Doc No

50 MVA, 33/132 KV SUBSTATION AT, SANGARH, RAJASTHAN


IBVSI/RJ/SANGRAH/EE/RE
LAY/GTP/12

TITLE : CONTROL RELAY PANEL SCHEME GTP

ib vogt SOLAR INDIA Pvt. Ltd.


CLIENT : GURUGRAM, HARYANA INDIA – 122018

SHAKTI ENGINEERS AND CONSULTANTS,


CLIENT
BANGALORE-560097
CONSULTANT :

1 09.12.23 AC HP AC 5
0 16.11.2023 AC HP AC 5 FOR APPROVAL

NO. OF
REV. DATE PREPARED BY. CHECKED BY. APPROVED BY. REMARKS
SHEETS
Document: CONTROL RELAY PANEL SCHEME
Document Number: IBVSI/RJ/SANGRAH/EE/RELAY/GTP/12

Sr. No. Description Required Data Manufacturer Data

Transformer CRP Line CRP

1 Quantity

Transformer CRP 1No.


Line CRP 1No.

2 Panel Designations C&R panel

3 Technical Specification IBVSI/RJ/SANGRAH/EE/RELAY/TS/1


2
4 Type of construction Control and Relay panel
a. Simple / Duplex / Desk-cum panel Simplex Type, Floor mounted
b. Construction type Sheet steel enclosed dust and vermin
proof floor mounting, free standing,
formed on a framework of standard
sections, The Front access door shall
be with glass door.
5 Type of sheet steel (hot/cold rolled) CRCA Sheet (Cold Rolled)

6 Thickness of sheet steel

Front 3.0mm
Back 3.0mm

Sides 2.5mm

Baseframe 100mm Height

Page 1 Rev. 01
Sr. No. Description Required Data Manufacturer Data

Transformer CRP Line CRP

Ant vibration pad 15mm (minimum)


7 Paint treatment and colour shades (external External – RAL 70XX (shall be
& internal) Mounting base plate confirmed during detail engineering).
Internal - Black

8 Weight of each panel section Manufacturer to specify


9 Dimensions of each panel section Manufacturer to specify
(Width x depth x height) (Height of the panel should be
2200mm)

10 Mimic bus, material & colour 132kV – Signal Red (Shade 537 as per
IS 5)
-Mimic diagram with semaphore
indication for isolator and earth switch
and circuit breaker.

11 Earthing Material 25x6 Tinned Copper


12 Semaphore Indicator - In Mimic - -
- NA in case of BCU type
13 Instruments, components etc. transported Mounted on Panel
mounted on panels or separately packed
14 Mounting of instrument and control gears and Front mounted only
relays
15 Termination Gland Removable undrilled gland plate of
3mm thickness
16 Cable Entry Bottom

Page 2 Rev. 01
Sr. No. Description Required Data Manufacturer Data

Transformer CRP Line CRP

17 Panel illumination LED Lamps working on 240V AC,


operated by door switches shall be
provided for internal panel illumination.
A 240V, 1-Phase, 16A, 5 Pin Socket
shall be provided in the panel corridor
or interior of each cubicle with on-off
switch for connection of hand lamps.
This socket shall be metal clad type
with a spring loaded flap.
18 Control and Protection System

19 The schedule of particulars of protective


relaying, metering and control equipment
shall include the following
20 Mimic Diagram/BCU 1 No.

21 L/R Selector Switch 1 No.


22 Wiring 1.5mm² (PT), 2.5mm² (CT and
Earthing)
FRLS Type
23 Label Aluminium Anodized

24 Ingression Protection IP 42
25 Terminals 6mm² Elmex/ Connectwell make with
20% spare.

26 Special Requirement As per local UTILITY requirement.


27 Line CRP

BCPU 50, 50N, 51, 51N, BCU, 67, 67N, 27,

Page 3 Rev. 01
Sr. No. Description Required Data Manufacturer Data

Transformer CRP Line CRP


50LBB, 59
(Make and Model- Manufacturer to
specify)
Relay 87L
(Make and Model- Manufacturer to
specify)

Meter ABT Meter, ASS, A, VSS, V


(Make and Model- Manufacturer to
specify)
Relay Communication Protocol IEC 61850

Meter Communication Protocol RS 485 Modbus

28 Transformer CRP
Relay-1 64RLV, 51GLV, 51HHV, 87T
(Make and Model- Manufacturer to
specify)
Relay-2 (BCU) 51, 51, 50N, 51N, 67, 67N, 50LBB
(Make and Model- Manufacturer to
specify)

Relay-3 64RHV
(Make and Model- Manufacturer to
specify)
Meter TVM, ASS, A, VSS, V
(Make and Model- Manufacturer to
specify)

Page 4 Rev. 01
Sr. No. Description Required Data Manufacturer Data

Transformer CRP Line CRP

Relay Communication Protocol IEC 61850


Meter Communication Protocol RS 485 Modbus

29 Type Test Report Manufacturer to submit and confirm.

30 Proven Track Record (PTR) Manufacturer to submit and confirm.


31 SLD Compliance Manufacturer to confirm.
(Document IBVSI/RJ/SANGRAH/EE/001)
32 Relay Mounting Flush Mounted

33 Annunciator Minimum 24 window with RS 485


Modbus communication protocol
34 PQM Meter for Line CRP Required

35 BCU Required for Bay control of Isolator and Required


Circuit breaker with all indication status

General

36 Each Relay Port Two Numbers for IEC 61850


communication protocol

Page 5 Rev. 01