Transformer Magazine Vol-8-Issue-1
Transformer Magazine Vol-8-Issue-1
INTERVIEW:
VERONIQUE LANDRAIN
Managing Director at NovAcec Services
NovAcec Services is a company offering installation, maintenance,
repair and refurbishment for transformers and tap changers
worldwide. As a total solution provider operating a laboratory with
brand new equipment, state-of-the-art techniques and engineers
with over 30 years of experience, NovAcec also delivers lifetime
extension programs, training, spare parts and oil analysis.
10
INTERVIEW:
JULIAN MONTERO
Head of predictive and corrective maintenance for power transformers
Julian Montero from i-DE, Spanish distribution system operator, part
of IBERDROLA Group, one of the largest power utilities worldwide,
talks about their power transformer maintenance and testing
program. They operate power transformers from 10 MVA up to
450 MVA, and voltage ratings ranging from 30 kV to 400 kV.
26
COLUMN: TRANSFORMER DEMAND FROM 2019 TO 2029 AND
BEYOND - THE IMPACT OF COVID-19 ON FUTURE MARKETS
Steve AUBERTIN
Previous, pre-COVID-19 analyses and estimates projected the
average yearly growth rate (CAGR) of the transformer’s market to
be 3.48 % up to 2028. However, those projections have to be re-
evaluated due to the global COVID-19 pandemic and its impact on
36 Contrary to the usual, in 2019, the UAE was the largest market of
transformers with Saudi Arabia being second, followed by Oman.
SAVE
the
see you at
Coiltech
DATE
Ulm See here
the Exhibitor
19-20 May list of Coiltech
Deutschland 2021 Deutschland
The next coil & winding spring event • In the heart of the German market
At the show
www.visitcoiltechulm.com
16
designed for the brazing of copper, brass, aluminium, bus bars,
cables and wires in the transformer industry.
86
not on the origin, it is valid for unused and recycled insulating mineral
oils and is the answer to higher industry, environmental, and sustainabi-
lity requirements. This article brings the news in the Ed. 5 of the standard.
Subscribe now!
Tomas Arenius
tomas.arenius@transformers-magazine.com
Tel: +49 1717328152
India:
Ashutosh Kumar Govil
Subscribe to Transformers Magazine and govil48@gmail.com
Tel: +91 99 750 975 34
keep track of the latest news and trends in Italy:
the power transformer industry. Ales Bertuzzi
ales.bertuzzi@transformers-magazine.com
Tel: +39 327 761 7581
PRINT SUBSCRIPTION Japan:
Junichi Tsuru
tsuru@kikuden.co.jp
Tel : +81 (0)80 1006 5183
Each USD 115 / one year/ 4 issues
Middle East:
Discount 10% for more than 10 pcs. M. Shakeel Sadique Shaikh
shakeel@skypowertech.com
Tel: +97 1508909031
Nordic Countries:
Tomas Arenius
DIGITAL SUBSCRIPTION tomas.arenius@transformers-magazine.com
Tel: +49 1717328152
People`s Republic of China:
Individual digital subscription: Eric Chen
USD 54 eric.chen@weidmann-group.com
Tel: +86 139 9821 235
Russian Federation:
Alexander Drobyshevski
Corporate digital subscription S: alexander.drobyshevski@gmail.com
Tel: +79 03 618 33 42
USD 190 (for companies up to 30 employees) South Korea:
Joseph Nam
j.nam@artex-corp.com
Corporate digital subscription M: Tel: +82 10 4706 5336
USD 320 (for companies with 30 to 100 employees) Southern Africa:
Peter Busch
peterhoekwil2@gmail.com
Corporate digital subscription L: Tel: +27 82 559 9970
W
Arne Petersen, Consulting engineer, Australia
Zhao Yongzhi, Shandong Electrical Engineering hile writing this message nearing has increased by about 25 %, the number
& Equipment Group Co., Ltd, China the end of 2020, I think back of the of website visitors by approximately 30 %,
Barry M. Mirzaei, LargePowerTransformers Inc., previous years in Transformers average visit duration has increased by over
Canada
Magazine, when we frequently wrote of the 30 %, the number of newsletter subscribers
EDITORS market dynamics, upcoming changes, their by about 50 %, the number of page sessions
Daosheng Liu, Jiangxi University of Science and
Technology, China
impacts and risks for which we all needed by around 90 %, etc.
Mislav Trbusic, University of Maribor, Slovenia to prepare ourselves, as well as of the best
Dr. Mohammad Yazdani-Asrami, University of ways to get prepared for those changes and These growth rates were difficult to imagine
Strathclyde, United Kingdom risks. First and foremost, we emphasized a year ago and they have been the best
Dr. Shuhong Wang, Xi’an Jiaotong University, the importance of innovation and market indicator of how Transformers Magazine,
China
communication. Transformers Academy and Transformers
ASSISTANT EDITOR Forum have jointly allowed for a unique
Pedro Henrique Aquino Barra, MSc,
EESC/USP – University of São Paulo, Brazil
Even so, only a year ago, it was very hard synergy of innovation and market
to imagine all the changes that have communication applicable to basically all
Art Director: Momir Blazek happened in the meantime. Those changes, company profiles on our market. These
Photo: Shutterstock.com
Front page image: Aurtra to which we and our associates have often growth rates also play a significant role in
Language Editor: Lidija Kasik pointed out, could have easily caught us reference to the materials that we publish,
off-balance. Luckily, we started developing for they guarantee excellent visibility and
ADVERTISING AND SUBSCRIPTION
Ante Prlic our innovation, by which I primarily mean a global reach. More importantly, the high
+44 20 373 474 69 Transformers Academy as well as other ranking of our platforms has contributed
ante.prlic@merit-media.com solutions, early enough to be prepared to the high ranking of the material we
TRANSFORMERS MAGAZINE at the crucial moment not only to face publish, because they reflect the integrity
Transformers Magazine is published quarterly our own challenges but also to respond and work ethics of all our associates, for
by Merit Media Int. d.o.o., Setaliste 150. brigade to the challenges that our associates and which I am especially grateful, and I am
10, 10 090 Zagreb, Croatia. Published arti very proud of them.
cles do not represent official position of Merit customers have faced. The thing we always
Media Int. d.o.o. Merit Media Int. d.o.o. is not like to point out is that a great majority of
responsible for the content. The responsibil these solutions has come to life with the Finally, I wish to invite everyone who
ity for articles rests upon the authors, and the
responsibility for ads rests upon advertisers. support of our associates and key customers wants to be a part of this inclusive, ever-
Manuscripts, photos and other submitted and much of the credit for everything we do growing story to contact us. Here, you will
documents are not returned. goes to them. have many opportunities for learning and
Subscription rates: development through subscription to the
Print edition: $115 (1 year, 4 issues) If I had to sum up our most important magazine and educational programmes
Digital edition: $54 (1 year, 4 issues) results, I would first have to mention the of the academy, as well as for presentation
Online edition - full access: $19 (1 year, 4 issues)
Online edition - free access: free of charge for launching and positioning of Transformers of your solutions through articles in the
registered users Academy as an outstanding e-learning and magazine and academy e-lessons, but also
www.transformers-magazine.com digital cooperation platform within our an opportunity for innovation that we are
REPRINT niche. In only a couple of months it hosted always willing to support, so feel free to
Libraries are permitted to photocopy for the around 30 top quality sessions and we have send your suggestions and ideas.
private use of patrons. Abstracting is permited recorded more than 7,300 registrations. A
with credit to the source. A per-copy fee must
be paid to the Publisher, contact Subscription. number of new high-quality programmes May you find this issue a useful and
For other copying or republication permissions, and some completely new opportunities pleasurable read. I wish you all good health,
contact Subscription. All rights reserved. are already being prepared. happiness, and prosperity in 2021.
Publisher: Merit Media Int. d.o.o.
Setaliste 150. brigade 10,
10 090 Zagreb, Croatia We have had equally valuable achievements
Contact: +385 1 7899 507 with our magazine, having published
Contact: +44 20 373 474 69 UK around 80 articles of exceptional quality, as
VAT number: HR09122628912
www.transformers-magazine.com well as an abundance of other material. The
Bank name: Zagrebacka banka number of followers on our social networks Mladen Banovic, Editor-in-Chief
Bank identifier code: ZABAHR2X
Bank IBAN: HR8023600001102375121
Director: Ana Jelcic
w w w . t ra n sfo r m e r s - m a g a z i n e . co m 9
INTERVIEW
VERONIQUE LANDRAIN
Managing Director at NovAcec Services
V
eronique Landrain is the Ma- CG Holdings Services division after ban- are able to offer our services all over the
naging Director of NovAcec kruptcy of CG in Belgium. The company world and on all types and brands of
Services S.A. Prior to that, she was created with the support of a Belgian transformers and tap changers.
worked at Pauwels Trafo Ser- industrial investment fund and Vero-
vices, holding various positions in the nique Landrain as the managing director.
One-stop shop for transformer
company from 2008. The company be-
came CG Holdings Services in 2009 and The history of the company goes all services
from 2014 to 2020, Veronique Landrain the way back to the 1980s, drawing its NovAcec’s main activities are services for
held the position of General Manager. origin from the ACEC company and transformers of up to 750 MVA and 400
from the Pauwels Trafo Service compa- kV that include installation and reloca-
She holds a master’s degree in environ- ny founded in 1986, which became CG tion, on-site preventive and corrective
mental science and in physical sciences Holdings Services in 2009. Hence, it is maintenance, repair works on-site and in
from Universities in Belgium. a succession of companies that has led our state-of-the-art repair shop of 3000
the experienced service staff to NovAcec m2 in Charleroi, refurbishment, expertise,
Services. measurements and tests, lifetime extensi-
Re-branded experience
on programs for shell and core-type trans-
NovAcec Services is a transformer ser- NovAcec Services employs about 35 formers, oil sampling and analysis, spare
vice company founded in March 2020, employees, former experienced engi- parts supply and trainings. Essentially, our
having acquired the business activities neers and technicians from CG Holdings team of experienced engineers and tech-
and the experienced team of the former Services. It is important to note that we nicians offers the following services rela-
NovAcec’s state-of-the-art value-added service and asset Full retrofit of 400 kV transformer
management solutions
w w w . t ra n sfo r m e r s - m a g a z i n e . co m 11
INTERVIEW
ted to transformers and tap changers: to power transformers up to 400 kV. This
dedicated repair shop is particularly im-
• Installation, relocation and commis- portant when repair cannot be performed
sioning at a customer site, which is often the case
• Expertise, oil analysis, tests and mea- when we need to intervene on active parts
surements of transformers.
• Preventive and corrective mainte-
nance We can perform maintenance and re-
• Repair on site or in our repair shop pair, on site and in the repair shop, for all
(leak repair, active parts repair, replace- brands and not only for our main brands
ment of accessories, painting, etc.) ACEC, Pauwels and CG. Since we now
• Oil treatment and oil refills own the ACEC brand for transformers,
• Upgrade and replacement of tap we have access to drawings of all trans-
changers and motor drive units formers manufactured in Charleroi and
• Modification, manufacturing and in- in Gent under the brand ACEC. Given customers all over the world. The fact that
stallation of cable boxes that these transformers are still present on we have access to technical details means
• Upgrade or replacement of cooling different markets, in Ireland, Belgium and that we can precisely and rapidly define
systems, replacement of HV, MV, LV in other countries, in Africa for instance, what has to be offered to the customers to
bushings we continue to offer our services for this satisfy their needs.
• Lifetime extension programs for tap specific brand.
changers and transformers up to 400 kV We also have a dedicated new oil analysis
• Spare parts delivery Also, in terms of brands, since we have laboratory in the north of Belgium (Kon-
• On-demand trainings acquired CG Holdings Services, we have tich). Decades of experience have showed
negotiated to have an exclusive access to us that having an own lab that can analy-
Our repair shop, located in the south of the drawings of CG and Pauwels transfor- se the condition of the insulation oil of a
Belgium (Charleroi), is equipped with a mers, which were manufactured in Belgi- transformer is critical for any transformer
crane of 175 t capacity and a full equip- um. This means that we can offer approp- service providing company, not only to
ped test bay, which allows us to repair all riate and accurate repair, maintenance and gain know-how to evaluate the status of
types of transformers, from distribution spare parts deliveries for these units to our the insulation and provide reliable con-
ditional maintenance, but also to be able We offer on-demand training sessions for
to keep the whole process of sampling-
measuring-evaluating-intervening and any customer in need of specific training on
saving a transformer in hand and react
rapidly.
transformers or OLTCs
Our team of 35 people includes specialists
with long-term experience in transformer In our new laboratory with brand new For more than 30 years, we have been
business, services and operation. We have equipment, state-of-the-art techniques correlating DGA results with actual faults
experts in our technical department with and engineers with over 30 years of ex- inside a transformer and now we know
over 30 years of experience, which gives perience, our customers get full service, what kind of DGA image an actual fault in
us potential for a large offer in the repair ranging from sampling to evaluation and a transformer can create. For this reason,
and maintenance business. Among other advice. we understand transformer failure modes
things, we are able to conduct studies for very well.
cooling systems and we also offer full On account of our huge experience in
retrofits of transformers, extending the transformer measurements and evalua- Our task is to keep clients’ transformers in
lifetime of critical assets belonging to our tions, we can guarantee high accuracy of good condition and intervene when this is
customers. For example, we can inspect results and evaluations and we can provi- jeopardised. We provide this service based
and re-tighten active parts of 400 kV shell de these services quickly at very competi- on measurements and knowledge. For the
type transformers and renew all critical tive rates. lab, these measurements are a series of re-
accessories (bushings, cooling systems, levant measures of oil quality and DGA.
etc.), allowing them to operate about 20 Most labs are experienced in measuring
years longer than they usually would. This oil and DGA and use evaluations based Today, DGA is the most powerful and
is all thanks to our technical department, on statistics and in line with standards, most effective technique to perform a
as well as our experienced technicians. but they have seldom seen what actually transformer’s health check and determi-
happens inside a transformer. We, on the ne the type of faults that can be expected.
other hand, have both: more than 30 years Clients sometimes ask for oil measure-
Focus on our new oil analysis
of experience in measuring transformer ments without DGA, which is surprising.
laboratory oil and knowledge of transformer design, One has to bear in mind that oil measu-
Most clients primarily want sampling, a materials, weak points, etc. Due to our vast rements, such as breakdown voltage, tan
clear evaluation and report of the status of experience in transformer manufacturing, delta, acidity and so forth, give you infor-
their transformer and oil, but most of all, evaluation and services, we can use our mation on the status of the oil, but DGA
they also like personal contact and back- knowledge of electrical and thermal phe- shows the health status of a transformer.
ground information when they have ques- nomena in a transformer and their effects Both are equally important, and NovAcec
tions about the results. on oil, insulation and, eventually, gassing. Services is equipped to deliver both!
w w w . t ra n sfo r m e r s - m a g a z i n e . co m 13
INTERVIEW
Since we use state-of-the-art techniques results in significantly better (lower) It allows us to draw exact conclusions
and equipment, we can provide reliable detection levels than with other ext- when evaluating measurements.
and accurate measurements. raction methods. Low detection limits
are important, especially in detecting
Following an appropriate method for incipient faults. Another important
sampling is also critical to ensure accurate advantage of the full degassing method
results. Therefore, NovAcec Services also is that there is no need for calculations
offers on-site sampling by our specialists. based on solubilities, like in the head-
space method. This is very important
A DGA-measurement when measuring insulation liquids
method of highest quality other than mineral oil. For instance,
one cannot simply measure esters cor-
There are different ways to get the rectly with the head-space coefficients
gas out of the oil and inject it in a gas for mineral oil. In general, measuring Contacts:
chromatograph. Most techniques are and evaluation of alternative insulation Headquarter - NovAcec Services SA
based on speed, numbers and gene- fluids that are becoming increasingly Rue Vital Françoisse 220
ral systems, using stripping or the so important in the transformer industry B-6001 Charleroi
called “head-space method”, in which has to be done carefully, taking into
only a limited part of the gas in the oil account specific aspects of different NovAcec Services SA
is used, and thus a poorer detection fluids. Prins Boudewijnlaan 9 – Unit 6
limit is achieved. NovAcec laboratory, B-2550 Kontich
on the contrary, uses the “full degas- Since we have experience with nearly all
sing method” where gases are nearly modern insulation fluids, we perfectly services.quotation@novacec.com
completely extracted from the oil and understand their different advantages and +32 71 44 10 20
injected into a gas chromatograph. This disadvantages and how to evaluate them. www.novacec.com
40 years of oxyhydrogen
gas generators with
Oweld
OXYWELD, headquartered in the Ital- “Oxyweld is extremely proud to be celebrate this anniversary because the
ian province of Pordenone, is a company celebrating its 40th anniversary, a sig- future of the industry looks particu-
specialised in the production of oxyhy- nificant milestone that few companies larly bright. The demand for environ-
drogen gas generators for brazing. This manage to achieve nowadays”, says Di- mentally friendly and safe technolo-
is a special year because OWELD brand ego Andreetta, Sales Director. “We have gies continues to grow, and Oxyweld is
marks its 40th anniversary. By combin- overcome many challenges in the past, at the forefront, building new products
ing passion and innovation, the compa- thanks to our tenacity and efficient and investing significant resources in
ny has become an important player in strategy. It is particularly gratifying to the R&D”.
this industry. In 1981, Enrico Andreetta,
the founder of Oxyweld, set the goal of
producing fire from water. The compa- Oxyweld’s environmentally friendly brazing
ny, which started in a small garage in the
town of Conegliano in the northeast of technologies transform water into oxyhy-
Italy, currently supports thousands of
small to large companies in more than 75
drogen gas and replace the conventional
countries. oxy-fuel cylinders
16 TRANSFORMERS MAGAZINE | Volume 8, Issue 1 | 2021
Advertorial
Oxyweld’s environmentally friendly With a strong spirit of innovation and commitment to Oxyweld. We hope to
brazing technologies transform water avenues of growth on the horizon, Oxy- be able to share the celebration of our
into oxyhydrogen gas and replace the weld moves on to the future. 40th anniversary with you throughout
conventional oxy-fuel cylinders (i.e., the year” concludes Diego Andreetta.
the most common being oxy-acetylene, “This anniversary gives us more en-
oxy-propane or oxy-natural gas). In thusiasm and a positive charge for the A preview of the new 40th-anniversa-
the transformer industry, thanks to the future. I would like to express thanks ry logo that will accompany Oxyweld
flame properties, the system is specif- to all our internal collaborators, the throughout the year is available on ow-
ically designed for the brazing of cop- global sales network, customers, stake- eld.com website. Below some pictures of
per, brass, aluminium, bus bars, cables holders and friends for their continued Oweld equipment.
and wires ranging from small size up to
large cross-sections. The same flame is
also used to remove resin from the CTC
(continuously transposed cable) in the From the safety aspect, the system works at
power industry. low pressure, below 0.5 bar, without storage
From the safety aspect, the system works gas because it is produced only on demand
at low pressure, below 0.5 bar, without
storage gas because it is produced only
on demand. Without optical radiation
and toxic fumes from the flame, opera-
tors can work more efficiently and in a
safer environment. In addition to that,
Oweld products are adopted for the sim-
plicity of usage and superior comfort in
brazing, thanks to a light torch.
w w w . t ra n sfo r m e r s - m a g a z i n e . co m 17
COLUMN
Transformer
demand from
2019 to 2029
and beyond
The impact of Covid-19 on future
markets
T
he purpose of this analysis that were being proposed at the start
is to assess the future of the of 2020.
global market for transform-
ers following the global pan- Much has changed in the period be-
demic that has swept the world since tween December 2019 and the fall of
the start of 2020. Our original esti- 2020 and the ramifications of those
mates were produced during the last changes in a few short months will
quarter of 2019 and therefore pre-dat- be present – at least for the next 10
ed the pandemic. The scale and feroc- years - if not longer.
ity of the spread of the virus became
clear during the first and second quar- Pre-Covid-19 the future demand for
ters of 2020, and the disruption to life GSU (generator step-up) transform-
worldwide is becoming clear. This ers was estimated to grow at 3.48 %
has prompted a re-examination and a through to 2028; details are shown in
re-calibration of the future scenarios Table 1.
w w w . t ra n sfo r m e r s - m a g a z i n e . co m 19
COLUMN
After GDP drop of 5 % on the worldwide level to “bridge the gap”. Projects in design or
in construction phases may be subjected
during 2020, The International Monetary to delays caused by Covid-19 restrictions,
Fund estimates recovery in 2021 and the but it looks as though GSU transformer
demand may not be impacted too greatly.
growth of 4 % However, the future – and these forecasts
– are far from certain and will depend on
a number of factors, including speed of re-
covery, second or subsequent virus waves,
These estimates produced in Q4 2019 include the replacement of redundant government spending / debt, world com-
need to be reviewed in order to estimate plant during the forecast period and the modity and oil prices, etc. The June review
demands following the disrupted peri- power factor effect on generating MVA, does explore some of these scenarios,
od and its impact on future growth. The we calculated that this would result in a and as a result, the recovery illustrated in
generator step-up transformer demand total 10-year demand of 4,238 GVA of Fig. 1 may be delayed but up to 3, 4 or 5
differs from other transformers’ utilities GSU capacity. years into the future. In this case, the abil-
demand principally because it is capital ity of the industry to “bridge the gap” will
expenditure-driven and closely linked The International Monetary Fund has re- definitely be compromised to the point
with GDP growth, whereas the system cently published a June 2020 update to the that if global electricity demand does not
and distribution transformer segments World Economic Outlook series of publi- increase, the need for new generating ca-
are disproportionately affected by oper- cations. This edition revised the projected pacity will also largely disappear.
ational expenditure in addition to capex. growth and GDP forecasts from the earli-
The change in the forecasts for these seg- er April edition downwards. The details by On the basis that if we do not know what
ments are discussed later in this article, major regions are shown in Table 2. the future will be, let us look back to see if
but firstly it is logical to reset the GSU history can provide any valid indication
forecasts. Fig. 1 graphically illustrates the short- that will help with the analysis. There
term forecasts. have been many recessions, conflicts and
The original forecast CAGR for gener- periods of negative growth, but only a
ating capacity from 2018 to 2028 was Given that most generating plant devel- few during the period of time when elec-
estimated to be 3.48 %. This took into opment projects are planned several years tricity has been a major utility product.
account the relatively low growth rates ahead of commissioning and that GSU The 1914–1918 war and the Wall Street
in fossil and nuclear capacity and the transformers are ordered over a year in ad- depression of the 1920s were globally
high growth rates expected for renew- vance of grid synchronisation on the face devastating but probably too far back
able technologies. When computed to of it, the industry activity should be able in time to shed light on the 21st centu-
Of which:
w w w . t ra n sfo r m e r s - m a g a z i n e . co m 21
COLUMN
Figure 2. Global GDP & installed capacity growth rate comparison from 2004 to 2014
The global growth of the installed capaci- that short of the decimation of the global
population, or total economic stagnation,
ties is stable during the last 30 years and the global installed capacity is likely to
continue to grow at between 1 % and 5 %
has a rate between 1 % and 5 % for the next 20 to 30 years.
w w w . t ra n sfo r m e r s - m a g a z i n e . co m 23
COLUMN
It is estimated that the growth rate of the principally a commodity business, and
orders are often placed on a call-off ba-
transmission system transformers mar- sis from stock. The market is driven to
ket between 2019 and 2024 will be 2.83 % a lesser extent by grid development in
“new installations” or predominantly by
CAGR, and it will increase to 3.84 % between maintenance and replacement of existing
2024 and 2029 networks.
Table 5. Global transformer market estimates pre- and post-Covid-19 from 2019 to 2029
w w w . t ra n sfo r m e r s - m a g a z i n e . co m 25
INTERVIEW
Transformer Team (from left to right): Julian Montero, Andrés Aguado, Diego Lumbreras
JULIAN MONTERO
Head of Predictive and Corrective
Maintenance for Power Transformers
V
ictor Lozano, Sales & Applica- Geographically, we are covering the area
tion Engineer for OMICRON where i-DE operates in Spain, taking care
Spain talked to Julian Montero of power transformers from 10 MVA up
from i-DE, Spanish distribution to 450 MVA, and voltage ratings ranging
system operator, part of IBERDROLA from 30 kV to 400 kV.
Group, one of the largest power utilities
worldwide, about their power transformer In addition to the people mentioned
maintenance and testing program. above, there are nine fieldwork teams
assigned to the regional operation and
Julian Montero has been responsible maintenance units in five regions, ma-
for the area of predictive and corrective king up a total of 24 people. These field-
maintenance within the Power Transfor- work teams check the proper operation
mers standardization and maintenance of OLTCs (On Load Tap Changers) and
department at I-DE (Group Iberdrola) perform electrical testing of the power
since 2014. Previously he worked as a transformers defined in both predictive
project engineer at Elecnor, Gamesa and and corrective maintenance programs.
Iberdrola Engineering, always related to
the development of new HV lines and What are the most important tools
substations in Spain and Brazil. that you are using for these tasks?
Dear Mr. Montero, can you briefly We are using diverse test equipment to
explain your role at Iberdrola? carry out measurements such as Insulation
Resistance (IR), Sweep Frequency Response
Our work within i-DE is related to the Analysis (SFRA) and Dielectric Frequency
area of maintenance and standardization Response (DFR) in order to evaluate the
of Power Transformers. Internally, our moisture content within the transformer.
group is called NMTP (Spanish acronym The main device that we use is the CPC 100,
standing for Power Transformers Main- which we use to perform most of the tests.
tenance and Standardization).
Currently, there is a total of eleven CPC
This specialized group consists of ten 100 in service, nine of which are assigned
people, divided into three main areas. to the regional maintenance units and
The first team is responsible for the stan- two are assigned to the NMTP depart-
dardization of new transformers; then ment. We are not using the CPC 100 as
we have a team focused on transportati- an individual unit but combined with
on and relocation of transformers; and, CP TD1 to measure capacitance and dis-
finally, a team responsible for mainte- sipation factor, and CP SB1 to minimize
nance policies, which also leads any si- the connection time and to automate the
gnificant corrective maintenance. These tests controlling the OLTC. So, our eleven
three areas are coordinated, obviously. test sets are composed of CPC 100, CP
w w w . t ra n sfo r m e r s - m a g a z i n e . co m 27
INTERVIEW
w w w . t ra n sfo r m e r s - m a g a z i n e . co m 29
RISK
ABSTRACT
Accurate assessment of transformer
insulation risk is a complex problem
that requires sophisticated analysis
of a dynamic environment, rarely in
equilibrium. With online monitoring
and an understanding of the detailed
relationship between temperature
and water activity in both the paper
and oil, a complete and useful auto-
mated assessment is possible.
Moisture and temperature are the biggest
KEYWORDS drivers of irreversible transformer aging
aging, condition monitoring, depoly
merisation, insulation, moisture
Accurate
determination
of transformer
insulation risk
and remaining
life
Introduction to insulation ing effect. For example, perfectly dry Kraft
breakdown paper (< 0.5 % moisture and medium ox-
ygen [1]) operated at 80 degrees will last
Moisture and temperature are the biggest > 20 years before it is critically damaged.
drivers of irreversible transformer aging. Add 2 % moisture and the usable life left
The critical issue is that temperature caus- falls to 3 years. Add 4 % moisture and it
es polymer chains in the paper to break falls to just over one year.
down. At start-of-life, the paper insula-
tion within a transformer consists of long
Measuring temperature and
intertwined cellulose chains, which make
it structurally strong, tough and durable moisture
to resist mechanical and electrical stresses. Measuring the temperature of a trans-
former is relatively easy, in comparison
Over time, chemical breakdown of these with measuring the water content of the
chains ultimately makes the paper me- paper. For example, sensors can be locat-
chanically weak, brittle and unable to ed throughout the transformer winding.
withstand normal operating stress. This Alternatively, close estimates can be made
stress is caused mainly by heating cycles from measuring the top oil temperature as
and transient electrical forces. Cracks and it exits the core or enters the radiator.
breaks become more probable and the
risk of electrical breakdown and structural On the other hand, assessing the water
instability increases. Eventually, the struc- content is much more difficult. Precision
tural strength of the paper and pressboard requires sampling the paper, which is not
cannot withstand the mechanical stress, possible without removing the transform-
and the electrical insulation role it plays is er from service. Using the measurements
compromised, resulting in a failure of the from the oil is far more difficult. Water
transformer. Moisture exacerbates this ag- Content of Oil (WCO) vs Water Content
w w w . t ra n sfo r m e r s - m a g a z i n e . co m 31
RISK
of Paper (WCP) relationships have been the example of a modest size transform- ple molecular diffusion phenomenon.
developed and refined for decades by er, which may have 1000 kg of paper and Effectively, when there is a difference in
some of the best practitioners and re- 3000 litres of oil. At 3 % WCP, this equates water pressures across a boundary, wa-
searchers. Unfortunately, these methods to 30 kg total of moisture in paper. At 3 % ter molecules will move from the area of
remain prone to serious error for funda- WCP, the WCO at normal operating tem- higher pressure to lower pressure. This
mental reasons discussed below. peratures will be between 10 and 50 ppm, mathematical theory was developed by
which equates to a maximum of 150 ml of Adolf Fick in 1855 (specifically Fick’s
total water in the oil. As a useful rule, 95 % second law). The pressure of the water in
The diffusion phenomenon
of the moisture in a transformer is in the a material divided by the pressure above
Moisture in transformers is mostly con- paper. liquid water, at the same temperature, is
tained in the paper. WCP is measured as by definition the relative saturation or wa-
a percentage (or parts per 100). WCO is The balance between the moisture in the ter activity (aw) [2]. Therefore, the water
measured in parts per million, ppm. Take paper and the moisture in the oil is a sim- activity difference across a boundary is in
fact the driving force for diffusion (as the
denominator is constant). Further, when
the water activity in each of the materials
either side of a boundary are equal, no dif-
fusion occurs. This is when the materials
are in equilibrium.
Figure 1. Water activity response to 10 °C temperature steps using 4 % wet Kraft paper
So, when in equilibrium (i.e., when water
in an oil bath migration across the boundary between
the oil and the paper stops), then the water
content of the oil will be a direct indica-
tion of the water content of the paper, as
their water activity will be the same. Un-
fortunately, equilibrium rarely occurs in
an active transformer due to its oscillating
load, plus there are further complicating
factors to consider.
A complex relationship
Some of the complex issues to consider
when analysing moisture in a transformer
include:
w w w . t ra n sfo r m e r s - m a g a z i n e . co m 33
RISK
With Aurtra HealthSense, these complex “oil-test” observation is therefore like try-
ing to understand the dynamic state of a
analyses are immediately available to as- power system using a single point mea-
sess, track and forecast the insulation state surement. You know something, but not
quite what.
and life left across the transformer fleet
Online monitoring is key to
ture of the top sections falls before equilib- Like the complex excitation and loading accuracy
rium is reached, the reverse process starts of an electrical power system, equilibri- Water content of the oil is a function of
immediately, and the oil moisture content um is rarely achieved. Understanding the the oil’s ability to hold moisture at the spe-
remains continuously out of balance with state of the transformer (moisture levels at cific aw and is driven by the aw and WCP
either the hot or cold areas. different locations) from a single sporadic of the hottest paper in the transformer.
Importantly, aw is the driving parameter
not WCO. Measuring WCO therefore
provides an indication of the aw in the hot
WATER CONTENT OF PAPER areas but it is complicated by the oil’s char-
acteristics and the dynamic state of the
pumping process. Averaging over time
helps to remove the effects of the dynam-
ic processes, but this requires continuous
monitoring, not spot observations. Sys-
tems that directly measure the aw, togeth-
er with the top temperatures, provide a
much greater level of accuracy in WCP
estimation and therefore consequential
calculations such as paper age and life left.
Complex computational
problem solved
To complete a detailed and accurate as-
sessment of the moisture profile of a trans-
former, the age profile of the transformer
at top, bottom and hotspot must therefore
also be considered in the calculations. This
is a difficult computational process which
can only be done by means of an iterative
solution using an observation-matching
algorithm.
Forecast DP and life left. Correlate oil test results.
Observations of aw need to be made to-
Figure 5. Aurtra HealthSense DP Analysis and Forecast gether with temperature at a sufficient rate
Bibliography
[1] Lelekakis, Nick, et al. “Ageing Rate of Prioritise replacement by insulation risk and life left
Paper Insulation Used in Power Trans-
formers Part 2: Oil/Paper System with Figure 7. Aurtra HealthSense Fleet Life Left
Medium and High Oxygen Concentra-
tion.” IEEE Transactions On Dielectrics
And Electrical Insulation, vol. 19, no. 6, Author
2012, pp. 2009–2018. Richard Harris, PhD
CTO & Founder of Aurtra Pty Ltd. Aurtra is an
[2] D. Martin et al, Improving the Deter- Australian company focused on providing innovative
mination of Water Content of Power solutions in asset condition monitoring and assessment
Transformer Insulation Paper near the to the electricity market. Dr Harris is an experienced
End of Its Functional Life, Australasian technology entrepreneur, having founded a number
Universities Power Engineering Confer- of successful companies in the telecommunications
ence (AUPEC), 2016, pp. 1–6. and high voltage electronics fields. He is the holder of
numerous patents and an Adjunct Professor with the Queensland University
[3] CIGRE Moisture Equilibrium and School of Information Technology and Electrical Engineering.
Moisture Migration Within Transform- Contact: ask@aurtra.net
er Insulation Systems, 2008, A.23
w w w . t ra n sfo r m e r s - m a g a z i n e . co m 35
COLUMN
ABSTRACT
GCC market has been having its ups and
downs in the last few years. What used
to be one of the most attractive T&D
equipment markets might be losing its
high place in the eyes of international
manufacturers. A big part of it has to do
with the region’s dependency on oil rev-
GCC transformers
enues, which, in the last few years, have
not been stable, owing to the lower oil
prices. Infrastructure consumption has
reduced significantly over the years with
austerity measures in place. In addition
to this, the overall geopolitical situation
in the Middle-East region has had its toll
on the GCC markets, making it difficult
market
for international manufacturers to do Is the region still an attractive market
business in the rest of the region using
GCC countries as a regional base. for manufacturers?
GCC market has been having its ups and high place in the eyes of international
KEYWORDS downs in the last few years. What used manufacturers. A big part of it has to do
to be one of the most attractive T&D with the region’s dependency on oil rev-
COVID-19, distribution transformers, equipment markets might be losing its enues, which have not been stable in the
future trends, GCC, Gulf countries,
market overview, power transformers
last few years owing to lower oil prices. online again in lieu of the mega projects in Local content requirements
Infrastructure consumption has reduced the region. Against the backdrop of these
significantly over the years with austerity developments, it is important to note that Countries in the GCC, especially Saudi
measures in place. In addition to this, the GCC market has been undergoing the fol- Arabia, are trying to encourage foreign
overall geopolitical situation in the Mid- lowing changes. companies to participate actively in the
dle East region has taken its toll on the
GCC markets, making it difficult for in-
ternational manufacturers to do business
in the rest of the region using GCC coun- Local distribution transformer suppliers are
tries as a regional base. leading the market, whereas, due to limited
Changes in the regional market
power transformer manufacturing, foreign
The situation is expected to ease up a little
players with no local manufacturing hold a
with infrastructure projects coming back higher share of the market
w w w . t ra n sfo r m e r s - m a g a z i n e . co m 37
COLUMN
Current megaprojects, coupled with large 2015, oil prices have been significantly
lower due to decreased oil revenues and
power generation projects in UAE, Oman, hence lower investments. More recently,
Saudi Arabia, and some petrochemical proj- the Russia – OPEC+ agreement has been
signed, leading to a slight improvement
ects will contribute to a stable transformers in the prices, but overall revenues remain
low. This has impacted the regional invest-
demand at least for the next few years ments in the power grid sector too, with
even large buyers such as the Saudi elec-
tric company not placing orders as large as
before.
local economy. Frameworks like Saudiza- tions ranging from 10 % upwards in the
tion, vision 2030 local content, and UAE’s score. Infrastructure projects reviving
ADLC / ICV have been in place encour- slowly
aging local production. Companies must rethink their approach
in terms of local content if they want to Despite the oil prices fluctuating, there is
Manufacturers operating in the region continue having a presence in the region. an increasing focus from the Gulf states
now need to have local production, lo- Today it practically means that in the to create alternate sources of revenue in
cal partnerships, and local workforce to transformers business, local distribution addition to oil, which will lead to infra-
be able to do business in the region. And transformer suppliers are leading the mar- structure consumption. However, this
this is true not only for utilities but also ket, whereas, due to limited power trans- is primarily due to mega projects like
for the state-owned oil and gas compa- former manufacturing, foreign players NEOM, King Abdullah Economic City,
nies like Saudi Aramco, ADNOC, and with no local manufacturing have a higher Expo 2020, and other large initiatives to
Kuwait Petroleum, which are also large share of the market as well. promote the tourism and services sector
buyers of transformers. These programs in the region. These megaprojects, cou-
do not necessarily mean that foreign Funding problems due to oil prices pled with large power generation projects
businesses with no local presence cannot in UAE, Oman, Saudi Arabia, and some
do business in these countries. It means Unstable oil and gas prices play a huge role petrochemical projects (e.g., ADNOC-
they have a disadvantage in bid evalua- in infrastructure development. Starting in OMV-ENI) will contribute to a stable
Infrastructure
Development Plans
Efforts for economic diversification
resulting in infrastructure
development plans e.g. new cities.
Saudi Arabian policy is to give 10 % advan- GCC still be an attractive market in the
future as it used to be, beyond the current
tage to the local product manufacturers megaprojects?
compared to foreign manufacturers in order With local content requirements increas-
to encourage the local production and sup- ing in time, the geopolitical situation is
changing, foreign manufacturers, espe-
pliers cially those in the west, are reluctant to
heavily invest in the power grid business
in the region. A little promise of returns
Vision 2030 economic diversification uation, among the qualifying suppliers from the rest of the MENA region might
program which will drive the market based on technical features, locally pro- not be enough for the manufacturers to
of transformers in the Kingdom. duced products are given a 10 % advan- consider the region as the base for a larg-
• Historically, Saudi Arabia has re- tage compared to foreign products, fa- er market, maybe for software solutions
lied on crude oil to fuel its electricity vouring the evaluation for local suppliers. business.
needs, but with the Kingdom’s plans to
move from its dependence on oil re- Today, however, there is still a decent de-
COVID-19 impact and beyond
sources, for the first time in the history mand to be fulfilled in the region for the
of KSA, large renewable energy proj- COVID-19 situation has adversely affect- next couple of years. Moving forward, the
ects are planned under Vision 2030 to ed the GCC market in two ways. First, the success of these mega projects in shifting
achieve 27.3 GW of clean energy by demand for transformers was decreased, the dependence of the GCC economy on
2024, which will, in turn, lead to trans- especially in Q2, with demand shifting oil revenues will decide how attractive
formers demand. to Q4 and onwards. Second, disruption the market is for both local and foreign
• To accommodate this injection of in the supply chain as it has been diffi- manufacturers.
power into the system, a lot of green- cult for local manufacturers to import
field investments are planned by Saudi raw materials and components on time,
Bibliography
Electric Company (SEC) to expand resulting in longer lead times and fulfil-
T&D infrastructure in the future ment delays. The situation has eased up [1] Power Transformers Market Research,
years. a little as the main component / raw ma- Power Technology Research, 2020,
terial supply factories in China and India https://powertechresearch.com/services/
Another important element of the Sau- are slowly coming back online operating grid/power-transformers/
di Arabian market is the local content on higher capacity. Local projects are also
guidelines. Saudi Arabia has some of the coming back online with order in-take [2] Distribution Transformers Market Re-
strictest local content requirements in the becoming better. However, despite this search, Power Technology Research, 2020,
region to encourage foreign companies to short-term recovery from COVID-19’s https://powertechresearch.com/services/
participate actively in the development of effect, the big question remains: Would grid/distribution-transformers
local economy and workforce (Saudiza-
tion) in addition to the Kingdom’s goal of
promoting local companies into becom-
ing regional entities. The Kingdom’s Vi-
Despite recent recoveries, COVID-19 has
sion 2030 program goal is to localise 70 % negatively influenced the market and sup-
of the procurement and services by 2021.
Looking at the two major transformers ply chains, but the question that remains is,
buyers in the country for their specific will the GCC still be an attractive market in
local content programs:
the future as it used to be before?
Saudi Aramco
w w w . t ra n sfo r m e r s - m a g a z i n e . co m 41
TECHNOLOGY
Transformer
design and
manufacturing
for natural
ester fluids
VTC Engineering Department
w w w . t ra n sfo r m e r s - m a g a z i n e . co m 43
TECHNOLOGY
Ester FR3 is a fire-resistant fluid created additives. It does not contain any petro-
leum, halogens or silicones. It is tinted
from edible seed oil and food-grade per- green in colour, and a has fire point of
formance-enhancing additives that make it 360 °C and flash point of 330 °C. Natural
esters can hold a higher amount of water
biodegradable and environmentally friendly than mineral oil. Due to this property,
the water content in newly received oil
can be 200 mg/kg as per IEEE. Table 2
of the standard [4] provides acceptable
VTC/GTC team has successfully de- Properties of natural esters values for ester fluids. The moisture is
signed and tested a 150 MVA trans- bonded to the oil molecule and does not
former insulated with natural ester En- Virginia Transformer has developed En- affect the insulation. Also, the power fac-
virotemp™ FR3™ fluid, one of the largest virotemp™ FR3™ ester-filled transformers tor of 1 % in ester is equivalent to 0.5 %
FR3 insulated transformers built in the for biodegradable applications as well as in mineral oil. The viscosity of the fluid
USA. Our team has built and tested for indoor applications based on custom- is 4 times that of mineral oil for the op-
units up to 750 kVp Basic Insulation er requirements. Ester FR3 is a fire-resis- erating temperature of 80 °C, shown in
Level. Envirotemp™ FR3™ is a product tant fluid created from edible seed oil Fig. 1.
of Cargill. and food-grade performance-enhancing
Design
Designing a transformer using natural
ester requires a fundamental under-
standing of the fluid’s electrical, thermal
and physical properties. Electrical prop-
erties such as breakdown strength and
discharge ignition of the liquid under
power frequency and lightning impulse
condition play an immense role in the
electrical design of the transformer. The
fluid properties which govern the design
are tabulated below.
Electrical design
Dielectric performance of the ester fluid is
different than what is understood for the
mineral oil fluids. Based on the literature
available in various technical forums, it
is indicated that ester fluid performance
is poorer for the field around sharp elec-
trodes (highly non-uniform fields). The
Figure 1. The viscosity of different fluids
transformer has many surfaces / edges
which are not perfectly smooth and can
Table 1. Comparison of properties cause field gradient to rise and go beyond
the limit. Traditionally transformers are
Material Property Mineral oil Natural Ester designed with stress limited in the oil duct
around electrodes, as oil carries the high
Dielectric stresses due to material property. Weid-
2.2 3.2
constant mann has published the partial discharge
Oil
inception limit of oil ducts for different
Viscosity 3.5 cSt 12 cSt configurations for mineral oil years back,
and this has been followed by the industry
Dielectric
Paper constant 3.2 3.4 around the world [5].
Low-density pressboard Dielectric 4.4 4.6 There are no such partial discharge incep-
constant tion curves available for the ester fluid due
Dielectric to the newness of the fluid, and research
High-density pressboard 4.4 4.6 is still going on to predict the breakdown
constant
values less than 1 % probability. For a typi-
Dielectric
Moulded Pressboard constant 3.5 4 cal insulation arrangement, field distribu-
tion is shown in Fig. 2. Field distribution of
w w w . t ra n sfo r m e r s - m a g a z i n e . co m 45
TECHNOLOGY
The viscosity of ester fluid is almost 4 times the early 2000s. We have dedicated equip-
ment in the shop for storage and process-
that of the mineral oil for 80 °C temperature ing requirements, design rules, and pro-
and approximately 40 °C temperature dif- cess guidelines for each plant based on the
plant capacity to cater to the needs of the
ference brings the viscosity of the natural customers requiring ester fluids.
ester close to the mineral oil
References
[1] IEEE Std C57.12.00-2015, IEEE Stan-
of the lead stress for insulated lead to the under a positive pressure of nitrogen. FR3 dard for General Requirements for Liq-
ground plane for mineral oil and ester flu- fluid is recommended to be stored indoor uid-Immersed Distribution, Power, and
id is given in the table below. and dedicated oil hoses, and pumps are to Regulating Transformers
be used. Separate in-house processes are
to be maintained for the oil received in [2] IEEE Std C57.12.90-2015, IEEE Stan-
Thermal design totes and in tankers. dard Test Code for Liquid-Immersed
The viscosity of ester fluid is almost 4 times Distribution, Power, and Regulating
that of the mineral oil for 80 °C tempera- Approximately 40 °C temperature differ- Transformers
ture. The viscosity of the fluid introduces ence brings the viscosity close to mineral
complexity in the thermal performance of oil for the natural ester. Oil filling is rec- [3] IEEE Std C57.12.10-2017, IEEE Standard
the transformer even though paper deg- ommended to be done within the tem- Requirements for Liquid-Immersed
radation is not compromised. IEEE limit perature range of 60–80 °C and in vacu- Power Transformers
[3] for the hot-spot rise is 80 °C for 65 °C um to improve the impregnation process.
winding rise transformer. To meet the Settling time after oil filling is roughly [4] IEEE Std C57.147-2018, IEEE Guide
thermal performance radiators and fans doubled compared to the mineral oil for for Acceptance and Maintenance of
need to be selected based on a thermal the oil temperatures of 60–70 °C. Natural Ester Fluids in Transformers
calculation considering flow resistance
and tested the performance of the units [5] V. Dahinden, K. Schultz and A. Kuchler,
already built. Special design radiators and Conclusion Function of Solid Insulation in Trans-
number of plates need to be adopted for VTC/GTC understands the properties of formers, Transform 98
catering to the ester fluid requirement. Oil ester fluids and has been building hun-
ducts closer to the winding need to be se- dreds of transformers with FR3 fluid from [6] FR3 brochures from www.cargill.com
lected by analysis for the oil to flow in the
narrow room available close to the wind-
ing. Duct size needs to be selected to meet
the thermal and dielectric requirements. Authors
LET US
HELP YO
U!
Transformers Magazine’s experts have
vast experience and technical knowledge
in producing the perfect professional ma-
terial for your needs.
ABSTRACT
Nowadays, the huge demand for
Super large
capacity
long-distance UHVDC transportation
prompts research on the super large
capacity converter transformer. Es-
converter
pecially in China, UHVDC projects are
widely built and put into use. This ar-
ticle reviews the history of converter
transformer research and introduces
transformer
details in the design of the converter
transformer. The recent advances in
the fundamental study of converter
transformers such as partial discharge,
space charge, and material perfor-
mance test are also introduced in the 1. Introduction and the demand for electric energy are in-
article. In the end, this article summa- Driven by the growing prosperity of creasing. According to the forecast of the
rizes the application status of the con- fast-growing developing economies, the International Energy Agency (IEA) [1],
verter transformer in China and looks demand for energy will continue to grow the share of electricity in terminal energy
forward to its future prospects. in the future. In order to cope with the consumption may exceed that of oil by
challenge of climate change, clean energy 2040, which is currently less than half of
KEYWORDS is more preferred in the world. Therefore, oil. Electricity demand will also increase
with the continuous development of the by 70 %, with more than 50 % of the de-
bushing; converter transformer; social economy, the proportion of electric mand growth coming from China and
partial discharge; space charge energy in terminal energy consumption India.
w w w . t ra n sfo r m e r s - m a g a z i n e . co m 49
COLUMN
UHV converter transformer is subject to way, the compact design of the main in-
sulation structure of ± 800 kV converter
complex stress, including long-term AC / DC transformer is realized.
superimposed electric field, high harmonic 3.2 Electric field control of outlet
voltage, serious DC magnetic bias, light- device
w w w . t ra n sfo r m e r s - m a g a z i n e . co m 51
COLUMN
The converter transformer's valve side out- a key role, it requires high reliability. The
manufacture, installation, and debugging
let is the key insulation structure connecting of the converter transformer are the key to
the valve side winding lead of the converter avoid any fault. Therefore, requirements
of the manufacturing environment and
transformer and DC high voltage bushing processing quality of the converter trans-
former are very strict.
4.1 Partial discharge Although partial discharge generally does discharge. And the discharge process is
not cause penetrating breakdown of the divided into the initial stage, development
According to the data on converter trans- insulation, it can cause partial damage to stage, and near breakdown stage.
former fault released by the CIGRE work- dielectric (especially organic dielectric).
ing group, the fault rate of the converter If partial discharge exists for a long time, 4.2 Space Charge
transformer is about twice that of an or- it will lead to insulation deterioration or
dinary power transformer, and the insu- even breakdown under certain condi- When the converter transformer is in op-
lation accident of a converter transformer tions, and serious accidents may occur. eration, the DC electric field component
accounts for about 50 %. A partial dis- Therefore, through a partial discharge test will make the oil-paper insulation accu-
charge is one of the main reasons for in- of the transformer, it is possible to moni- mulate space charge when its valve-side
sulation failure, and it is also an important tor the insulation condition of the equip- winding bears AC and DC superimposed
indicator to reflect the degree of electrical ment and promptly detect problems relat- electric field. Space charge accumulates in
ageing of the insulation. ed to manufacturing and installation time. the insulation medium, strengthening the
local electric field, which may cause early
In order to avoid discharge caused by a Chinese scholars have done a lot of re- insulation damage, and accelerate the age-
concentration of the local field strength, search on partial discharge characteristics ing of the insulation medium [4].
the electric field is barely uniform in trans- of the converter transformer. Lu Licheng
formers. However, in the actual operation and others of State Grid Corporation of It is generally believed that the space
process, a partial discharge is caused by China have discovered that the starting charge in the polymer is mainly composed
the concentration of partial electric field voltage of partial discharge is related to of two parts. Some of them are the carri-
due to mechanical deformation and in- different voltage components in differ- ers injected into the electrode and trans-
sulation ageing of oil-paper insulation. ent models. In the plate-plate electrode portable carriers. The other is due to the
When a partial discharge occurs at the model, only when the DC component ionization and migration of inorganic or
junction of the metal oil paperboard, or increases to a certain extent can a partial organic impurities in the medium under
when the discharge occurs near the pa- discharge in the oil be directly caused. Li the influence of voltage, which is the main
perboard and damages the paperboard, Chengrong et al. of North China Elec- factor when the electric field is low. Simul-
the partial discharge will develop along tric Power University have adopted dif- taneously, as the charge injects, charge
the paperboard and become the surface ferent methods to diagnose and analyze trapping is de-trapping, which causes a
partial discharge [3]. the relevant data in the process of partial recombination. The energy transfer and
w w w . t ra n sfo r m e r s - m a g a z i n e . co m 55
COLUMN
Why subscribe?
• Regularly follow the latest project and business opportunities
• Keep up to date with the latest news on technology and business
developments in the industry
• Keep regularly informed on the specific and global market trends
• Find out about the latest products and services on the market
• Follow global career opportunities
Transformer
assessment
using health
index – Part II
Sensitivity analysis and critical
discussion
work has been documented on the sitivity analysis which shows the mask-
sensitivity analysis of the “scoring” and ing of issue(s) using this approach. The
KEYWORDS
“weighting” method. This paper pre need for a risk of a failure-based ap- asset management, condition assess-
sents a critical review of the “scoring” and proach based on non-linear scoring is ment, fault tree analysis, health index,
“weighting” method by performing sen- discussed. risk of failure
w w w . t ra n sfo r m e r s - m a g a z i n e . co m 59
CONDITION ASSESSMENT
It is difficult to get the scoring and weight- but there is an issue with the foundation
and / or anchorage of the transformer,
ing correct; there is no standard to adhere from the visual inspection, a rating of E
to, and all the weighting factors differ de- with score = 0 is decided.
D (Score = 1) Poor, 4 items have problem With the worst ranking for thermogra-
phy and physical condition, TH1 = 60.
Very poor, more than 4 items have a This classifies as “fair” with the recom-
E (Score = 0) problem mendation to either maintain or revise
There is no risk of failure associated with Table 13. Transformer health index with a very poor visual inspection
this transformer with bad “thermogra-
Rating code Overall HI
phy” and “physical condition”. Similarly,
in [25,26] a HI model was developed HIF7 (visual inspection) = 0 93.3
that combined transformer test data: di-
electric and thermal conditions (DGA,
furan), mechanical conditions (sweep
frequency response analysis), oil condi- • Identification of different failure modes quality - be it the accuracy of data or
tion, and non-transformer dependent and prioritisation of failures. completeness of data. Sometimes the
data, such as lightning frequency, sub- • Identification and prioritisation of DGA data for the main tank is available
station layout, and external events. maintenance / refurbishment or re- whereas from the OLTC compartment
placement to control failure modes. it is not available. It is paramount to un-
Any of the above will result in trans- derstand what it means not to have data
former failure, and it is difficult to get the 3.5 Limitations of using health index or below-par data. It is essential to un-
weighting correct. Several permutations derstand the questions below:
and combinations that need to be car- 3.5.1 Masking of failure modes
ried out make this “scoring” and “weight- • Is the new incoming data “normal”?
ing” method difficult. Additionally, there The sensitivity analysis study clearly What is “normal”?
is no standard to adhere to, and all the demonstrated that the overall assess- • Is the new data a statistical outlier?
weighting factors differ depending on ment score masks a bad failure mode. As • Why is it important to know if it is an
the expert assessment. This shows that shown, when most of the failure mode outlier?
HI based models are not modelled on scores are good, and only one or two • Does the sensor output make sense at
reliability centred maintenance (RCM) failure mode scores are worse, the over- all?
approach. RCM always ensures the fol- all assessment will mask the issue asso- • Is there a trend? Is there a sudden
lowing: ciated with the worse failure mode. An trend? How critical or significant is the
option is to decouple failure modes or trend?
• Transformer functionality is always use the worst-case scoring in the overall • What is the reliability of the incoming
maintained. assessment. data?
• Every individual component of a trans-
former maintains its functionalities to 3.5.2 Data quality 3.5.3 “What next” scenario
maintain the overall transformer func- The quality of health assessment ul- Health index does not provide any indi-
tionality. timately depends on incoming data cation on the urgency of follow up action
DGA 1.2 3 20 24
OQA 1.2 3 20 24
FFA 1.2 3 20 24
Age 0.4 3 20 8
w w w . t ra n sfo r m e r s - m a g a z i n e . co m 61
CONDITION ASSESSMENT
Health index does not provide any indica- • Dielectric condition assessment - core
assessment, winding insulation
tion on the urgency of follow-up action for • Thermal condition assessment
transformers with poor scores, nor does it • Mechanical condition assessment
• Bushing condition assessment
provide any indication of what should be • Cable box assessment
done next • OLTC assessment
• Cooler / radiator condition assessment
• Oil (mineral / natural ester / synthetic
ester) assessment.
for transformers with poor scores, nor • Inclusion of the probability of failure
does it provide any indication of what and risk associated with failure The scoring matrix developed by the
should be done next. Whether the trans- • Inclusion of replacement or working group has six levels - Level A
former needs to be replaced, repaired or repair / refurbishment scoring based (minimal signs of deterioration) to Lev-
refurbished is not answered. on economics [30]. el E (very poor condition), with Level F
(denoting de-energise as soon as possi-
3.5.4 No associated risk The CIGRÉ Working Group A2.49 ble) not used for scoring but for imme-
There is no risk associated with the fail- [28] published the laid down general diate action. Each level is colour coded
ure of the transformer with a HI score = guidelines for transformer assessment for easy visualisation. The basic steps to
100. There is a need to address this con- index development, including the use develop the transformer assessment in-
cern. The question on “what if a trans- of on-line monitors. A detailed sum- dex (TAI) are listed below [28]:
former with good HI score fails” is not mary and advantages / disadvantages
answered by “scoring” and “weighting” of aggregation methods used to calcu- 1. Determine the purpose of the TAI
method. late HI has been listed. These methods 2. Identify the failure modes to be includ-
include: ed in the TAI
3. Determine how each failure mode will
4. The requirement of a new • Weighted sum be assessed
approach • Sum of non-linear scores 4. Design a calibrated system for cate-
The new approach / alternative to • Worst case gorising failure modes (scoring matrix)
HI based asset management strategy • Statistical regression 5. Calculate a TAI score for each trans-
should be based on the following: • Artificial intelligence former.
• Decoupled failure mode analysis - Detailed tables are provided for condition Fig. 2 shows the scoring assessment
probabilistic fault tree-based analysis assessment of different factors, such as: sheet for this new method. In [28], the
[29] scoring for replacement or repair / refur-
bishment has been introduced. The idea developed selects those failure modes • Bushing power factor and capacitance
behind introducing this is as mentioned for each of the components and brings • Bushing reference power factor and ca-
by CIGRÉ Working Group A2.49: to the “analysis matrix” those operation- pacitance as per manufacturer
al parameters that play a role in that spe- • Bushing voltage class
1. “High moisture content is not a driv- cific failure mode. It is very important • Bushing construction type
er for replacement, as the moisture can to note that parameters that are not cor- • Bushing inspection results - hot spots,
generally be removed as part of a refur- related or those that do not contribute cracked, oil, oil leak?
bishment. However, a transformer will to a given failure mode are not analysed • Bushing maintenance date.
not be considered for refurbishment if together with those directly associated
the paper is already significantly de- with a failure mode. After all major components and their
graded (high furans). Similarly, trans- failure modes are duly evaluated, a glob-
formers with high levels of partial dis- As an example, a bushing may fail due al associated probability of failure (POF)
charge or arcing will not be considered to several reasons such as design and score is produced out of the individual
for refurbishment as it is unlikely that manufacturing issues, storage, mainte- scores of each component. This score
these problems can be easily corrected nance and operations, external causes, is mapped in a criticality index matrix,
during the refurbishment process”. etc. In order to be properly assessed, designed to map the POF score against
each of these possible failures may re- the importance of the unit. This model
2. “Bushings can be replaced as part of quire different data inputs, such as: also incorporates the “expert system”
either the repair or refurbishment pro- within the fault tree-based assessment
cess. However, as replacing bushings • Bushing installation date method. One such example is the data
can be expensive if identical bushings
are not available, defective bushings are
also one of the drivers for replacement.”
w w w . t ra n sfo r m e r s - m a g a z i n e . co m 63
CONDITION ASSESSMENT
quality check and management by em- ers, 20th International Conference on [29] L. Cheim et al., A Novel Dynamic
ploying statistical packages within the Electricity Distribution (CIRED 2009), Fleet Wide Condition Assessment Tool
model. As data is generated every few Paper no 0686, 2009 of Power Transformers, CIGRÉ A2 &
minutes / hours from technology de- C4 Joint Colloquium, 2013
ployed within a smart grid, such as on- [25] F. Scatiggio and M. Pompili, Health
line DGA equipment or other online index: The Terna’s practical approach [30] M. Dong et.al, “A Novel Main-
devices, assessment of data quality by for transformers fleet management, tenance Decision Making Model of
manual methods becomes tedious. Sta- IEEE Electrical Insulation Conference Power Transformers Based on Reli-
tistical packages, such as outlier identi- (EIC), pp. 178–182, 2013 ability and Economy Assessment, IEEE
fication, box plots, piecewise linear ap- Access, Vol.7, pp.28778-28790, 2019
proximation, normal data distribution, [26] M. Pompili and F. Scatiggio,
etc., are inbuilt in this model to auto- Classification in Iso-Attention Classes [31] B. Sparling et al., Condition As-
matically process data and perform data of HV Transformer Fleets, IEEE Trans. sessment Methodology for Transform-
quality checks. The “expert system” raises Dielectrics and Elec. Ins, pp. 2676–2683, ers & Components, TechCon SE Asia,
flags for either causes or components 2015 2019
responsible for the causes. Based on the
causes or components, replacement or
refurbishment scores are calculated.
Authors
Bhaba P. Das is the Lead Digital Business Developer for
Conclusion Transformers Business Line, HUB (Asia-Pacific, Middle
The paper has presented a critical review East and Africa), ABB Power Grids, based in Singapore. He
of the limitations of weighting and scor- is part of the Application Engineering Team and spearheads
ing concept of the transformer health in- the digital transformation efforts of transformers in the Asia
dexing. This approach fails to maintain Pacific region. Prior to ABB Power Grids, he worked as the
the functionality of the transformer as a R&D engineer for a major transformer manufacturer in New
whole system and fails to identify indi- Zealand. He was awarded the Young Engineer of the Year
vidual components which are required 2017 by the Electricity Engineers Association of New Zealand for his work on the
for maintaining the overall transformer design and development of smart distribution transformers, fibre optics-based
functionality. Limitations of the tradi- sensors for transformers, and diagnostic software for fleet condition monitoring.
tional health index system are clearly He is a Senior Member of IEEE and Young Professional of IEC. He completed his
demonstrated. The need for a new index PhD in Electrical Engineering from the University of Canterbury, New Zealand.
which is based on the philosophy of re-
liability centred maintenance is clearly
Luiz Cheim joined ABB TRES North America in Au-
identified. A discussion on future assess-
gust 2009 as a consulting R&D engineer to support the
ment model is presented, which address-
Transformer Condition Assessment program through
es problems of the traditional health in-
advanced dissolved gas analysis, transformer aging ana-
dex system.
lytical tools, as well as online monitoring and diagnostic
systems. Cheim is part of an ABB global R&D organiza-
Bibliography tion that works on the development of those tools to sup-
port the customer’s efforts in maintaining critical assets
[23] W. Wattakapaiboon et al., The New through the new Smart Grid Initiatives. Cheim has been an active member
Developed Health Index for Trans- of CIGRÉ Paris since 1984, having acted as chairman of the Study Committee
former Condition Assessment, IEEE A2-Transformers in Brazil from 2000 to 2006. Cheim was awarded the title
International Conference on Condition CIGRÉ Distinguished Member and also given the Outstanding Contribution
Monitoring and Diagnosis (CMD), pp Award by the CIGRÉ Technical Committee, Paris, in 2006. Cheim is an active
32-35, 2016 member of the IEEE Transformer Committee and holds a PhD in electrical
electronic engineering from the University of Nottingham, UK, as well as an
[24] Y. Ghazali, TNB Experience in MSc and BSc in electrical electronic engineering from the Federal University
condition assessment and life manage- of Rio de Janeiro, Brazil.
ment of distribution power transform-
www.transformers-magazine.com/publish-with-us.html
COLUMN
ABSTRACT
DGA plays a vital role in the diagnos-
tics and maintenance of the trans-
formers. It is a multidisciplinary and
complex field that is not easy to
master. That is the reason why this
article is oriented to explaining the
learning and understanding the pro-
cess associated with DGA.
KEYWORDS
basics, DGA, diagnostics, gasses, oil,
principles
66
66 TRANSFORMERS MAGAZINE | Volume 8, Issue 1 | 2021
Marius GRISARU
Basic principles
of DGA - Part II
Learning, using, and creating your own view on DGA
Limits values for DGA tests and process for DGA interpretation. Using course, the challenge is inversely pro-
such general limits or normal or cut- portional to the size of the database. The
results
off values may lead to substantial pricey constrains of data securities imply mini-
The exact specification for DGA is consequences. mum size databases, and therefore more
something that all transformer users, extensive efforts to develop such kind of
managers, specific DGA software man- In this essential aspect, a new version of limits.
ufactures, online devices producers, and IEEE C57.107 [9] published the 90 % ap-
all the industry are looking for. For other proach of limits value, shown in Table 1. The countenance of these difficulties
oil test types, it is a usual behaviour to also comes into view from the new CI-
refer the measured value to the relevant This approach was previously present- GRÉ WG approach, as shown in Table
limit from the corresponding guide or ed in CIGRÉ WG on DGA [11] and is a 2. The selected values for two options of
standard. Having limits like for dissipa- significant step forward to improve the database size emphasise the importance
tion factor or oil acidity does not work uniqueness of the DGA limits values. of these selections and the meaning of
for DGA. It is probably the key obsta- the relation between the database size
cle for DGA manual or software-based The readers will be able to understand and the 90 % computed value.
diagnosis. The hard challenge here be- and exercise this statistical approach for
comes selecting values that represent the DGA limits. Even if it may seem simple An additional important factor that
specific equipment in the light of new to calculate a 90 % statistical limit, it is CIGRÉ BT 771 introduces and the em-
developments and knowledge, and also not a straightforward statistical calcu- phases is the fault severity and gas appa-
considering the maintenance policy of lation. The ones who need to compute rition. Here again, the unimportance of
the transformer owner. Adopting the are demanded to select different op- hydrogen is notable from Table 3. This
published and already processed value is tions from the primary and extensive gas appears in a minority of cases, and
an excellent stage for the initial learning database to the specific 90 % limits. Of even then, it indicates non-severe faults.
Note 1 - Table 1 assumes that no previous tests on the transformer for dissolved gas analysis have been made, or that no
recent history exists. If a previous analysis exists, it should be reviewed to determine if the situation is stable or unstable. Refer
to 6.5.2 for appropriate action(s) to be taken.
Note 2 - An ASTM round-robin indicated variability in gas analysis between labs. This should be considered when having gas
analysis made by different labs.
• TDCG – total dissolved combustion gas
w w w . t ra n sfo r m e r s - m a g a z i n e . co m 67
COLUMN
Table 2. Typical values of gas concentrations in the database of the WG and IEC 60599 [12]
Database of WG47 Number
Typical values in of DGA H2 CH4 C 2H 2 C 2H 4 C 2H 6 CO CO2
ppm results
The laboratory DGA tests are usually the in a specialised laboratory are, in most
cases, superior to the best available DGA
preferred choice compared to an online online monitor. In many circumstances,
the laboratory DGA tests are the preferred
DGA device since its efficiency and capabil- choice, not just because of their substan-
ities, in most cases, are superior to the best tial low cost compared to an online DGA
device. Some users unjustifiably abandon
available DGA online monitor all offline DGA performed in a monitored
lab after installing an online DGA device.
From this, Table 3 shows it is evident that CIGRÉ Technical Brochure 783 de- The comparison of performance DGA
the same gas may be sourced from differ- scribes the effectiveness of the number in laboratories versus online DGA is also
ent insulating materials, liquid (oil) and of gases for the online detector device elaborated in the last CIGRÉ brochure.
cellulose, and may indicate various phe- related to fault capability detection. Ta- Table 5 presents the developments in
nomena with totally different severity. In ble 4 shows the relevant table from this DGA analytical performances by those
addition to the different materials, the lo- brochure. two options in the previous 20 years.
cation of gas sources inside the transform-
er may also have a significant impact on Evidently, the costs of the online monitors In the last two decades, most of the labo-
the accurate diagnosis. highly depend on the number of the gases ratories have switched to a much hastier
detected, and therefore to the capability to DGA method, but with lower accuracy,
The readers will be able to realise and dis- detect the transformer internal faults. The repeatability, and dependability on much
cern among those options. efficiency and capabilities for offline DGA more factors. The influence of switching
Main products
Type: Main products formed Severity Severity
formed
D2 Very High
C, C2H2 C2H2, C
D2 Very High
Moderate
T3 C, C2H4, C 2H 4, C
M2 H2, CO
-may not detect
Fault faults D1, D2 in their
-none of the 10 faults
Detection M1 H2 early stages, only in
can be identified
their late, sometimes
Composite reading of catastrophic stages.
M1*
H2 and others gases
Table 5a. The accuracies of DGA methods through the methods and ages [13]
Method > 100 ppm < 8 ppm > 100 ppm < 8 ppm
A – Partial degassing 12 18 17 0
B – Stripping 19 65 60 63
C – Headspace 28 51 75 42
Accuracy of laboratories using gas extractions methods: A - Partial degassing, B - Stripping, C- Headspace
Table 5b. The accuracies of DGA online monitors through the ages [13]
w w w . t ra n sfo r m e r s - m a g a z i n e . co m 69
COLUMN
Table 6. Early DGA diagnosis method based on the gas ratio [14]
< 0.3 0 0 0 0 1
10 ≥ 2 3 1 3 2
Normal ageing of
0 0 0 0 0
insulant
Discharge of high
2 1 1 2/3 1
energy
Successful prediction in %
23-50 45-100 50-100 23-82
by Ref 19 *
Successful prediction in %
76.24 85.15 91.09 69.31
by Ref 20
*Different faults possess different successful prediction values
w w w . t ra n sfo r m e r s - m a g a z i n e . co m 71
DESIGN
ABSTRACT
Computer-aided
transformer
It is known that the deployment of
highly efficient power transformers is
crucial for the minimization of overall
network losses. Hence, the curricu-
lum of an elective senior-level course
was developed for Cairo University
students. This curriculum was de-
design capacity
building
veloped by industrially experienced
faculty members to mimic typical
tasks encountered by power trans-
former manufacturers. In addition to
classical methodologies, the course A sample industry-oriented senior level
offers students hands-on experience
in relevant finite-element analysis university course
tools and newly introduced artificial ing the value added in national industries.
intelligence techniques. Examples of
1. Introduction
Within the aforementioned context, a
student-developed design software Power transformers are considered curriculum of an elective senior-level
packages are given. It is evident that among the most important components course was developed a few years ago for
linking the course content to actual in any power network. Obviously, deploy- Cairo University Power Engineering stu-
real-life industrial scenarios results ment of highly efficient power transform- dents. Unlike traditional courses covering
in outstanding student performance. er units is indispensable for minimization the same topic, the curriculum was devel-
of overall network losses. While most of oped by industrially experienced faculty
the relevant power engineering curricu- members to mimic typical tasks encoun-
KEYWORDS la focus on power transformer operation tered in design and research and develop-
and maintenance technicalities, availabil- ment (R&D) offices of power transformer
artificial intelligence techniques, ity of design methodologies know-how is manufacturers. It should be mentioned
computer-aided design, design crucial to fulfilling national and regional that, in addition to power transformer de-
optimization, transformer design transformer manufacturers’ job needs as sign methodologies, the aforementioned
methodologies well as to support efforts aiming at boost- course is entitled: “Computer-Aided De-
Availability of design
methodologies know-
how is crucial to fulfill-
ing transformer manu-
facturers’ job needs as
well as to support ef-
forts aiming at boosting
the value added in na-
tional industries
sign (CAD) of Electrical Machines” and In other words, the course objectives tend Aside from covering all basics related to
also exposing students to design method- to help potential power transformer de- power transformer materials, the theory
ologies related to fractional horse-power sign engineers acquire necessary technical of operation and effect of the properties
(HP) induction motors (i.e., ratings less or capacity relevant to the industry as well as of every single component on the opera-
equal to 1 HP) [1]. The unique nature of to give them a flavour of what design chal- tion performance [1], a recently compiled
the course curriculum and teaching strat- lenges should be expected in real life. specifications-oriented design methodol-
egies with regards to power transformers ogy is mainly adopted [6]. According to
design mechanism are discussed in the 2.1 Specifications-oriented power this methodology, the main specification
following sections. transformers design approach requirements may be directly correlated
to four main design parameters. More
In real-life situations, whether a sophis- specifically, the Volt-Ampere Rating (S),
2. Course objectives and
ticated Finite Element Analysis (FEA) the overall ohmic Copper Losses (Pcu),
teaching methodologies transformer design software tool or a the ohmic No Load Losses (Pnl), and the
The main objectives of the course under simplistic analytical design approach is ohmic Reactance per Phase (X) may be
consideration are: adopted, the main challenge is to identi- correlated to the Window Height (Hw),
fy the detailed design specifics that would the Limb Diameter (D), the maximum
• to make students acquainted with the result in fulfilling a set of required speci- Core Flux Density (Bc), and the average
materials and theories related to speci- fications at the minimum possible cost conductors’ Current Density (J) in accor-
fications-oriented transformers design, (refer, for instance, to [4, 5]). Obviously, dance with the following equations:
• to give students hands-on experience the trade-off for using a simplistic analyt-
with some CAD tools currently used at ical design approach is the involvement of S = C1 f1(J, Bc, D, Hw) (1)
R&D and / or design offices of power safety factors to guarantee fulfilment of Pcu =C2 f2(J, D, Hw) (2)
transformer manufacturers (see, for the required specifications at the expense Pnl =C3 f3(Bc, D, Hw) (3)
example, [2, 3]), of uncertainty in achieving the minimum X = C4 f4(J, D, Hw) (4)
• to introduce students to typical opti-
mization and / or cost reduction chal-
lenges encountered by manufacturers.
It should be mentioned here that op- It is extremely important to give students
timization reduces to minimum both
the construction and running costs hands-on experience with some CAD tools
which are usually achieved by fulfilling currently used at R&D and / or design offices
the required design specifications yet
competing pricewise in sales tenders. of power transformer manufacturers
w w w . t ra n sfo r m e r s - m a g a z i n e . co m 73
DESIGN
In the era of the fourth industrial revolution and semester were subdivided into 22 differ-
ent groups. It should be mentioned that
its far-reaching consequences it is extremely the course topic proved to be appealing
important to expose students to non-tradition- to students interests since the registered
students represented 70 % of the total final
al artificial intelligence (AI) transformer design year students despite the fact that two oth-
techniques er elective courses were offered. Different
mini projects were assigned to the student
groups, where more than one group was
assigned the same project. This was espe-
In (1)-(4), C1, C2, C3 and C4 represent cross-sectional area within a given wind- cially important to highlight the possibili-
equation constants which take into ac- ing inner diameter. ty of adopting different optimization logic
count other design parameters such as: and / or design methodologies to achieve
frequency, voltages, winding connections, Students were also exposed to free student the same ultimate goal. All mini projects
window space factor, steel core stacking version two-dimensional (2D) FEA pack- involved the development of a software
factor, conductor resistivity, copper and ages [2, 3]. This was especially important tool equipped with a user-friendly GUI.
steel densities and specific core losses to give them a head start in comprehend- A very brief listing of some of those mini
(please refer to [6]). ing mathematical basics and limitations of projects, which had to be accomplished
such packages as well as to introduce them within a month duration, is given below:
Obviously, several approaches may be to how more sophisticated FEA packages
taken to solve the above four equations to may be well utilized within power trans- • Development of a software package
directly meet the main operating specifi- former manufacturer plants to further re- that can maximize the transformer
cations. More specifically, equations may fine preliminary design details that lead to core cross-sectional area for 5, 7 and 9
be solved simultaneously or iteratively the ultimate minimization of production step steel lamination stacks,
to offer a very good initial detailed de- material and, consequently, cost. It should • Development of a software package
sign guess. There is no doubt that a solid be stated here that some assignments fo- capable of identifying the minimum
technical background of design limita- cused on using the FEA packages in the number of lamination stacks required
tions is required to sort out non-realistic assessment and visualization of stray fields to achieve a certain required stacking
solutions that may be a consequence of leading to eddy current losses in winding factor,
unachievable specifications requirements. top and bottom edges, something hard • Getting acquainted with a free student
Examples of such non-realistic solutions to convey without such tools. Such FEA version of a 2D electromagnetic FEA
may include a maximum core flux den- assignments focused on demonstrating package to construct an energized
sity (Bc) exceeding the saturation range that minimization of the previously men- power transformer having specific di-
of the utilized steel core magnetization tioned losses related to the transformer mensions and use the package to iden-
curve and / or practical current density of window height to width ratio. tify eddy current losses in winding edg-
copper windings. It should be stated that es as well as to plot leakage flux and flux
once the four unknowns are determined, Given the implications of the Fourth In- density distribution at central parts of
all other design specifics, such as the num- dustrial Revolution [7], it was also ex- the core limbs,
ber of turns and winding cross-sections, tremely important to expose students • Development of a transformer design
may be calculated from other parameter to non-traditional artificial intelligence FFANN capable of identifying design
inter-relations. (AI) design techniques. In line with this details corresponding to the required
mandate, feedforward artificial neural specifications, provided that these
2.2 Hands-on experience with networks (FFANN) were introduced, and specifications fall within extreme spec-
different CAD tools relevant to means of training and usage were cov- ification values of a given set of 20 dif-
transformer design ered. Some assignments involved using ferent transformers used for the neural
an FFANN with inputs and outputs con- network (NN) training purposes,
A considerable percentage of the course forming to the eight variables given in • Development of a transformer design
work grade was related to the development equations (1)-(4) to recommend design software package based on the taught
of friendly software packages equipped details for a given set of required specifi- specifications-oriented analytical
with graphical user interfaces (GUI) that cations [8]. Obviously, this was possible methodologies.
would support real-life activities carried by training the same FFANN using a set
out in transformer manufacturer design of top-quality power transformers having Clearly and as previously stated, such mini
and / or R&D divisions. different specifications and with known projects were carefully chosen to give the
design details. students a flavour of what they might en-
Typical programming assignments in- counter in case they join a transformer
cluded the development of software 2.3 Sample assignments and manufacturer design and / or R&D office.
packages offering fast design support student work
based on the previously discussed spec- An example of the delivered student mini
ifications-oriented analytical approach. In addition to a total of 45 contact hour projects is shown in the cover figure where
Other examples involved optimiza- lectures, and 15 contact hour tutorials, the number of core steel stacks and their
tion techniques to maximize gross core 112 students registered in the Spring 2020 dimensions relative to the winding inner
w w w . t ra n sfo r m e r s - m a g a z i n e . co m 75
DESIGN
Figure 2. Non-iterative automation of the analytical specifications-oriented transformer design approach where, for a set of required specifications as
shown in (a), it is possible to obtain detailed design details in addition to an account of how the quality of steel sheets material could affect those details (b).
Conclusion mini projects developed by the students reported in this article) as well as the sup-
suggest that adopting the aforementioned port of Dr. H. Hassan and Eng. A. Abbas
This article has highlighted the need for curricula results in boosting the students’ who participated in the teaching efforts.
developing transformer design curricula motivation. Tertiary and / or tap changers
reflecting real-life industrial design chal- windings are also planned in future ver-
Bibliography
lenges. On a quest for these capacity-build- sions of the course. The author would like
ing efforts, hands-on knowledge transfer to conclude this article by acknowledging [1] A. K. Sawhney, A course in electri-
related to electromagnetic software pack- the great work of all 112 students who en- cal machine design, Dhanpat Rai & Sons,
ages and newly introduced artificial intel- rolled in the reported Spring 2020 course Delhi, 1984
ligence approaches is a must. Outstanding (of which sample design tools have been
[2] QuickField simulation software by
Tera Analysis Ltd., www.quickfield.com
Expect outstanding work from students as a [3] D. C. Meeker, Finite Element Meth-
od Magnetics, Version 4.2 (28 Feb 2018
result of being motivated by linking the course Build), http://www.femm.info
content and assignment requirements to actu- [4] M. A. Tsili, A. G. Kladas, P. S. Geor-
al real-life industrial scenarios gilakis, Computer aided analysis and de-
w w w . t ra n sfo r m e r s - m a g a z i n e . co m 77
COLUMN
Standards
relevant to
transformers
– Part IV
BSI has more than 100 years of history in
covering standards for transformers which
make them pioneers in the field
ABSTRACT
Last three parts of this series covered
the evolution of Standards / Techni-
cal Brochures related to Power Trans-
formers under IEC, IEEE and CIGRE
and listed current standards issued
by them. Now we see the evolution
of transformer standards in Britain
and the current position of European
Standards (EN) on Transformers.
KEYWORDS
standards, transformers, BSI, BESA,
CENELEC
w w w . t ra n sfo r m e r s - m a g a z i n e . co m 79
COLUMN
First tentative British standard exclusively half a century, undergoing several re-
visions. Later, these British Standards
for transformers was issued in 1917 as were replaced by individual national
Specification No. 72 ‘Electrical Performance standards or IEC standards, as the col-
onies became independent countries.
of Transformers for Power and Lighting’ In 1961, there were nearly 40 British
standards relevant to power and dis-
tribution transformers.
HD 538.1 S1:1992/AC:2011 Three-phase dry-type distribution transformers 50 Hz, from 100 to 2500 kVA, with
1 highest voltage for equipment not exceeding 36 kV - Part 1: General requirements and
(pr=23795) requirements for transformers with highest voltage for equipment not exceeding 24 kV
EN 50195:1996
2 Code of practice for the safe use of fully enclosed askarel-filled electrical equipment
(pr=5740)
EN 50216-1:2002
3 Power transformer and reactor fittings - Part 1: General
(pr=4783)
EN 50216-2:2002 Power transformer and reactor fittings - Part 2: Gas and oil actuated relay for liquid
4
(pr=216) immersed transformers and reactors with conservator
EN 50216-2:2002/A1:2002 Power transformer and reactor fittings - Part 2: Gas and oil actuated relay for liquid
5
(pr=14853) immersed transformers and reactors with conservator
EN 50216-3:2002 Power transformer and reactor fittings - Part 3: Protective relay for hermetically
6
(pr=5601) sealed liquid-immersed transformers and reactors without gaseous cushion
EN 50216-3:2002/A2:2006 Power transformer and reactor fittings - Part 3: Protective relay for hermetically
7
(pr=20479) sealed liquid-immersed transformers and reactors without gaseous cushion
EN 50216-4:2015 Power transformer and reactor fittings - Part 4: Basic accessories (earthing terminal,
8
(pr=22810) drain and filling devices, thermometer pocket, wheel assembly)
EN 50216-5:2002/A2:2005/
Power transformer and reactor fittings - Part 5: Liquid level, pressure and flow indica-
9 corrigendum Oct. 2006 tors, pressure relief devices and dehydrating breathers
(pr=26210)
EN 50216-5:2002 Power transformer and reactor fittings - Part 5: Liquid level, pressure and flow indica-
10
(pr=11501) tors, pressure relief devices and dehydrating breathers
EN 50216-5:2002/A2:2005 Power transformer and reactor fittings - Part 5: Liquid level, pressure and flow indica-
11
(pr=14950) tors, pressure relief devices and dehydrating breathers
EN 50216-5:2002/A3:2006 Power transformer and reactor fittings - Part 5: Liquid level, pressure and flow indica-
12
(pr=20506) tors, pressure relief devices and dehydrating breathers
EN 50216-6:2002 Power transformer and reactor fittings - Part 6: Cooling equipment - Removable radi-
13
(pr=7656) ators for oil-immersed transformers
w w w . t ra n sfo r m e r s - m a g a z i n e . co m 81
COLUMN
14 EN 50216-7:2002 Power transformer and reactor fittings - Part 7: Electric pumps for transformer oil
(pr=4784)
EN 50216-8:2005 Power transformer and reactor fittings - Part 8: Butterfly valves for insulating liquid
15
(pr=14952) circuits
16 EN 50216-9:2009 Power transformer and reactor fittings - Part 9: Oil-to-water heat exchangers
(pr=15198)
17 EN 50216-10:2009 Power transformer and reactor fittings - Part 10: Oil-to-air heat exchangers
(pr=15199)
18 EN 50216-11:2008 Power transformer and reactor fittings - Part 11: Oil and winding temperature indicators
(pr=20505)
25 CLC/TR 50462:2008 Rules for the determination of uncertainties in the measurement of the losses on
(pr=15968) power transformers and reactors
Three-phase oil-immersed distribution transformers 50 Hz, from 50 kVA to 2 500 kVA with
26 EN 50464-2-1:2007 highest voltage for equipment not exceeding 36 kV - Part 2-1: Distribution transformers
(pr=14815) with cable boxes on the high-voltage and/or low-voltage side - General requirements
Three-phase oil-immersed distribution transformers 50 Hz, from 50 kVA to 2 500 kVA
EN 50464-2-2:2007 with highest voltage for equipment not exceeding 36 kV - Part 2-2: Distribution trans-
27
(pr=14816) formers with cable boxes on the high-voltage and / or low-voltage side - Cable boxes
type 1 for use on distribution transformers meeting the requirements of EN 50464-2-1
Three-phase oil-immersed distribution transformers 50 Hz, from 50 kVA to 2 500 kVA
EN 50464-2-3:2007 with highest voltage for equipment not exceeding 36 kV - Part 2-3: Distribution trans-
28 formers with cable boxes on the high-voltage and / or low-voltage side - Cable boxes
(pr=14817)
type 2 for use on distribution transformers meeting the requirements of EN 50464-2-1
29 EN 50588-1:2017 Medium power transformers 50 Hz, with highest voltage for equipment not exceeding
(pr=64220) 36 kV - Part 1: General requirements
Medium power transformers 50 Hz, with highest voltage for equipment not exceeding
EN 50588-2:2018 36 kV - Part 2: Transformers with cable boxes on the high-voltage and / or low-volt-
30
(pr=65066) age side - General requirements for transformers with rated power less than or equal
to 3 150 kVA
Medium power transformers 50 Hz, with highest voltage for equipment not exceeding
EN 50588-3:2018 36 kV - Part 3: Transformers with cable boxes on the high-voltage and / or low-volt-
31
(pr=65067) age side - Cable boxes type 1 for use on transformers meeting the requirements of
EN 50588-2
Medium power transformers 50 Hz, with highest voltage for equipment not exceeding
EN 50588-4:2018 36 kV - Part 4: Transformers with cable boxes on the high-voltage and / or low-volt-
32
(pr=65069) age side - Cable boxes type 2 for use on transformers meeting the requirements of
EN 50588-2
EN 50629:2015
33 Energy performance of large power transformers (Um > 36 kV or Sr ≥ 40 MVA)
(pr=25005)
51 EN 60076-14:2013 Power transformers - Part 14: Liquid-immersed power transformers using high-tem-
(pr=24171) perature insulation materials
52 EN 60076-16:2011 Power transformers - Part 16: Transformers for wind turbines applications
(pr=22613)
54 EN 60076-19:2015 Power transformers - Part 19: Rules for the determination of uncertainties in the mea-
(pr=58616) surement of the losses on power transformers and reactors
55 EN IEC 60076-22-1:2019 Power transformers - Part 22-1: Power transformer and reactor fittings – Protective
(pr=63125) devices
56 EN IEC 60076-22-2:2019 Power transformers - Part 22-2: Power transformer and reactor fittings - Removable
(pr=63126) radiators
57 EN IEC 60076-22-3:2019 Power transformers - Part 22-3: Power transformer and reactor fittings - Insulating
(pr=63127) liquid to air heat exchangers
58 EN IEC 60076-22-4:2019 Power transformers - Part 22-4: Power transformer and reactor fittings - Insulating
(pr=63128) liquid to water heat exchangers
59 EN IEC 60076-22-7:2020 Power transformers - Part 22-7: Power transformer and reactor fittings - Accessories
(pr=67592) and fittings
60 EN IEC 60076-24:2020 Power transformers - Part 24: Specification of voltage regulating distribution trans-
(pr=66214) formers (VRDT)
9 EN 50386-2010 (pr=21708) Bushings up to 1 kV and from 250 A to 5 kA, for liquid filled transformers
EN 50386:2010/A1:2013
10 Bushings up to 1 kV and from 250 A to 5 kA, for liquid filled transformers
(pr=23287)
11 EN 50387-2002 (pr=14940) Bus bar Bushings up to 1 kV, 1.25 kA – 5 kA, for liquid filled transformers
12 CLC/TS 50458:2006 (pr=3760) Capacitance graded outdoor bushing 52 kV up to 420 kV for oil immersed transformers
13 EN 50673:2019 (pr=63364) Plug-in type bushings for 72,5 kV with 630 A and 1,250 A for electrical equipment
EN 60137:2017/AC:2018-08
14 Insulated bushings for alternating voltages above 1,000 V
(pr=67231)
15 EN 60137:2017 (pr=62435) Insulated bushings for alternating voltages above 1,000 V
EN IEC/IEEE 65700-19-03:
16 Bushings for DC application
2018/AC:2019-03 (pr=69149)
EN IEC/IEEE 65700-19-
17 Bushings for DC application
03:2018 (pr=64163)
Note: Standards having IEC number designation after EN are adopted from IEC by CENELEC without modification as per IEC/CENELEC agreement.
transformers-academy.com
FLUIDS
w w w . t ra n sfo r m e r s - m a g a z i n e . co m 87
FLUIDS
w w w . t ra n sfo r m e r s - m a g a z i n e . co m 89
FLUIDS
Table 3. Meaning of the identifying letter codes in the ordering designation of mineral oil according to IEC 60296
Example 1. For order for inhibited high grade recycled oil for transformers: TRAI.
Example 2. For order for uninhibited unused oil for transformers: TVBU.
Example 3. For order for inhibited high-grade unused oil for switchgear: SVAI.
Example 4. For order for trace inhibited recycled oil for switchgear: SRBT.
Transformer 0 1,800 − 10
Transformer − 20 1,800 − 30
Transformer − 30 1,800 − 40
a
for low ambient temperature applications; in other cases, the value shall be discussed between the user and manufacturer
All mineral insulating oils are physically ties are summarised in Chapter 7 of IEC 12. Conclusion
miscible with each other and are consid- 60296 (Ed. 5). Such general properties are,
ered to result, after homogenisation, in a e.g., electrostatic charging tendency (ECT), With the items listed above, IEC 60296
single homogeneous phase and without gassing tendency, thermal properties, aro- (Ed. 5) gives better answers to the indus-
precipitation of insoluble substances, or matic content, lubricating properties, par- try and also addresses environmental and
formation of turbidity. The mixture, how- ticle content, etc. In case limit values are sustainability requirements.
ever, can show different properties from necessary for the correct functioning of
the original oils, for example, density, a certain type of equipment, these values
viscosity, total sulphur content, oxidation must be clarified and negotiated between
Bibliography
stability, or stray gassing. customer and manufacturer. [1] IEC 60296, Ed. 4.0, Fluids for electro-
technical applications – unused miner-
Mineral insulating oils of the same class al insulating oils for transformers and
and type, the same group, same LCSET, 11. Transformer oil equivalents switchgear, Ed. 4.0, 2012
and containing the same types of additives (informative, new, Annex D of
are considered to be compatible with each IEC 60296) [2] TOR-WG D1.70, Functional prop-
other in mixtures up to 10 % with no need erties of modern insulating liquids
for additional testing. For all known oil parameters there are for transformers and similar electri-
standards for measuring as well as in the cal equipment, https://www.cigre.org/
If oils of a different class, type, group, ASTM and in the IEC world. Some of userfiles/files/News/2018/TOR_WG_
LCSET, or type of additives are mixed, the them deliver the same values, and some of D1_70_Functional_properties_of_mod-
resulting mixture shall be classified and them do not. It is sometimes difficult for a ern_insulating_liquids_for_transform-
tested according to Table 1 and Table 2. user to carry out an evaluation and com- ers_and_similar_electrical_equipment.
parison between results achieved with dif- pdf, current 4 September 2020
ferent standards.
10. General properties [3] IEC 60076-7, Power Transformers.
Of course, there are further mineral oil Annex D is the first attempt to provide Part 7: Loading Guide for mineral oil
properties, which can be of importance, but guidance on standard measuring procedure immersed power transformers, Ed. 2.0,
no general limit values exist. These proper- equivalents, based on equivalency of results. 2018
w w w . t ra n sfo r m e r s - m a g a z i n e . co m 91
COLUMN
ABSTRACT
German literature on power trans-
Books on power
transformers in
formers is covered from 1888 (first
book on transformers published any-
where, just three years after patent
German – Part II
ing transformers), up to most recent
publications issued in 2019. The pur-
pose of the compilation of published
books on power transformers is to
give a historical summary on the top-
ic, which may also be useful to other A bibliography 1920 – 1951
specialists in their research.
H. Kyser, Die elektrische Kraftuber- This book has survived 15 editions and Pages 702, 1921; Ed. 2.0, Pages 751,1925;
tragung, Band 1, Die Motoren, Um- a few reprints. At first it was a guide for Ed. 3.0, Birkhäuser, Basel, Pages 630,
former und Transformatoren (The manufacturing windings for electri- 1956
electric power transmission, Volume 1, cal machines and transformers. Then
The motors, converters and transform- the book was repeatedly expanded in In this book, a famous engineer, scien-
ers), Springer, Berlin, Pages 416, 1920; the direction of increasing the volume tist and chess player, Prof. Milan Wid-
Ed. 2.0, Pages 548, 1923; Ed. 3.0, Pages of repairs, adding faults, testing, and mar (1885–1962), outlines the basics
544, 1930 monitoring. At the same time, the title of designing and constructing power
of the book was changed, and its cov- transformers. The fundamental princi-
F. Raskop, Der Katechismus für die erage naturally expanded. In the bib- ples presented in it remain valid even
Ankerwickelei (The Catechism for an- liography, we have combined all avail- today, despite the development of the
chor winding), Meusser, Berlin, Pages able publications under the popular theory, great progress in the proper-
VIII+145, 1920; Ed. 2.0, 1922; Ed. 3.0, short historical name The Catechism ties of materials, technology, growth
1929; Ed. 4.0, M. Krayn, Berlin, Pages for anchor winding. Other books by in ultimate power and voltage classes,
224, 1933; Ed. 5.0, Pages VII+241, 1937; the author are indicated in the bib- and automation of the design pro-
Ed. 6.0, Pages XII+287, 1941; Ed. 8.0, De liography for 1929, 1938 and 1948. cess. The book has withstood many
Gruyter, Berlin, Pages XII+299, 1944;
editions and has been translated into
Ed. 10.0, Pages XI+416, 1951 and Re-
many languages. Other books by the
print 2019; Ed. 11.0, Pages 472, 1953; 1921 author are indicated in the bibliogra-
Ed. 12.0, Pages 516, 1957; Ed. 13.0, Pag-
phy for 1927, 1928, 1935, 1940 and
es 616, 1964; Ed. 14.0, 1967 and Reprint Milan Vidmar, Die Transformatoren
1945.
2019; Ed. 15.0, Pages 503, 1976 [28, 29] (The transformers), Springer, Berlin,
w w w . t ra n sfo r m e r s - m a g a z i n e . co m 93
COLUMN
w w w . t ra n sfo r m e r s - m a g a z i n e . co m 95
COLUMN
also be useful to other specialists in their Karl Muttersbach, Feststellung und Be-
research seitigung von Fehlern an elektrischen
Maschinen Transformatoren und
Geräten (Detection and elimination of
faults in electrical machines, transformers
1938 transformers List T I. Edition 1939), Koch and devices), Ed.4.0, Fachverlag, Frank-
& Sterzel, Dresden, Pages 40, 1939 furt, Pages 158, 1949
Karl Bolte, Rudolf Kuchler, Transforma-
toren mit Stufenregelung unter Last: Wilhelm Schäfer, Transformatoren, Rudolf Richter, Kurzes Lehrbuch der
Theorie, Aufbau, Anwendung (Trans- Sammlung Göschen Band 952 (Trans- Elektrischen Maschinen (Short textbook
formers with On-Load Tap-Changers: formers, Göschen Collection Volume on electrical machines), Springer, Berlin,
Theory, construction and application), 952), de Gruyter, Berlin, Pages 127, 1939; Pages 400, 1949
R. Oldenbourg, Munchen-Berlin, Pages Ed.2.0, 1949
182, 1938 1950
1940
Paul - Eduard Klein, Transformatoren W. Kehse, Handbuch des Transforma-
und Drosseln: Theorie, Bau und Berech- Milan Vidmar, Transformatoren - torenbaus (Manual of transformer con-
nung (Transformers with On-Load Kurzschluse, Sammlung Vieweg 118 struction), Enke, Stuttgart, Pages 380,
Tap-Changers: theory, construction, ap- (Transformers – under short circuit, 1950
plication), Ed. 2.0, J. Schneider, Berlin, Vieweg 118 collection), Braunschweig,
Pages 88, 1934; Ed. 3.0, Pages 128, 1938 Pages 136, 1940; Ed. 2.0, 1954 Franz Unger, Bemessung von Trans
formatoren (Dimensioning of transform-
Fritz Raskop, Isolierlacke, deren Eigen- 1944 ers), Wang Chong, Shanghai / China, Pag-
schaften und Anwendung in der Elek- es 28, 1950
trotechnik, insbesondere im Elektro- G. Haberland, Wechselstrommaschinen.
maschinen- und Transformatorenbau Transformatoren und Stromrichter. (AC 1951
(Insulating varnishes, their properties machines. Transformers and converters.),
and application in electrical engineering, M. Janecke, Leipzig, Pages 191, 1944 Adalbert Varduhn, Walter Nell, Hand-
especially in electrical machine and trans- buch der Elektrotechnik, Band 1, Grun-
former construction), Krayn, Berlin, Pag- 1945 dlagen der Elektrotechnik, Elektrische
es VII+132, 1938 Maschinen, Transformatoren, Strom-
Milan Vidmar, Transformazion und En- richter, Kondensatoren, Akkumulatoren
Friedrich Riepenber, Praktische Anlei- ergieubertragung (Transformation and (Manual of electrical engineering, Volume
tung zur Instandsetzung von Elektro- energy transfer), Kleinmeyer u. Bamberg, 1, Basics of electrical engineering, electri-
maschinen und Transformatoren sowie Laibach, Pages 754, 1945 cal machines, transformers, converters,
zur Herstellung von Elektromaschinen-
wicklungen und Transformatorenwick- 1948
lungen (Practical instructions for the
repair of electrical machines and trans- Herbert Kunze, Netz- und Kleintransfor-
formers as well as for the production of matoren (Large and small transformers),
electrical machine windings and trans- Deutscher Funk-Verlag, Berlin, Pages 40,
former windings), F. Klett, Berlin, Pages 1948 [44-46]
175, 1938; Pages 192, 1940; Ed. 5.0, Pages
182, 1947 [43] Fritz Raskop, Das Elektromaschinen-
bauer-Handwerk. Instandsetzung,
1939 Neuwicklung und Umbau elektrischer
Maschinen, Transformatoren und Ap-
Richard Elsner, Zur Theorie des schwi- parate. (The electrical engineering trade.
ngungsfreien Drehstromtransformators Repair, new development, and conversion
(The theory of the vibration-free three- of electrical machines, transformers and
phase transformer), Special print from apparatus.), Ed.2.0, Cram, Berlin, Pages
Springer, Berlin, Pages 23, 1939 384, 1948; Ed.3.0, 1949 [47,48]
Niederspannungs-Transformatoren 1949
Liste T I. Ausgabe 1939 (Low voltage Figure 3. Handbuch der Elektrotechnik,
J. Friedrich, H. Kroncke, Der zerlegbare Adalbert Varduhn and Walter Nell
[31] https://www.booklooker.de/B%C3%
BCcher/Angebote/titel=Zur+Kenntnis
+von+Transformatoren%C3%B6l+
Dissertation, current on 7 May, 2020 Authors
Vitaly Gurin graduated from Kharkov Polytechnic
[32] https://www.abebooks.de/servlet/ Institute (1962) and graduate school at the Leningrad
SearchResults?an=wotruba%20rudolf Polytechnic Institute. Candidate of technical sciences
&cm_sp=det-_-bdp-_-author, current on in the Soviet scientific system (1970). For 30 years he
7 May, 2020 tested transformers up to 1.150 kV at ZTZ, including
the largest one of that time in Europe, and statistically
[33] https://www.google.com.ua/search? analysed the test results. For over 25 years he was the Ex-
hl=uk&tbo=p&tbm=bks&q=inauthor:%22 ecutive Director of Trafoservis Joint-Stock Company in
Rudolf+Wotruba%22, current on 7 May, Sofia (the diagnosis, repair and modernisation in the operating conditions
2020 of transformers 20 – 750 kV). He has authored about 150 publications in
Russian and Bulgarian, and is the main co-author of GOST 21023.
[34] https://www.google.com.ua/search?
h l=u k&tb o=p&tbm=bks&q=inau -
thor:%22Adalbert+Stifter%22, current on P. Ramachandran started his career in transformer in-
7 May, 2020 dustry in 1966 at TELK, Kerala, a Hitachi Joint venture,
in India. He worked with ABB India during 1999-2020.
[35] https://www.zvab.com/servlet/Search He has more than 50 years of experience in the design
Results?an=roller%20ernst%20pricks%20 and engineering of power products including power
helmut&cm_sp=det-_-bdp-_-author, transformers, bushings, and tap-changers. He received
current on 7 May, 2020 Bachelor of Science Degree in Electrical Engineering
from the University of Kerala, India, and Master of Busi-
[36] https://www.springer.com/gp/book/ ness Administration Degree from Cochin University, India. He is a Fellow of
9783662002520, current on 7 May, 2020 Institution of Engineers (India), and he represented India in CIGRE Study
Committee A2 for transformers during 2002 – 2010.
[37] https://www.zvab.com/177-Schaltbild
w w w . t ra n sfo r m e r s - m a g a z i n e . co m 97
DIAGNOSTICS
ABSTRACT
Absorption Index (AI) remains valid
Absorption index
of insulation at
for old-aged unsealed transformers
as a simple and effective method of
non-destructive control insulation.
– Part I
condition and algorithm of the oper-
ating procedures are proposed de-
pending on the value of the measured
AI and its variation in time. Along with
AI, it is recommended to measure the
polarisation index (PI) and the PI-2
Old-aged transformers equipped with
(R600/R15 ratio). silica gel air breather
KEYWORDS vere problems in the power supply. The
Introduction
purpose of preventive testing is to de-
absorption index, cellulose insula- Transformers are the most important termine a runaway for the condition of
tion, insulation resistance, moisture, and most expensive equipment at a the complex system of the transformer
polarization index substation, and their failure leads to se- insulation from the initial state (at the
w w w . t ra n sfo r m e r s - m a g a z i n e . co m 99
DIAGNOSTICS
In the late 1940s and early 1950s, Sovi- expensive device is required to carry out
the measurements, and interpretation of
et specialists in the transformer field were DFRT results is much more complicated
discussing the suitable criterion for evalua- compared to AI.
w w w . t ra n sfo r m e r s - m a g a z i n e . co m 101
DIAGNOSTICS
By comparing the test data obtained after value off AI is correspondingly less than
when voltage is applied to the HV. This
the failure with the results of the previous hypothesis needs additional verification.
tests, it is possible to assume the nature of In practice, for comparison, it is required
to use the scheme (HV - LV or LV - HV)
the transformer failure that was in the previous test.
Table 2. Unit transformer T-8 (200 MVA 342 / 15.75 kV) Nevinnomysskaya TPP, Russia, manufactured by ZTZ in 1964
Transformer tem-
35 °С 45 °С
perature
R15, R60, R15, R60,
Test AI AI
MΩ MΩ MΩ MΩ
w w w . t ra n sfo r m e r s - m a g a z i n e . co m 103
DIAGNOSTICS
Table 3. Unit transformer Т-7 (200 MVA121/15.75 kV) Nevinnomysskaya TPP, Russia. [2] IEEE Guide for Diagnostic Field Test-
T manufactured by ZTZ in 1965 ing of Fluid-Filled Power Transform-
ers, Regulators, and Reactors, IEEE Std
Year 1965 1994 C57.152™-2013
Transformer [3] S. A. Gorodetsky, Application of the
46 °С 34 °С
temperature
absorption method to control the hu-
midity of the insulation of transformer
Test site Plant TPP
windings, Elektricheskija stanzii, No. 8,
1952
LV - HV 3,51 1,22
[4] Power transformers, Methods of
HV - tank 1,33 1,35 measuring dielectric insulation param-
eters, ST SEV 5266-85
[7] V.J. Filippishin, A.S. Tutkevich, Instal- librium-and-moisture-migration-with- Bulgarian energy facilities, Energetika,
lation of power transformers (Trans- in-transformer-insulation-systems, No. 5, 1997
former Series, Vol. 38), Energoizdat, current 2 September 2020
Moscow, 1981 (in Russian)_ http://pad- [15] Rules for the technical operation of
abum.com/d.php?id=220663 [13] A. Bogoev, et al., Diagnostics, re- power plants and networks, Energiya,
pair and extension of the service life Moskow, 1977
[8] SOU-N EE 20.302:2007, Norms for of power transformers. Experience of
testing electrical equipment, Kiev, https:// AEC “Kozloduy”, Energetika, No.7-8, [16] V. V. Gurin, M.R. Papazyan, A.S. Tutkev-
dbn.co.ua/load/normativ y/sou_n_ 1995 ich, The method of restoration of insulation
ee_20_302/61-1-0-1134, current 2 Sep- of oil-filled equipment (Метод за възстанов
tember 2020 [14] V. Gurin, K. Medarov, M. Papazyan, яване изоляцията на маслонаполнени
Trafoservice-AD experience in the di- електрос ъоружения), Patent of the
[9] IEEE Guide for Dielectric Frequency agnosis, repair and modernization of Republic of Bulgaria No. 63060, 03/03/2001,
Response Test, IEEE Std C57.161™-2018 15-400 kV transformers operating in Application No. 101592, 06/11/1997
w w w . t ra n sfo r m e r s - m a g a z i n e . co m 105
DIAGNOSTICS
Measurement, localisation,
and monitoring of partial
discharges on a power
transformer
Introduction
ABSTRACT after onsite installation, and are used as a
Power transformers, a vital element of the tool for condition-based maintenance for
A partial discharge measurement is electrical grid, are subjected to different matured assets.
a sensitive tool to assess the insula- levels of electrical, thermal, mechanical,
tion integrity of a high voltage appara- and chemical stress during service. To PD is a local electrical breakdown of a
tus. This article discusses measure- ensure reliable and safe operation, it is weak region within the electrical insula-
ments, localisation and monitoring of critical to continuously assess the ageing tion system, resulting in fast current im-
partial discharges on a power trans-
of the system insulation during a trans- pulses. These electrical signals are often
former’s life cycle. Partial discharge (PD) accompanied by other physical effects,
former after transportation.
measurements are a non-destructive tool such as pressure waves, electromagnetic
which allows for measurement, assess- signals, chemical effects or optical effects
KEYWORDS ment, and localisation of weak spots in [1]. PD measurements of the different ef-
complex insulation systems. PD measure- fects using conventional and unconven-
measurement, monitoring, partial ments on power transformers are typical- tional tools and combining the findings
discharges (PD), PD localisation, ly carried out during the manufacturing will lead to a more meaningful assess-
transformer, trending process as a part of quality assurance, ment.
PD is a local electrical
breakdown of a weak re-
gion within the electrical
insulation system, re-
sulting in a fast burst of
the current impulses
Figure 1. View of the 300 MVA transformer Figure 2. Setup for PD measurements on phases 1U and 1V
w w w . t ra n sfo r m e r s - m a g a z i n e . co m 107
DIAGNOSTICS
Acoustic PD measurement
and localisation
The localisation of PD sources is per-
formed by means of differences in the
runtime of the acoustic signal between
the fault location and multiple acous-
tic emission (AE) sensors. Possible fault
locations are calculated from the signal
runtimes, using the speed of sound and
the known geometrical positions of the
Figure 4. Artificial impulse injected directly at the bushing tap sensors on the tank wall.
Figure 6. MPD Suite software; logarithmic-bipolar view of the PRPD pattern at 1U, the trigger window and corresponding time and frequency signal
w w w . t ra n sfo r m e r s - m a g a z i n e . co m 109
DIAGNOSTICS
Figure 7. Acoustic signals without averaging (left) and the averaging of 100 events (right) using the electrical signal as the trigger
w w w . t ra n sfo r m e r s - m a g a z i n e . co m 111
DIAGNOSTICS
Dissolved Gas Analysis (DGA) insulation part does not necessarily lead to formers are often only triggered by DGA
an increase of dissolved gases. results. The case study on the 300 MVA
The DGA results before and after the trans- transformer highlights that an electri-
portation did not indicate any failure or cal PD measurement and trending can
Conclusion
PD activity. Hydrogen slightly increased be more sensitive and instantaneously
during operation, but the overall amount In this article, the importance of electri- compared to the analysis of dissolved
of dissolved gases were below typical val- cal PD measurement, localisation, mon- gases in the oil. Analysing the unfiltered
ues, thus no reliable assessment could be itoring and trending is discussed. Onsite signals in time and frequency domain as
performed [4]. A local defect inside a solid PD measurements on liquid-filled trans- well as performing acoustical PD locali-
Figure 14. 3PARD filtered PRPD pattern and development of the pattern obtained during Phase 1V
The case study on the 300 MVA transformer highlights that an electrical
PD measurement and trending can be more sensitive and instantaneously
compared to the analysis of dissolved gases in the oil
sation with three or more piezo sensors
can provide valuable information when Authors
it comes to localisation, interpretation Udo Ranninger started working for OMICRON
and risk assessment. The transformer, electronics in 2007. He is currently working as an
with active but stable discharges in two application engineer focusing on partial discharge
phases, remains online and is further measurements after having had several different positions
monitored. in the company. He graduated from the Institute of
Higher Technical Education in Rankweil (Austria) in
2006, where he specialised in telecommunications and
Bibliography high-frequency technology.
[1] CIGRÉ WG D1.29, Technical Bro- udo.ranninger@omicronenergy.com
chure 676: Partial Discharges in Trans-
formers
Michael Krüger has worked with OMICRON Energy
[2] IEC 60270: Edition 3.1, 2015, in Klaus, Austria since 1999. After working as a product
High-voltage test techniques - Partial manager and head of engineering services, he is now a
discharge measurements, International consulting engineer for “Testing and Diagnosis of Electric
Electrotechnical Commission, Geneva, Power Equipment”. He studied electrical engineering at the
Switzerland Technical University of Aachen (RWTH), the Technical
University of Kaiserslautern (Germany) and graduated in
[3] C57.127 (2007), IEEE Guide for the 1976 (Dipl.-Ing.). In 1990 he received his PhD in electrical
Detection and Location of Acoustic engineering from the Technical University of Vienna.
Emissions from Partial Discharges in Michael Krüger has more than 40 years of experience in high-voltage
Oil-Immersed Power Transformers and engineering and testing and diagnosis on power and instrument transformers,
Reactors, The Institute of Electrical and rotating electrical machines, gas-insulated switchgear (GIS) and power cables.
Electronics Engineers, Inc. New York, He has published over 50 technical papers about electrical measurement on
USA, 2007 power and instrument transformers, rotating electrical machines, GIS and
cables, and holds 15 patents. He has been a member of VDE for 40 years, Cigre
[4] IEC 60599: Edition 3.0, 2015, Mineral and is a Senior Member of IEEE. He also works in several working groups of
oil-filled electrical equipment in service OEVE, IEC and Cigre.
– Guidance on the interpretation of dis- michael.krueger@omicronenergy.com
solved and free gases analysis
w w w . t ra n sfo r m e r s - m a g a z i n e . co m 113
DIAGNOSTICS
w w w . t ra n sfo r m e r s - m a g a z i n e . co m 115
DIAGNOSTICS
1 Good Dyn1 -2012 Electric Power Service 12.5 MVA, 34.5 / 13.8 kV
YNa0d1-1971
Fault on LV 33 MVA, 230 / 99.4 kV
H-X
1) ∆25Hz = 0.023 %
2) SFRA ratio is reasonably close to NP
ratio. The expected ∆25Hz is within
± 0.5 %.
3) No fault detected
1) ∆25 Hz = 0.095 %
2) SFRA ratio is reasonably close to NP
ratio.
3) No fault detected
1) ∆25 Hz = 10.56 %
2) SFRA ratio values on each phase
drastically deviate from the NP ratio.
3) H3-X3 trace is higher than traces
of the other two phases, indicating
that fault is present in phase 3 of X
winding.
1) ∆25 Hz = 4.26 %
2) SFRA ratio values deviate from the
NP ratio.
3) H2-X2 trace is higher than traces for
the other two phases, indicating that
fault is present in the phase 2 of X
winding.
1) ∆25 Hz = 0.72 %
2) SFRA ratio is reasonably close to NP
ratio.
3) H1-X1 trace is lower than traces of
the other two phases, indicating that
fault is present in the phase 1 of H
winding.
1) ∆25 Hz = 19.52 %
2) SFRA ratio in phase 1 significantly
deviates from both the NP and SFRA
ratio values in other phases.
3) H1-X1 trace is higher than the traces
of the other two phases, indicating
that fault is present in the phase 1 of
X winding.
w w w . t ra n sfo r m e r s - m a g a z i n e . co m 119
DIAGNOSTICS
1) ∆25 Hz = 8.61 %
2) SFRA ratio in phase 1 significantly
deviates from both the NP and
SFRA ratio values in other phases.
3) H1-Y1 trace is higher than traces of
the other two phases, indicating that
fault is present in the phase 1 of Y
winding.
1) ∆25 Hz = 12.62 %
2) SFRA ratio in phase 1 deviates from
both the NP and SFRA ratio values
in other phases.
3) X1-Y1 trace is lower than traces
of the other two phases, indicating
that fault is present in the phase 1
of X winding. This suggests that X
winding has a higher percentage of
shorted turns than Y winding.
Publish with us
We invite authors to submit manuscripts by 28 February 2021.
Promote
Promote your products and services to the targeted audience through
this Special Edition. Find all details on our website or contact us.
www.transformers-magazine.com/contact-us.html
TRANSMISSION
& DISTRIBUTION
CRITICAL &
BACKUP POWER
SMART SOLUTIONS
RENEWABLE
ENERGY
ENERGY CONSUMPTION
& MANAGEMENT
OLTC Course
Water in
transformer course
Condition
assessment course
Transformer oil
course
celmetransformers.com
we make
transformers
RENEWABLE
BESS
RENEWABLE
PHOTOVOLTAIC / WIND
INDUSTRIAL
DISTRIBUTION