NOTES

KEY PLAN

GE-006
A B C D E F G H I J K L

2
45750
2200 4050 2300 3650 5950 2500 2800 5850 5400 5400 5650

NetCol8000-
A060U
CRAC
BC-UPS-ME-B1 BC-UPS-ESP-B1 BC-UPS-ME-B2

SMDB-ESP-A1

SMDB-ESP-B1
SMDB-ME-B1

SMDB-ME-B2
UPS-ESP-A1

UPS-ESP-B1
UPS-ME-B1

UPS-ME-B2
150kVA

300kVA

150kVA

300kVA
BC-UPS-ME-A2
4550

DISTRIBUTION AREA UPS ROOM LI BATTERY ROOM


FUTURE EQUIPMENT ROOM BC-UPS-ME-A1
SC-05 CORRIDOR SC-01

A/C DB-4A A/C DB-4B


SC-04

SMDB-ME-A1

SMDB-ME-A2
UPS-ME-A1

UPS-ME-A2
300kVA

300kVA
BC-UPS-ESP-A1

NetCol8000-
A060U
CRAC
CRAC CRAC
NetCol8000- NetCol8000-

2 A045U A045U

SHAFT
FR-09
2050

1 OCT 2023 ISSUED FOR APPROVAL


3 BATTERY ROOM-01 BATTERY ROOM-02
13300

0 SEP 2023 ISSUED FOR APPROVAL


TR.2B/AC , 380/220V
TR.1B/IT , 380/220V

TR.3B/IT , 380/220V
950 500 950

4 DCP-03, FEED UPS-3 DCP-04, FEED UPS-4 DCP-07, FEED UPS-7 DCP-01, FEED UPS-1 DCP-02, FEED UPS-2 DCP-05, FEED UPS-5 DCP-06, FEED UPS-6
PP-ESS 4B PP-ESS 2B PP-ESS 1B PP-ESS 3B
REV DATE DESCRIPTIONS

BATTERY STRING 1 - 40 CELLS 12 V BATTERIES (TWO TIER)

BATTERY STRING 1 - 40 CELLS 12 V BATTERIES (TWO TIER)

BATTERY STRING 1 - 40 CELLS 12 V BATTERIES (TWO TIER)

BATTERY STRING 1 - 40 CELLS 12 V BATTERIES (TWO TIER)


BATTERY STRING 1 - 40 CELLS 12 V BATTERIES (ONE TIER)

BATTERY STRING 2 - 40 CELLS 12 V BATTERIES (ONE TIER)

BATTERY STRING 1 - 40 CELLS 12 V BATTERIES (ONE TIER)

BATTERY STRING 2 - 40 CELLS 12 V BATTERIES (ONE TIER)

BATTERY STRING 1 - 40 CELLS 12 V BATTERIES (ONE TIER)

BATTERY STRING 2 - 40 CELLS 12 V BATTERIES (ONE TIER)

BATTERY STRING 1 - 40 CELLS 12 V BATTERIES (ONE TIER)

BATTERY STRING 2 - 40 CELLS 12 V BATTERIES (ONE TIER)


5 81 55

1 80 56 1
GE-005 79 57
GE-005 REVISIONS

BATTERY STRING 2 - 40 CELLS 12 V BATTERIES

BATTERY STRING 2 - 40 CELLS 12 V BATTERIES

BATTERY STRING 2 - 40 CELLS 12 V BATTERIES

BATTERY STRING 2 - 40 CELLS 12 V BATTERIES


6 IT-AC 1B IT-AC 3B IT-AC 2B IT-AC 4B 78
77
58
59
ATS-10 ATS-18 ATS-19 ATS-17 ATS-20 ATS-07 ATS-13 ATS-14 ATS-11 ATS-12
76 60
OWNER:

DCP-08, FEED UPS-8


75 61
ATS-08 ATS-09 ATS-15 ATS-16 ATS-03 ATS-05 ATS-06 ATS-01 ATS-02 ATS-04 ELEVATOR
74 62
IT-AC 1A IT-AC 3A IT-AC 2A IT-AC 4A 73 63
4300

72 64
ELEC EQUIPMENT ROOM 71 65
SC-07 70 66
69 67
TR.2A/AC , 380/220V

TR.4B/AC , 380/220V
TR.4A/AC , 380/220V
TR.1A/IT , 380/220V

TR.3A/IT , 380/220V

68
PP-ESS 4A PP-ESS 2A PP-ESS 1A PP-ESS 3A
STAIR
SC-06
7 SHAFT SHAFT
FR-08 GR-07
Saudi Data & AI Authority National Information Center

GE-006
2
CONTRACTOR:

Huawei Tech. Investment Saudi Arabia Co., Ltd.


District Cooling and Data Center Consultant
DC Pro Engineering Co.
P.O.BOX 22851 SHARJAH,
TEL. : 971 6 5566880 FAX. : 971 6 5566881
P.O.BOX 99352 DUBAI,
TEL. : 971 4 3432110 FAX. : 971 4 3432113
P.O.BOX 110512 ABU DHABI,
TEL. : 971 2 6316782 FAX. : 971 2 6316783
P.O.BOX 18927 RIYADH,
TEL. : 966 1 460 3301 FAX. : 966 1 4603302

PROJECT NAME:

ALLAM DC PROJECT

TITLE:

GENERAL ARRANGEMENT
SECOND FLOOR PLAN

DRAWN: SURVEY BY: SCALE: DATE: REV.:

1:100 SEP 2023 1

DESIGNED: Omar W. DRAWING NO: HW-NIC-ALLAM-DD-GE-003

CHECKED BY: Ahmad Abu H. PROJECT NO: