TECHNICAL SPECIFICATION - LV POWER CABLE - Hyundai Engineering - WP-1 LINE Project - LSAG 25NOV2022

You might also like

Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 30

REQ No. : Ref. No.

: LSAG-22-PD2204020
User / Customer : Hyundai Engineering Page No. : 1 of 28
Title : WP-1 LINE Project
Manufacture : LSAG Cable Indonesia
Document Title :

Technical Specification for


LV Power Cable Flame Retardant Cat.C
Non Armoured
N2XY - 0.6/1(1.2)kV
(Cu/XLPE/PVC-FR)

Armoured
N2XR(Al)Y - 0.6/1(1.2)kV
(Cu/XLPE/AWA/PVC-FR) - 0.6/1(1.2)kV
N2XRY - 0.6/1(1.2)kV
(Cu/XLPE/SWA/PVC-FR) ) - 0.6/1(1.2)kV
N2XSRY - 0.6/1(1.2)kV
(Cu/XLPE/CTS/SWA/PVC-FR) ) - 0.6/1(1.2)kV
N2XCRY - 0.6/1(1.2)kV
(Cu/XLPE/CWS/CTS/SWA/PVC-FR) ) - 0.6/1(1.2)kV

0 30 May 2022 Original Issue Yanuar R Teguh S W.Y Jung


Rev. No. Date Descriptions Prepared By Reviewed By Approved By
1. SCOPE

1.1. This specification covers 0.6/1 (1.2) kV copper conductor, cross-linked polyethylene
insulated (XLPE) and PVC over sheathed armoured and non armoured power cable
generally in accordance with SNI IEC 60502-1 unless otherwise specified in this
specification.
1.2. The types of power cable included in this specification :

Cable description Cable type

0.6/1(1.2)kV Copper conductor, XLPE insulated,


Cu/XLPE/PVC FR Cat.C
PVC over sheathed cables Flame Retardant Cat.
(N2XY)
C

0.6/1(1.2)kV Copper conductor, XLPE insulated, Cu/XLPE/AWA/PVC FR Cat.C


Aluminum Wire armour, PVC over sheathed (N2XR(Al)Y)
cables Flame Retardant Cat. C

0.6/1(1.2)kV Copper conductor, XLPE insulated,


Cu/XLPE/SWA/PVC FR Cat.C
Steel Wire armour, PVC over sheathed cables
(N2XRY)
Flame Retardant Cat. C

0.6/1(1.2)kV Copper conductor, XLPE insulated,


Cu/XLPE/CTS/SWA/PVC FR Cat.C
Copper Tape screen, Steel Wire armour, PVC
(N2XSRY)
over sheathed cables Flame Retardant Cat. C

0.6/1(1.2)kV Copper conductor, XLPE insulated,


Cu/XLPE/CWS/CTS/SWA/PVC FR Cat.C
Copper Wire screen, Steel Wire armour, PVC
(N2XCRY)
over sheathed cables Flame Retardant Cat. C

2. REFERENCE STANDARDS

IEC 60228 : Conductors of insulated cables


SNI IEC 60502-1 : Power cables with extruded insulation and their accessories for rated
voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) - Part 1:
Cables for rated voltages from 1 kV (Um = 1,2 kV) up to 3 kV (Um = 3,6
kV)
IEC 60811 : Common test methods for insulating and sheathing materials of electric
cables
IEC 60332-3-24 : Test on electric and optical fibre cables under fire conditions (Cat.C)
SNI 0225 : 2011 : Persyaratan Umum Instalasi Listrik 2011

3. CONSTRUCTION AND MATERIAL

3.1. Conductor
The conductor shall be the plain annealed copper conductor complying with IEC 60228
(Class 2). The shape of conductor shall be round stranded for size under 16 sqmm,
compacted circular stranded for size 16 sqmm and above.
3.2. Insulation

TECHNICAL SPECIFICATION_LV POWER CABLE 2 of 28


The insulation shall be extruded layer of cross-linked polyethylene (XLPE) compound
complying with SNI IEC 60502-1.
The minimum thickness at any point shall not fall below 90% of the nominal value by
more than 0.1 mm.

3.3. Assembly and fillers (for multi-cores cable only).


The cores shall be laid up together and suitable direction. Where necessary, non-
hygroscopic filler may be used to give the completed cable substantially circular cross-
section with suitable binder tape

3.4. Inner sheath / Separation Sheath (for armour type)


The inner sheath shall be an extruded layer of black PVC complying with SNI IEC
60502-1.
The minimum thickness at any point shall not fall below the value given in the attached
1 till 5. by more than 20% + 0.2mm

3.5. Metallic Screen (for VSD cable N2XSRY or N2XCRY)


The metallic screen shall consist of one or more copper tapes or combination of copper
wire and copper tape(s).

3.6. Armoured
The armoured type of cable covered use aluminum round wire (AWA) for single core
cable and galvanized steel round wire armour (SWA) for multicore cable.
3.7. Over sheath
The over sheath shall be an extruded layer of black flame retardant PVC/ST2
compound with water penetration resistant comply to SNI IEC 60502-1. The minimum
thickness at any point shall not fall below the value given in the attached table 1. by
more than 20% + 0.2mm.

4. CORE IDENTIFICATION
Each core of cable shall be identified by color :
- 1 cores : Black
- 2 cores : Brown – Black
- 2 cores with Ground (1P+N+G) : Brown – Black - Yellow w/ Green Stripe
- 3 cores : Brown - Black - Grey
- 3 cores with Ground (3P+G) : Brown - Black – Grey - Yellow w/ Green Stripe
- 3 cores with Ground (3P+3G) : Brown - Yellow w/ Green Stripe (1) - Black – Yellow w/
Green Stripe (2) - Grey - Yellow w/ Green Stripe (3)
- 4 cores (3P+N) : Brown - Black - Grey - Blue
- 4 cores with Ground (3P+G+N) : Brown - Black - Grey - Yellow w/ Green Stripe – Blue

5. TEST

The test shall be carried out in accordance with SNI IEC 60502-1 & IEC 60332-3-24. For
detail test will be inform in Inspection Test Plan (ITP) document.

TECHNICAL SPECIFICATION_LV POWER CABLE 3 of 28


6. MARKING

6.1. Cable Marking


The following legend shall be printed on the surface of over sheath throughout the
length of cable. Maximum interval between marking should not exceed 550 mm.
− Ref. standard no. : SNI IEC 60502-1

− Brand name : LSAG

− Cable type : Cu/XLPE/SWA/PVC

− Flame retardant grade : FR Cat. C

− Common Indonesian cable type : (N2XRY)

− Nos. of core & Conductor size

− Rated voltage : 0.6/1(1.2)kV

− Year of manufacture
− Length marking per meter

ex) IEC 60502-1 LSAG Cu/XLPE/SWA/PVC FR Cat.C (N2XRY) 3x150 0.6/1(1.2)kV 2022 0001M

6.2. Drum Marking


The Following information shall be marked.
− Rated voltage and cable type

− Nos. of core and conductor size

− Cable length

− Net weight

− Gross weight

− Direction of rotation

− End position of cable

− Manufacturer’s name

− Year of manufacture

− Drum Number

7. PACKING

The completed cables shall be supplied a non-returnable wooden or steel drum to prevent
from damage during the transportations.
The end of cable shall be sealed to prevent the ingress of moisture.
The diameter of wooden drum shall be complied manufacturer’s standard.

TECHNICAL SPECIFICATION_LV POWER CABLE 4 of 28


TECHNICAL SPECIFICATION_LV POWER CABLE 5 of 28
Attached table 1. : DESIGN PARTICULAR

A. Non Armoured Cable

B.1. Cu/XLPE/PVC FR Cat.C (N2XY) - 0.6/1 (1.2) kV Single Core

Current-Carrying
Conductor Thickness DC Short
Thickness Weight Capacity
Nominal of Overal Resistance circuit
Cross- Of of
Over Diameter At current
sectional No. of Outside Insulation Cable in air in
Sheath 20oC at 1 sec
Area Wire Diameter at ground
300C at 200C
(min) Approx. (nom.) (nom.) Approx. Approx. Max. Max. Max. Max.
2
mm - mm mm mm mm kg/km (Ω/km) (A) (A) (kA)

120 15 13.0 1.2 1.5 18.5 1,211 0.153 312 257 17.16

150 18 14.5 1.4 1.6 21.0 1,492 0.124 342 287 21.45

240 30 18.5 1.7 1.8 25.5 2,415 0.0754 450 375 34.32

300 34 20.5 1.8 1.8 28.0 2,986 0.0601 514 419 42.90

400 34 23.5 2.0 2.0 32.0 3,824 0.047 648 513 57.20

500 53 26.5 2.2 2.1 35.0 4,847 0.0366 747 570 71.50

630 53 30.5 2.4 2.2 39.0 6,196 0.0283 864 638 90.09

B.2. Cu/XLPE/PVC FR Cat.C (N2XY) - 0.6/1 (1.2) kV Two Core

Current-Carrying
Conductor Thickness DC Short
Thickness Weight Capacity
Nominal of Overal Resistance circuit
Cross- of of
Over Diameter at current
sectional No. of Outside Insulation Cable in air in
Sheath 20oC at 1 sec
Area Wire Diameter at ground
300C at 200C
(min) Approx. (nom.) (nom.) Approx. Approx. Max. Max. Max. Max.
2
mm - mm mm mm mm kg/km (Ω/km) (A) (A) (kA)

4 6 2.5 0.7 1.8 12.0 187 4.61 45 43 0.57


6 6 3.5 0.7 1.8 13.0 235 3.08 58 53 0.86
10 6 4.0 0.7 1.8 15.0 330 1.83 69 80 1.43
16 6 5.0 0.7 1.8 16.5 440 1.15 91 107 2.29
25 6 6.0 0.9 1.8 19.5 647 0.727 119 138 3.58
35 6 7.0 0.9 1.8 21.5 838 0.524 148 171 5.01
50 6 8.5 1.0 1.8 24.5 1,114 0.387 175 209 7.15
70 12 10.0 1.1 1.9 28.5 1,551 0.268 269 213 10.01
95 15 11.5 1.1 2.0 32.0 2,058 0.193 328 252 13.59
120 18 13.0 1.2 2.1 35.5 2,559 0.153 382 271 17.16
150 18 14.5 1.4 2.2 39.5 3,139 0.124 441 306 21.45
185 30 16.0 1.6 2.4 44.0 3,920 0.0991 506 343 26.46
240 34 18.5 1.7 2.5 49.0 5,054 0.0754 599 395 34.32

TECHNICAL SPECIFICATION_LV POWER CABLE 6 of 28


B.3. Cu/XLPE/PVC FR Cat.C (N2XY) - 0.6/1 (1.2) kV Two Core with One Ground (1P+N+G)

Short
Current-Carrying
Conductor Thickness Thickness DC Resistance circuit current
Nominal Weight Capacity
of of Overal at 20oC at 1 sec
Cross-sectional of
Insulation Over Diameter
Area Cable
No. of Wire Outside Diameter (approx.) Sheath
in air in ground Phase
(min.) (approx.) Phase Ground at 300C at 200C
Phase Ground Phase Ground Phase Ground Phase Ground (nom.) Approx. Approx. Max. Max. Max. Max. Max.
2 2
mm mm min. min. mm mm mm mm mm mm kg/km (Ω/km) (Ω/km) (A) (A) (kA)

4 4 6 6 2.5 2.5 0.7 0.7 1.8 12.5 238 4.61 4.61 40 36 0.57
6 6 6 6 3.5 3.5 0.7 0.7 1.8 14.0 304 3.08 3.08 52 44 0.86
10 10 6 6 4.0 4.0 0.7 0.7 1.8 16.0 440 1.83 1.83 71 58 1.43
16 16 6 6 5.0 5.0 0.7 0.7 1.8 17.5 599 1.15 1.15 96 75 2.29
25 25 6 6 6.0 6.0 0.9 0.9 1.8 21.0 896 0.727 0.727 119 96 3.58
35 25 6 6 7.0 6.0 0.9 0.9 1.8 23.0 1,101 0.524 0.727 147 115 5.01
50 25 6 6 8.5 6.0 1.0 0.9 1.8 26.0 1,361 0.387 0.727 179 135 7.15
70 35 12 6 10.0 7.0 1.1 0.9 1.9 30.5 1,886 0.268 0.524 229 167 10.01
95 50 15 6 11.5 8.5 1.1 1.0 2.0 34.0 2,510 0.193 0.387 278 197 13.59
120 70 18 12 13.0 10.0 1.2 1.1 2.2 38.5 3,224 0.153 0.268 322 223 17.16
150 95 18 15 14.5 11.5 1.4 1.1 2.3 42.5 4,034 0.124 0.193 371 251 21.45
185 95 30 15 16.0 11.5 1.6 1.1 2.6 50.0 5,174 0.0991 0.193 424 281 26.46
240 120 34 18 18.5 13.0 1.7 1.2 2.7 53.0 6,208 0.0754 0.153 500 324 34.32

TECHNICAL SPECIFICATION_LV POWER CABLE 6 of 28


B.4. Cu/XLPE/PVC FR Cat.C (N2XY) - 0.6/1 (1.2) kV Three Core

Current-Carrying
Conductor Thickness DC Short
Thickness Weight Capacity
Nominal of Overal Resistance circuit
Cross- of of
Over Diameter at current
sectional No. of Outside Insulation Cable in air in
Sheath 20oC at 1 sec
Area Wire Diameter at ground
300C at 200C
(min) Approx. (nom.) (nom.) Approx. Approx. Max. Max. Max. Max.
2
mm - mm mm mm mm kg/km (Ω/km) (A) (A) (kA)

4 6 2.5 0.7 1.8 12.5 238 4.61 40 36 0.57


6 6 3.5 0.7 1.8 14.0 304 3.08 52 44 0.86
10 6 4.0 0.7 1.8 16.0 440 1.83 71 58 1.43
16 6 5.0 0.7 1.8 17.5 599 1.15 96 75 2.29
25 6 6.0 0.9 1.8 21.0 896 0.727 119 96 3.58
35 6 7.0 0.9 1.8 23.0 1,174 0.524 147 115 5.01
50 6 8.5 1.0 1.8 26.0 1,562 0.387 179 135 7.15
70 12 10.0 1.1 1.9 30.5 2,192 0.268 229 167 10.01
95 15 11.5 1.1 2.0 34.0 2,928 0.193 278 197 13.59
120 18 13.0 1.2 2.2 38.5 3,672 0.153 322 223 17.16
150 18 14.5 1.4 2.3 42.5 4,511 0.124 371 251 21.45
185 30 16.0 1.6 2.5 47.0 5,640 0.0991 424 281 26.46
240 34 18.5 1.7 2.7 53.0 7,323 0.0754 500 324 34.32

TECHNICAL SPECIFICATION_LV POWER CABLE 7 of 28


B.5. Cu/XLPE/PVC FR Cat.C (N2XY) - 0.6/1 (1.2) kV Three Core with One Ground (3P+1G)

Short
Current-Carrying
Conductor Thickness Thickness DC Resistance circuit current
Nominal Weight Capacity
of of Overal at 20oC at 1 sec
Cross-sectional of
Insulation Over Diameter
Area Cable
No. of Wire Outside Diameter (approx.) Sheath
in air in ground Phase
(min.) (approx.) Phase Ground at 300C at 200C
Phase Ground Phase Ground Phase Ground Phase Ground (nom.) Approx. Approx. Max. Max. Max. Max. Max.
2 2
mm mm min. min. mm mm mm mm mm mm kg/km (Ω/km) (Ω/km) (A) (A) (kA)

2.5 2.5 6 6 2.0 2.0 0.7 0.7 1.8 12.5 224 7.41 7.41 30 28 0.36
4 4 6 6 2.5 2.5 0.7 0.7 1.8 13.5 295 4.61 4.61 40 36 0.57
6 6 6 6 3.5 3.5 0.7 0.7 1.8 15.0 383 3.08 3.08 52 44 0.86
10 10 6 6 4.0 4.0 0.7 0.7 1.8 17.0 561 1.83 1.83 71 58 1.43
16 16 6 6 5.0 5.0 0.7 0.7 1.8 19.0 771 1.15 1.15 96 75 2.29
25 25 6 6 6.0 6.0 0.9 0.9 1.8 23.0 1,164 0.727 0.727 119 96 3.58
35 25 6 6 7.0 6.0 0.9 0.9 1.8 25.0 1,463 0.524 0.727 147 115 5.01
50 25 6 6 8.5 6.0 1.0 0.9 1.9 29.0 1,863 0.387 0.727 179 135 7.15
70 35 12 6 10.0 7.0 1.1 0.9 2.0 34.0 2,596 0.268 0.524 229 167 10.01
95 50 15 6 11.5 8.5 1.1 1.0 2.2 38.0 3,484 0.193 0.387 278 197 13.59
120 70 18 12 13.0 10.0 1.2 1.1 2.3 42.5 4,420 0.153 0.268 322 223 17.16
150 95 18 15 14.5 11.5 1.4 1.1 2.5 47.5 5,535 0.124 0.193 371 251 21.45
185 95 30 15 16.0 11.5 1.6 1.1 2.6 52.0 6,667 0.0991 0.193 424 281 26.46
240 120 34 18 18.5 13.0 1.7 1.2 2.9 59.0 8,642 0.0754 0.153 500 324 34.32

TECHNICAL SPECIFICATION_LV POWER CABLE 8 of 28


B.6. Cu/XLPE/PVC FR Cat.C (N2XY) - 0.6/1 (1.2) kV Four Core

Current-Carrying
Conductor Thickness DC Short
Thickness Weight Capacity
Nominal of Overal Resistance circuit
Cross- of of
Over Diameter at current
sectional No. of Outside Insulation Cable in air in
Sheath 20oC at 1 sec
Area Wire Diameter at ground
300C at 200C
(min) Approx. (nom.) (nom.) Approx. Approx. Max. Max. Max. Max.
2
mm - mm mm mm mm kg/km (Ω/km) (A) (A) (kA)

4 6 2.5 0.7 1.8 13.5 295 4.61 40 36 0.57


6 6 3.5 0.7 1.8 15.0 383 3.08 52 44 0.86
10 6 4.0 0.7 1.8 17.0 561 1.83 71 58 1.43
16 6 5.0 0.7 1.8 19.0 771 1.15 96 75 2.29
25 6 6.0 0.9 1.8 23.0 1,164 0.727 119 96 3.58
35 6 7.0 0.9 1.8 25.0 1,534 0.524 147 115 5.01
50 6 8.5 1.0 1.9 29.0 2,064 0.387 179 135 7.15
70 12 10.0 1.1 2.0 34.0 2,902 0.268 229 167 10.01
95 15 11.5 1.1 2.2 38.0 3,902 0.193 278 197 13.59
120 18 13.0 1.2 2.3 42.5 4,868 0.153 322 223 17.16
150 18 14.5 1.4 2.5 47.5 6,011 0.124 371 251 21.45
185 30 16.0 1.6 2.6 52.0 7,487 0.0991 424 281 26.46
240 34 18.5 1.7 2.9 59.0 9,758 0.0754 500 324 34.32

TECHNICAL SPECIFICATION_LV POWER CABLE 9 of 28


B.7. Cu/XLPE/PVC FR Cat.C (N2XY) - 0.6/1 (1.2) kV Four Core with One Ground (4P+1G)

Short
Current-Carrying
Conductor Thickness Thickness DC Resistance circuit current
Nominal Weight Capacity
of of Overal at 20oC at 1 sec
Cross-sectional of
Insulation Over Diameter
Area Cable
No. of Wire Outside Diameter (approx.) Sheath
in air in ground Phase
(min.) (approx.) Phase Ground at 300C at 200C
Phase Ground Phase Ground Phase Ground Phase Ground (nom.) Approx. Approx. Max. Max. Max. Max. Max.
2 2
mm mm min. min. mm mm mm mm mm mm kg/km (Ω/km) (Ω/km) (A) (A) (kA)

4 4 6 6 2.5 2.5 0.7 0.7 1.8 15.0 358 4.61 4.61 40 36 0.57
6 6 6 6 3.5 3.5 0.7 0.7 1.8 16.5 466 3.08 3.08 52 44 0.86
10 10 6 6 4.0 4.0 0.7 0.7 1.8 19.0 774 1.83 1.83 71 58 1.43
16 16 6 6 5.0 5.0 0.7 0.7 1.8 20.5 952 1.15 1.15 96 75 2.29
25 25 6 6 6.0 6.0 0.9 0.9 1.8 25.5 1,547 0.727 0.727 119 96 3.58
35 25 6 6 7.0 6.0 0.9 0.9 1.8 28.0 1,844 0.524 0.727 147 115 5.01
50 25 6 6 8.5 6.0 1.0 0.9 2.0 32.0 2,392 0.387 0.727 179 135 7.15
70 35 12 6 10.0 7.0 1.1 0.9 2.2 37.5 3,362 0.268 0.524 229 167 10.01
95 50 15 6 11.5 8.5 1.1 1.0 2.3 42.0 4,485 0.193 0.387 278 197 13.59
120 70 18 12 13.0 10.0 1.2 1.1 2.5 47.0 5,697 0.153 0.268 322 223 17.16
150 95 18 15 14.5 11.5 1.4 1.1 2.6 52.5 7,082 0.124 0.193 371 251 21.45
185 95 30 15 16.0 11.5 1.6 1.1 2.8 58.0 8,630 0.0991 0.193 424 281 26.46
240 120 34 18 18.5 13.0 1.7 1.2 3.1 65.5 11,192 0.0754 0.153 500 324 34.32

TECHNICAL SPECIFICATION_LV POWER CABLE 10 of 28


B. Armoured Cable
B.1. Cu/XLPE/AWA/PVC FR Cat.C (N2XR(Al)Y) - 0.6/1 (1.2) kV Single Core

Current-Carrying
Conductor Thickness DC Short
Thickness Weight Capacity
Nominal of Overal Resistance circuit
Cross- of of
Outside Over Diameter at current
sectional No. of Insulation Cable in air in
Diamete Sheath 20oC at 1 sec
Area Wire at ground
r 300C at 200C
(min) Approx. (nom.) (nom.) Approx. Approx. Max. Max. Max. Max.
mm2 - mm mm mm mm kg/km (Ω/km) (A) (A) (kA)

120 15 13.0 1.2 1.8 22.5 1,575 0.153 312 257 17.16
150 18 14.5 1.4 1.8 24.5 1,881 0.124 342 287 21.45
185 18 16.0 1.6 1.9 26.0 2,284 0.0991 384 324 26.46
240 30 18.5 1.7 1.9 28.5 2,884 0.0754 450 375 34.32
300 34 20.5 1.8 2.1 31.0 3,622 0.0601 514 419 42.90
400 34 23.5 2.0 2.2 34.5 4,541 0.047 648 513 57.20
500 53 26.5 2.2 2.3 38.0 5,638 0.0366 747 570 71.50
630 53 30.5 2.4 2.5 42.0 7,237 0.0283 864 638 90.09

B.2. Cu/XLPE/SWA/PVC FR Cat.C (N2XRY) - 0.6/1 (1.2) kV Two Core

Thicknes DC Current-Carrying
Conductor Thicknes Short
s Overal Weight Resistanc Capacity
Nominal s circuit
Cross- of Diamete of e
Outside of current
sectional No. of Over r Cable at in air in
Diamete Insulation at 1 sec
Area Wire Sheath 20oC at ground
r 300C at 200C
(min) Approx. (nom.) (nom.) Approx. Approx. Max. Max. Max. Max.
2
mm - mm mm mm mm kg/km (Ω/km) (A) (A) (kA)

4 6 2.5 0.7 1.8 15.5 567 4.61 45 43 0.57


6 6 3.5 0.7 1.8 17.5 653 3.08 58 53 0.86
10 6 4.0 0.7 1.8 19.0 802 1.83 69 80 1.43
16 6 5.0 0.7 1.8 20.5 954 1.15 91 107 2.29
25 6 6.0 0.9 1.8 24.5 1,419 0.727 119 138 3.58
35 6 7.0 0.9 1.8 26.5 1,676 0.524 148 171 5.01
50 6 8.5 1.0 1.9 29.5 2,058 0.387 175 209 7.15
70 12 10.0 1.1 2.1 34.5 2,921 0.268 269 213 10.01
95 15 11.5 1.1 2.2 38.0 3,622 0.193 328 252 13.59
120 18 13.0 1.2 2.3 42.0 4,288 0.153 382 271 17.16
150 18 14.5 1.4 2.5 47.0 5,519 0.124 441 306 21.45
185 30 16.0 1.6 2.6 51.5 6,530 0.0991 506 343 26.46
240 34 18.5 1.7 2.8 57.0 7,996 0.0754 599 395 34.32

TECHNICAL SPECIFICATION_LV POWER CABLE 11 of 28


B.3. Cu/XLPE/SWA/PVC FR Cat.C (N2XRY) - 0.6/1 (1.2) kV Two Core with One Ground (1P+N+G)

Short
Current-Carrying
Conductor Thickness Thickness DC Resistance circuit current
Nominal Weight Capacity
of of Overal at 20oC at 1 sec
Cross-sectional of
Insulation Over Diameter
Area Cable
No. of Wire Outside Diameter (approx.) Sheath
in air in ground Phase
(min.) (approx.) Phase Ground at 300C at 200C
Phase Ground Phase Ground Phase Ground Phase Ground (nom.) Approx. Approx. Max. Max. Max. Max. Max.
2 2
mm mm min. min. mm mm mm mm mm mm kg/km (Ω/km) (Ω/km) (A) (A) (kA)

4 4 6 6 2.5 2.5 0.7 0.7 1.8 17.5 644 4.61 4.61 40 36 0.57
6 6 6 6 3.5 3.5 0.7 0.7 1.8 18.5 738 3.08 3.08 52 44 0.86
10 10 6 6 4.0 4.0 0.7 0.7 1.8 20.5 939 1.83 1.83 71 58 1.43
16 16 6 6 5.0 5.0 0.7 0.7 1.8 23.0 1,287 1.15 1.15 96 75 2.29
25 25 6 6 6.0 6.0 0.9 0.9 1.8 26.0 1,711 0.727 0.727 119 96 3.58
35 25 6 6 7.0 6.0 0.9 0.9 1.9 28.45 2,002 0.524 0.727 147 115 5.01
50 25 6 6 8.5 6.0 1.0 0.9 2.0 32.0 2,389 0.387 0.727 179 135 7.15
70 35 12 6 10.0 7.0 1.1 0.9 2.2 37.5 3,411 0.268 0.524 229 167 10.01
95 50 15 6 11.5 8.5 1.1 1.0 2.3 41.5 4,199 0.193 0.387 278 197 13.59
120 70 18 12 13.0 10.0 1.2 1.1 2.4 46.0 5,495 0.153 0.268 322 223 17.16
150 95 18 15 14.5 11.5 1.4 1.1 2.6 51.0 6,627 0.124 0.193 371 251 21.45
185 95 30 15 16.0 11.5 1.6 1.1 2.7 55.5 7,645 0.0991 0.193 424 281 26.46
240 120 34 18 18.5 13.0 1.7 1.2 2.9 62.0 9,402 0.0754 0.153 500 324 34.32

TECHNICAL SPECIFICATION_LV POWER CABLE 12 of 28


B.4. Cu/XLPE/SWA/PVC FR Cat.C (N2XRY) - 0.6/1 (1.2) kV Three Core

Current-Carrying
Conductor Thickness DC Short
Thickness Weight Capacity
Nominal of Overal Resistance circuit
Cross- of of
Over Diameter at current
sectional No. of Outside Insulation Cable in air in
Sheath 20oC at 1 sec
Area Wire Diameter at ground
300C at 200C
(min) Approx. (nom.) (nom.) Approx. Approx. Max. Max. Max. Max.
2
mm - mm mm mm mm kg/km (Ω/km) (A) (A) (kA)

4 6 2.5 0.7 1.8 17.5 644 4.61 40 36 0.57


6 6 3.5 0.7 1.8 18.5 738 3.08 52 44 0.86
10 6 4.0 0.7 1.8 20.5 939 1.83 71 58 1.43
16 6 5.0 0.7 1.8 23.0 1,287 1.15 96 75 2.29
25 6 6.0 0.9 1.8 26.0 1,711 0.727 119 96 3.58
35 6 7.0 0.9 1.9 28.5 2,088 0.524 147 115 5.01
50 6 8.5 1.0 2.0 32.0 2,590 0.387 179 135 7.15
70 12 10.0 1.1 2.2 37.5 3,716 0.268 229 167 10.01
95 15 11.5 1.1 2.3 41.5 4,616 0.193 278 197 13.59
120 18 13.0 1.2 2.4 46.0 5,943 0.153 322 223 17.16
150 18 14.5 1.4 2.6 51.0 7,103 0.124 371 251 21.45
185 30 16.0 1.6 2.7 55.5 8,464 0.0991 424 281 26.46
240 34 18.5 1.7 2.9 62.0 10,517 0.0754 500 324 34.32

TECHNICAL SPECIFICATION_LV POWER CABLE 13 of 28


B.5. Cu/XLPE/SWA/PVC FR Cat.C (N2XRY) - 0.6/1 (1.2) kV Three Core with One Ground (3P+G)

Short
Current-Carrying
Conductor Thickness Thickness DC Resistance circuit current
Nominal Weight Capacity
of of Overal at 20oC at 1 sec
Cross-sectional of
Insulation Over Diameter
Area Cable
No. of Wire Outside Diameter (approx.) Sheath
in air in ground Phase
(min.) (approx.) Phase Ground at 300C at 200C
Phase Ground Phase Ground Phase Ground Phase Ground (nom.) Approx. Approx. Max. Max. Max. Max. Max.
mm2 mm2 min. min. mm mm mm mm mm mm kg/km (Ω/km) (Ω/km) (A) (A) (kA)

4 4 6 6 2.5 2.5 0.7 0.7 1.8 18.5 725 4.61 4.61 40 36 0.57
6 6 6 6 3.5 3.5 0.7 0.7 1.8 19.5 851 3.08 3.08 52 44 0.86
10 10 6 6 4.0 4.0 0.7 0.7 1.8 22.5 1,225 1.83 1.83 71 58 1.43
16 16 6 6 5.0 5.0 0.7 0.7 1.8 24.5 1,514 1.15 1.15 96 75 2.29
25 25 6 6 6.0 6.0 0.9 0.9 1.9 28.5 2,047 0.727 0.727 119 96 3.58
35 25 6 6 7.0 6.0 0.9 0.9 1.9 31.0 2,431 0.524 0.727 147 115 5.01
50 25 6 6 8.5 6.0 1.0 0.9 2.1 35.5 3,223 0.387 0.727 179 135 7.15
70 35 12 6 10.0 7.0 1.1 0.9 2.3 41.0 4,233 0.268 0.524 229 167 10.01
95 50 15 6 11.5 8.5 1.1 1.0 2.4 46.0 5,714 0.193 0.387 278 197 13.59
120 70 18 12 13.0 10.0 1.2 1.1 2.6 51.0 6,961 0.153 0.268 322 223 17.16
150 95 18 15 14.5 11.5 1.4 1.1 2.8 56.0 8,331 0.124 0.193 371 251 21.45
185 95 30 15 16.0 11.5 1.6 1.1 2.9 61.0 9,810 0.0991 0.193 424 281 26.46
240 120 34 18 18.5 13.0 1.7 1.2 3.1 68.0 12,111 0.0754 0.153 500 324 34.32

TECHNICAL SPECIFICATION_LV POWER CABLE 14 of 28


B.6. Cu/XLPE/SWA/PVC FR Cat.C (N2XRY) - 0.6/1 (1.2) kV Four Core (3P+N)

Current-Carrying
Conductor Thickness DC Short
Thickness Weight Capacity
Nominal of Overal Resistance circuit
Cross- of of
Over Diameter at current
sectional No. of Outside Insulation Cable in air in
Sheath 20oC at 1 sec
Area Wire Diameter at ground
300C at 200C
(min) Approx. (nom.) (nom.) Approx. Approx. Max. Max. Max. Max.
2
mm - mm mm mm mm kg/km (Ω/km) (A) (A) (kA)

4 6 2.5 0.7 1.8 18.5 725 4.61 40 36 0.57


6 6 3.5 0.7 1.8 19.5 851 3.08 52 44 0.86
10 6 4.0 0.7 1.8 22.5 1,225 1.83 71 58 1.43
16 6 5.0 0.7 1.8 24.5 1,514 1.15 96 75 2.29
25 6 6.0 0.9 1.9 28.5 2,047 0.727 119 96 3.58
35 6 7.0 0.9 1.9 31.0 2,516 0.524 147 115 5.01
50 6 8.5 1.0 2.1 35.5 3,424 0.387 179 135 7.15
70 12 10.0 1.1 2.3 41.0 4,538 0.268 229 167 10.01
95 15 11.5 1.1 2.4 46.0 6,131 0.193 278 197 13.59
120 18 13.0 1.2 2.6 51.0 7,409 0.153 322 223 17.16
150 18 14.5 1.4 2.8 56.0 8,807 0.124 371 251 21.45
185 30 16.0 1.6 2.9 61.0 10,629 0.0991 424 281 26.46
240 34 18.5 1.7 3.1 68.0 13,226 0.0754 500 324 34.32

TECHNICAL SPECIFICATION_LV POWER CABLE 15 of 28


B.7. Cu/XLPE/SWA/PVC FR Cat.C (N2XRY) - 0.6/1 (1.2) kV Four Core with One Ground (3P+G+N)

Short
Current-Carrying
Conductor Thickness Thickness DC Resistance circuit current
Nominal Weight Capacity
of of Overal at 20oC at 1 sec
Cross-sectional of
Insulation Over Diameter
Area Cable
No. of Wire Outside Diameter (approx.) Sheath
in air in ground Phase
(min.) (approx.) Phase Ground at 300C at 200C
Phase Ground Phase Ground Phase Ground Phase Ground (nom.) Approx. Approx. Max. Max. Max. Max. Max.
2 2
mm mm min. min. mm mm mm mm mm mm kg/km (Ω/km) (Ω/km) (A) (A) (kA)

4 4 6 6 2.5 2.5 0.7 0.7 1.8 19.5 820 4.61 4.61 40 36 0.57
6 6 6 6 3.5 3.5 0.7 0.7 1.8 21.0 967 3.08 3.08 52 44 0.86
10 10 6 6 4.0 4.0 0.7 0.7 1.8 24.0 1,405 1.83 1.83 71 58 1.43
16 16 6 6 5.0 5.0 0.7 0.7 1.8 26.0 1,743 1.15 1.15 96 75 2.29
25 25 6 6 6.0 6.0 0.9 0.9 1.9 30.5 2,393 0.727 0.727 119 96 3.58
35 25 6 6 7.0 6.0 0.9 0.9 2.1 34.4 3,154 0.524 0.727 147 115 5.01
50 25 6 6 8.5 6.0 1.0 0.9 2.2 39.0 3,902 0.387 0.727 179 135 7.15
70 35 12 6 10.0 7.0 1.1 0.9 2.4 45.5 5,498 0.268 0.524 229 167 10.01
95 50 15 6 11.5 8.5 1.1 1.0 2.6 51.0 6,96 0.193 0.387 278 197 13.59
120 70 18 12 13.0 10.0 1.2 1.1 2.7 55.5 8,379 0.153 0.268 322 223 17.16
150 95 18 15 14.5 11.5 1.4 1.1 2.9 61.5 10,131 0.124 0.193 371 251 21.45
185 95 30 15 16.0 11.5 1.6 1.1 3.1 67.0 11,951 0.0991 0.193 424 281 26.46
240 120 34 18 18.5 13.0 1.7 1.2 3.4 76.0 15,778 0.0754 0.153 500 324 34.32

TECHNICAL SPECIFICATION_LV POWER CABLE 16 of 28


B.8. Cu/XLPE/CTS/SWA/PVC FR Cat.C (N2XSRY) - 0.6/1 (1.2) kV Two Core

Current-Carrying
Conductor Thickness DC Short
Thickness Weight Capacity
Nominal of Overal Resistance circuit
Cross- of of
Over Diameter at current
sectional No. of Outside Insulation Cable in air in
Sheath 20oC at 1 sec
Area Wire Diameter at ground
300C at 200C
(min) Approx. (nom.) (nom.) Approx. Approx. Max. Max. Max. Max.
2
mm - mm mm mm mm kg/km (Ω/km) (A) (A) (kA)

4 6 2.5 0.7 1.8 19.5 633 4.61 37 39 0.57


6 6 3.5 0.7 1.8 20.5 707 3.08 48 49 0.86
10 6 4.0 0.7 1.8 23.0 974 1.83 66 65 1.43
25 6 6.0 0.9 1.8 28.0 1,462 0.727 117 107 3.58
35 6 7.0 0.9 1.9 30.0 1,728 0.524 144 128 5.01

B.9. Cu/XLPE/CTS/SWA/PVC FR Cat.C (N2XSRY) - 0.6/1 (1.2) kV Three Core

Current-Carrying
Conductor Thickness DC Short
Thickness Weight Capacity
Nominal of Overal Resistance circuit
Cross- of of
Over Diameter at current
sectional No. of Outside Insulation Cable in air in
Sheath 20oC at 1 sec
Area Wire Diameter at ground
300C at 200C
(min) Approx. (nom.) (nom.) Approx. Approx. Max. Max. Max. Max.
2
mm - mm mm mm mm kg/km (Ω/km) (A) (A) (kA)

2.5 6 2.0 0.7 1.8 19.0 618 7.41 30 28 0.36


4 6 2.5 0.7 1.8 20.0 698 4.61 40 36 0.57
6 6 3.5 0.7 1.8 21.5 799 3.08 52 44 0.86
10 6 4.0 0.7 1.8 24.0 1,121 1.83 71 58 1.43
16 6 5.0 0.7 1.8 25.5 1,337 1.15 96 75 2.29
25 6 6.0 0.9 1.9 29.0 1,764 0.727 119 96 3.58
35 6 7.0 0.9 2.0 31.5 2,136 0.524 147 115 5.01
50 6 8.5 1.0 2.1 36.0 2,876 0.387 179 135 7.15
70 12 10.0 1.1 2.3 40.5 3,740 0.268 229 167 10.01
95 15 11.5 1.1 2.4 45.5 5,002 0.193 278 197 13.59
120 18 13.0 1.2 2.5 49.5 5,921 0.153 322 223 17.16
150 18 14.5 1.4 2.7 54.5 7,105 0.124 371 251 21.45
185 30 16.0 1.6 2.9 59.0 8,482 0.0991 424 281 26.46
240 34 18.5 1.7 3.1 66.0 10,556 0.0754 500 324 34.32

TECHNICAL SPECIFICATION_LV POWER CABLE 17 of 28


B.10 Cu/XLPE/CTS/SWA/PVC FR Cat.C (N2XSRY) - 0.6/1 (1.2) kV Three Core with One Ground (3P+G)

Short
Current-Carrying
Conductor Thickness Thickness circuit current
Nominal Weight DC Resistance Capacity
of of Overal at 1 sec
Cross-sectional of at 20oC
Insulation Over Diameter
Area Cable
No. of Wire Outside Diameter (approx.) Sheath
in air in ground Phase
(min.) (approx.)
Phase Ground at 300C at 200C
Phase Ground Phase Ground Phase Ground Phase Ground (nom.) Approx. Approx. Max. Max. Max. Max. Max.
2 2
mm mm min. min. mm mm mm mm mm mm kg/km (Ω/km) (Ω/km) (A) (A) (kA)

240 120 34 18 18.3 12.9 1.7 1.2 3.2 71.5 11,289 0.0754 0.153 500 324 34.32

B.11 Cu/XLPE/CTS/SWA/PVC FR Cat.C (N2XSRY) - 0.6/1 (1.2) kV Three Core with Three Ground (3P+3G)
Short
Current-Carrying
Conductor Thickness Thickness circuit current
Nominal Weight DC Resistance Capacity
of of Overal at 1 sec
Cross-sectional of at 20oC
Insulation Over Diameter
Area Cable
No. of Wire Outside Diameter (approx.) Sheath
in air in ground Phase
(min.) (approx.)
Phase Ground at 300C at 200C
Phase Ground Phase Ground Phase Ground Phase Ground (nom.) Approx. Approx. Max. Max. Max. Max. Max.
2 2
mm mm min. min. mm mm mm mm mm mm kg/km (Ω/km) (Ω/km) (A) (A) (kA)

240 50 34 6 18.3 8.1 1.7 1.0 3.0 65.0 11,340 0.0754 0.387 500 324 34.32

B.12 Cu/XLPE/CWS/SWA/PVC FR Cat.C (N2XCRY) - 0.6/1 (1.2) kV Three Core

Current-Carrying
Conductor Thickness DC Short
Thickness Weight Capacity
Nominal of Overal Resistance circuit
Cross- of of
Over Diameter at current
sectional Insulation Cable
No. of Outside Sheath 20oC in air at 1 sec
Area at in ground
Wire Diameter
300C at 200C
(min) Approx. (nom.) (nom.) Approx. Approx. Max. Max. Max. Max.
2
mm - mm mm mm mm kg/km (Ω/km) (A) (A) (kA)

240 34 18.3 1.7 3.1 68.0 10,925 0.0754 500 324 34.32

TECHNICAL SPECIFICATION_LV POWER CABLE 18 of 28


Attached table 1. : DRAWING for SUBMITTAL

VOLTAG CONDUCTOR
0.6/1 (1.2)kV NO. OF CORE 1 120 – 630 sqmm
E SIZE
Cable type : Cu/XLPE/PVC FR Cat.C (N2XY)

ITEM DESCRIPTION DETAILS

1 Conductor Annealed copper stranded conductor

2 Insulation Extruded XLPE compound

3 Over Sheath Extruded Black PVC FR Cat. C compound

REMARK : * - Suitable non hygroscopic filler and tape may be applied on laying up cores

TECHNICAL SPECIFICATION_LV POWER CABLE 19 of 28


VOLTAG CONDUCTOR
0.6/1 (1.2)kV NO. OF CORE 2-4 4 – 240 sqmm
E SIZE
Cable type : Cu/XLPE/PVC FR Cat.C (N2XY)

2
3
4

ITEM DESCRIPTION DETAILS

1 Conductor Annealed copper stranded conductor

2 Insulation Extruded XLPE compound

*3 Filler Non Hygroscopic Filler

*4 Binder Non Hygroscopic Tape

5 Over Sheath Extruded Black PVC FR Cat. C compound

REMARK : * - Suitable non hygroscopic filler and tape may be applied on laying up cores

TECHNICAL SPECIFICATION_LV POWER CABLE 20 of 28


2P+1
G
VOLTAG 0.6/1 NO. OF 3P+1 CONDUCTOR
4 - 240 sqmm
E (1.2)kV CORE G SIZE
4P+1
G
Cable type : Cu/XLPE/PVC FR Cat.C (N2XY)

3
4
5

ITEM DESCRIPTION DETAILS

1 Phase Conductor Annealed copper stranded conductor

2 Earth Conductor Annealed copper stranded conductor

3 Insulation Extruded XLPE compound

*4 Filler Non-Hygroscopic Filler

*5 Binder Non-Hygroscopic Tape

6 Over Sheath Extruded Black PVC FR Cat. C compound

REMARK : * - Suitable non hygroscopic filler and tape may be applied on laying up cores

TECHNICAL SPECIFICATION_LV POWER CABLE 21 of 28


VOLTAG CONDUCTOR
0.6/1 (1.2)kV NO. OF CORE 1 120 – 630 sqmm
E SIZE
Cable type : Cu/XLPE/AWA/PVC FR Cat.C (N2XR(AL)Y)

3
4

ITEM DESCRIPTION DETAILS

1 Conductor Annealed copper stranded conductor

2 Insulation Extruded XLPE compound

3 Inner Sheath Extruded Black PVC compound

4 Armour Aluminium round wire

*5 Binder Non metallic tape

6 Over Sheath Extruded Black PVC FR Cat. C compound

REMARK : - Suitable non metallic tape may be applied on armour as a binder

TECHNICAL SPECIFICATION_LV POWER CABLE 22 of 28


VOLTAG CONDUCTOR
0.6/1 (1.2)kV NO. OF CORE 2-4 4 – 240 sqmm
E SIZE
Cable type : Cu/XLPE/SWA/PVC FR Cat.C (N2XRY)

2
3
4
5

6
7

ITEM DESCRIPTION DETAILS

1 Conductor Annealed copper stranded conductor

2 Insulation Extruded XLPE compound

*3 Filler Non Hygroscopic Filler

*4 Binder Non Hygroscopic Tape

5 Inner Sheath Extruded Black PVC compound

6 Armour Galvanized steel round wire

*7 Binder Non metallic tape

8 Over Sheath Extruded Black PVC FR Cat. C compound

REMARK : * - Suitable non hygroscopic filler and tape may be applied on laying up cores

- Suitable non metallic tape may be applied on armour as a binder

TECHNICAL SPECIFICATION_LV POWER CABLE 23 of 28


2P+1
G
VOLTAG 0.6/1 NO. OF 3P+1 CONDUCTOR
4 - 240 sqmm
E (1.2)kV CORE G SIZE
4P+1
G
Cable type : Cu/XLPE/SWA/PVC FR Cat.C (N2XRY)

1
2
3
4
5

7
8

ITEM DESCRIPTION DETAILS

1 Phase Conductor Annealed copper stranded conductor

2 Earth Conductor Annealed copper stranded conductor

3 Insulation Extruded XLPE compound

*4 Filler Non Hygroscopic Filler

*5 Binder Non Hygroscopic Tape

6 Inner Sheath Extruded Black PVC compound

7 Armour Galvanized steel round wire

*8 Binder Non metallic tape

9 Over Sheath Extruded Black PVC FR Cat. C compound

REMARK : * - Suitable non hygroscopic filler and tape may be applied on laying up cores

- Suitable non metallic tape may be applied on armour as a binder

TECHNICAL SPECIFICATION_LV POWER CABLE 24 of 28


TECHNICAL SPECIFICATION_LV POWER CABLE 25 of 28
VOLTAG 0.6/1 NO. OF CONDUCTOR
2-3 2.5 - 240 sqmm
E (1.2)kV CORE SIZE
Cable type : Cu/XLPE/CTS/SWA/PVC FR Cat.C (N2XSRY)

1
2
3
4
5
6
7
8
9

10

ITEM DESCRIPTION DETAILS

1 Conductor Annealed copper stranded conductor

2 Insulation Extruded XLPE compound

*3 Filler Non Hygroscopic Filler

*4 Binder Non Hygroscopic Tape

5 Inner Sheath Extruded Black PVC compound

6 Screen Copper Tape

7 Separation Sheath Extruded Black PVC compound

8 Armour Galvanized steel round wire

*9 Binder Non metallic tape

10 Over Sheath Extruded Black PVC FR Cat. C compound

REMARK : * - Suitable non hygroscopic filler and tape may be applied on laying up cores

- Suitable non metallic tape may be applied on armour as a binder

TECHNICAL SPECIFICATION_LV POWER CABLE 26 of 28


VOLTAG 0.6/1 NO. OF CONDUCTOR 3x240 + 120
E (1.2)kV CORE 3P+G SIZE sqmm
Cable type : Cu/XLPE/CTS/SWA/PVC FR Cat.C (N2XSRY)

ITEM DESCRIPTION DETAILS

1 Phase Conductor Annealed copper stranded conductor

2 Earth Conductor Annealed copper stranded conductor

3 Insulation Extruded XLPE compound

*4 Filler Non Hygroscopic Filler

*5 Binder Non Hygroscopic Tape

6 Inner Sheath Extruded Black PVC compound

7 Screen Copper Tape

8 Separation Sheath Extruded Black PVC compound

9 Armour Galvanized steel round wire

*10 Binder Non metallic tape

11 Over Sheath Extruded Black PVC FR Cat. C compound

REMARK : * - Suitable non hygroscopic filler and tape may be applied on laying up cores

- Suitable non metallic tape may be applied on armour as a binder

TECHNICAL SPECIFICATION_LV POWER CABLE 27 of 28


VOLTAG 0.6/1 NO. OF 3P+3 CONDUCTOR 3x240 + 3x50
E (1.2)kV CORE G SIZE sqmm
Cable type : Cu/XLPE/CTS/SWA/PVC FR Cat.C (N2XSRY)

2
3
4
5
6
7
8
9
10

11

ITEM DESCRIPTION DETAILS

1 Phase Conductor Annealed copper stranded conductor

2 Earth Conductor Annealed copper stranded conductor

3 Insulation Extruded XLPE compound

*4 Filler Non Hygroscopic Filler

*5 Binder Non Hygroscopic Tape

6 Inner Sheath Extruded Black PVC compound

7 Screen Copper Tape

8 Separation Sheath Extruded Black PVC compound

9 Armour Galvanized steel round wire

*10 Binder Non metallic tape

11 Over Sheath Extruded Black PVC FR Cat. C compound

REMARK : * - Suitable non hygroscopic filler and tape may be applied on laying up cores

- Suitable non metallic tape may be applied on armour as a binder

TECHNICAL SPECIFICATION_LV POWER CABLE 28 of 28


VOLTAG 0.6/1 NO. OF CONDUCTOR 240/120 sqmm
E (1.2)kV CORE 3 SIZE (Screen)
Cable type : Cu/XLPE/CTS/SWA/PVC FR Cat.C (N2XCRY)

2
3
4
5
6
7
8
9
10
11

12

ITEM DESCRIPTION DETAILS

1 Conductor Annealed copper stranded conductor

2 Insulation Extruded XLPE compound

*3 Filler Non Hygroscopic Filler

*4 Binder Non Hygroscopic Tape

5 Inner Sheath Extruded Black PVC compound

6&7 Screen Copper Round Wire + Copper Tape

*8 Binder Non Metallic Tape

9 Separation Sheath Extruded Black PVC compound

10 Armour Galvanized steel round wire

*11 Binder Non metallic tape

12 Over Sheath Extruded Black PVC FR Cat. C compound

REMARK : * - Suitable non hygroscopic filler and tape may be applied on laying up cores

- Suitable non metallic tape may be applied on screen or armour as a binder

TECHNICAL SPECIFICATION_LV POWER CABLE 29 of 28