A1 Updated Comments Summary

1. RFI responses: RSC02012-RFI-000317 provided on 18/01/2024 hold good,


and no update to the drawings are necessary.
1. Please update IFC drawings accordingly and re-send. WSP has communicated this with RSG and confirmed by them.

This section does not match SB11 profile as per WSP reply.

a.

b.

c.

d.
2. IFC highlights steel members in LVL +28.835 but ETABS model models these members as RC
members.
2. Updated to RHCF 450X250X10, Refer to attached Etabs model

The drawing is still missing,


and it is not available with N3
revision, please check and
3. Missing drawing no. 1TB02012-012D03-UNA-A1-R1-DWG-ST-70008.provide.
3. Submitted the drawing on 19 October 2023 with N3 revision
4. Profile for façade members in truss top chord is not given in IFC drawings.4. Member profile mentioned on drawing as typical
(i.e SHS250X250X10), refer to attached below image.
a. Calculation of load on façade members it not given. 4.a) For facade loading refer to facade access/specialist drawings.
5. No loads placed on secondary members added into the ETABS model.
6. Wind calculations are not taking into consideration wind on columns.
7. Additional steel members from updated IFC drawings missing from latest ETABS model.
SB
SB01

7060

7060

7060

7060

7075

CW07
2200 2200
CW09

C30
CN-17 SB14 SC03
P SC03 CN-20 C30 3400
P SB14
CW19

2625
450

5. The loads are applied to the primary members and the secondary members 20 4025
SB

20

SB SB
SB
SB17

SB13
SB13

20
SB
20
SB17

20

The highlighted members in 500 SB18 SB18 SB18 CW07


CW09

P P P P P 29
4050

SB13

SB14 SC03 SB14 SC03 SB13 SC03 SB13 SC03 SB14 SC03
3900

C26
SB17

SB17

5075 SB20 SB20


SB20
SB20 SB20 SB20 SB20 SB20

shall be designed by the façade contractor, not by WSP. SB20 SB20


SB17

SB17

1400

C36 SB18 SB18 CN-19


20

SB12 SB18

the drawing are missing in the


100

SB

SB12 SB12 CW06


100

SB20 SB20 CW09


SB20
SB17
SB17

SB20 SB16 SB16


CN-16
SB17

SB16 SB16 10

ETABS model.
SB17

SB12

SB12
SB12

-ANGLE 100X100X10
SB12
PLAN BRACING (TYP) RHS150X150X10 (TYP) STEEL PEDESTAL

6. Wind load has been calculated based on the tributary areas and applied on
SB15

TOS +29.752
SB15

SB20 AS PER FACADE ACCESS REQUIREMENT


SB17

SB20
SB20 SB17 SB17 SB17 SB20
SB17

TOS +30.640
SB16 SB16

P
P P
SC03 SB12 SB12 SB12 SC03 SB12 SHS250X250X10 STEEL BEAM (TYP)

the primary members supporting the façade which are beams Hence the load SB20
SB20
SC03 SC03
SB20
TO SUPPORT THE STEEL PEDESTAL
TOB +30.205
TRUSS-2

SB20
P
SB17
SB17

SB16 SB16 SB16 SB16 SB16 SB16


TRUSS-1

SB12

LIGHTWEIGHT ROOF SYSTEM -


SB12

SB12

applied on horizontal members does not require to be applied on the columns. 264
2012-012D03-UNA-A1-ZZ-DWG-ST-30027
SC03

SB
SB16
SB11

SB16
SC03

SB
SB12

SB16
SC03

SB
SB12

SB16 SB16
SB11

SB
SB16
INSULATED PANELS/ SOFT ROOF AS
PER ARCHITECTURAL DRAWINGS &
SPECIFICATIONS

20 20 SB 20 20 20 SB 20 20 20
20 20
SB15

SB 20 20
SB17

SB17

SB SB SB SB SB
SB15

SB16 SB16 SB16 SB16 SB16 SB16


TOP OF STEEL MEMBERS
P TOS+30.205 (UNO)
SB12 SC03 SB12 SC03 SB12 SC03 SB12

7. Please clarify the comment. SB13 SB13 SB13


P

SB13 SB13 SB13

SB17 SB17 SB17 SB17 L-ANGLE 100X100X10 SB17


PLAN BRACING (TYP)
TOS +29.752

268 263 269


1TB02012-012D03-UNA-A1-ZZ-DWG-ST-30029 1TB02012-012D03-UNA-A1-ZZ-DWG-ST-30027 1TB02012-012D03-UNA-A1-ZZ-DWG-ST-30029

ROOF LEVEL - A1 HOTEL TRUSS TOP CHORD


1 : 100