PREPARE BY DR- Majid Albana

majidalbana@hotmail.com
+9647702724811

Notes

THE BUILDING SYSTEM WILL BE


CONSIDER AS SHEAR WALL
BUILDING WITH COLUMNS AND THE
SLAB WILL BE AS FLAT SLAB .THE
SOFTWARE USED IN DESIGN (CSI
ETABS2022, AND CSI SAFE2022+
PROKON) IS THE GENERAL
PROGRAM USED IN THIS DESIGN

job title

Commercial building
Structural
Drawings

DRWG. TITLE:

DESIGNED BY DR-Majid Albana


CHECKED BY

SCALE As Shown

DATE 3 /2023

SHEET NO. Str. 1


ABBREVIATIONS :-
GENERAL :- REINFORCED CONCRETE :- ADD ADDITIONAL
ARCH ARCHITECTURAL
1. ALL DIMENSIONS TO TAKE PRECEDENCE OVER SCALE SHOWN ON PLANS, SECTIONS AND 1. COMPRESIVE STRENGTH OF CONCRETE SHOULD BE DETERMIND BY THE TABLE BELOW :- Walk Way B BEAM
B.R.C (no. 63)
DETAILS, (DO NOT SCALE FROM DRAWINGS). Out Door Yard BOTT BOTTOM
1 LAYER OF B.R.C(gage 63) 2Ø10 C1 COLUMN TYP C1
x
MINIMUM 28 DAYS Joint Every 25 m² B.R.C (no. 63)
2. ALL DIMENSIONS ARE IN MILLIMETRES AND ALL LEVELS IN METRES (UNO). LOCATIONS x CANT CANTILEVER
CUBE COMPRESSIVE x
CJ CONSTRUCTION JOIN
AGGREGATE X X X X X
3. THE STRUCTURAL DRAWINGS SHOULD BE USED IN CONJUNCTION WITH THE ARCHITECTURAL, STRENGTH (Fcu) X X X X X X X X X X X X Nylon Sheet CL CENTRE
MEMBER MAX. SIZE Ø10/200 x
MECHANICAL,CIVIL,PLUMBING AND ELECTRICAL DRAWINGS. C COULMN
TYPE ( MPa ) 2Ø12
150mmSub-base 90% CONC CONCRETE
4. ALL OPENINGS SIZE AND LOCATION SHOULD BE VERIFIED AND CHECKED WITH SERVICES DET DETAIL
SCREED 20 10 mm Nylon Sheet 150mmSub-base 90%
DRAWINGS,WHERE OPENINGS SIZES ARE NOT SHOWN ON THE STRUCTURAL DRAWINGS, DIM DIMENSION
SITE ENGINEER SHALL INTRODUCE SUCH OPENINGS WITH PROPER FRAMING INCLUDING BLINDING OR LEAN CONCRETE 20 20 mm DWG DRAWING
ANY REVISION TO THE SIZES SHOWN ON THE DRAWINGS. D DEPTH
SLABS 35 20 mm Typical Detail Of Out Door Yard Typical Sec. For Stair On Earth E.A EACH
5. DESIGN STANDARED & LOADS :-
PILES - 20-38 mm E.F EACH FACE
DESIGN & CONSTRUCTION OF REINFORCED CONCRETE STRUCTURES MEMBERS SHALL E.J EXPANSION JOINT
FOUNDATIONS 40 20 mm ELEV ELEVATION
IN ACCORDANCE WITH ACI-318-95 (ULTIMATE STRENGTH DESIGN METHOD).
COLUMNS AND SHEAR WALLS 50 20 mm E.W EACH WAY
ALL RETANING WALL STRUCTURE SHOULD BE AS BRITISH 8 97- 110 or ACI - 93 - 318. EXP EXPANSION
SUSPENDED SLAB, BEAMS F FOOTING
40 20 mm
MASONARY BRICK OR CONCRETE BLOCK ACCORDING TO B.S - 5628. AND WALLS F1 FOOTING TYPE-1
WATER RETAINING STRUCTURES - 20 mm FDN FOUNDATION
6. LOADING :- F.F.L FINISH FLOOR LEVEL
PLAIN CONCRETE 25 20 mm GEN GENERAL
MINIMUM DESIGN LOAD (LIVE LOAD) ACCORDING TO IBC-09. B.R.C No.63 x x GL GRID LINE
x
SEISMIC LOAD ACCORDING TO IRAQI SEISMIC CODE 1997. x LL LIVE LOAD
100mm plain conc. x MAX MAXIMIM
WIND LOAD ACCORDING TO ASCE-05. 2. SULPHATE RESISTANT CEMENT TYPE 5 SHOULD BE USED IN ALL CONCERET WORK IN x
B.R.C No.63

15
CONTACT WITH EARTH OR BELOW D.P.C LEVEL. Nylon Sheet x MECH MECHANICAL
Nylon Sheet
7. FOR TYP. SECTIONS & DETAILS SEE ST-G2. x MIN MINIMUM

0
x
3. REINFORCMENT STEEL CONFORM TO ASTM A615 & A616 OR A617 BARS SHOULD BE GRADE x x 2Ø10 x
mm MILLIMETRES
x
400 FY=410N/mm (60000psi). x SEC SECTION
FOUNDATION AND EARTH WORK :- 150mmSub-base 90%
150mmSub-base 90%
4. PLACING OF REINFORCEMENT SHOULD BE ACCORDING TO ACI-315 DETAILING MANUAL. Ø10/200
1. FOUNDATION DESIGN BASED ACCORDING TO THE SOIL REPORT 2Ø10
5. MINIMUM BARS COVER :-
CONSTRUCTION OF PARTITION
2. BEARING CAPACITY ACCORDING TO THE SOIL by assume IS (9K/ m²) ON GROUND SLAB
BELOW THE EXISTING N.G.L. MEMBER (mm) Typical Sec. Of Ramp
provid construction joint for max.(5mx5m)
3. A WELL COMPACTED SUB-BASE LAYERS OF A TOTAL THICK AS INDICATED IN THE DWG. SLABS 25
SHOULD BE USED UNDER FOOTING WITH FOLLOWING SPECIFICATIONS :- BEAMS & GIRDERS 40 2∅16
THE DIMENSION OF THE SUB-BASE LAYERS SHOULD BE LARGER THAN THE DIMENSIONS OF ∅10 @ 200
COLUMNS 40 ∅10 @ 200
THE FOUNDATION FROM ALL SIDES BY 0.25m.
INTERIOR WALLS 25
THE VALUE OF CALIFORNIA BEARING RATIO (C.B.R) SHALL NOT BE LESS THAN (35% ASTM D) 2∅16
1883 AT 95% OF THE MAXIMUM DRY DENSITY ESTABLISHED ACCORDING TO (ASTM D)1557. EXTERIOR FACE OF WALL 40
FORMED FOUNDATION 50 Arround all windos for loovers
LIQUID LIMIT ≤ 25%.
NON-FORMED FOUNDATION 75
PLASTICITY INDEX ≤ 6%. 2-Ø16(typ.)
ORGANIC MATERIAL ≤ 2%. T&B
6. MINIMUM BARS SPACING :-
SO3 ≤ 5%. 2-Ø10
CLEAR SPACING BETWEEN PARALLEL BARS SHALL NOT BE LESS THAN BAR DIAMETER Ø10@200
OR 4/3 OF MAXIMUM AGGREGATE SIZE BUT NOT LESS THAN 25mm.
TOTAL SOLUBLE SALTS ≤ 5%.
CLEAR SPACING BETWEEN LAYERS OF BARS TO BE NOT LESS THAN 25mm AND THE
GYPSUM CONTENT ≤ 10.75%.
UPPER BARS SHOULD BE OVER THE LOWER BARS .
RELATIVE COMPACTION 95% ( MODIFIED PROCTOR).
IN COLUMNS CLEAR DISTANCE BETWEEN LONGITUDINAL BARS SHOULD BE NOT LESS TYPICAL REINF. AROUND TYPICAL UP STAND DETAIL
4. SULPHATE RESISTANT CEMENT TYPE 5 SHOULD BE USED IN ALL CONCERET WORK IN THAN 1.5 BAR DIAMETER NOR LESS THAN 40mm.
CONTACT WITH EARTH OR BELOW D.P.C. LEVEL.
OPENNINGS UP TO 600 ROOF OPENNINGS
7. MINIMUM LAP LENGTH (UNLESS NOTED ON DRAWINGS) SHOULD BE AS TABLE BELWO :-
5. BACKFILL AROUND FOOTINGS AND UTILITY TRENCH WITHIN THE BUILDING AREA SHOULD
BE DONE WITH APPROVED SELECTED CLASSIFIED MATERIAL FREE OF CLAY AND SHOULD
BE MECHANICALLY COMPACTED IN LAYERS, NOT EXCEEDING 250mm LOOSE THICKNESS BAR DIA.(mm) 10 12 16 18 20 22 25
TO 90% OF MAXIMUM PROCTOR DENSITY. LAP LENGTH (mm) IN 400 500 600 650 700 800 900
COLUMNS
LAP LENGTH (mm) IN PROVID 2-Ø6 PLATE (300 * 250 * 3 )
400 600 700 800 900 1000 1250
ELSE WHERE AT EVERY 5TH COURSE OF BRICK AT EVERY 5TH COURSE OF BRICK
CONSTRUCTION JOINT AND WATERPROOFING :-
1. CONSTRUCTION JOINT :- LAP LOCATION IN SLABS AND BEAMS :-

CONSTRUCTION JOINT IN FLOORS SHOULD BE LOCATED WITHIN THE MIDDLE THIRD OF * AT SUPPORT FOR BOTTOM BARS.
SPANS OF SLABS ,BEAMS & GIRDERS,JOINT IN GIRDER SHOULD BE OFFSET A MINIMUM
DISTANCE OF TWO TIMES THE WIDTH OF INTERSECTING BEAMS. * AT MID SPAN FOR TOP BARS.

AT CONSTRUCTION JOINTS SURFACES SHOULD BE ROUGHENED BY BROOMING OUT LAP LOCATION IN FOUNDATION :-
MORTAR, EXPOSING 12mm OF COARSE AGGREGATE TWO HOURS AFTER PLACING
* AT SUPPORT FOR TOP BARS.
CONCRETE.
* AT MID SPAN FOR BOTTOM BARS.
CONSTRUCTION JOINTS FOR STRUCTURAL SLAB / FOUNDATION / WALLS ETC. AND
VOLUME OF CASTING IN A POUR SHOULD BE APPROVED BY THE ENGINEER. CONECTION BETWEEN BRICK WALL CONECTION BETWEEN BRICK WALL
8. VERTICAL REINFORCEMENT IN COLUMN :-
AND R.C. COLUMN AND R.C. COLUMN
CONSTRUCTION JOINTS SHOULD BE DOWELED, KEYED AND THOROUGHLY CLEANED, ALL
CONSTRUCTION JOINTS SHOULD BE CONSTRUCTED IN ACCORDANCE WITH THE TYPICAL
WHERE COLUMN FACE ARE OFFSET 75mm OR MORE SPLICE OF VERTICAL BARS proposel 1 proposel 2
TO THE OFFSET FACE SHOULD BE MADE BY SEPARATE DOWELS OVER LAP AS SPECIFIED
CONSTRUCTION JOINT DETAILS SHOWN ON THE STRUCTURAL DRAWINGS,CONTRACTOR ABOVE.
HAVE TO PREPARE ANY MISSING DETAILS NOT COVERED IN THE STRUCTURAL DRAWINGS
AND SUBMIT FOR ENGINEER'S APPROVAL. WHERE A LONGITUDINAL BARS ARE OFFSET AT SPLICE THE SLOPE OF INCLINED ADJACENT
PORTION SHALL NOT EXCEED 1:6 (HORIZANTAL:VERTICAL). no. date initials revision
2. WATERPROOFING :-
CHANGING OF REINFORCEMENT BETWEEN FLOORS WHERE SUCH SITUATION OCCURS
WATER STOPS SHOULD BE USED AT ALL CONSTRUCTION,CONTRACTION & EXPANSION THE REINFORCEMENT OFF SHOULD BE CUT OFF AT DISTANCE 75mm BELOW FLOOR
JOINTS,WHERE WATERPROOFING SYSTEM IS APPLIED ALL INTERSECTION PIECES OF LEVEL SPACED 100mm AND PLACED BEFOR THE POINT OF BEND. A
WATER STOPS SHOULD BE FACTORY MOLDED.
a job title
WHERE LONGITUDINAL BARS OFFSET,PROVIDE 4TIES. A
ALL CONCRETE WORKS IN CONTACT WITH SOIL FOR NORMAL STRUCTURE SHOULD BE Ø10@200
COATED WITH PROTECTIVE LAYER. 9. HOT & COLD WETHERING SHOULD BE ACCORDING TO ACI-305R-99. B

h
(A)
10. ALL REINFORCING BAR BENDS TO BE MADE COLD. 250 250 drawing title
a B
11. IN ONE-WAY SLAB, SHRINKAGE & TEMPERATURE REINF. STEEL EXTENDING IN THE LONG
. all dim. from ARCH D.W.G. DIRECTION SHALL BE PLACED IN THE PLACE OF, AND TIED TO THE MAIN REINF.
EXTENDING IN THE SHORT DIRECTION.
L<2000, h=200 , A=B=2-Ø12
SEC. ( a - a )
designed
GENERAL NOTES
project manager
L<5000, h=400 , A=2-Ø12 , B=2-Ø16 ENG : DR-Majid Albana
checked scale date
12. MIXING & PLACING CONCRETE SHOULD BE DONE ACCORDING TO ACI - 318M - 95 (CHAPTER 5)
CONDUIT OR PIPE SIZE SHALL NOT EXCEED 30% OF SLAB THICKNESS UNLESS SPECIFICALLY LINTEL REINFORCEMENT job no. sheet no.

2
drawn
DETAILED,OTHERWISE CONCENTRATIONS OF CONDUITS OR PIPES SHOULD BE AVOIDED EXCEPT
WHERE DETAILED OPENINGS ARE PROVIDED, ALL SUBJECTED TO ENGINEER'S APPROVAL. approved
EXCAVATION, BACK FILLING & FOUNDATION THE DESIGN LOADS

1) SUPER IMPOSED DEAD LOAD (SDL) :

2) LIVE LOADS:

GENERAL NOTES :-

3) WIND LOADS:

no. date initials revision

6) CONSTRUCTION JOINTS AND CONTROL JOINTS:

job title

Frameworks removal time :


(A)
Type of framework Min. period before striking formworks
Vertical framework of the column 24 hrs
drawing title
Vertical framework of the shear walls 2-3 days

framework of the slab and beam


a. span up to 6 m 14 days
THE DESIGN LOADS
a. span from 6-8 m 20 days
designed project manager
ENG :DR- Majid Albana
checked scale date
1-100 3 /2023
drawn job no. sheet no.

approved
3 ST/D/03
A B C D E F G H I J
1

Ø20@200 B. MESH
12X6-Ø12@100 B
2

12X6-Ø12@100 B 1.35
12X6-Ø12@100 B
3

Ø20@200 B. MESH
Ø12@100

8Ø20
4

12X6-Ø12@100 B

CONCRETE COVERS

-SLABS = 25 mm

-BEAMS = 40 mm

-COLUMNS = 40 mm

-WALLS = 25 mm

-SLAB ON GRADE = 50 mm
no. date initials revision
-RAFT FOUNDATION = 75 mm

BOT. REINFORCEMENT job title

(A)
-THE BUILDING IS DESIGNED FOR GROUND drawing title

Foundation Plan
PLAN OF FOUNDATION
FLOOR + 2nd+3rd+4th FLOORS + PENT-HOUSE
REINFORCEMENT&SEC.
designed project manager
ENG : Majid Albana
checked scale date

THICK. = 800 mm . all dim. from ARCH D.W.G. drawn


ENG : Majid Albana
job no.
1-100 3/2023

4
sheet no.
ENG : Majid Albana
approved ST/D/04
A B C D E F G H I J
1

Ø20@175 T. MESH
2

1.35
12X6-Ø12@100 B
3

Ø20@175 T. MESH
Ø12@100

8Ø20
4

CONCRETE COVERS

-SLABS = 25 mm

-BEAMS = 40 mm

-COLUMNS = 40 mm

-WALLS = 25 mm

-SLAB ON GRADE = 50 mm
TOP REINFORCEMENT -RAFT FOUNDATION = 75 mm
no. date initials revision

job title

(A)
-THE BUILDING IS DESIGNED FOR GROUND drawing title

Foundation Plan
PLAN OF FOUNDATION
FLOOR + 2nd+3rd+4th FLOORS + PENT-HOUSE
REINFORCEMENT&SEC.
designed project manager
ENG : Majid Albana
checked scale date

THICK. = 800 mm . all dim. from ARCH D.W.G. drawn


ENG : Majid Albana
job no.
1-100 3/2023

5
sheet no.
ENG : Majid Albana
approved ST/D/04
B' A'

250

0 12 No. Ø12
0 /15
Ø1 0
2 /15
Ø1

00
2/2
Ø1

SECTION A'-A' (between Foundation &


landing )

Slab Reinf.

250

250

0
0 /15
Ø1
50 Ø12@150
10/1
50 Slab Reinf. Ø
2/1
250 Ø1
Ø12/200 0 Slab Reinf.
2 /20
Ø1 0
2/20
Ø1
Ø12/200

200 Slab Reinf.


2T16

SECTION A'-A' (between slab & landing ) 200mm

no. date initials revision

job title

(A)
drawing title

Stairs detail
. all dim. from ARCH D.W.G. designed
ENG : DR-Majid Albana
checked
project manager

scale date
1-100 3 /2023
drawn job no. sheet no.

approved
6 ST/D/07
A B C D E F G H I J
1

C1 C1
C2 C2 C2 C2 SCHEDULE OF COLUMNS AND WALLS
COLUMNS SIZE
OR WALLS LENGTH WIDTH REMARK
ID (mm) (mm)

B
2

C2 C2 C2 1.35 C2 C2 C1 700 300


C2 700 300
Notes
3

CONCRETE COVERS

C2 C2 C2 C2 -SLABS = 25 mm

-BEAMS = 40 mm

-COLUMNS = 40 mm

-WALLS = 25 mm

-SLAB ON GRADE = 50 mm

-RAFT FOUNDATION = 75 mm
4

C1 C2 C2 C2 C1

-THE GEOTECHNICAL INVESTIGATION REPORT


DIDN'T DONE BY THE CLIENT,AND ALL
FOUNDATIONS SHOULD BE REDESIGNED AFTER
no. date initials revision
FINISHING THE GEOTECHNICAL INVESTIGATION
AND THE BEARING CAPACITY OF THE SOIL
ASSUMED TO 90 kN/m2
-THE BUILDING IS DESIGNED FOR GROUND 1
ST+2nd+3rd& 4th FLOOR + PENT-HOUSE job title

(A)
drawing title

COLUMNS & WALL KEY PLAN


COLUMNS & WALL KEY PLAN designed
ENG : DR-Majid Albana
checked
project manager

scale date

. all dim. from ARCH D.W.G. drawn


1-100
job no.
3/2023

7
sheet no.

approved ST/D/08
12 - Ø20 10 - Ø20
Ø10@200 Ø10@200
Main Bar Roof Floor 2Ties/Set 2Ties/Set

Column Reinf.
Ties

Rest See
C 50 700 700

Section

300 300

2nd Floor

Main Bar 1ST Floor 12 - Ø25 10 - Ø25


Ties Ø10@200 Ø10@200
2Ties/Set 2Ties/Set

Rest See Column Reinf.


C50

Section
700 700
Ground Level
foundation
level
300 300

12 - Ø25 10 - Ø25
Dowels
C1 C2

Rest See Column Reinf.


no. date initials revision

job title

(A)
drawing title
SCHEDULE OF COLUMN
Typ. Sec. For Column
designed project manager
ENG : DR-Majid Albana
TYPICAL INTERNAL COLUMN TO BEAM DETAIL TYPICAL EDGE COLUMN TO BEAM DETAIL checked scale date
1-100 3/2023
drawn job no. sheet no.

. all dim. from ARCH D.W.G. approved 8


W1
B

B
Lift

3Ø16

3Ø16

Ø10@200

VERTICAL REINFORCEMENT

HORIZONTAL REINFORCEMENT 3Ø16


door opening

3Ø16 arround
W1 W1 door opening

3Ø16
DETAIL A

700 DETAIL A
Ø20mm@175cm c/c
Top (Y-Direction)

700

W1 Reinf. no. date initials revision

Section job title

B-B (A)
drawing title

Section A'-A' lift


detail
designed project manager
ENG : Majid Albana
checked scale date
1-100 3 /2023
drawn job no. sheet no.

approved
9 ST/D/06
Notes

CONCRETE COVERS

-SLABS = 25 mm

-BEAMS = 40 mm

-COLUMNS = 40 mm

-WALLS

-SLAB ON GRADE
= 25 mm

= 50 mm
A B C D E F G H I J
-RAFT FOUNDATION = 75 mm

B2
1

-THE GEOTECHNICAL INVESTIGATION REPORT


DIDN'T DONE BY THE CLIENT,AND ALL
FOUNDATIONS SHOULD BE REDESIGNED AFTER
FINISHING THE GEOTECHNICAL INVESTIGATION
AND THE BEARING CAPACITY OF THE SOIL
ASSUMED TO 90 kN/m2
B2
-THE BUILDING IS DESIGNED FOR GROUND 1
ST+2nd+3rd& 4th FLOOR + PENT-HOUSE B2 B2
2

1.35

B2 H.B B2
3

H.B
4

B2
no. date initials revision

job title

(A)
drawing title

BEAM KEY PLAN


designed project manager
ENG : DR-Majid Albana
checked scale date

BEAM KEY PLAN . all dim. from ARCH D.W.G. drawn


1-100
job no.
3/2023
sheet no.

approved
10 ST/D/08
4 3 2 1

24.10

1.38 4.37 4.22 4.21

3
3Φ25 2Φ25
2-25

10@250 mm

2-20 2-20 2-20 2-20


2Φ12 2Φ12

0.7
CANTLIVER

Φ10@250 Φ10@250

B2:Elevation
2Φ20 2Φ20
0.25

0.70

Ø12@150 B2:Sect:1 B2:Sect:2


CANTLIVER

8Ø12

H.B

2Φ20 2Φ22 2Φ25

2Φ12 2Φ12 2Φ12

Φ10@250 Φ10@250
no. date initials revision

2Φ25 2Φ25 2Φ20


job title

SCHEDULE OF BEAMS
B1 B1 B2:Sect:3
TYPICAL BEAM LONGITUDINAL SECTION

(A)
drawing title

designed project manager


ENG : DR-Majid Albana
checked scale date
1-100 3/2023
drawn job no. sheet no.

approved
11
A B C D E F G H I J

35 mm
camber

Ø12@150 B .
2

12X6-Ø12@100 B 12X6-Ø12@100 B
1.35

35 mm
camber
35 mm
3

camber

Ø12@100

8Ø12

Ø12@150 B

35 mm
4

camber

35 mm 35 mm
camber camber 35 mm
camber
35 mm
Camber Slab Camber 35 mm
BOT. REINFORCEMENT

SLAB REINFORCEMENT (GROUN & 1ST FLOOR )


SLAB THICKNESS = 220 mm

no. date initials revision

colum Reinf.
MINIMUM LAP LENGTH (UNLESS NOTED ON DRAWINGS) SHOULD BE AS TABLE BELWO :-

TOP REINFORCEMENT BAR DIA.(mm) 10 12 16 18 20 22 25 job title


Slab Reinf.
LAP LENGTH (mm) IN COLUMNS 400 500 600 650 700 800 900

LAP LENGTH (mm) IN SLAB & BEAMS 400 600 700 800 900 1000 1250 (A)
drawing title
BOTTOM REINFORCEMENT
PLAN OF SLAB
REINFORCEMENT&SEC.
Typica SLAB reinforcement . all dim. from ARCH D.W.G. designed
ENG : DR-Majid Albana
checked
project manager

scale date
1-100 3 /2023
drawn job no. sheet no.

approved
12 ST/D/11
A B C D E F G H I J

Ø16@150 TOP L=4m .

ADDITIONAL
Ø16@150 mm
ADDITIONAL
Ø16@150 mm
BOTTOM L=3m
ADDITIONAL
Ø16@150 mm
ADDITIONAL
BOTTOM L=3m BOTTOM L=3m

Ø16@150 mm

Ø12@150T .
TOP L=3m
2

1.35

ADDITIONAL ADDITIONAL
Ø16@150 mm Ø16@150 mm
BOTTOM L=3m BOTTOM L=3m

35 mm
3

camber

Ø12@150 T
Ø16@150 TOP L=4m .

35 mm
4

camber

35 mm
Camber Slab Camber 35 mm
TOP REINFORCEMENT
SLAB REINFORCEMENT (GROUN & 1ST FLOOR )
SLAB THICKNESS = 220 mm

no. date initials revision

colum Reinf.
MINIMUM LAP LENGTH (UNLESS NOTED ON DRAWINGS) SHOULD BE AS TABLE BELWO :-

TOP REINFORCEMENT BAR DIA.(mm) 10 12 16 18 20 22 25 job title


Slab Reinf.
LAP LENGTH (mm) IN COLUMNS 400 500 600 650 700 800 900

LAP LENGTH (mm) IN SLAB & BEAMS 400 600 700 800 900 1000 1250 (A)
drawing title
BOTTOM REINFORCEMENT
PLAN OF SLAB
REINFORCEMENT&SEC.
Typica SLAB reinforcement . all dim. from ARCH D.W.G. designed
ENG : DR-Majid Albana
checked
project manager

scale date
1-100 3 /2023
drawn job no. sheet no.

approved
13 ST/D/11
2-16
A B C D E F G H I J

0.4

B1 0.6
1

10@250 mm

Ø12@150 B&T.
B1
B1
35 mm
camber

3-16
2

Ø12@150 B&T 0.25

B1

B1
3
4

35 mm
Camber Slab Camber 35 mm

SLAB REINFORCEMENT (PEN HOUSE )


SLAB THICKNESS = 200 mm

no. date initials revision

colum Reinf.
MINIMUM LAP LENGTH (UNLESS NOTED ON DRAWINGS) SHOULD BE AS TABLE BELWO :-

TOP REINFORCEMENT BAR DIA.(mm) 10 12 16 18 20 22 25 job title


Slab Reinf.
LAP LENGTH (mm) IN COLUMNS 400 500 600 650 700 800 900

LAP LENGTH (mm) IN SLAB & BEAMS 400 600 700 800 900 1000 1250 (A)
drawing title
BOTTOM REINFORCEMENT
PLAN OF SLAB
REINFORCEMENT&SEC.
Typica SLAB reinforcement . all dim. from ARCH D.W.G. designed
ENG : DR-Majid Albana
checked
project manager

scale date
1-100 3 /2023
drawn job no. sheet no.

approved
14 ST/D/11
Reinf. conc. Raft Ø12@15cm C/C
foundation .
5 cm plain concrete Ø12@20cm C/C
2layers Bitumen 1cm thick. min
with bitumen felts between them
(1:2:4) 10cm Blinding 1.26

w/c = 0.45 , coarse agg. 5-19 mm


1.13

25cm Sub base 95% comp. 1.89

25cm Bolder
Sub grade ( stiff & stable ) 2.52

1.50 250 250

Ø12@200 E.F

1.90 Ø12@200 E.F


Raft foundation

1000
Well compacted subbase 95 % blinding

Typical section (B-B) for concrete wall of elevator

no. date initials revision

SECTION IN RAFT FOUNDATION &


STAIR NECK
Foundation Plan
job title

(A)
drawing title

COLUMNS & WALL KEY PLAN


THICK. = 900 mm designed
ENG : DR-Majid Albana
project manager

checked scale date

. all dim. from ARCH D.W.G. drawn


1-100
job no.
3/2023

7
sheet no.

approved ST/D/08