
009.0101.01 Failure EN100 Link Channel 1 (Ch1) ON 01.06.2023 06:45:32.064 Spontaneous
Com.Issued=AutoLocal
00381 >Single-phase trip permitted from ext.AR ON 24.04.2023 20:53:00.952 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P ON 24.04.2023 20:53:00.946 Spontaneous
00381 >Single-phase trip permitted from ext.AR OFF 24.04.2023 20:07:38.652 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P OFF 24.04.2023 20:07:38.643 Spontaneous
00381 >Single-phase trip permitted from ext.AR ON 24.04.2023 19:59:21.042 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P ON 24.04.2023 19:59:21.038 Spontaneous
00381 >Single-phase trip permitted from ext.AR OFF 24.04.2023 19:53:14.282 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P OFF 24.04.2023 19:53:14.282 Spontaneous
00381 >Single-phase trip permitted from ext.AR ON 24.04.2023 19:45:14.383 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P ON 24.04.2023 19:45:14.381 Spontaneous
00381 >Single-phase trip permitted from ext.AR OFF 24.04.2023 18:52:11.842 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P OFF 24.04.2023 18:52:11.834 Spontaneous

Page 143 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 11-08-2023 12:31:23.369 (SIGNALS\BM000012.SFP)(6)


Number Indication Value Date and time Cause State

00381 >Single-phase trip permitted from ext.AR ON 04.02.2023 23:13:00.413 Spontaneous


Com.Issued=AutoLocal
PREPARE 3P ON 04.02.2023 23:13:00.405 Spontaneous
M CB_BO OFF 04.02.2023 22:50:42.199 Spontaneous
M CB_YO OFF 04.02.2023 22:50:42.199 Spontaneous
M CB_RO OFF 04.02.2023 22:50:42.199 Spontaneous
M CB_RO ON 04.02.2023 10:32:22.733 Spontaneous
M CB_BO ON 04.02.2023 10:32:22.731 Spontaneous
00004 >Trigger Waveform Capture ON 04.02.2023 10:32:22.722 Spontaneous
Com.Issued=AutoLocal
M CB_YO ON 04.02.2023 10:32:22.718 Spontaneous
00381 >Single-phase trip permitted from ext.AR OFF 04.02.2023 09:40:46.192 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P OFF 04.02.2023 09:40:46.187 Spontaneous
M1_TRIP OFF 28.01.2023 01:49:52.054 Spontaneous
00301 Power System fault 447 - OFF 28.01.2023 01:49:52.053 Spontaneous
Com.Issued=AutoLocal
ON/OFF (SP) OFF 28.01.2023 01:49:52.050 Spontaneous
ON/OFF (SP) ON 28.01.2023 01:49:52.050 Spontaneous
07152 Backup O/C is BLOCKED ON 28.01.2023 01:49:52.050 Spontaneous
Com.Issued=AutoLocal
07131 >Enable I-STUB-Bus function OFF 28.01.2023 01:49:52.050 Spontaneous
Com.Issued=AutoLocal
07130 >BLOCK I-STUB ON 28.01.2023 01:49:52.050 Spontaneous
Com.Issued=AutoLocal
ON/OFF (SP) ON 28.01.2023 01:49:52.023 Spontaneous
07152 Backup O/C is BLOCKED OFF 28.01.2023 01:49:52.023 Spontaneous
Com.Issued=AutoLocal
07131 >Enable I-STUB-Bus function ON 28.01.2023 01:49:52.023 Spontaneous
Com.Issued=AutoLocal
00004 >Trigger Waveform Capture ON 28.01.2023 01:49:52.014 Spontaneous
Com.Issued=AutoLocal

Page 144 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 11-08-2023 12:31:23.369 (SIGNALS\BM000012.SFP)(7)


Number Indication Value Date and time Cause State

M1_TRIP ON 28.01.2023 01:49:52.004 Spontaneous


00301 Power System fault 447 - ON 28.01.2023 01:49:52.012 Spontaneous
Com.Issued=AutoLocal
ON/OFF (SP) OFF 28.01.2023 01:49:52.001 Spontaneous
07130 >BLOCK I-STUB OFF 28.01.2023 01:49:52.001 Spontaneous
Com.Issued=AutoLocal
00301 Power System fault 446 - OFF 31.12.2022 02:28:50.658 Spontaneous
Com.Issued=AutoLocal
00301 Power System fault 446 - ON 31.12.2022 02:28:50.608 Spontaneous
Com.Issued=AutoLocal
00381 >Single-phase trip permitted from ext.AR ON 29.12.2022 23:47:46.982 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P ON 29.12.2022 23:47:46.974 Spontaneous
M CB_BO OFF 29.12.2022 23:20:12.651 Spontaneous
M CB_YO OFF 29.12.2022 23:20:12.651 Spontaneous
M CB_RO OFF 29.12.2022 23:20:12.651 Spontaneous
M CB_RO ON 29.12.2022 09:01:26.665 Spontaneous
M CB_BO ON 29.12.2022 09:01:26.664 Spontaneous
00004 >Trigger Waveform Capture ON 29.12.2022 09:01:26.662 Spontaneous
Com.Issued=AutoLocal
M CB_YO ON 29.12.2022 09:01:26.660 Spontaneous
00381 >Single-phase trip permitted from ext.AR OFF 29.12.2022 08:37:31.662 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P OFF 29.12.2022 08:37:31.656 Spontaneous
00301 Power System fault 444 - OFF 27.12.2022 22:57:43.650 Spontaneous
Com.Issued=AutoLocal
00301 Power System fault 444 - ON 27.12.2022 22:57:43.610 Spontaneous
Com.Issued=AutoLocal
00301 Power System fault 443 - OFF 14.11.2022 12:31:23.889 Spontaneous
Com.Issued=AutoLocal
00301 Power System fault 443 - ON 14.11.2022 12:31:23.869 Spontaneous
Com.Issued=AutoLocal

Page 145 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 11-08-2023 12:31:23.369 (SIGNALS\BM000012.SFP)(8)


Number Indication Value Date and time Cause State

00301 Power System fault 442 - OFF 02.11.2022 00:41:24.471 Spontaneous


Com.Issued=AutoLocal
00301 Power System fault 442 - ON 02.11.2022 00:41:24.431 Spontaneous
Com.Issued=AutoLocal
M CB_BO OFF 13.10.2022 21:29:14.276 Spontaneous
M CB_YO OFF 13.10.2022 21:29:14.276 Spontaneous
M CB_RO OFF 13.10.2022 21:29:14.276 Spontaneous
00381 >Single-phase trip permitted from ext.AR ON 13.10.2022 20:11:34.042 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P ON 13.10.2022 20:11:34.034 Spontaneous
00381 >Single-phase trip permitted from ext.AR OFF 13.10.2022 20:11:32.472 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P OFF 13.10.2022 20:11:32.463 Spontaneous
00381 >Single-phase trip permitted from ext.AR ON 13.10.2022 20:10:09.672 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P ON 13.10.2022 20:10:09.668 Spontaneous
00381 >Single-phase trip permitted from ext.AR OFF 13.10.2022 20:10:02.842 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P OFF 13.10.2022 20:10:02.838 Spontaneous
00381 >Single-phase trip permitted from ext.AR ON 13.10.2022 20:10:02.762 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P ON 13.10.2022 20:10:02.760 Spontaneous
00381 >Single-phase trip permitted from ext.AR OFF 13.10.2022 20:10:02.582 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P OFF 13.10.2022 20:10:02.582 Spontaneous
00381 >Single-phase trip permitted from ext.AR ON 13.10.2022 20:08:51.912 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P ON 13.10.2022 20:08:51.909 Spontaneous
00381 >Single-phase trip permitted from ext.AR OFF 13.10.2022 20:08:27.332 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P OFF 13.10.2022 20:08:27.329 Spontaneous
00381 >Single-phase trip permitted from ext.AR ON 13.10.2022 20:08:27.252 Spontaneous
Com.Issued=AutoLocal

Page 146 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 11-08-2023 12:31:23.369 (SIGNALS\BM000012.SFP)(9)


Number Indication Value Date and time Cause State

PREPARE 3P ON 13.10.2022 20:08:27.251 Spontaneous


00381 >Single-phase trip permitted from ext.AR OFF 13.10.2022 20:08:27.062 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P OFF 13.10.2022 20:08:27.062 Spontaneous
00381 >Single-phase trip permitted from ext.AR ON 13.10.2022 19:23:56.613 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P ON 13.10.2022 19:23:56.613 Spontaneous
00381 >Single-phase trip permitted from ext.AR OFF 13.10.2022 19:23:28.623 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P OFF 13.10.2022 19:23:28.615 Spontaneous
00381 >Single-phase trip permitted from ext.AR ON 13.10.2022 18:40:03.763 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P ON 13.10.2022 18:40:03.754 Spontaneous
00381 >Single-phase trip permitted from ext.AR OFF 13.10.2022 18:39:53.533 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P OFF 13.10.2022 18:39:53.524 Spontaneous
00381 >Single-phase trip permitted from ext.AR ON 13.10.2022 18:39:53.363 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P ON 13.10.2022 18:39:53.359 Spontaneous
00381 >Single-phase trip permitted from ext.AR OFF 13.10.2022 18:39:06.042 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P OFF 13.10.2022 18:39:06.041 Spontaneous
00381 >Single-phase trip permitted from ext.AR ON 13.10.2022 18:39:05.932 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P ON 13.10.2022 18:39:05.925 Spontaneous
00381 >Single-phase trip permitted from ext.AR OFF 13.10.2022 18:39:04.982 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P OFF 13.10.2022 18:39:04.981 Spontaneous
00381 >Single-phase trip permitted from ext.AR ON 13.10.2022 18:39:04.692 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P ON 13.10.2022 18:39:04.691 Spontaneous
00381 >Single-phase trip permitted from ext.AR OFF 13.10.2022 18:39:04.422 Spontaneous
Com.Issued=AutoLocal

Page 147 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 11-08-2023 12:31:23.369 (SIGNALS\BM000012.SFP)(10)


Number Indication Value Date and time Cause State

PREPARE 3P OFF 13.10.2022 18:39:04.415 Spontaneous


00381 >Single-phase trip permitted from ext.AR ON 13.10.2022 18:37:10.412 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P ON 13.10.2022 18:37:10.407 Spontaneous
00381 >Single-phase trip permitted from ext.AR OFF 13.10.2022 18:37:10.162 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P OFF 13.10.2022 18:37:10.155 Spontaneous
00381 >Single-phase trip permitted from ext.AR ON 13.10.2022 18:37:10.022 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P ON 13.10.2022 18:37:10.017 Spontaneous
00381 >Single-phase trip permitted from ext.AR OFF 13.10.2022 18:37:00.453 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P OFF 13.10.2022 18:37:00.448 Spontaneous
00381 >Single-phase trip permitted from ext.AR ON 13.10.2022 18:36:56.023 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P ON 13.10.2022 18:36:56.021 Spontaneous
00381 >Single-phase trip permitted from ext.AR OFF 13.10.2022 18:36:49.633 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P OFF 13.10.2022 18:36:49.632 Spontaneous
00381 >Single-phase trip permitted from ext.AR ON 13.10.2022 18:36:16.102 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P ON 13.10.2022 18:36:16.095 Spontaneous
00381 >Single-phase trip permitted from ext.AR OFF 13.10.2022 18:35:39.812 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P OFF 13.10.2022 18:35:39.807 Spontaneous
00381 >Single-phase trip permitted from ext.AR ON 13.10.2022 18:24:57.962 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P ON 13.10.2022 18:24:57.961 Spontaneous
00381 >Single-phase trip permitted from ext.AR OFF 13.10.2022 18:24:47.242 Spontaneous
Com.Issued=AutoLocal
PREPARE 3P OFF 13.10.2022 18:24:47.236 Spontaneous
00381 >Single-phase trip permitted from ext.AR ON 13.10.2022 18:24:46.852 Spontaneous
Com.Issued=AutoLocal

Page 148 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Event Log - 11-08-2023 12:31:23.369 (SIGNALS\BM000012.SFP)(11)


Number Indication Value Date and time Cause State

PREPARE 3P ON 13.10.2022 18:24:46.847 Spontaneous

6.13 Trip Log - 000258 21-12-2016 01:09:46.334 (SIGNALS\FAULT\NS000001.SFP)

Trip Log - 000258 21-12-2016 01:09:46.334 (SIGNALS\FAULT\NS000001.SFP)


Number Indication Value Date and time Cause State

00301 Power System fault 258 - ON 21.12.2016 01:09:46.334


00302 Fault Event 259 - ON 21.12.2016 01:09:46.334
10240 Uph-e> Pickup ON 1 ms
10243 Uph-e>(>) Pickup L2 ON 1 ms
10240 Uph-e> Pickup OFF 21 ms
10243 Uph-e>(>) Pickup L2 OFF 21 ms

6.14 Trip Log - 000256 20-12-2016 02:06:11.441 (SIGNALS\FAULT\NS000002.SFP)

Trip Log - 000256 20-12-2016 02:06:11.441 (SIGNALS\FAULT\NS000002.SFP)


Number Indication Value Date and time Cause State

00301 Power System fault 256 - ON 20.12.2016 02:06:11.441


00302 Fault Event 257 - ON 20.12.2016 02:06:11.441
10240 Uph-e> Pickup ON 0 ms
10242 Uph-e>(>) Pickup L1 ON 0 ms
10244 Uph-e>(>) Pickup L3 ON 140 ms
10247 Uph-e>(>) TRIP command ON 3998 ms
00533 Primary fault current IL1 0.00 kA 3999 ms
00534 Primary fault current IL2 0.00 kA 3999 ms
00535 Primary fault current IL3 0.00 kA 3999 ms
10240 Uph-e> Pickup OFF 5061 ms
10242 Uph-e>(>) Pickup L1 OFF 5061 ms

Page 149 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Trip Log - 000256 20-12-2016 02:06:11.441 (SIGNALS\FAULT\NS000002.SFP)(2)


Number Indication Value Date and time Cause State

10244 Uph-e>(>) Pickup L3 OFF 5061 ms


00511 Relay GENERAL TRIP command OFF 5061 ms

6.15 Trip Log - 000255 20-12-2016 02:01:25.615 (SIGNALS\FAULT\NS000003.SFP)

Trip Log - 000255 20-12-2016 02:01:25.615 (SIGNALS\FAULT\NS000003.SFP)


Number Indication Value Date and time Cause State

00301 Power System fault 255 - ON 20.12.2016 02:01:25.615


00302 Fault Event 256 - ON 20.12.2016 02:01:25.615
10240 Uph-e> Pickup ON 0 ms
10242 Uph-e>(>) Pickup L1 ON 0 ms
10244 Uph-e>(>) Pickup L3 ON 20 ms
10247 Uph-e>(>) TRIP command ON 3999 ms
00533 Primary fault current IL1 0.00 kA 3999 ms
00534 Primary fault current IL2 0.00 kA 4000 ms
00535 Primary fault current IL3 0.00 kA 4000 ms
10240 Uph-e> Pickup OFF 5059 ms
10242 Uph-e>(>) Pickup L1 OFF 5059 ms
10244 Uph-e>(>) Pickup L3 OFF 5059 ms
00511 Relay GENERAL TRIP command OFF 5059 ms

6.16 Trip Log - 000253 18-12-2016 21:58:32.199 (SIGNALS\FAULT\NS000004.SFP)

Trip Log - 000253 18-12-2016 21:58:32.199 (SIGNALS\FAULT\NS000004.SFP)


Number Indication Value Date and time Cause State

00301 Power System fault 253 - ON 18.12.2016 21:58:32.199


00302 Fault Event 254 - ON 18.12.2016 21:58:32.199
10240 Uph-e> Pickup ON 0 ms

Page 150 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Trip Log - 000253 18-12-2016 21:58:32.199 (SIGNALS\FAULT\NS000004.SFP)(2)


Number Indication Value Date and time Cause State

10244 Uph-e>(>) Pickup L3 ON 0 ms


10240 Uph-e> Pickup OFF 20 ms
10244 Uph-e>(>) Pickup L3 OFF 20 ms

6.17 Trip Log - 000251 17-12-2016 22:01:31.944 (SIGNALS\FAULT\NS000005.SFP)

Trip Log - 000251 17-12-2016 22:01:31.944 (SIGNALS\FAULT\NS000005.SFP)


Number Indication Value Date and time Cause State

00301 Power System fault 251 - ON 17.12.2016 22:01:31.944


00302 Fault Event 252 - ON 17.12.2016 22:01:31.944
10240 Uph-e> Pickup ON 1 ms
10243 Uph-e>(>) Pickup L2 ON 1 ms
10240 Uph-e> Pickup OFF 20 ms
10243 Uph-e>(>) Pickup L2 OFF 20 ms

6.18 Trip Log - 000249 16-12-2016 22:59:02.085 (SIGNALS\FAULT\NS000006.SFP)

Trip Log - 000249 16-12-2016 22:59:02.085 (SIGNALS\FAULT\NS000006.SFP)


Number Indication Value Date and time Cause State

00301 Power System fault 249 - ON 16.12.2016 22:59:02.085


00302 Fault Event 250 - ON 16.12.2016 22:59:02.085
10240 Uph-e> Pickup ON 0 ms
10242 Uph-e>(>) Pickup L1 ON 0 ms
10240 Uph-e> Pickup OFF 20 ms
10242 Uph-e>(>) Pickup L1 OFF 20 ms

Page 151 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39
Trip Log - 000247 14-12-2016 20:09:36.200 (SIGNALS\FAULT\NS000007.SFP)
NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

6.19 Trip Log - 000247 14-12-2016 20:09:36.200 (SIGNALS\FAULT\NS000007.SFP)

Trip Log - 000247 14-12-2016 20:09:36.200 (SIGNALS\FAULT\NS000007.SFP)


Number Indication Value Date and time Cause State

00301 Power System fault 247 - ON 14.12.2016 20:09:36.200


00302 Fault Event 248 - ON 14.12.2016 20:09:36.200
03684 Distance Pickup L2E ON 0 ms
03702 Distance Loop L2E selected forward ON 0 ms
01335 Earth fault protection Trip is blocked ON 8 ms
01358 E/F picked up FORWARD ON 9 ms
01337 E/F phase selector L2 selected ON 9 ms
01357 E/F 3I0p PICKED UP ON 9 ms
04006 >Dis.Tele. Carrier RECEPTION Channel 1 ON 35 ms
04007 >Dis.Tele.Carrier RECEPTION Channel 1,L1 ON 35 ms
04008 >Dis.Tele.Carrier RECEPTION Channel 1,L2 ON 35 ms
04009 >Dis.Tele.Carrier RECEPTION Channel 1,L3 ON 35 ms
04010 >Dis.Tele. Carrier RECEPTION Channel 2 ON 35 ms
03803 Distance TRIP command - Only Phase L2 ON 35 ms
00534 Primary fault current IL2 2.34 kA 38 ms
00592 Single pole open detected in L2 ON 52 ms
14083 E/F 3I0p is blocked ON 58 ms
01332 Earth fault protection is BLOCKED ON 58 ms
03671 Distance PICKED UP OFF 59 ms
03702 Distance Loop L2E selected forward OFF 59 ms
01337 E/F phase selector L2 selected OFF 59 ms
01345 Earth fault protection PICKED UP OFF 59 ms
01124 Fault Locator Loop L2E ON 20 ms
01117 Flt Locator: secondary RESISTANCE 3.36 Ohm 20 ms
01118 Flt Locator: secondary REACTANCE 13.34 Ohm 20 ms
01114 Flt Locator: primary RESISTANCE 12.23 Ohm 20 ms
01115 Flt Locator: primary REACTANCE 48.53 Ohm 20 ms
01119 Flt Locator: Distance to fault 158.1 km 20 ms

Page 152 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Trip Log - 000247 14-12-2016 20:09:36.200 (SIGNALS\FAULT\NS000007.SFP)(2)


Number Indication Value Date and time Cause State

01120 Flt Locator: Distance [%] to fault 81.9 % 20 ms

6.20 Trip Log - 000245 26-09-2016 03:22:30.770 (SIGNALS\FAULT\NS000008.SFP)

Trip Log - 000245 26-09-2016 03:22:30.770 (SIGNALS\FAULT\NS000008.SFP)


Number Indication Value Date and time Cause State

00301 Power System fault 245 - ON 26.09.2016 03:22:30.770


00302 Fault Event 246 - ON 26.09.2016 03:22:30.770
10240 Uph-e> Pickup ON 0 ms
10244 Uph-e>(>) Pickup L3 ON 0 ms
10240 Uph-e> Pickup OFF 20 ms
10244 Uph-e>(>) Pickup L3 OFF 20 ms

6.21 Trip Log - 001112 08-04-2018 05:16:37.059 (SIGNALS\FAULT\NS000009.SFP)

Trip Log - 001112 08-04-2018 05:16:37.059 (SIGNALS\FAULT\NS000009.SFP)


Number Indication Value Date and time Cause State

00301 Power System fault 1112 - ON 08.04.2018 05:16:37.059


00302 Fault Event 1114 - ON 08.04.2018 05:16:37.059
03684 Distance Pickup L2E ON 1 ms
03702 Distance Loop L2E selected forward ON 1 ms
01335 Earth fault protection Trip is blocked ON 5 ms
01358 E/F picked up FORWARD ON 6 ms
01337 E/F phase selector L2 selected ON 6 ms
01357 E/F 3I0p PICKED UP ON 6 ms
03805 Distance TRIP command Phases L123 ON 400 ms
00533 Primary fault current IL1 0.97 kA 405 ms
00534 Primary fault current IL2 2.89 kA 405 ms

Page 153 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Trip Log - 001112 08-04-2018 05:16:37.059 (SIGNALS\FAULT\NS000009.SFP)(2)


Number Indication Value Date and time Cause State

00535 Primary fault current IL3 0.09 kA 405 ms


03671 Distance PICKED UP OFF 452 ms
03702 Distance Loop L2E selected forward OFF 452 ms
01337 E/F phase selector L2 selected OFF 457 ms
01345 Earth fault protection PICKED UP OFF 457 ms
00302 Fault Event 1115 - ON 08.04.2018 05:16:37.531
10240 Uph-e> Pickup ON 472 ms
10242 Uph-e>(>) Pickup L1 ON 472 ms
10244 Uph-e>(>) Pickup L3 ON 472 ms
01335 Earth fault protection Trip is blocked OFF 497 ms
01124 Fault Locator Loop L2E ON 422 ms
01117 Flt Locator: secondary RESISTANCE 0.59 Ohm 422 ms
01118 Flt Locator: secondary REACTANCE 13.57 Ohm 422 ms
01114 Flt Locator: primary RESISTANCE 2.14 Ohm 422 ms
01115 Flt Locator: primary REACTANCE 49.34 Ohm 422 ms
01119 Flt Locator: Distance to fault 160.8 km 422 ms
01120 Flt Locator: Distance [%] to fault 83.3 % 422 ms
00511 Relay GENERAL TRIP command OFF 502 ms
00592 Single pole open detected in L2 ON 507 ms
14083 E/F 3I0p is blocked ON 507 ms
01332 Earth fault protection is BLOCKED ON 507 ms
00592 Single pole open detected in L2 OFF 1184 ms
14083 E/F 3I0p is blocked OFF 1214 ms
01332 Earth fault protection is BLOCKED OFF 1214 ms
10247 Uph-e>(>) TRIP command ON 5468 ms
00533 Primary fault current IL1 0.00 kA 5468 ms
00534 Primary fault current IL2 0.00 kA 5469 ms
00535 Primary fault current IL3 0.00 kA 5469 ms
10244 Uph-e>(>) Pickup L3 OFF 08.04.2018 05:18:32.105
10240 Uph-e> Pickup OFF 08.04.2018 05:26:48.391

Page 154 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Trip Log - 001112 08-04-2018 05:16:37.059 (SIGNALS\FAULT\NS000009.SFP)(3)


Number Indication Value Date and time Cause State

10242 Uph-e>(>) Pickup L1 OFF 08.04.2018 05:26:48.391


00511 Relay GENERAL TRIP command OFF 08.04.2018 05:26:48.391

6.22 Trip Log - 001115 08-04-2018 06:37:42.049 (SIGNALS\FAULT\NS000010.SFP)

Trip Log - 001115 08-04-2018 06:37:42.049 (SIGNALS\FAULT\NS000010.SFP)


Number Indication Value Date and time Cause State

00301 Power System fault 1115 - ON 08.04.2018 06:37:42.049


00302 Fault Event 1118 - ON 08.04.2018 06:37:42.049
10240 Uph-e> Pickup ON 0 ms
10242 Uph-e>(>) Pickup L1 ON 0 ms
10247 Uph-e>(>) TRIP command ON 4998 ms
00533 Primary fault current IL1 0.00 kA 5000 ms
00534 Primary fault current IL2 0.00 kA 5000 ms
00535 Primary fault current IL3 0.00 kA 5000 ms
10240 Uph-e> Pickup OFF 08.04.2018 06:40:22.736
10242 Uph-e>(>) Pickup L1 OFF 08.04.2018 06:40:22.736
00511 Relay GENERAL TRIP command OFF 08.04.2018 06:40:22.736

6.23 Trip Log - 001114 08-04-2018 05:41:38.949 (SIGNALS\FAULT\NS000011.SFP)

Trip Log - 001114 08-04-2018 05:41:38.949 (SIGNALS\FAULT\NS000011.SFP)


Number Indication Value Date and time Cause State

00301 Power System fault 1114 - ON 08.04.2018 05:41:38.949


00302 Fault Event 1117 - ON 08.04.2018 05:41:38.949
10240 Uph-e> Pickup ON 0 ms
10242 Uph-e>(>) Pickup L1 ON 0 ms
10247 Uph-e>(>) TRIP command ON 4998 ms

Page 155 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Trip Log - 001114 08-04-2018 05:41:38.949 (SIGNALS\FAULT\NS000011.SFP)(2)


Number Indication Value Date and time Cause State

00533 Primary fault current IL1 0.00 kA 4999 ms


00534 Primary fault current IL2 0.00 kA 4999 ms
00535 Primary fault current IL3 0.00 kA 4999 ms
10244 Uph-e>(>) Pickup L3 ON 08.04.2018 06:02:47.757
10244 Uph-e>(>) Pickup L3 OFF 08.04.2018 06:05:48.693
10240 Uph-e> Pickup OFF 08.04.2018 06:26:25.526
10242 Uph-e>(>) Pickup L1 OFF 08.04.2018 06:26:25.526
00511 Relay GENERAL TRIP command OFF 08.04.2018 06:26:25.526

6.24 Trip Log - 001113 08-04-2018 05:26:48.531 (SIGNALS\FAULT\NS000012.SFP)

Trip Log - 001113 08-04-2018 05:26:48.531 (SIGNALS\FAULT\NS000012.SFP)


Number Indication Value Date and time Cause State

00301 Power System fault 1113 - ON 08.04.2018 05:26:48.531


00302 Fault Event 1116 - ON 08.04.2018 05:26:48.531
10240 Uph-e> Pickup ON 0 ms
10242 Uph-e>(>) Pickup L1 ON 0 ms
10247 Uph-e>(>) TRIP command ON 4996 ms
00533 Primary fault current IL1 0.00 kA 4999 ms
00534 Primary fault current IL2 0.00 kA 4999 ms
00535 Primary fault current IL3 0.00 kA 4999 ms
10240 Uph-e> Pickup OFF 08.04.2018 05:41:38.609
10242 Uph-e>(>) Pickup L1 OFF 08.04.2018 05:41:38.609
00511 Relay GENERAL TRIP command OFF 08.04.2018 05:41:38.609

Page 156 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39
Trip Log - 001109 31-10-2017 19:12:30.344 (SIGNALS\FAULT\NS000013.SFP)
NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

6.25 Trip Log - 001109 31-10-2017 19:12:30.344 (SIGNALS\FAULT\NS000013.SFP)

Trip Log - 001109 31-10-2017 19:12:30.344 (SIGNALS\FAULT\NS000013.SFP)


Number Indication Value Date and time Cause State

00301 Power System fault 1109 - ON 31.10.2017 19:12:30.344


00302 Fault Event 1111 - ON 31.10.2017 19:12:30.344
10240 Uph-e> Pickup ON 1 ms
10242 Uph-e>(>) Pickup L1 ON 1 ms
10240 Uph-e> Pickup OFF 40 ms
10242 Uph-e>(>) Pickup L1 OFF 40 ms

6.26 Trip Log - 001108 31-10-2017 19:06:11.983 (SIGNALS\FAULT\NS000014.SFP)

Trip Log - 001108 31-10-2017 19:06:11.983 (SIGNALS\FAULT\NS000014.SFP)


Number Indication Value Date and time Cause State

00301 Power System fault 1108 - ON 31.10.2017 19:06:11.983


00302 Fault Event 1110 - ON 31.10.2017 19:06:11.983
10240 Uph-e> Pickup ON 0 ms
10242 Uph-e>(>) Pickup L1 ON 0 ms
10247 Uph-e>(>) TRIP command ON 4998 ms
00533 Primary fault current IL1 0.00 kA 4999 ms
00534 Primary fault current IL2 0.00 kA 4999 ms
00535 Primary fault current IL3 0.00 kA 4999 ms
10240 Uph-e> Pickup OFF 31.10.2017 19:11:08.722
10242 Uph-e>(>) Pickup L1 OFF 31.10.2017 19:11:08.722
00511 Relay GENERAL TRIP command OFF 31.10.2017 19:11:08.722

Page 157 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39
Trip Log - 001106 31-10-2017 16:38:00.798 (SIGNALS\FAULT\NS000015.SFP)
NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

6.27 Trip Log - 001106 31-10-2017 16:38:00.798 (SIGNALS\FAULT\NS000015.SFP)

Trip Log - 001106 31-10-2017 16:38:00.798 (SIGNALS\FAULT\NS000015.SFP)


Number Indication Value Date and time Cause State

00301 Power System fault 1106 - ON 31.10.2017 16:38:00.798


00302 Fault Event 1108 - ON 31.10.2017 16:38:00.798
10240 Uph-e> Pickup ON 0 ms
10241 Uph-e>> Pickup ON 0 ms
10242 Uph-e>(>) Pickup L1 ON 0 ms
10243 Uph-e>(>) Pickup L2 ON 0 ms
10244 Uph-e>(>) Pickup L3 ON 0 ms
10247 Uph-e>(>) TRIP command ON 48 ms
00533 Primary fault current IL1 0.00 kA 49 ms
00534 Primary fault current IL2 0.00 kA 49 ms
00535 Primary fault current IL3 0.00 kA 49 ms
10240 Uph-e> Pickup OFF 649 ms
10241 Uph-e>> Pickup OFF 649 ms
10242 Uph-e>(>) Pickup L1 OFF 649 ms
10243 Uph-e>(>) Pickup L2 OFF 649 ms
10244 Uph-e>(>) Pickup L3 OFF 649 ms
00511 Relay GENERAL TRIP command OFF 649 ms

6.28 Trip Log - 001105 31-10-2017 16:32:34.163 (SIGNALS\FAULT\NS000016.SFP)

Trip Log - 001105 31-10-2017 16:32:34.163 (SIGNALS\FAULT\NS000016.SFP)


Number Indication Value Date and time Cause State

00301 Power System fault 1105 - ON 31.10.2017 16:32:34.163


00302 Fault Event 1107 - ON 31.10.2017 16:32:34.163
10240 Uph-e> Pickup ON 0 ms
10241 Uph-e>> Pickup ON 0 ms
10242 Uph-e>(>) Pickup L1 ON 0 ms
10243 Uph-e>(>) Pickup L2 ON 0 ms

Page 158 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Trip Log - 001105 31-10-2017 16:32:34.163 (SIGNALS\FAULT\NS000016.SFP)(2)


Number Indication Value Date and time Cause State

10244 Uph-e>(>) Pickup L3 ON 0 ms


10247 Uph-e>(>) TRIP command ON 48 ms
00533 Primary fault current IL1 0.00 kA 49 ms
00534 Primary fault current IL2 0.00 kA 49 ms
00535 Primary fault current IL3 0.00 kA 49 ms
10240 Uph-e> Pickup OFF 860 ms
10241 Uph-e>> Pickup OFF 860 ms
10242 Uph-e>(>) Pickup L1 OFF 860 ms
10243 Uph-e>(>) Pickup L2 OFF 860 ms
10244 Uph-e>(>) Pickup L3 OFF 860 ms
00511 Relay GENERAL TRIP command OFF 860 ms

6.29 Trip Log - 001122 01-06-2018 18:36:42.938 (SIGNALS\FAULT\NS000017.SFP)

Trip Log - 001122 01-06-2018 18:36:42.938 (SIGNALS\FAULT\NS000017.SFP)


Number Indication Value Date and time Cause State

00301 Power System fault 1122 - ON 01.06.2018 18:36:42.938


00302 Fault Event 1125 - ON 01.06.2018 18:36:42.938
01358 E/F picked up FORWARD ON 0 ms
01357 E/F 3I0p PICKED UP ON 0 ms
01345 Earth fault protection PICKED UP OFF 50 ms

6.30 Trip Log - 001121 31-05-2018 02:14:36.626 (SIGNALS\FAULT\NS000018.SFP)

Trip Log - 001121 31-05-2018 02:14:36.626 (SIGNALS\FAULT\NS000018.SFP)


Number Indication Value Date and time Cause State

00301 Power System fault 1121 - ON 31.05.2018 02:14:36.626


00302 Fault Event 1124 - ON 31.05.2018 02:14:36.626

Page 159 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Trip Log - 001121 31-05-2018 02:14:36.626 (SIGNALS\FAULT\NS000018.SFP)(2)


Number Indication Value Date and time Cause State

01358 E/F picked up FORWARD ON 0 ms


01357 E/F 3I0p PICKED UP ON 0 ms
01345 Earth fault protection PICKED UP OFF 60 ms

6.31 Trip Log - 001120 17-05-2018 17:01:26.023 (SIGNALS\FAULT\NS000019.SFP)

Trip Log - 001120 17-05-2018 17:01:26.023 (SIGNALS\FAULT\NS000019.SFP)


Number Indication Value Date and time Cause State

00301 Power System fault 1120 - ON 17.05.2018 17:01:26.023


00302 Fault Event 1123 - ON 17.05.2018 17:01:26.023
01358 E/F picked up FORWARD ON 0 ms
01357 E/F 3I0p PICKED UP ON 0 ms
01345 Earth fault protection PICKED UP OFF 50 ms

6.32 Trip Log - 001119 14-05-2018 20:26:38.562 (SIGNALS\FAULT\NS000020.SFP)

Trip Log - 001119 14-05-2018 20:26:38.562 (SIGNALS\FAULT\NS000020.SFP)


Number Indication Value Date and time Cause State

00301 Power System fault 1119 - ON 14.05.2018 20:26:38.562


00302 Fault Event 1122 - ON 14.05.2018 20:26:38.562
01358 E/F picked up FORWARD ON 0 ms
01357 E/F 3I0p PICKED UP ON 0 ms
01345 Earth fault protection PICKED UP OFF 50 ms

Page 160 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39
Trip Log - 001118 13-05-2018 05:35:05.085 (SIGNALS\FAULT\NS000021.SFP)
NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

6.33 Trip Log - 001118 13-05-2018 05:35:05.085 (SIGNALS\FAULT\NS000021.SFP)

Trip Log - 001118 13-05-2018 05:35:05.085 (SIGNALS\FAULT\NS000021.SFP)


Number Indication Value Date and time Cause State

00301 Power System fault 1118 - ON 13.05.2018 05:35:05.085


00302 Fault Event 1121 - ON 13.05.2018 05:35:05.085
01358 E/F picked up FORWARD ON 1 ms
01357 E/F 3I0p PICKED UP ON 1 ms
01345 Earth fault protection PICKED UP OFF 70 ms

6.34 Trip Log - 001117 13-05-2018 05:24:12.581 (SIGNALS\FAULT\NS000022.SFP)

Trip Log - 001117 13-05-2018 05:24:12.581 (SIGNALS\FAULT\NS000022.SFP)


Number Indication Value Date and time Cause State

00301 Power System fault 1117 - ON 13.05.2018 05:24:12.581


00302 Fault Event 1120 - ON 13.05.2018 05:24:12.581
01358 E/F picked up FORWARD ON 0 ms
01357 E/F 3I0p PICKED UP ON 0 ms
01345 Earth fault protection PICKED UP OFF 50 ms

6.35 Trip Log - 001116 08-04-2018 10:42:22.570 (SIGNALS\FAULT\NS000023.SFP)

Trip Log - 001116 08-04-2018 10:42:22.570 (SIGNALS\FAULT\NS000023.SFP)


Number Indication Value Date and time Cause State

00301 Power System fault 1116 - ON 08.04.2018 10:42:22.570


00302 Fault Event 1119 - ON 08.04.2018 10:42:22.570
10240 Uph-e> Pickup ON 0 ms
10242 Uph-e>(>) Pickup L1 ON 0 ms
10240 Uph-e> Pickup OFF 120 ms
10242 Uph-e>(>) Pickup L1 OFF 120 ms

Page 161 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39
Trip Log - 001138 09-02-2019 23:27:51.813 (SIGNALS\FAULT\NS000024.SFP)
NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

6.36 Trip Log - 001138 09-02-2019 23:27:51.813 (SIGNALS\FAULT\NS000024.SFP)

Trip Log - 001138 09-02-2019 23:27:51.813 (SIGNALS\FAULT\NS000024.SFP)


Number Indication Value Date and time Cause State

00301 Power System fault 1138 - ON 09.02.2019 23:27:51.813


00302 Fault Event 1141 - ON 09.02.2019 23:27:51.813
03689 Distance Pickup L31 ON 0 ms
03706 Distance Loop L31 selected forward ON 1 ms
01335 Earth fault protection Trip is blocked ON 1 ms
03805 Distance TRIP command Phases L123 ON 5 ms
04056 Dis. Telep. Carrier SEND signal ON 5 ms
00533 Primary fault current IL1 6.07 kA 9 ms
00534 Primary fault current IL2 0.44 kA 9 ms
00535 Primary fault current IL3 6.44 kA 9 ms
04006 >Dis.Tele. Carrier RECEPTION Channel 1 ON 24 ms
04007 >Dis.Tele.Carrier RECEPTION Channel 1,L1 ON 24 ms
04008 >Dis.Tele.Carrier RECEPTION Channel 1,L2 ON 24 ms
04009 >Dis.Tele.Carrier RECEPTION Channel 1,L3 ON 24 ms
04010 >Dis.Tele. Carrier RECEPTION Channel 2 ON 24 ms
10240 Uph-e> Pickup ON 45 ms
10244 Uph-e>(>) Pickup L3 ON 45 ms
03671 Distance PICKED UP OFF 50 ms
03706 Distance Loop L31 selected forward OFF 50 ms
01370 E/F Inrush picked up ON 50 ms
01358 E/F picked up FORWARD ON 50 ms
01338 E/F phase selector L3 selected ON 50 ms
01357 E/F 3I0p PICKED UP ON 50 ms
10240 Uph-e> Pickup OFF 65 ms
10244 Uph-e>(>) Pickup L3 OFF 65 ms
01370 E/F Inrush picked up OFF 70 ms
01338 E/F phase selector L3 selected OFF 70 ms
01345 Earth fault protection PICKED UP OFF 70 ms

Page 162 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Trip Log - 001138 09-02-2019 23:27:51.813 (SIGNALS\FAULT\NS000024.SFP)(2)


Number Indication Value Date and time Cause State

01128 Fault Locator Loop L3L1 ON 13 ms


01117 Flt Locator: secondary RESISTANCE 0.03 Ohm 13 ms
01118 Flt Locator: secondary REACTANCE 6.66 Ohm 13 ms
01114 Flt Locator: primary RESISTANCE 0.11 Ohm 13 ms
01115 Flt Locator: primary REACTANCE 24.23 Ohm 13 ms
01119 Flt Locator: Distance to fault 78.9 km 13 ms
01120 Flt Locator: Distance [%] to fault 40.9 % 13 ms

6.37 Trip Log - 000155 17-04-2019 16:12:35.947 (SIGNALS\FAULT\NS000025.SFP)

Trip Log - 000155 17-04-2019 16:12:35.947 (SIGNALS\FAULT\NS000025.SFP)


Number Indication Value Date and time Cause State

00301 Power System fault 155 - ON 17.04.2019 16:12:35.947


00302 Fault Event 155 - ON 17.04.2019 16:12:35.947
03684 Distance Pickup L2E ON 0 ms
03702 Distance Loop L2E selected forward ON 0 ms
03803 Distance TRIP command - Only Phase L2 ON 0 ms
04056 Dis. Telep. Carrier SEND signal ON 0 ms
00534 Primary fault current IL2 11.99 kA 4 ms
01335 Earth fault protection Trip is blocked ON 4 ms
03692 Distance Pickup L23E ON 5 ms
03703 Distance Loop L3E selected forward ON 5 ms
03705 Distance Loop L23 selected forward ON 5 ms
03805 Distance TRIP command Phases L123 ON 5 ms
01358 E/F picked up FORWARD ON 6 ms
01357 E/F 3I0p PICKED UP ON 6 ms
00533 Primary fault current IL1 0.78 kA 9 ms
00535 Primary fault current IL3 12.40 kA 9 ms
07131 >Enable I-STUB-Bus function ON 23 ms

Page 163 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Trip Log - 000155 17-04-2019 16:12:35.947 (SIGNALS\FAULT\NS000025.SFP)(2)


Number Indication Value Date and time Cause State

07152 Backup O/C is BLOCKED OFF 23 ms


07163 Backup O/C PICKUP L2 ON 30 ms
07164 Backup O/C PICKUP L3 ON 30 ms
07182 Backup O/C Pickup L23 ON 30 ms
07201 O/C I-STUB Pickup ON 30 ms
03671 Distance PICKED UP OFF 49 ms
03702 Distance Loop L2E selected forward OFF 49 ms
03703 Distance Loop L3E selected forward OFF 49 ms
03705 Distance Loop L23 selected forward OFF 49 ms
10240 Uph-e> Pickup ON 50 ms
10242 Uph-e>(>) Pickup L1 ON 50 ms
07161 Backup O/C PICKED UP OFF 59 ms
07201 O/C I-STUB Pickup OFF 59 ms
10240 Uph-e> Pickup OFF 69 ms
10242 Uph-e>(>) Pickup L1 OFF 69 ms
01345 Earth fault protection PICKED UP OFF 75 ms
01124 Fault Locator Loop L2E ON 22 ms
01117 Flt Locator: secondary RESISTANCE 0.54 Ohm 22 ms
01118 Flt Locator: secondary REACTANCE 2.84 Ohm 22 ms
01114 Flt Locator: primary RESISTANCE 1.97 Ohm 22 ms
01115 Flt Locator: primary REACTANCE 10.34 Ohm 22 ms
01119 Flt Locator: Distance to fault 33.7 km 22 ms
01120 Flt Locator: Distance [%] to fault 17.5 % 22 ms

6.38 Trip Log - 000227 01-10-2021 18:20:35.754 (SIGNALS\FAULT\NS000026.SFP)

Trip Log - 000227 01-10-2021 18:20:35.754 (SIGNALS\FAULT\NS000026.SFP)


Number Indication Value Date and time Cause State

00301 Power System fault 227 - ON 01.10.2021 18:20:35.754

Page 164 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Trip Log - 000227 01-10-2021 18:20:35.754 (SIGNALS\FAULT\NS000026.SFP)(2)


Number Indication Value Date and time Cause State

00302 Fault Event 228 - ON 01.10.2021 18:20:35.754


04284 SOTF-O/C Pickup L3 ON 0 ms
04295 SOTF-O/C TRIP command L123 ON 0 ms
00533 Primary fault current IL1 0.26 kA 5 ms
00534 Primary fault current IL2 0.36 kA 5 ms
00535 Primary fault current IL3 1.59 kA 5 ms
03688 Distance Pickup L3E ON 11 ms
03703 Distance Loop L3E selected forward ON 11 ms
01335 Earth fault protection Trip is blocked ON 11 ms
07131 >Enable I-STUB-Bus function ON 33 ms
07152 Backup O/C is BLOCKED OFF 33 ms
07164 Backup O/C PICKUP L3 ON 36 ms
07178 Backup O/C Pickup - Only L3 ON 36 ms
07201 O/C I-STUB Pickup ON 36 ms
00590 Line closure detected OFF 40 ms
14083 E/F 3I0p is blocked OFF 40 ms
01332 Earth fault protection is BLOCKED OFF 40 ms
03671 Distance PICKED UP OFF 46 ms
03703 Distance Loop L3E selected forward OFF 46 ms
07161 Backup O/C PICKED UP OFF 56 ms
07201 O/C I-STUB Pickup OFF 56 ms
04281 SOTF-O/C PICKED UP OFF 70 ms

6.39 Trip Log - 000250 22-04-2022 12:47:37.632 (SIGNALS\FAULT\NS000027.SFP)

Trip Log - 000250 22-04-2022 12:47:37.632 (SIGNALS\FAULT\NS000027.SFP)


Number Indication Value Date and time Cause State

00301 Power System fault 250 - ON 22.04.2022 12:47:37.632


00302 Fault Event 251 - ON 22.04.2022 12:47:37.632

Page 165 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Trip Log - 000250 22-04-2022 12:47:37.632 (SIGNALS\FAULT\NS000027.SFP)(2)


Number Indication Value Date and time Cause State

03688 Distance Pickup L3E ON 0 ms


03703 Distance Loop L3E selected forward ON 0 ms
03804 Distance TRIP command - Only Phase L3 ON 0 ms
04056 Dis. Telep. Carrier SEND signal ON 0 ms
00535 Primary fault current IL3 4.59 kA 4 ms
01335 Earth fault protection Trip is blocked ON 4 ms
01358 E/F picked up FORWARD ON 5 ms
01338 E/F phase selector L3 selected ON 5 ms
01357 E/F 3I0p PICKED UP ON 6 ms
07131 >Enable I-STUB-Bus function ON 17 ms
04006 >Dis.Tele. Carrier RECEPTION Channel 1 ON 17 ms
04007 >Dis.Tele.Carrier RECEPTION Channel 1,L1 ON 17 ms
04008 >Dis.Tele.Carrier RECEPTION Channel 1,L2 ON 17 ms
04009 >Dis.Tele.Carrier RECEPTION Channel 1,L3 ON 17 ms
04010 >Dis.Tele. Carrier RECEPTION Channel 2 ON 17 ms
07152 Backup O/C is BLOCKED OFF 17 ms
07164 Backup O/C PICKUP L3 ON 20 ms
07178 Backup O/C Pickup - Only L3 ON 20 ms
07201 O/C I-STUB Pickup ON 20 ms
00593 Single pole open detected in L3 ON 44 ms
14083 E/F 3I0p is blocked ON 44 ms
01332 Earth fault protection is BLOCKED ON 44 ms
01338 E/F phase selector L3 selected OFF 45 ms
01345 Earth fault protection PICKED UP OFF 45 ms
03671 Distance PICKED UP OFF 55 ms
03703 Distance Loop L3E selected forward OFF 55 ms
07161 Backup O/C PICKED UP OFF 60 ms
07201 O/C I-STUB Pickup OFF 60 ms
01125 Fault Locator Loop L3E ON 11 ms
01117 Flt Locator: secondary RESISTANCE 3.85 Ohm 11 ms

Page 166 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Trip Log - 000250 22-04-2022 12:47:37.632 (SIGNALS\FAULT\NS000027.SFP)(3)


Number Indication Value Date and time Cause State

01118 Flt Locator: secondary REACTANCE 5.92 Ohm 11 ms


01114 Flt Locator: primary RESISTANCE 14.02 Ohm 11 ms
01115 Flt Locator: primary REACTANCE 21.52 Ohm 11 ms
01119 Flt Locator: Distance to fault 70.1 km 11 ms
01120 Flt Locator: Distance [%] to fault 36.3 % 11 ms

6.40 Trip Log - 000252 22-04-2022 12:47:38.756 (SIGNALS\FAULT\NS000028.SFP)

Trip Log - 000252 22-04-2022 12:47:38.756 (SIGNALS\FAULT\NS000028.SFP)


Number Indication Value Date and time Cause State

00301 Power System fault 252 - ON 22.04.2022 12:47:38.756


00302 Fault Event 253 - ON 22.04.2022 12:47:38.756
04284 SOTF-O/C Pickup L3 ON 0 ms
04295 SOTF-O/C TRIP command L123 ON 0 ms
03688 Distance Pickup L3E ON 1 ms
03703 Distance Loop L3E selected forward ON 1 ms
00533 Primary fault current IL1 0.34 kA 5 ms
00534 Primary fault current IL2 0.74 kA 5 ms
00535 Primary fault current IL3 4.85 kA 5 ms
01335 Earth fault protection Trip is blocked ON 10 ms
14083 E/F 3I0p is blocked OFF 30 ms
01332 Earth fault protection is BLOCKED OFF 30 ms
07131 >Enable I-STUB-Bus function ON 34 ms
07152 Backup O/C is BLOCKED OFF 34 ms
07164 Backup O/C PICKUP L3 ON 36 ms
07178 Backup O/C Pickup - Only L3 ON 36 ms
07201 O/C I-STUB Pickup ON 36 ms
01358 E/F picked up FORWARD ON 41 ms
01338 E/F phase selector L3 selected ON 41 ms

Page 167 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Trip Log - 000252 22-04-2022 12:47:38.756 (SIGNALS\FAULT\NS000028.SFP)(2)


Number Indication Value Date and time Cause State

01357 E/F 3I0p PICKED UP ON 41 ms


00590 Line closure detected OFF 45 ms
03671 Distance PICKED UP OFF 45 ms
03703 Distance Loop L3E selected forward OFF 45 ms
07161 Backup O/C PICKED UP OFF 55 ms
07201 O/C I-STUB Pickup OFF 55 ms
01338 E/F phase selector L3 selected OFF 71 ms
01345 Earth fault protection PICKED UP OFF 71 ms
04281 SOTF-O/C PICKED UP OFF 80 ms

6.41 Trip Log - 000253 22-04-2022 12:47:38.901 (SIGNALS\FAULT\NS000029.SFP)

Trip Log - 000253 22-04-2022 12:47:38.901 (SIGNALS\FAULT\NS000029.SFP)


Number Indication Value Date and time Cause State

00301 Power System fault 253 - ON 22.04.2022 12:47:38.901


00302 Fault Event 254 - ON 22.04.2022 12:47:38.901
10240 Uph-e> Pickup ON 0 ms
10242 Uph-e>(>) Pickup L1 ON 1 ms
10243 Uph-e>(>) Pickup L2 ON 20 ms
10243 Uph-e>(>) Pickup L2 OFF 40 ms
04006 >Dis.Tele. Carrier RECEPTION Channel 1 ON 52 ms
04007 >Dis.Tele.Carrier RECEPTION Channel 1,L1 ON 52 ms
04008 >Dis.Tele.Carrier RECEPTION Channel 1,L2 ON 52 ms
04009 >Dis.Tele.Carrier RECEPTION Channel 1,L3 ON 52 ms
04010 >Dis.Tele. Carrier RECEPTION Channel 2 ON 52 ms
10240 Uph-e> Pickup OFF 60 ms
10242 Uph-e>(>) Pickup L1 OFF 60 ms

Page 168 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39
Trip Log - 000256 28-07-2022 10:30:17.710 (SIGNALS\FAULT\NS000030.SFP)
NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

6.42 Trip Log - 000256 28-07-2022 10:30:17.710 (SIGNALS\FAULT\NS000030.SFP)

Trip Log - 000256 28-07-2022 10:30:17.710 (SIGNALS\FAULT\NS000030.SFP)


Number Indication Value Date and time Cause State

00301 Power System fault 256 - ON 28.07.2022 10:30:17.710


00302 Fault Event 257 - ON 28.07.2022 10:30:17.710
03682 Distance Pickup L1E ON 0 ms
03701 Distance Loop L1E selected forward ON 0 ms
01335 Earth fault protection Trip is blocked ON 0 ms
04006 >Dis.Tele. Carrier RECEPTION Channel 1 ON 3 ms
04007 >Dis.Tele.Carrier RECEPTION Channel 1,L1 ON 3 ms
04008 >Dis.Tele.Carrier RECEPTION Channel 1,L2 ON 3 ms
04009 >Dis.Tele.Carrier RECEPTION Channel 1,L3 ON 3 ms
04010 >Dis.Tele. Carrier RECEPTION Channel 2 ON 3 ms
01358 E/F picked up FORWARD ON 10 ms
01336 E/F phase selector L1 selected ON 10 ms
01357 E/F 3I0p PICKED UP ON 10 ms
03802 Distance TRIP command - Only Phase L1 ON 45 ms
00533 Primary fault current IL1 2.65 kA 49 ms
07131 >Enable I-STUB-Bus function ON 51 ms
07152 Backup O/C is BLOCKED OFF 51 ms
07162 Backup O/C PICKUP L1 ON 55 ms
07172 Backup O/C Pickup - Only L1 ON 55 ms
07201 O/C I-STUB Pickup ON 55 ms
00591 Single pole open detected in L1 ON 93 ms
03671 Distance PICKED UP OFF 94 ms
03701 Distance Loop L1E selected forward OFF 94 ms
07161 Backup O/C PICKED UP OFF 95 ms
07201 O/C I-STUB Pickup OFF 95 ms
14083 E/F 3I0p is blocked ON 99 ms
01332 Earth fault protection is BLOCKED ON 99 ms
01336 E/F phase selector L1 selected OFF 100 ms

Page 169 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Trip Log - 000256 28-07-2022 10:30:17.710 (SIGNALS\FAULT\NS000030.SFP)(2)


Number Indication Value Date and time Cause State

01345 Earth fault protection PICKED UP OFF 100 ms


01123 Fault Locator Loop L1E ON 28.07.2022 10:30:17.703
01117 Flt Locator: secondary RESISTANCE 14.99 Ohm 28.07.2022 10:30:17.703
01118 Flt Locator: secondary REACTANCE 23.58 Ohm 28.07.2022 10:30:17.703
01114 Flt Locator: primary RESISTANCE 54.50 Ohm 28.07.2022 10:30:17.703
01115 Flt Locator: primary REACTANCE 85.73 Ohm 28.07.2022 10:30:17.703
01119 Flt Locator: Distance to fault 279.3 km 28.07.2022 10:30:17.703
01120 Flt Locator: Distance [%] to fault 144.7 % 28.07.2022 10:30:17.703

6.43 Trip Log - 000453 05-08-2023 23:22:37.117 (SIGNALS\FAULT\NS000031.SFP)

Trip Log - 000453 05-08-2023 23:22:37.117 (SIGNALS\FAULT\NS000031.SFP)


Number Indication Value Date and time Cause State

00301 Power System fault 453 - ON 05.08.2023 23:22:37.117


00302 Fault Event 454 - ON 05.08.2023 23:22:37.117
10240 Uph-e> Pickup ON 0 ms
10242 Uph-e>(>) Pickup L1 ON 0 ms
10240 Uph-e> Pickup OFF 3622 ms
10242 Uph-e>(>) Pickup L1 OFF 3622 ms

6.44 Trip Log - 000450 14-07-2023 18:15:05.092 (SIGNALS\FAULT\NS000032.SFP)

Trip Log - 000450 14-07-2023 18:15:05.092 (SIGNALS\FAULT\NS000032.SFP)


Number Indication Value Date and time Cause State

00301 Power System fault 450 - ON 14.07.2023 18:15:05.092


00302 Fault Event 451 - ON 14.07.2023 18:15:05.092
01358 E/F picked up FORWARD ON 0 ms
01337 E/F phase selector L2 selected ON 0 ms

Page 170 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Trip Log - 000450 14-07-2023 18:15:05.092 (SIGNALS\FAULT\NS000032.SFP)(2)


Number Indication Value Date and time Cause State

01357 E/F 3I0p PICKED UP ON 0 ms


01370 E/F Inrush picked up ON 30 ms
01370 E/F Inrush picked up OFF 40 ms
01337 E/F phase selector L2 selected OFF 40 ms
01345 Earth fault protection PICKED UP OFF 40 ms

6.45 Trip Log - 000449 23-06-2023 20:42:52.688 (SIGNALS\FAULT\NS000033.SFP)

Trip Log - 000449 23-06-2023 20:42:52.688 (SIGNALS\FAULT\NS000033.SFP)


Number Indication Value Date and time Cause State

00301 Power System fault 449 - ON 23.06.2023 20:42:52.688


00302 Fault Event 450 - ON 23.06.2023 20:42:52.688
03684 Distance Pickup L2E ON 0 ms
03702 Distance Loop L2E selected forward ON 0 ms
01335 Earth fault protection Trip is blocked ON 5 ms
01358 E/F picked up FORWARD ON 6 ms
01337 E/F phase selector L2 selected ON 6 ms
01357 E/F 3I0p PICKED UP ON 6 ms
04006 >Dis.Tele. Carrier RECEPTION Channel 1 ON 18 ms
04007 >Dis.Tele.Carrier RECEPTION Channel 1,L1 ON 18 ms
04008 >Dis.Tele.Carrier RECEPTION Channel 1,L2 ON 18 ms
04009 >Dis.Tele.Carrier RECEPTION Channel 1,L3 ON 18 ms
04010 >Dis.Tele. Carrier RECEPTION Channel 2 ON 18 ms
03803 Distance TRIP command - Only Phase L2 ON 18 ms
00534 Primary fault current IL2 1.82 kA 19 ms
07131 >Enable I-STUB-Bus function ON 26 ms
07152 Backup O/C is BLOCKED OFF 26 ms
07163 Backup O/C PICKUP L2 ON 30 ms
07174 Backup O/C Pickup - Only L2 ON 30 ms

Page 171 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Trip Log - 000449 23-06-2023 20:42:52.688 (SIGNALS\FAULT\NS000033.SFP)(2)


Number Indication Value Date and time Cause State

07201 O/C I-STUB Pickup ON 30 ms


00592 Single pole open detected in L2 ON 64 ms
14083 E/F 3I0p is blocked ON 64 ms
01332 Earth fault protection is BLOCKED ON 64 ms
03671 Distance PICKED UP OFF 65 ms
03702 Distance Loop L2E selected forward OFF 65 ms
01337 E/F phase selector L2 selected OFF 66 ms
01345 Earth fault protection PICKED UP OFF 66 ms
07161 Backup O/C PICKED UP OFF 70 ms
07201 O/C I-STUB Pickup OFF 70 ms
01124 Fault Locator Loop L2E ON 10 ms
01117 Flt Locator: secondary RESISTANCE 8.05 Ohm 10 ms
01118 Flt Locator: secondary REACTANCE 18.74 Ohm 10 ms
01114 Flt Locator: primary RESISTANCE 29.27 Ohm 10 ms
01115 Flt Locator: primary REACTANCE 68.16 Ohm 10 ms
01119 Flt Locator: Distance to fault 222.1 km 10 ms
01120 Flt Locator: Distance [%] to fault 115.1 % 10 ms

6.46 Trip Log - 000447 28-01-2023 01:49:52.012 (SIGNALS\FAULT\NS000034.SFP)

Trip Log - 000447 28-01-2023 01:49:52.012 (SIGNALS\FAULT\NS000034.SFP)


Number Indication Value Date and time Cause State

00301 Power System fault 447 - ON 28.01.2023 01:49:52.012


00302 Fault Event 448 - ON 28.01.2023 01:49:52.012
01358 E/F picked up FORWARD ON 0 ms
01337 E/F phase selector L2 selected ON 0 ms
01357 E/F 3I0p PICKED UP ON 0 ms
07131 >Enable I-STUB-Bus function ON 11 ms
07152 Backup O/C is BLOCKED OFF 11 ms

Page 172 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Trip Log - 000447 28-01-2023 01:49:52.012 (SIGNALS\FAULT\NS000034.SFP)(2)


Number Indication Value Date and time Cause State

01370 E/F Inrush picked up ON 30 ms


01337 E/F phase selector L2 selected OFF 30 ms
07131 >Enable I-STUB-Bus function OFF 38 ms
07152 Backup O/C is BLOCKED ON 38 ms
01370 E/F Inrush picked up OFF 40 ms
01345 Earth fault protection PICKED UP OFF 40 ms

6.47 Trip Log - 000446 31-12-2022 02:28:50.608 (SIGNALS\FAULT\NS000035.SFP)

Trip Log - 000446 31-12-2022 02:28:50.608 (SIGNALS\FAULT\NS000035.SFP)


Number Indication Value Date and time Cause State

00301 Power System fault 446 - ON 31.12.2022 02:28:50.608


00302 Fault Event 447 - ON 31.12.2022 02:28:50.608
01358 E/F picked up FORWARD ON 0 ms
01336 E/F phase selector L1 selected ON 0 ms
01357 E/F 3I0p PICKED UP ON 0 ms
01336 E/F phase selector L1 selected OFF 10 ms
01345 Earth fault protection PICKED UP OFF 50 ms

6.48 Trip Log - 000444 27-12-2022 22:57:43.610 (SIGNALS\FAULT\NS000036.SFP)

Trip Log - 000444 27-12-2022 22:57:43.610 (SIGNALS\FAULT\NS000036.SFP)


Number Indication Value Date and time Cause State

00301 Power System fault 444 - ON 27.12.2022 22:57:43.610


00302 Fault Event 445 - ON 27.12.2022 22:57:43.610
01358 E/F picked up FORWARD ON 0 ms
01357 E/F 3I0p PICKED UP ON 0 ms
01345 Earth fault protection PICKED UP OFF 40 ms

Page 173 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39
Trip Log - 000443 14-11-2022 12:31:23.869 (SIGNALS\FAULT\NS000037.SFP)
NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

6.49 Trip Log - 000443 14-11-2022 12:31:23.869 (SIGNALS\FAULT\NS000037.SFP)

Trip Log - 000443 14-11-2022 12:31:23.869 (SIGNALS\FAULT\NS000037.SFP)


Number Indication Value Date and time Cause State

00301 Power System fault 443 - ON 14.11.2022 12:31:23.869


00302 Fault Event 444 - ON 14.11.2022 12:31:23.869
01358 E/F picked up FORWARD ON 0 ms
01357 E/F 3I0p PICKED UP ON 0 ms
01370 E/F Inrush picked up OFF 20 ms
01345 Earth fault protection PICKED UP OFF 20 ms

6.50 Trip Log - 000442 02-11-2022 00:41:24.431 (SIGNALS\FAULT\NS000038.SFP)

Trip Log - 000442 02-11-2022 00:41:24.431 (SIGNALS\FAULT\NS000038.SFP)


Number Indication Value Date and time Cause State

00301 Power System fault 442 - ON 02.11.2022 00:41:24.431


00302 Fault Event 443 - ON 02.11.2022 00:41:24.431
01358 E/F picked up FORWARD ON 0 ms
01357 E/F 3I0p PICKED UP ON 0 ms
01345 Earth fault protection PICKED UP OFF 40 ms

6.51 General Interrogation

nothing allocated

6.52 Spontaneous Annunciation

nothing allocated

Page 174 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39
Statistics - 21-12-2016 11:00:37.079 (MEASURED\ST010000.SFP)
NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

6.53 Statistics - 21-12-2016 11:00:37.079 (MEASURED\ST010000.SFP)

Statistics - 21-12-2016 11:00:37.079 (MEASURED\ST010000.SFP)


Number Measured value Value

01001 Number of breaker TRIP commands L1 99


01002 Number of breaker TRIP commands L2 98
01003 Number of breaker TRIP commands L3 98
01027 Accumulation of interrupted current L1 221.18 kA
01028 Accumulation of interrupted current L2 176.43 kA
01029 Accumulation of interrupted current L3 175.08 kA
01030 Max. fault current Phase L1 19.10 kA
01031 Max. fault current Phase L2 13.06 kA
01032 Max. fault current Phase L3 13.06 kA
31000 Q0 operationcounter= 0
31001 Q1 operationcounter= 0
31002 Q2 operationcounter= 0
31008 Q8 operationcounter= 0
31009 Q9 operationcounter= 0

6.54 Statistics - 08-04-2018 11:04:26.533 (MEASURED\ST010001.SFP)

Statistics - 08-04-2018 11:04:26.533 (MEASURED\ST010001.SFP)


Number Measured value Value

01001 Number of breaker TRIP commands L1 286


01002 Number of breaker TRIP commands L2 285
01003 Number of breaker TRIP commands L3 285
01027 Accumulation of interrupted current L1 545.53 kA
01028 Accumulation of interrupted current L2 386.31 kA
01029 Accumulation of interrupted current L3 263.24 kA
01030 Max. fault current Phase L1 19.10 kA
01031 Max. fault current Phase L2 13.06 kA
01032 Max. fault current Phase L3 13.06 kA

Page 175 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Statistics - 08-04-2018 11:04:26.533 (MEASURED\ST010001.SFP)(2)


Number Measured value Value

31000 Q0 operationcounter= 0
31001 Q1 operationcounter= 0
31002 Q2 operationcounter= 0
31008 Q8 operationcounter= 0
31009 Q9 operationcounter= 0

6.55 Statistics - 13-06-2018 17:10:13.247 (MEASURED\ST010002.SFP)

Statistics - 13-06-2018 17:10:13.247 (MEASURED\ST010002.SFP)


Number Measured value Value

01001 Number of breaker TRIP commands L1 286


01002 Number of breaker TRIP commands L2 285
01003 Number of breaker TRIP commands L3 285
01027 Accumulation of interrupted current L1 545.53 kA
01028 Accumulation of interrupted current L2 386.31 kA
01029 Accumulation of interrupted current L3 263.24 kA
01030 Max. fault current Phase L1 19.10 kA
01031 Max. fault current Phase L2 13.06 kA
01032 Max. fault current Phase L3 13.06 kA
31000 Q0 operationcounter= 0
31001 Q1 operationcounter= 0
31002 Q2 operationcounter= 0
31008 Q8 operationcounter= 0
31009 Q9 operationcounter= 0

Page 176 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39
Statistics - 11-08-2023 12:31:39.758 (MEASURED\ST010003.SFP)
NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

6.56 Statistics - 11-08-2023 12:31:39.758 (MEASURED\ST010003.SFP)

Statistics - 11-08-2023 12:31:39.758 (MEASURED\ST010003.SFP)


Number Measured value Value

01001 Number of breaker TRIP commands L1 437


01002 Number of breaker TRIP commands L2 438
01003 Number of breaker TRIP commands L3 434
01027 Accumulation of interrupted current L1 749.11 kA
01028 Accumulation of interrupted current L2 626.27 kA
01029 Accumulation of interrupted current L3 494.27 kA
01030 Max. fault current Phase L1 19.10 kA
01031 Max. fault current Phase L2 13.06 kA
01032 Max. fault current Phase L3 13.06 kA
31000 Q0 operationcounter= 0
31001 Q1 operationcounter= 0
31002 Q2 operationcounter= 0
31008 Q8 operationcounter= 0
31009 Q9 operationcounter= 0

Page 177 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39
Measurement
NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

7 Measurement

7.1 Operational values, secondary - 21-12-2016 11:00:40.998 (MEASURED\MW020000.SFP)

Operational values, secondary - 21-12-2016 11:00:40.998 (MEASURED\MW020000.SFP)


Number Measured value Value

00601 I L1 0.000 A
00602 I L2 0.000 A
00603 I L3 0.000 A
00613 3I0par (parallel line neutral) 0.000 A
00610 3I0 (zero sequence) 0.000 A
00619 I1 (positive sequence) 0.000 A
00620 I2 (negative sequence) 0.000 A
00621 U L1-E 1.65 V
00622 U L2-E 1.69 V
00623 U L3-E 1.75 V
00624 U L12 2.72 V
00625 U L23 3.11 V
00626 U L31 2.95 V
00627 Uen 0.00 V
00631 3U0 (zero sequence) 0.22 V
00684 U0 (zero sequence) 0.07 V
00634 U1 (positive sequence) 0.13 V
00635 U2 (negative sequence) 1.69 V
00644 Frequency -----
00643 Power Factor -----

7.2 Operational values, secondary - 08-04-2018 11:04:28.704 (MEASURED\MW020001.SFP)

Operational values, secondary - 08-04-2018 11:04:28.704 (MEASURED\MW020001.SFP)


Number Measured value Value

00601 I L1 0.000 A

Page 178 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Operational values, secondary - 08-04-2018 11:04:28.704 (MEASURED\MW020001.SFP)(2)


Number Measured value Value

00602 I L2 0.000 A
00603 I L3 0.000 A
00613 3I0par (parallel line neutral) 0.000 A
00610 3I0 (zero sequence) 0.000 A
00619 I1 (positive sequence) 0.000 A
00620 I2 (negative sequence) 0.000 A
00621 U L1-E 1.67 V
00622 U L2-E 1.70 V
00623 U L3-E 1.75 V
00624 U L12 2.78 V
00625 U L23 3.11 V
00626 U L31 2.96 V
00627 Uen 0.00 V
00631 3U0 (zero sequence) 0.22 V
00684 U0 (zero sequence) 0.07 V
00634 U1 (positive sequence) 0.11 V
00635 U2 (negative sequence) 1.70 V
00644 Frequency -----
00643 Power Factor -----

7.3 Operational values, secondary - 13-06-2018 17:10:14.810 (MEASURED\MW020002.SFP)

Operational values, secondary - 13-06-2018 17:10:14.810 (MEASURED\MW020002.SFP)


Number Measured value Value

00601 I L1 0.522 A
00602 I L2 0.510 A
00603 I L3 0.539 A
00613 3I0par (parallel line neutral) 0.000 A
00610 3I0 (zero sequence) 0.000 A

Page 179 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Operational values, secondary - 13-06-2018 17:10:14.810 (MEASURED\MW020002.SFP)(2)


Number Measured value Value

00619 I1 (positive sequence) 0.524 A


00620 I2 (negative sequence) 0.016 A
00621 U L1-E 66.53 V
00622 U L2-E 64.50 V
00623 U L3-E 64.89 V
00624 U L12 113.89 V
00625 U L23 111.99 V
00626 U L31 113.45 V
00627 Uen 0.01 V
00631 3U0 (zero sequence) 2.55 V
00684 U0 (zero sequence) 0.85 V
00634 U1 (positive sequence) 65.32 V
00635 U2 (negative sequence) 0.66 V
00644 Frequency 49.94 Hz
00643 Power Factor 0.97

7.4 Operational values, secondary - 11-08-2023 12:31:42.538 (MEASURED\MW020003.SFP)

Operational values, secondary - 11-08-2023 12:31:42.538 (MEASURED\MW020003.SFP)


Number Measured value Value

00601 I L1 0.394 A
00602 I L2 0.383 A
00603 I L3 0.407 A
00613 3I0par (parallel line neutral) 0.000 A
00610 3I0 (zero sequence) 0.000 A
00619 I1 (positive sequence) 0.395 A
00620 I2 (negative sequence) 0.014 A
00621 U L1-E 65.63 V
00622 U L2-E 63.76 V

Page 180 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39

NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

Operational values, secondary - 11-08-2023 12:31:42.538 (MEASURED\MW020003.SFP)(2)


Number Measured value Value

00623 U L3-E 64.40 V


00624 U L12 112.33 V
00625 U L23 111.01 V
00626 U L31 112.31 V
00627 Uen 0.01 V
00631 3U0 (zero sequence) 2.42 V
00684 U0 (zero sequence) 0.81 V
00634 U1 (positive sequence) 64.58 V
00635 U2 (negative sequence) 0.50 V
00644 Frequency 50.06 Hz
00643 Power Factor 0.98

7.5 User Defined - 21-12-2016 11:00:42.541 (MEASURED\MW060000.SFP)

nothing allocated

7.6 User Defined - 08-04-2018 11:04:31.322 (MEASURED\MW060001.SFP)

nothing allocated

7.7 User Defined - 13-06-2018 17:10:16.294 (MEASURED\MW060002.SFP)

nothing allocated

7.8 User Defined - 11-08-2023 12:31:45.078 (MEASURED\MW060003.SFP)

nothing allocated

Page 181 of 182


7SA522 V4_7 Var_Hyd#4_prn_15_47_39
Set Points (Measured Values) - 21-12-2016 11:00:43.552 (MEASURED\GW010000.SFP)
NTPC RAMAGUNDAM /
SIMATIC 400kv Lines / 7SA522 V4.7 18.10.23 15:47:39

7.9 Set Points (Measured Values) - 21-12-2016 11:00:43.552 (MEASURED\GW010000.SFP)

Set Points (Measured Values) - 21-12-2016 11:00:43.552 (MEASURED\GW010000.SFP)


Number Measured value Value

Lower setting limit for Power Factor 0.8

7.10 Set Points (Measured Values) - 08-04-2018 11:04:32.304 (MEASURED\GW010001.SFP)

Set Points (Measured Values) - 08-04-2018 11:04:32.304 (MEASURED\GW010001.SFP)


Number Measured value Value

Lower setting limit for Power Factor 0.8

7.11 Set Points (Measured Values) - 13-06-2018 17:10:17.201 (MEASURED\GW010002.SFP)

Set Points (Measured Values) - 13-06-2018 17:10:17.201 (MEASURED\GW010002.SFP)


Number Measured value Value

Lower setting limit for Power Factor 0.8

7.12 Set Points (Measured Values) - 11-08-2023 12:31:46.993 (MEASURED\GW010003.SFP)

Set Points (Measured Values) - 11-08-2023 12:31:46.993 (MEASURED\GW010003.SFP)


Number Measured value Value

Lower setting limit for Power Factor 0.8

Page 182 of 182

You might also like