Connection Example

VLT® HVAC Drive Software: 2.7

A fan is to be controlled between 10 to 50Hz. A 0-10V DC potentiometer is used as the speed reference.

Relevant Parameters
Par. Function Settings
FC 102 0-02 Motor Speed Unit [1] Hz
+24 V 12 3-00 Reference Range [0] Min - Max
+24 V 13 3-02 Minimum Reference 10Hz
D IN 18 Start / Stop 3-03 Maximum Reference50Hz
D IN 19 3-41 Ramp up time 20s
COM 20 3-42 Ramp down time 20s
D IN 27 Coast Inverse
D IN 29
D IN 32
D IN 33
D IN (S.Stopp)**37 Safety Stop

+10 V 50
A IN (S201 U-I) 53 Analog Input 0-10V DC
A IN (S202 U-I) 54
COM 55
A OUT 42
A OUT 39

01
Relay 1

02
03

*04
Relay 2

*05
*06

NOTE: Erstellt von: Schulung


All settings are based on factory settings.
It is recommended to set all the motor parameters in Par. 1-20 to 1-26 and then perform Automatic Motor
Adaption (AMA) in Par. 1-29.