Generator
G1
20
KV Base = × 150=20 KV
150
MVABase = 100 MVA
ZLama = 20%
KVLama = 20 KV
MVALama = 350 MVA
( )( )
2
MVA Baru KV Lama
Z 1G 1=Z Lama
MVA Lama KV Baru
( )( )
2
100 20
Z 1G 1=0.2
350 20
Z 1G 1=0.057 2 pu
G2
20
KV Base = × 150=20 KV
150
MVABase = 100 MVA
ZLama = 20%
KV Lama = 20 KV
MVALama = 300 MVA
( )( )
2
MVA Baru KV Lama
Z 1G 2=Z Lama
MVA Lama KV Baru
( )( )
2
100 20
Z1 G 2 =0.2
300 20
Z 1G 2=0.06 67 pu
G3
8 √3
KV Base = × 150=13.95 KV
86 √ 3
MVABase = 100 MVA
ZLama = 20%
KVLama = 14 KV
MVALama = 200 MVA
( )( )
2
MVA Baru KV Lama
Z 1G 3=Z Lama
MVA Lama KV Baru
( )( )
2
100 14
Z1 G 3 =0.2
200 13 , 95
Z 1G 3=0.1 pu
Transformator
T1
KV Base = 150 KV
MVABase = 100 MVA
ZLama = 10%
KVLama = 150 KV
MVALama = 400 MVA
( )( )
2
MVA Baru KV Lama
Z 1T 1 =Z Lama
MVA Lama KV Baru
( )( )
2
100 150
Z 1T 1 =0.1
400 150
Z 1T 1 =0.025 pu
T2
KV Base = 150 KV
MVABase = 100 MVA
ZLama = 10%
KVLama = 150 KV
MVALama = 350 MVA
( )( )
2
MVA Baru KV Lama
Z 1T 2 =Z Lama
MVA Lama KV Baru
( )( )
2
100 150
Z 1T 2 =0.1
350 150
Z 1T 2 =0.02 9 pu
T3
KV Base = 150 KV
MVABase = 100 MVA
ZLama = 10%
MVALama (3∅ ) = 300 MVA
( )( )
2
MVA Baru KV Lama
Z 1T 3 =Z Lama
MVA Lama KV Baru
( )( )
2
100 8
Z 1T 3 =0.1
300 14
Z 1T 3 =0. 011 pu
Transmission Line
KV Base = 150 KV
MVABase = 100 MVA
2
KV Base
Z Base =
MVA Base
2
150
Z Base =
100
Z Base =225 Ohm
L1
Z 1 L1= ( 0.5225x 7 0 )
Z 1 L1=0.1 556 pu
L2
Z 1 L2= ( 0.5225x 6 0 )
Z 1 L2=0.1 333 pu
L3
Z 1 L3= ( 0.5225x 65 )
Z 1 L3=0.1 444 pu
L4
Z 1 L4 = ( 0.5225x 75 )
Z 1 L4 =0.1 667 pu
L5
Z 1 L5= ( 0.5225x 50 )
Z 1 L5=0.1 11 pu
b) Urutan Negatif
Generator
G1
Karena
ZLama positif = ZLama negatif, maka
Z 2G 1=Z 1G 1=0.057 2 pu
G2
Karena
ZLama positif = ZLama negatif, maka
Z 2G 2=Z 1G 2=0.06 67 pu
G3
Karena
ZLama positif = ZLama negatif, maka
Z 2G 3 =Z 1G 3=0.1 pu
Transformator
T1
Karena
ZLama negatif = ZLama positif, maka
Z 2T 1 =Z 1T 1=0.025 pu
T2
Karena
ZLama negatif = ZLama positif, maka
Z 2T 2=Z 1T 2=0.02 9 pu
T3
Karena
ZLama negatif = ZLama positif, maka
Z 2T 3 =Z 1T 3=0.011 pu
Transmission Line
L1
Karena
ZLama positif = ZLama negatif, maka
L2
Karena
ZLama positif = ZLama negatif, maka
Z 2 L2=Z 1 L2=0.1333 pu
L3
Karena
ZLama positif = ZLama negatif, maka
Z 2 L3=Z 1 L3=0.1 444 pu
L4
Karena
ZLama positif = ZLama negatif, maka
Z 2 L4 =Z 1L 4=0.1667 pu
L5
Karena
ZLama positif = ZLama negatif, maka
Z 2 L5=Z 1 L5=0.111 pu
c) Urutan Nol
Generator
G1
KV Base = 20 KV
MVABase = 100 MVA
ZLama = 5%
KVLama = 20 KV
MVALama = 350 MVA
( )( )
2
MVA Baru KV Lama
Z 1G 1=Z Lama
MVA Lama KV Baru
( )( )
2
100 20
Z 1G 1=0.05
350 20
Z 1G 1=0.014 2 pu
G2
KV Base = 20 KV
MVABase = 100 MVA
ZLama = 5%
KVLama = 20 KV
MVALama = 300 MVA
( )( )
2
MVA Baru KV Lama
Z 1G 2=Z Lama
MVA Lama KV Baru
( )( )
2
100 20
Z1 G 2 =0.05
300 20
Z 1G 2=0.016 pu
G3
KVBase = 13.95 KV
MVABase = 100 MVA
ZLama = 5%
KVLama = 14 KV
MVALama = 200 MVA
( )( )
2
MVA Baru KV Lama
Z 1G 3=Z Lama
MVA Lama KV Baru
( )( )
2
100 14
Z1 G 3 =0.05
200 13.95
Z 1G 3=0.025 pu
Transformator
T1
Karena
ZLama nol = ZLama negatif = ZLama positif, maka
Z 0T 1=Z 2T 1 =Z 1T 1=0.025 pu
T2
Karena
ZLama nol = ZLama negatif = ZLama positif, maka
Z 0T 2=Z 2T 2 =Z 1T 2=0.02 9 pu
T3
Karena
ZLama nol = ZLama negatif = ZLama positif, maka
Z 0T 3=Z 2T 3=Z 1T 3=0.011 pu
Transmission Line
KV Base = 150 KV
MVABase = 100 MVA
2
KV Base
Z Base =
MVA Base
2
150
Z Base =
100
Z Base =225 Ohm
L1
Z 1 L1= ( 1.25225x 7 0 )
Z 1 L1=0. 38 pu
L2
Z 1 L2= ( 1.25225x 6 0 )
Z 1 L2=0.3 pu
L3
Z 1 L3= ( 1.25225x 65 )
Z 1 L3=0.3 61 pu
L4
Z 1 L4 = ( 1.25225x 75 )
Z 1 L4 =0. 416 pu
L5
Z 1 L5= ( 1.25225x 50 )
Z 1 L5=0.27 pu