Professional Documents
Culture Documents
W6 - Lecture 6 (1) - 220418 - 123913
W6 - Lecture 6 (1) - 220418 - 123913
W6 - Lecture 6 (1) - 220418 - 123913
Per-unit quantities
In power system analysis, per unit (pu) system is used to express a physical variable as a
fraction of base or reference value. Per Unit (pu) is commonly used for the calculation of
voltage, current , impedance, and power in power flow and related calculations.
For circuits connected by the transformers, per unit system is particularly suitable. By
choosing suitable base kV for the circuits the per unit reactance remains the same, referred to
either side of the transformer.
This method is ideal for eliminate ideal transformers as circuit components since the typical
power system contains many transformers and this is non trivial saving
Sqrt (3) factor in the three phase circuit calculations is eliminated
Per Unit Conversion Procedure-Single Phase
In per unit notation, the physical quantity is expressed as a fraction of the reference value, i.e.
Per Unit value = actual value/base value in the same unit.
e.g. V(in per unit) = V(in kV) / V base (in kV)
base kVA1
Base current, A
base voltage, kVLN
Therefore, to change from per-unit impedance on a given base to per-unit impedance on a new
base, the following equation applies:
Example 2
The reactance of a generator is given as 0.25 per-unit based on the generator’s of 18 kV, 500
MVA. Find its per-unit reactance on a base of 20 kV, 100 MVA.
Base values for a transformer
Let
n1,n2 be the number of turns in primary and secondary winding respectively
Z1, Z2 be the primary and secondary winding impedance respectively
Then total impedance referred to primary
ZT1 = Z1 + (n1/n2)2 × Z2
and total impedance referred to secondary
ZT2 = Z2 + (n2/n1)2 × Z1 = (n2/n1)2 × ZT1
ignored)
Example 3
A single phase 9.6 kVA, 500 V / 1.5 kV transformer has an impedance of 1.302 Ω with respect to
primary side. Find its per-unit impedance with respect to primary and secondary sides.
J1 Ω J24 Ω J1 Ω
10 Ω
8∠ 00 KV ~Z
1:10 5:1
Example 4
82 (kV) 2
Z BLeft 0.64
100MVA
802 (kV) 2
Z BMiddle 64
100MVA
162 (kV) 2
Z BRight 2.56
100MVA
J1.56 Ω J0.375 Ω J0.39 Ω
3.91 Ω
8 ∠00 KV
~Z
Example 4
1.00
I 0.22 30.8 p.u. (not amps)
3.91 j 2.327
VL 1.00 0.22 30.8
p.u.
2
VL
SL *
VL I L 0.189 p.u.
Z
SG 1.00 0.2230.8 30.8p.u.
I
Example 4
To convert back to actual values just multiply the per
unit values by their per unit base
synchronous motors over 25-km transmission line having transformers at both ends. The motors, all rated 6.0 kV, 66
MVA and 50 MVA for M1 and M2, respectively. For both motors X” = 15%. The single phase transformer T1 is rated
150 MVA, 132/12 kV with leakage reactance of 12%. Transformer T2 is rated 132/6.6 kV, 40 MVA with leakage
reactance of 10%. Series reactance of the transmission line is 0.4 Ω/km. Draw the impedance diagram, with all
impedances marked in per-unit. Select the generator rating as base in the generator circuit.
Example 7
Example 7